AVR Interface List

Read carefully AVR instructions before connecting to controller!

Basler: APR 63-5, AEC 63-7, KR-FX, KR-FFX


AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

AVRi output is connected instead of external resistor for voltage adjusting.

Basler: DECS 100


AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

AVRi output is connected instead of external resistor for voltage adjusting.

BASLER: DESC 200


AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

Stamford SX 460
iG 230/400VAC From AVRi trim to minimum
-
18VAC AVRi 0VAC generator counterclockwise.
TRANS

AVRI OUT Volt/PF ctrl:


1 OUT2 AVRi+
AVRI COM AVR DCout bias = 50%
AVRi- VoltRegChar = POSITIVE
2 OUT1

AVRi output is connected instead of external resistor for voltage adjusting.


STAMFORD SX 440, AS440, MX 321, SX 421
iG 230/400VAC From AVRi trim to minimum
-
18VAC AVRi 0VAC generator counterclockwise.
TRANS

AVRI OUT Volt/PF ctrl:


AVRi+
A1 OUT2 AVRI COM AVR DCout bias = 50%
AVRi- VoltRegChar = POSITIVE
A2 OUT1

PFC3 module is not required.

InteliGenNT, InteliSysNT, InteliMainsNT – Installation Guide r3, ©ComAp – August 2010 80


IGS-NT-2.4-Installation Guide r3.PDF
STAMFORD MX 341
iG 230/400VAC From AVRi trim to minimum
-
18VAC AVRi 0VAC generator counterclockwise.
TRANS

AVRI OUT Volt/PF ctrl:


AVRi+
A1 GND AVRI COM AVR DCout bias = 50%
AVRi- VoltRegChar = POSITIVE
A2 OUT1

Hint:
Disconnect the droop CT (terminal S1 & S2) and short the droop CT leads
short the terminal S1,S2 on the AVR

Leroy Somer: R 438 LS, R448


Kutai EA448
AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

AVRi output is connected instead Remote voltage trimmer 470 ohm to


terminals ST4. Module R726 is not required.
Leroy Somer: R 449
AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

Module R726 is not required.


Leroy Somer: R 129
iG 230/400VAC From AVRi trim to minimum
- generator
18VAC AVRi 0VAC counterclockwise.
TRANS

AVRI OUT Volt/PF ctrl:


AVRi+
AVRi

GND AVRI COM


iG-

AVR DCout bias = 50%


J2 AVRi-
OUT1 VoltRegChar = POSITIVE

AVRi output is connected instead Remote voltage trimmer 470 ohm to


terminal J2. Module R726 is not required.

InteliGenNT, InteliSysNT, InteliMainsNT – Installation Guide r3, ©ComAp – August 2010 81


IGS-NT-2.4-Installation Guide r3.PDF
Leroy Somer: R 221, R 222

Module R726 is not required.


AVRi trim to minimum counterclockwise +5%.

Volt/PF ctrl:
AVR DCout bias = 24%
VoltRegChar = POSITIVE

InteliGenNT, InteliSysNT, InteliMainsNT – Installation Guide r3, ©ComAp – August 2010 82


IGS-NT-2.4-Installation Guide r3.PDF
Leroy Somer: R 230

iG 230/ 400VAC from generator


-
AVRi 0 VAC
TRANS

AVRI OUT
AVRi+
OUT2
AVRI COM
OUT1 AVRi -

Module R726 is not required.


AVRi trim to minimum counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

Leroy Somer: R 438 LS, R448


AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

AVRi output is connected instead Remote voltage trimmer 470 ohm to


terminals ST4.
Module R726 is not required.

InteliGenNT, InteliSysNT, InteliMainsNT – Installation Guide r3, ©ComAp – August 2010 83


IGS-NT-2.4-Installation Guide r3.PDF
Leroy Somer: R 449
AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

Leroy Somer: R 129


iG 230/400VAC From AVRi trim to minimum
- generator
18VAC AVRi 0VAC counterclockwise.
TRANS

AVRI OUT Volt/PF ctrl:


AVRi+
AVRi

GND AVRI COM


iG-

AVR DCout bias = 50%


J2 AVRi-
OUT1 VoltRegChar = POSITIVE

AVRi output is connected instead Remote voltage trimmer 470 ohm to


terminal J2.

