SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Reinstatement of Portable Fire Protection Systems SAIC-B-2017 15-Nov-17 MECH-


PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME

SAUDI ARAMCO USE ONLY


SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

A General Requirements

Prior to entering service, all new fire extinguishers to be installed have


been delivered to Local Fire Control Unit for inspection (using GI-1781 GI-1781.001,
A1
checklists), commissioning, tagging, & SA numbering. Para 5.12.1

Fire Protection Equipment Layout Drawings are checked against GI-1781.001,


A2
installation locations (numbers marked on all extinguishers). Para 7.6.12

NCRs (damages upon receipt) are resolved or detail final disposition & Sch Q, Att III,
A3
resolution. Punch list items (on receipt) are identified for follow-up Para. 3.24

Dry Chem 12.2 Kg Class BC (SAMS-21-102-840) extinguishers use SAES-B-019 Para


A4
Purple K (potassium bicarbonate) as the extinguishing agent. 4.2

Multi-purpose Dry Chemical Class ABC (SAMS-21-02-775) SAES-B-019 Para


A5
extinguishers use monoammonium phosphate (extinguishing agent). 4.2

Hand-type portable extinguishers in process plant areas are installed SAES-B-019 Para
A6
at 30 m intervals. 4.3.1

Where extinguishers protect individual equipment, they are located at SAES-B-019 Para
A7
least 7.5 m from equipment. 4.3.2

Placement of portable extinguishers in buildings complies with SAES-


B-019 as listed below:
A) Uniform distribution has been provided
B) Easy accessibility has been provided
C) Unobstructed access (from storage areas & equipment) exists
SAES-B-019 Para
A8 D) Located near normal paths of travel
4.3.3
E) Located near entrance and exit doors
F) Located where there is no potential of physical damage
G) Located where readily visible
H) Located on a floor-by-floor basis

Dry chemical extinguishers are located on the building exterior of SAES-B-019 Para
A9
control buildings & electrical substations, near entrances. 4.3.4

Carbon dioxide (CO2) extinguishers are located inside control room SAES-B-019 Para
A10
buildings & electrical substations. 4.3.5

Pressurized water extinguishers are located in areas subject to Class A SAES-B-019 Para
A11
(wood, paper, cardboard) fires. 4.3.6
Hand-type portable extinguishers are mounted in easily accessible
locations at grade or first level operating decks near access stairs. SAES-B-019 Para
A12
Their locations are marked in red to 4.4
attract attention
Extinguishers weighing less than 18 kg are mounted so that tops are SAES-B-019 Para
A13
not more than 1.5 meters above floors or deck levels. 4.5

Saudi Aramco: Company General Use


Extinguishers weighing more than 18 kg are mounted so that tops are SAES-B-019 Para
A14
not more than 1.05 1.0 meters above floors or deck levels 4.5

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Reinstatement of Portable Fire Protection Systems SAIC-B-2017 15-Nov-17 MECH-


PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Two-wheel cart-type dry chemical, 68 kg extinguishers are covered


with manufacturer cover or housed inside a roofed shed.* SAES-B-019 Para
A15
*Shed access door faces opposite of 4.6
hydrocarbon handling equip.

SAES-B-067,
A16 Portable & fixed fire protection systems are safety red.
Para 4.2.1

Mounting backgrounds (fire extinguishers, portable equipment) and SAES-B-067,


A17
shelters for portable fire-fighting equipment are safety red. Para 4.2.1.b

Occupant organizations (Contractors) immediately inform proponent


GI 1781.001 Para
A18 organization & local fire control units anytime fire protection equipment is
5.13.3
activated, used, damaged, or taken from service.

