EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A General Requirements
NCRs (damages upon receipt) are resolved or detail final disposition & Sch Q, Att III,
A3
resolution. Punch list items (on receipt) are identified for follow-up Para. 3.24
Hand-type portable extinguishers in process plant areas are installed SAES-B-019 Para
A6
at 30 m intervals. 4.3.1
Where extinguishers protect individual equipment, they are located at SAES-B-019 Para
A7
least 7.5 m from equipment. 4.3.2
Dry chemical extinguishers are located on the building exterior of SAES-B-019 Para
A9
control buildings & electrical substations, near entrances. 4.3.4
Carbon dioxide (CO2) extinguishers are located inside control room SAES-B-019 Para
A10
buildings & electrical substations. 4.3.5
Pressurized water extinguishers are located in areas subject to Class A SAES-B-019 Para
A11
(wood, paper, cardboard) fires. 4.3.6
Hand-type portable extinguishers are mounted in easily accessible
locations at grade or first level operating decks near access stairs. SAES-B-019 Para
A12
Their locations are marked in red to 4.4
attract attention
Extinguishers weighing less than 18 kg are mounted so that tops are SAES-B-019 Para
A13
not more than 1.5 meters above floors or deck levels. 4.5
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
SAES-B-067,
A16 Portable & fixed fire protection systems are safety red.
Para 4.2.1
Halogenated agent extinguishers are charged with a proper type & Section
NFPA 10, 7.7.3
B12 weight of agent as specified on the extinguisher nameplate
Section 7.7.3
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
E) Wheels turn freely & tires are inflated properly in good condition.
F) Tamper seal and safety pin are intact. GI-1781.001,
D1
G) Nitrogen pressure gauge reads full (at least 1600 psi). Supplement 10.0
H) Extinguisher has no obvious damage or corrosion.
i) Rubber hose is coiled properly and in good condition.
J) Nozzle moves freely, is in holder, unplugged & in good condition.
K) Dry chemical level and type is correct with no caking.
L) Cap gasket is in good condition & bursting disc is intact
M) Hydrotest date (label) &
inspection tag is current (dates).
REMARKS:
REFERENCE DOCUMENTS:
1- Saudi Aramco GI-1781.001 -- Inspection, Test, and Maintenance of Fire Protection Equipment, 3 January 2009
2- SAES-B-019 -- Portable, Mobile and Special Fixed Firefighting Equipment, 22 July 2012