Leroy Somer: R 250


iG 230/400VAC From AVRi trim to minimum
- generator
18VAC AVRi 0VAC counterclockwise.
TRANS

AVRI OUT VoltRegChar = POSITIVE


AVRi+
AVRi

GND AVRI COM


iG-

AVRDCout bias = 50%


J2 AVRi-
OUT1

Mecc Alte Spa: U.V.R.6


AVRi trim to maximum
clockwise.

Volt/PF ctrl:
AVR DCout bias = 75%
VoltRegChar = NEGATIVE

AVRi output is connected instead Remote voltage trimmer 100Kohm Hint:


(OUT1=top position wire and GND =second top position). VoltRegChar = POSITIVE is
achived with IG-AVRi OUT2
and GND connection.
Mecc Alte Spa: S.R.7/2
iG 230/400VAC From AVRi trim to maximum
18VAC -
AVRi 0VAC generator clockwise.
TRANS

AVRI OUT Volt/PF ctrl:


AVRi+
AVRi

GND
iG-

AVRI COM AVR DCout bias = 75%


AVRi- VoltRegChar = NEGATIVE
OUT1

InteliGenNT, InteliSysNT, InteliMainsNT – Installation Guide r3, ©ComAp – August 2010 84


IGS-NT-2.4-Installation Guide r3.PDF
Mecc Alte DSR

AVRi trim = 1/16 from minimum ( =6,25% => max. = 2,5V).

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

The Vext input (connector CN1 – terminals 10 and 11) permits analogical remote control of output voltage
with a programmable variation range of up to ±10% (parameter 16, by default the setting is ±5%) with respect
to the value set. If you want to use continuous voltage, it will be effective if it is in the range between 0V and
+2,5V. The input tolerates voltages from –5V to +5V, but for values exceeding the limits of 0V / +2,5V (or in
the event of disconnection) it is automatically disabled and the voltage adjustment goes back to the value set
through the trimmer (if enabled) or through parameter 19 (as shown on the picture).
Changing of DSR parameters requires PC with dedicated software and DI1-DSR unit!
DSR automatically detects presence of transformer for parallel operation (if used it works with droop, if not
used it works isochronous).

InteliGenNT, InteliSysNT, InteliMainsNT – Installation Guide r3, ©ComAp – August 2010 85


IGS-NT-2.4-Installation Guide r3.PDF
Piller
AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 39%
VoltRegChar = POSITIVE

AVRi output is connected instead Remote voltage trimmer 100Kohm.


Catterpillar VR6, VR3F
AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

For VR3F link 4-7 has to be removed.

Caterpillar VR6-B
AVRi trim to minimum
counterclockwise.

Volt/PF ctrl:
AVR DCout bias = 0%
VoltRegChar = POSITIVE
Voltage range (-2V; 2V)

Caterpillar CDVR
AVRi trim to 50%

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

Pin 44 on DVR – PF regulation directly from DVR is not connected.

Catterpillar DVR
AVRi trim to 25%

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

Pin 44 on DVR – PF regulation directly from DVR is not connected.

AVK Newage MA330


AVRi trim to minimum
counterclockwise

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

InteliGenNT, InteliSysNT, InteliMainsNT – Installation Guide r3, ©ComAp – August 2010 86


IGS-NT-2.4-Installation Guide r3.PDF
AVK Newage Cosimat N+

Volt/PF ctrl:
AVR DCout bias = 25%
VoltRegChar = NEGATIVE

Marathon DVR2000E
AVRi trim to 1/3 clockwise

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

MarelliMotori Mark I (M40FA640A/A)


iG 230/ 400VAC From AVRi trim to 20%
- generator
18VAC AVRi 0 VAC
TRANS
Volt/PF ctrl:
AVRI OUT
AVRi+ AVR DCout bias = 50%
AVRi

OUT2
iG-

8 AVRI COM VoltRegChar = POSITIVE


6 OUT1 AVRi-

MarelliMotori (M40FA610A)

Volt/PF ctrl:
AVR DCout bias = 50%
VoltRegChar = POSITIVE

InteliGenNT, InteliSysNT, InteliMainsNT – Installation Guide r3, ©ComAp – August 2010 87


IGS-NT-2.4-Installation Guide r3.PDF