Once installed, maintenance & inspection of all portable extinguishers


SAES-B-019 Para
A19 meets the requirements of GI-1781.001.
4.7
See Specific Checklist Sections 3, 4 & 5 as applicable

B Maintenance & Recharging (NFPA 10 Requirements)


Fire extinguishers are subjected to maintenance at intervals of not more NFPA 10,
B1 than 1 year, at the time of hydrostatic test, or when specifically indicated
by an inspection or electronic notification. Section 7.3.3

Stored-pressure types (loaded stream agent) are disassembled on an


annual basis & subjected to complete maintenance: NFPA 10,
B2 A) Prior to disassembly, fire extinguisher is fully discharged.
B) During discharge, valve & pressure Section 7.3.2.4
gauge operation is checked.
All CO2 hose assemblies receive an annual conductivity test:
A) Hose assemblies
NFPA 10,
found to be nonconductive are replaced.
B3
B) Hose assemblies that pass a conductivity test:
Section 7.4
• A metallic label (1/2 X 3") is affixed to hose by a
heatless process
NFPA 10,
All rechargeable-type fire extinguishers are recharged after any use or as
B4
indicated by inspection or when performing maintenance.
Section 7.7.1
When recharging, manufacturer recommendations are followed.
A) Amount of recharge agent is verified by weighing. NFPA 10,
B5 B) Recharged gross weight is the same as that
marked on the label. C) If no gross weight Section 7.7.1
lable exists, one is affixed to the cylinder.
NFPA 10,
After recharging, a leak test is performed on stored-pressure and self-
B6
expelling types of fire extinguishers.
Section 7.7.1
NFPA 10,
Pump tank water & calcium chloride-based antifreezes for fire
B7
extinguishers are all recharged with new water/chemicals annually.
Section 7.7.1
NFPA 10,
Wetting Agents for stored-pressure extinguishers are replaced annually
B8
with same agents specified on the extinguisher nameplate.
Section 7.7.2
NFPA 10,
Mixing of Dry Chemicals (Multipurpose dry chemicals) is not performed
B9
with alkaline-based dry chemicals.
Section
NFPA 10, 7.7.3
B10 Dry Powders (agents) are covered & replaced if found damp. NFPA 10,
B11 Nonwater extinguisher moisture is removed before recharging Section 7.7.3

Halogenated agent extinguishers are charged with a proper type & Section
NFPA 10, 7.7.3
B12 weight of agent as specified on the extinguisher nameplate
Section 7.7.3

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Reinstatement of Portable Fire Protection Systems SAIC-B-2017 15-Nov-17 MECH-


PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Halogenated agent Re-use & handling is performed as follows:


A) Halogenated Agent Re-use (removal of Halon
1211) is done only with a listed halon closed recovery system
B) Empty Halogenated agent fire
extinguishers are examined internally and are free of contamination or NFPA 10,
B13 corrosion, or both. C)
Halogenated agent retained in system recovery is re-used only if no Section 7.7.3
evidence of extinguisher cylinder contamination was found.
D) Halogenated agents removed from extinguishers
exhibiting internal contamination/corrosion are processed (per
manufacturer)
Carbon Dioxide quality (analysis) is as per NFPA 10:
A) Vapor phase is not
less than 99.5 percent carbon dioxide. NFPA 10,
B14 B) The water content shall be not more than 60 parts per million
(ppm) by weight at −52°F (−47°C) dew point. Section 7.7.3.9
C) Oil content of carbon dioxide does not
exceed 10 ppm by weight

Pressurized Water extinguisher recharging is determined by use of the


proper amount of liquid agent by a method listed below:
NFPA 10,
A) Exact measurement by weight
B15
B) Exact measurement in volume
Section 7.7.3
C) An anti-overfill tube, if provided
D) A fill mark on fire extinguisher shell, if provided

Wet Chemical Agent Re-use is not allowed:


