Conditions in Use For Ce Marking Conformity: SUNX Limited
Conditions in Use For Ce Marking Conformity: SUNX Limited
The I/O devices for S-LINK are CE marking conforming products complying with EMC
Directive. The harmonized standard with regard to immunity that applies to this product
is EN 61000-6-2 and the following condition must be met to conform to that standard.
Be sure to meet the condition 1 and, furthermore, the condition either 2 or
3 should also be met.
Ɣ Condition
1. Cable length between the main power supply and the S-LINK controller
should be under 10m.
2. When the power is supplied from S-LINK controller to I/O devices at a
cable distance of more than 10m, add a surge absorber between 24V
and 0V at a cable distance of under 10m.
Recommended surge absorber:
ERZ05D390 (Manufactured by Panasonic Electronic Components Co., Ltd.)
3. Use a local power supply at a cable distance of under 10m from each I/O device.
Main power supply
Hook-up
S-LINK
Hook-up connector connectors Hook-up connector
controller
Surge absorber
Under Hook-up or local power
Surge absorber connector
10m supply
or local power
supply I/O device
Under 10m Under 10m
Hook-up Under
Hook-up
connector 10m
connectors
I/O devices I/O device
Under 10m
Surge absorber
or local power
supply I/O devices
I/O device
Note: Do not connect a surge absorber between D and G.