ALTERNATOR TECHNICAL DESCRIPTION 1


LSA 50.2 M6 / 4p
LS Reference: 30569 1

Date: 1/28/2019 V4.08 - 11/2018


Project Manager : OC 1
Moteurs Leroy-Somer leroysomer.singapore@mail.nidec.com
Leroy Somer (SEA) Pte Ltd +65 6266 1726 xx
36 Lok Yang Way, Jurong - Singapore 628641 OC

Main data C 1
Generator type: LSA 50.2 M6 / 4p 1
Power: 1 000 kVA 800 kWe 839 kWm 1
Voltage: 400 V Star serial 1
Rated voltage range: +5/-5% 1
Power factor - Lagging: 0,8 1
Frequency: 50 Hz 1
Speed: 1500 rpm 1
Nominal current: 1 443 A 1
Winding type: p2/3 1
Classes (Insulation / Temperature Rise): H/F 1
Ambient Temperature: 40 °C 1
Altitude: 1000 m 1
-
Installation Quantity 1 1
Prime mover: Reciprocating engine 1
Manufacturer: - 1
Type: - 1
Duty: Base Rating 1
Industry: Industrial Applications 1
-
Mechanical Construction IM1201 1
Type of construction: Single bearing 1
Mounting arrangement: Horizontal Axis 1
Direction of rotation: Clockwise (seen when facing the drive end - DE) 1
Bearing type: Anti-friction 1
Bearing Lubrication: Greased for life 1
Bearing insulation: Not insulated 1
Flector type: To defined later 1
Balancing - Class (ISO 1940/1): Without key - G2,5 (std) 1
Flange: To defined later 1
Shaft height: 450 mm 1
Width: 750 mm 1
-
Additional specificities 1
Stabilized Runaway speed: 1800 rpm - 2 min. 1
-
Cooling Method IC01 1
Degree of protection: IP23 1
Coolant: Air / Temperature: 40 °C 1
Air quality: Tropical Amb. 1
Ventilation (internal): Self-ventilated 1
Filters: Without 1
Ducting for air inlet: No 1
Ducting for air outlet: No 1

30569 rev. 1 Page 1 / 7


1

ALTERNATOR TECHNICAL DESCRIPTION 1


LSA 50.2 M6 / 4p
LS Reference: 30569 1

Date: 1/28/2019 V4.08 - 11/2018


Project Manager : OC 1
-
Connection, Excitation & Regulation 1
Parallel operation: Island mode (0F) - no //CT 1
Excitation: Self-excited - Brushless - Type: AREP + PMI 1
Sustained 3-phase Isc: > 3 x FLC for 10s. 1
AVR type: R450 1
AVR location: In terminal box 1
Alternator Voltage sensing: In terminal box 1
-
Terminal box
Power connection: 4 connectors (brought out neutral) 1
Main Terminal box location: On Top 1
Line side outlet: Left hand side (seen when facing the drive end - D) 1
Gland plate: Non magnetic - Cable gland plate not drilled 1
- 1
-
Protection and measurement accessories 1
1
Temperature detection 1
Stator windings: 6 x 3-wire Pt100 RTDs 1
Guide bearing - NDE: 1 x 3-wire Pt100 RTD 1
1
Anti-condensation heating 1
Voltage: 230 V - 1Ph / Power: 500 W 1
-
-
Various items
Paint: PE - Primary - RAL 7032 1
Documentation: PDF manual 1
Documentation Language: English 1
Client Label 1
-
Controls
QUAL/INES/006 001 Measurement of winding resistance 1
QUAL/INES/006 021 Insulation check on sensors (when fitted) 1
QUAL/INES/006 002 Voltage balance and phase order check 1
QUAL/INES/006 007 Overspeed test (according to test bench limitation) 1
QUAL/INES/006 009 High potential test 1
QUAL/INES/006 010 Insulation resistance measurement 1
-

30569 rev. 1 Page 2 / 7


1

ALTERNATOR ELECTRICAL DATA


LSA 50.2 M6 / 4P
LS Reference: 30569

Date: 1/28/2019 V4.08 - 11/2018

Main data: C
Power: 1 000 kVA 800 kWe 839 kWm 1
Voltage: 400 V Frequency: 50 Hz 1
Rated voltage range: +5% / -5% Speed: 1500 rpm 1
Power factor - Lagging: 0,8 1
Nominal current: 1 443 A Phases 3
Insulation / Temperature rise: H/F Connexion Star serial 1
Cooling: IC01 Winding type: p2/3 1
Winding: 6 S # 6Fils - 6 Wires 1
Ambient Temperature: 40 °C 1
Altitude: 1000 m Overspeed (rpm) 1800 1
Duty: Base Rating Total Harmonic Distortion (THD) < 5% 1

Efficiency ( Base 800 kWe ) IEC


25% 50% 75% 100% 110%
Power factor - Lagging: 0,8 92,72 95,14 95,48 95,32 95,19 1
Power factor - Lagging: 1 93,15 95,85 96,47 96,57 96,55 1

Reactances (%) - ( Base 1000 kVA )


Unsaturated Saturated Unsaturated Saturated
Direct axis Quadrature axis
Synchronous reactance Xd 314 256 Xq 160 130 1
Transient reactance X'd 18,2 15,4 X'q 160 130 1
Subtransient reactance X"d 15,5 13,2 X''q 16,3 13,9 1

Negative sequence reactance X2 15,9 13,5

X0 57,3 Zero sequence reactance 1


Xl 7,8 Stator leakage reactance
Xr 10,8 Rotor leakage reactance
Kc 0,39 Short-circuit ratio 1