A) Wet chemical extinguisher's partially discharged NFPA 10,
B16 require that all remaining wet chemical be discarded.
B) Discard & replace wet chemical Section 7.7.3
agents (hydrostatic test interval)
Pressure Gauges are used as follows:
A) Replacements have proper indicated charge
NFPA 10,
(service) pressure B) Gauges are
B17
marked for use with the agent in the extinguisher
Section 7.8
C) Gauges are compatible with the extinguisher valve body
material
Pressurize rechargeable stored-pressure-type fire extinguishers only to
the charging pressure specified on extinguisher nameplate.
A) The manufacturer's pressurizing adapter shall
be connected to the valve assembly before the fire extinguisher is
NFPA 10,
pressurized. B) Regulated
B18
pressure sources, set no higher than 25 psi above operating (service)
Section 7.7.4
pressure are used for pressurization.
C) Gauge used to set regulated pressure is calibrated
annually. D) Extinguishers are never left
connected for extended periods.
Only standard industrial-grade nitrogen with a maxi-mum dew point of
NFPA 10,
−60°F (−51°C), in accordance with CGA G-10.1, Commodity Specification
B19
for Nitrogen, shall be used to pressurize stored-pressure dry chemical and
Section 7.7.4
halogenated-type fire extinguishers that use nitrogen as a propellant.
NFPA 10,
Class D fire extinguishers are pressurized with argon and are
B20
repressurized only with expellant gas listed on extinguisher label.
Section 7.7.4
NFPA 10,
A Tag or Label securely affixed to each extinguisher indicates the month
B21
& year of recharging & the service personnel responsible.
Section 7.7.4.8

Verification of Service Collar (for Maintenance or Recharging):


A) Collar installion is tamper-proof & used to identify
NFPA 10,
valve removal. B) Collar includes
B22
month & year serviced (perforation, hand punch)
Section 7.7.4.8
C) Liquefied gas, halogen agent, CO2, & Cartridge/cylinder
operated extinguishers (without valve removal) do not require collars.

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Reinstatement of Portable Fire Protection Systems SAIC-B-2017 15-Nov-17 MECH-


PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

C Specific Inspection Portable hand type extinguishers

Pressurized Water 9.5L (2.5 gallon) Class A (21-104-550):


A) Identified & numbered per
facility/building fire protection layout B) Located at designated
location, accessible & unobstructed site C) Storage area is not
exposed to direct sunlight or corrosive atmospheres or in environments
exceeding 120°F.
D) Extinguisher mounting brackets or shelves are available.
E) Gauge reading is 95-100 psi or indicates full.
GI-1781.001,
C1 F) Gauge and glass is undamaged.
Supplement 6.0
G) Operating instructions are legible and facing outward.
H) Safety pin and seal are intact.
i) No sign of physical damage or corrosion exists.
J) Hose is free from cracks and cuts.

K) Nozzle is clear and not plugged.


L) Hydrotest date from manufacturer is shown on label.
M) Inspection tag exists showing last inspection date.

CO2 4.5 Kg (10 lb) Class BC Extinguisher (SAMS 21-102-223):


A) Identified & numbered per facility/building fire protection layout
B) Located at designated location, accessible & unobstructed site
C) Storage area is not exposed to direct sunlight or
corrosive atmospheres or in environments exceeding 120°F.
D) Extinguisher mounting brackets or shelves are available.
E) Not sign of physical damage or corrosion exists. GI-1781.001,
C2
F) Operating instructions are legible and facing outward. Supplement 7.0
G) Safety pin and seal are intact.
H) Horn is nonmetallic, clear and unplugged.
i) Hydrotest date from manufacturer is shown on label.
J) Weigh cylinder(s) to determine if fully charged.
K) Inspection tag exists showing last inspection date.

