Professional Documents
Culture Documents
3 PRODUCT SCOPE
The MiCOM P642, P643 and P645 preserves transformer service life by offering fast
protection for transformer faults. Hosted on an advanced IED platform, the P64x
incorporates differential, REF, thermal, and overfluxing protection, plus backup protection
for uncleared external faults. Model variants cover two and three winding transformers
(including autotransformers), with up to five sets of 3-phase CT inputs. Large CT counts
are common in ring bus or mesh corner applications, where the P64x summates currents
to create each total winding current, easing application of backup protection. Backup
overcurrent can be directionalized, where the user includes the optional 3-phase VT input
in their chosen model.
47 A one-stage negative phase sequence overvoltage protection element is P642/ P643/ P645
available. It is DT only.
81U/O Four-stage Definite Time underfrequency and two-stage Definite Time P642/ P643/ P645
overfrequency protection is provided for load shedding and back-up protection.
RTD Ten RTDs (PT100) are available to monitor the ambient and top oil temperature Option P642/ P643/
accurately. Each RTD has an instantaneous alarm and Definite Time trip stage. P645
50BF A two-stage circuit breaker failure function is provided with a 3-pole initiation P642/ P643/ P645
input from external protection.
37P Phase undercurrent elements are available for use with, for example, the circuit P642/ P643/ P645
breaker fail function.
VTS Voltage transformer supervision is provided (1, 2 & 3-phase fuse failure P642/ P643/ P645
detection) to prevent mal-operation of voltage-dependent protection elements
when a VT input signal is lost.
CTS Current transformer supervision prevents mal-operation of current-dependent P642/ P643/ P645
protection elements when a CT input signal is lost.
CLIO Four analog or current loop inputs are provided for transducers such as vibration Option P642/ P643/
sensors and tachometers. Each input has a Definite Time trip and alarm stage, P645
each input can be set to ‘Over’ or ‘Under’ operation, and each input can be
independently selected as 0 to 1, 0 to 10, 0 to 20 or 4 to 20 mA.
Four analogue (or current loop) outputs are provided for the analogue
measurements in the relay. Each output can be independently selected as 0 to
1, 0 to 10, 0 to 20 or 4 to 20 mA.
CT saturation and no gap detection algorithms have been included to enhance
to low set differential element operating time
External fault detection algorithm has bee included to maintain stability during
external faults.
Zero crossing detection algorithm has been included to prevent circuit breaker
failure mal-operations due to subsidence current.
Phase rotation. The rotation of the phases ABC or ACB for all 3-phase current P642/ P643/ P645
and voltage channels can be selected. Also, for pumped storage applications,
the swapping of two phases can be emulated independently for the 3-phase
voltage and 3-phase current channels.
32 programmable user alarms P642/ P643/ P645
10 programmable function keys P642/ P643/ P645
18 programmable LEDs (tri-color P645, red P642 / P643) P642/ P643/ P645
8 to 24 digital inputs (order option) depending on the model P642/ P643/ P645
Front communication port (EIA(RS)232) P642/ P643/ P645