Time constants (s)


Direct axis Quadrature axis
Open circuit transient time constant T'do 3,63 T'qo NA 1
Short-circuit transient time constant T'd 0,211 T'q NA 1
Open circuit subtransient time constant T''do 0,021 T''qo 0,159 1
Subtransient time constant T"d 0,018 T"q 0,016 1

Ta 0,027 Armature time constant 1

Resistances (%)
Ra 1,9 Armature resistance R0 19,1 Zero sequence resistance 1
X/R X/R ratio (without unit) R2 3,2 Negative sequence resistance

Voltage accuracy: 1%

rating is provided for the specified temperature rise, by resistance measurement according to IEC60034-1
According to: I.E.C. 60034.1 - 60034.2 - NEMA MG 1-32
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments,
improve the design or change conditions of utilization.

30569 rev. 1 Page 3 / 7


1

ALTERNATOR MAIN CURVES


LSA 50.2 M6 / 4P
LS Reference: 30569

Date: 1/28/2019 1000kVA - 400V - 50 Hz V4.08 - 11/2018

Umax + 5% 420 V
Capability Curve Un 400 V
Umin - 5% 380 V

PF -0,8 PF -0,9 PF -0.95 kWe // rated


kWe ratedkVA
kVA PF 0.95 PF 0,9 PF 0,8
1 0,8
PF -0,7 PF 0,7

0,8
PF -0,6 PF 0,6

0,6
PF -0,5 PF 0,5

PF -0,4 PF 0,4
0,4

PF -0,3 PF 0,3

PF -0,2 0,2 PF 0,2

PF -0,1 PF 0,1

0
-1,0 -0,8 -0,6 -0,4 -0,2 0,0 0,2 0,4 0,6 0,8 1,0
kVAr // rated
kVAr rated kVA
kVA

Efficiency Curves According to: IEC

PF 1 PF 0,8
97,0
96,57 96,55
96,47
96,5
Efficiency - Rendement en %

95,85
96,0

95,5
95,49
95,0 95,32
95,13 95,19

94,5

94,0

93,5
93,15
93,0
92,73
92,5
25 50 75 100 125
Load (% of rated kWe) - Charge (% kWe nominaux)

30569 rev. 1 Page 4 / 7


1

ALTERNATOR MAIN CURVES


LSA 50.2 M6 / 4P
LS Reference: 30569

Date: 1/28/2019 1000kVA - 400V - 50 Hz V4.08 - 11/2018

Stator Current decrement curves


Symmetrical phase to neutral short-circuit initial 5 151 A 3,6 x In
Symmetrical two phase short-circuit max 9 306 A 6,4 x In In = 1443 A
Symmetrical three phase short-circuit value 10 816 A 7,5 x In
Thermal Limit

Isc ( Short circuit current per rated current - Courant de court circuit / In )
Symetrical Phase to neutral short circuit
12 Symetrical two phase short circuit
Symetrical three phase short circuit
Thermal limit curve
court circuit aux bornes de l'alternateur

10
short circuit at generator terminals -

0
0,001 0,01 0,1 1 10 100
Time - Temps (second.)

Asymmetrical three phase short-circuit IP 15 391 A 10,7 x In

Isc ( Short circuit current per rated current - Courant de court circuit / In )
Symetrical three phase short circuit (rms)
12
Asymetrical three phase short circuit (peak)

Thermal limit curve


short circuit at generator terminals -

10
court circuit aux bornes

0
0,001 0,01 0,1 1 10 100
Time - Temps (second.)

30569 rev. 1 Page 5 / 7


1

ALTERNATOR MAIN CURVES


LSA 50.2 M6 / 4P
LS Reference: 30569

Date: 1/28/2019 1000kVA - 400V - 50 Hz V4.08 - 11/2018

Transient Voltage Variation

Transient voltage dip curve versus load impact


Load inrush - Appel de charge - per kVA
0 500 1 000 1 500 2 000 2 500 3 000
0%
Voltage dip - Chute de Tension (% of rated voltage)

5%

10%

15%

20%

25%

30%
PF = 0,8 PF = 0,6 PF = 0,3 PF = 0,6 100%

Transient voltage rise curve versus load rejection


kVA shedding at P.F. Delestage de charge - per rated kVA
40%
Voltage rise - Surtension (% of rated voltage)

35%

30%

25%

20%

15%

10%

5%

0%
0 500 1 000 1 500 2 000 2 500 3 000

PF = 0,8 100%

30569 rev. 1 Page 6 / 7


1

ALTERNATOR MAIN CURVES


LSA 50.2 M6 / 4P
LS Reference: 30569

Date: 1/28/2019 1000kVA - 400V - 50 Hz V4.08 - 11/2018

Thermal Damage Curve

Stator current
(per rated current)
6

5,5

4,5

3,5

2,5

1,5

1
1 10 100 1000 10000
Maximum duration - durée maximum (second.)

Unbalance Load Curve Stator Earth Fault Current

Negative phase sequence Current Fault Current - Courant de défaut (A)


courant inverse (per rated current)
3 75
C : Extensive damage
B : Considerable damage
A : Acceptable damage

2 50 C

B
1 25

A
0 0
1 10 100 1000 10000 0 1 2 3 4 5 6 7 8 9 10 11 12
Maximum duration of fault - Maximum duration of fault -
Durée max. du defaut (second.) Durée max. du defaut (second.)

30569 rev. 1 Page 7 / 7