Dry Chemical 12.2 Kg Class BC (SAMS-21-102-840) & the Multi-


purpose Dry Chemical Class ABC (21-102-775):
A) Identified & numbered per facility/building fire protection layout
B) Located at designated location and is in an accessible site
C) Storage area is not exposed to direct sunlight or corrosive
atmospheres or in environments exceeding 120°F.
D) Extinguisher mounting brackets or shelves are available.
E) Not sign of physical damage or corrosion exists.
F) Operating instructions are legible and facing outward.
GI-1781.001,
C3 G) Safety pin and seal are intact.
Supplement 8.0
H) CO2 cartridge disc is intact, weigh cartridge to check for leaks.
i) Cap gasket is in good condition. J)
Puncture lever operates freely.
i) Nozzle is clear and unplugged
J) Dry chemical level and type is correct with no caking.
K) Hydrotest date from manufacturel is shown on label.
L) Inspection tag exists showing last inspection date.
Use checklist for both types dry chem extinguishers listed

D Wheeled cart type extinguisher (2 types)

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Reinstatement of Portable Fire Protection Systems SAIC-B-2017 15-Nov-17 MECH-


PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Dry Chem 68 Kg Type BC (SAMS-21-106-650):


A) Identified & numbered per facility/building fire protection layout
B) Located at designated location, accessible & unobstructed site
C) Storage area (no direct sunlight, below 120°F, non-corrosive)
D) Manufacturer weather cover is in good condition.

E) Wheels turn freely & tires are inflated properly in good condition.
F) Tamper seal and safety pin are intact. GI-1781.001,
D1
G) Nitrogen pressure gauge reads full (at least 1600 psi). Supplement 10.0
H) Extinguisher has no obvious damage or corrosion.
i) Rubber hose is coiled properly and in good condition.
J) Nozzle moves freely, is in holder, unplugged & in good condition.
K) Dry chemical level and type is correct with no caking.
L) Cap gasket is in good condition & bursting disc is intact
M) Hydrotest date (label) &
inspection tag is current (dates).

CO2 with dual 23 kg cylinders Type BC (SAMS-21-106-690):


A) Identified & numbered per facility/building fire protection layout
B) Located at designated location, accessible & unobstructed site
C) Storage area is not exposed to direct sunlight or corrosive
atmospheres or in environments exceeding 120°F.
D) Hose is free from cracks & cuts.
E) Hose is coiled properly.
GI-1781.001,
F) Tamper seal and safety pin are intact.
D2 Supplement
G) Wheels rotate freely.
Section 11.0
H) Tires are properly inflated and in good condition
i) Manufacturer's weather cover is in good condition. J)
No obvious corrosion or physical damage exists.
K) Hydrotest date from manufacturel is shown on label.

L) Inspection tag exists showing last inspection date.

Twin agent Extinguishers (Unit Skid or trailer)


E

Inspect the Twin Agent Unit Skid or Trailer Extinguisher:


A) Identified & numbered per facility/building fire protection layout
B) Located at designated location, accessible & unobstructed site
C) Storage area is not exposed to direct sunlight or corrosive
atmospheres or in environments exceeding 120°F.
D) Unit has a Mfg's cover (or will be housed in shed, sunshade).
E) No obvious corrosion or physical damage.
F) Tires are properly inflated and in good condition.
GI-1781.001,
G) Seal and safety pin are intact.
E1 Supplement
H) Hoses are free from cracks, unplugged, & in good condition.
Section 12.0
i) Dry chemical level and type is correct with no caking.
J) Nitrogen pressure gauge reads at least 2000 psi.
K) CO2 cartridge disc is intact.
L) Foam (light water) solution is used.
M) Cap gasket in good condition.
N) Hydrotest date from manufacturer is shown on label.
O) Inspection tag exists showing last inspection date.

REMARKS:
REFERENCE DOCUMENTS:
1- Saudi Aramco GI-1781.001 -- Inspection, Test, and Maintenance of Fire Protection Equipment, 3 January 2009
2- SAES-B-019 -- Portable, Mobile and Special Fixed Firefighting Equipment, 22 July 2012

3 - SAES-B-067 -- Safety Identification and Safety Colors, 11March 2015

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Reinstatement of Portable Fire Protection Systems SAIC-B-2017 15-Nov-17 MECH-


PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

4- Schedule Q JAZAN Project Specific, February 2008


5- NFPA 10 -- Standard for Portable Fire Extinguishers, 2013 Edition
Contractor / Third-Party Saudi Aramco
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED