You are on page 1of 3

Nelson Mandela Bay Municipality

Scientific Services Laboratory


Office 14 1st floor, Lillian Diedericks Building,
191 Govan Mbeki Avenue, Port Elizabeth
6000, Republic Of South Africa
tel: +27(41) 506 2338, fax: +27(41) 506 2181
e-mail: pmatyolo@mandelametro.gov.za

Micro Results Report - Taps (Week 2)

From: 2022-01-24 To: 2022-01-26

Heterotrophic Plate Count (TPC) Avg

Heterotrophic Plate Count


Membrane Filtration

Membrane Filtration
Sample Number
Sampling Point
Sampled Date

Total Coliforms
(cfu/100mL)

(cfu/100mL)

(cfu/mL)
E.Coli
24-01-2022 Kwazakhele Police Station 50;701 22 >200 1000

24-01-2022 Veeplaas Clinic 50;702 0 19 158

24-01-2022 Missionvale Clinic 50;703 0 0 1

24-01-2022 Pieter Rademeyer Hall, Algoa Park 50;704 0 0 123

24-01-2022 New Brighton Great Centenary Hall 50;705 0 0 65

24-01-2022 Jarman Hall Clinic 50;706 0 1 73

24-01-2022 Chatty Clinic 50;707 0 1 45

24-01-2022 Shell Garage, Stanford Road 50;708 0 0 362

24-01-2022 Gail Road Depot 50;709 0 3 32

24-01-2022 Riviera Swimming pool 50;710 0 78 41

24-01-2022 Airport 50;711 0 0 61

24-01-2022 Motherwell_NU9_Spar 50;712 0 0 18

24-01-2022 Raymand Mhlaba Hall, Motherwell 50;713 0 0 0

24-01-2022 Motherwell NU10 Police Station 50;714 0 0 0

24-01-2022 Linton Grange Clinic 50;715 0 14 212

24-01-2022 Walmer Library 50;716 0 0 0

24-01-2022 Cape Receife School 50;717 0 0 0

24-01-2022 N/P Builders Express 50;718 0 0 0

24-01-2022 Nursery, Walmer Downs 50;719 2 >200 129

24-01-2022 Sidwell Fire Station 50;720 0 3 5

24-01-2022 Harrower Road Depot 50;721 0 7 89

Report Date: 28-January-2022 Page 1 of 3


Micro_Results
Heterotrophic Plate Count (TPC) Avg

Heterotrophic Plate Count


Membrane Filtration

Membrane Filtration
Total Coliforms
(cfu/100mL)

(cfu/100mL)

(cfu/mL)
E.Coli
24-01-2022 Charlo Shopping Centre 50;722 0 0 2

24-01-2022 Spar Supermarket, Swartkops 50;723 0 0 46

24-01-2022 Despatch 3 - Municipal Offices - Lethuli St. 50;724 2 56 35

24-01-2022 Despatch Logistics Park 50;725 0 26 20

24-01-2022 Colchester Restaurant 50;726 0 0 238

24-01-2022 Port of Ngqura Entrance, NPA 50;727 0 0 6

24-01-2022 Seaview Police Station 50;728 0 0 44

24-01-2022 Wells Estate Clinic 50;729 0 0 0

24-01-2022 Uitenhage Cuyler Street depot 50;730 0 0 0

24-01-2022 Shop, Cnr Gavin & Errol Street , Uitenhage 50;731 0 0 0

24-01-2022 Orsmond TB Clinic, Uitenhage 50;732 0 0 0

24-01-2022 Letitia Bam Day Hospital, KwaNobuhle 50;733 1 18 87

24-01-2022 Mkoko Police Station, KwaNobuhle 50;734 0 82 37

24-01-2022 Bantom Street Clinic, KwaNobuhle 50;735 0 19 28

24-01-2022 KwaDwesi Police Station 50;736 0 9 6

24-01-2022 Govan Mbeki Fire Station 50;737 0 19 12

24-01-2022 Linton Tap 2 50;738 0 0 0

26-01-2022 Kwazakhele Police Station 50;739 0 8 1000

26-01-2022 Veeplaas Clinic 50;740 0 55 1000

26-01-2022 Riviera Swimming pool 50;741 0 >200 1000

26-01-2022 Linton Grange Clinic 50;742 0 0 71

26-01-2022 Nursery, Walmer Downs 50;743 0 0 358

26-01-2022 Despatch 3 - Municipal Offices - Lethuli St. 50;744 0 54 320

26-01-2022 Letitia Bam Day Hospital, KwaNobuhle 50;745 0 18 370

26-01-2022 Mkoko Police Station, KwaNobuhle 50;746 0 79 617

26-01-2022 Bantom Street Clinic, KwaNobuhle 50;747 0 >200 173

26-01-2022 Govan Mbeki Fire Station 50;748 0 3 1000

Report Date: 28-January-2022 Page 2 of 3


Micro_Results
According to SANS 241:2015 the standard for drinking water, 11 samples did not comply. 10 re-samples were submitted and only two
samples complied. Sample from Gustav Lamour Clinic Despatch was not submitted to the laboratory.

Result Specifications

Specification Component Specification

Micro Tests for Potable Water according to SANS241


E.Coli <1

Micro Tests for Potable Water according to SANS241


Faecal Coliforms <1

Micro Tests for Potable Water according to SANS241


Heterotrophic Plate Count (TPC)<Avg
1000

Micro Tests for Potable Water according to SANS241


Total Coliforms <= 10

Senior Lab Technician : ___________________________

Technical Signatory : ___________________________

Assistant Director : ___________________________

This report relates only to sample/s supplied to the SCIENTIFIC SERVICES DIVISION and does not relate to similar samples. This report
may not be reproduced, except in full, without the written approval of the Chief Scientific Officer. Although SCIENTIFIC SERVICES will
endeavour to perform analyses correctly, neither SCIENTIFIC SERVICES not its members shall be liable for loss or damage attributed
directly or indirectly to the inaccuracy of analysis or their interpretation. Results not queried within 10 working days of the issuing of the
report will result in the disposal of the original samples, unless SCIENTIFIC SERVICES are advised to the contrary.

Report Date: 28-January-2022 Page 3 of 3