INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE

D0496-04-EN 1/78

Equipment: S3C / S3CT / S3C2T


Type: DOUBLE SIDE-BREAK DISCONNECTOR
Rated voltage: 245 (252) kV
Rated current: 1250 ÷ 3150 A

Notes:

4 B119037 21.12.2009 Zozzolotto De-Matteis

3 111885 31.01.2007 Perissinotto Panighel

2 107600 20.12.2004 Perissinotto Panighel

1 Release 10.06.2004 Studio DS Panighel


Revision Description Date Compiled Approved

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 2/78

CONTENTS

1. SAFETY INSTRUCTIONS ......................................................................................................5


1.1 SPECIAL SAFETY REQUIREMENTS.............................................................................................5
1.2 GENERAL SAFETY REQUIREMENTS ..........................................................................................5
2. DESCRIPTION ......................................................................................................................6
2.1 GENERAL........................................................................................................................................6
3. PACKAGING AND SHIPMENT ...............................................................................................7
3.1 TYPES OF PACKAGES ..................................................................................................................7
3.1.1 Shipping cases.................................................................................................................................7
3.2 SYSTEMATIC SHIPPING UNITS....................................................................................................7
4. RECEIPT AND STORAGE .....................................................................................................7
4.1 RECEIPT .........................................................................................................................................7
4.2 STORAGE .......................................................................................................................................8
4.2.1 Short-time storage (less than three months) ...................................................................................8
4.2.2 Long-time storage (longer than three months) ................................................................................8
5. UNPACKING AND LIFTING ...................................................................................................8
6. INSTALLATION AND ADJUSTMENT ....................................................................................10
6.1 CONDITIONS AND PRELIMINARY OPERATIONS BEFORE INSTALLATION...........................10
6.2 INSTALLATION OF THE S3C DISCONNECTOR.........................................................................11
6.2.1 Fixed bases (Fig. 1, 5, 5A).............................................................................................................11
6.2.2 Installation of the insulators (Fig. 1, 2D, 5) ....................................................................................11
6.2.3 Fixed contacts (Fig. 1,3) ................................................................................................................11
6.2.4 Mobile live parts (Fig. 1, 2, 2A, 2B, 2C, 2D) ..................................................................................12
6.2.5 Vertical drive shaft and drive of the disconnector (Fig. 7, 7A).......................................................12
6.2.6 Installation of the horizontal transmission rods of the disconnector (Fig. 5) .................................13
6.2.7 Arcing-contact device (IEC 62271-102 Att. B) (Fig. 3A) ................................................................14
6.3 INSTALLATION OF THE S3CT DISCONNECTOR ......................................................................14
6.3.1 Fixed bases (Fig. 1A, 1B, 5B, 5C, 5D, 5E) ....................................................................................14
6.3.2 Installation of the insulators (Fig. 1A 1B, 2D, 5B, 5D) ...................................................................14
6.3.3 Main fixed contacts with fixed contacts for the earthing switches (Fig. 1A, 1B, 3, 8, 9)................15
6.3.4 Mobile live parts (Fig. 1, 2, 2A, 2B, 2C, 2D) ..................................................................................15
6.3.5 Vertical drive shaft and drive of the disconnector (Fig. 7 and 7A).................................................16
6.3.6 Installation of the horizontal transmission rods of the disconnector (Fig. 5B, 5D) ........................17
6.3.7 Installation of the horizontal transmission rods of the earthing switches (Fig. 5B, 5C, 5D, 5E) ....17
6.3.8 Earthing switches (Fig. 5B, 5C, 5D, 5E, 8) ....................................................................................18
6.3.9 Installation of the balancing springs of the earthing switches (Fig. 5H) ........................................19
6.3.10 Vertical drive shaft and drive of the earthing switches (Fig. 7 and 7A) .........................................20
6.3.11 Mechanical interlocking device (Fig. 5B, 5C, 5D, 5E) ...................................................................21
6.3.12 Arcing-contact device (IEC 62271-102 Att. B) (Fig. 3A) ................................................................21
6.4 INSTALLATION OF THE S3C2T DISCONNECTOR ....................................................................22
6.4.1 Fixed bases (Fig. 1C, 5F, 5G) .......................................................................................................22
6.4.2 Installation of the insulators (Fig. 1C, 2D, 5F) ...............................................................................22
6.4.3 Main fixed contacts with fixed contacts for the earthing switches (Fig. 1C, 3, 8, 9) ......................22
6.3.4 Mobile live parts (Fig. 1, 2, 2A, 2B, 2C, 2D) ..................................................................................23
6.4.5 Vertical drive shaft and drive of the disconnector (Fig. 7 and 7A).................................................23
6.4.6 Installation of the horizontal transmission rods of the disconnector (Fig. 5F) ...............................24
6.4.7 Installation of the horizontal transmission rods of the earthing switches (Fig. 5F, 5G) .................25
6.4.8 Earthing switches (Fig. 5F, 5G, 8) .................................................................................................25
6.4.9 Installation of the balancing springs of the earthing switches (Fig. 5H) ........................................26
6.4.10 Vertical drive shaft and drive of the earthing switches (Fig. 7 and 7A) .........................................27
6.4.11 Mechanical interlocking device (Fig. 5F, 5G) ................................................................................28
6.4.12 Arcing-contact device (IEC 62271-102 Att. B) (Fig. 3A) ................................................................28
6.5 ADJUSTMENT OF THE S3C / S3CT / S3C2T DISCONNECTORS .............................................29
6.5.1 Adjustment of the live parts of the disconnector (Fig. 2, 2A, 2B, 2C, 3)........................................29
6.5.2 Adjustment of the earthing switches (Fig. 8 and 9) .......................................................................29

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 3/78
6.5.2 Horizontal transmission rods of the earthing switches (Fig. 5B, 5C, 5D, 5E, 5F, 5G)...................30
7. CONNECTIONS, FINAL CHECKS AND FINE-TUNING .........................................................31
7.1 CONNECTIONS ............................................................................................................................31
7.2 FINAL CHECKS AND FINE-TUNING............................................................................................31
8. MAINTENANCE PLAN .........................................................................................................32
TABLE NTC-1955/E ..........................................................................................................................................33
9. DISASSEMBLING THE APPARATUS AND REPLACEMENT OF MAIN PARTS ......................34
9.1 DISASSEMBLING THE APPARATUS ..........................................................................................36
9.1.1 Disconnection ................................................................................................................................36
9.1.2 Disassembly...................................................................................................................................36
9.2 DISASSEMBLING THE EQUIPMENT AND REPLACEMENT OF MAIN PARTS.........................37
9.2.1 Mobile contacts of the disconnector (Fig. 2, 2A, 2B, 2C) ..............................................................37
9.2.2 Fixed contacts (Fig. 3) ...................................................................................................................37
9.2.3 Drive (operating mechanism) (Fig. 7) ............................................................................................37
9.2.4 Ball joints of the adjustable thrust linkages....................................................................................38
10. LIST OF TOOLS ..................................................................................................................38
11. SPARE PARTS ...................................................................................................................39

ATTACHMENTS

ATTACHMENT "A": SPECIFICATIONS FOR THE S3C / S3CT / S3C2T DISCONNECTORS........................76


ATTACHMENT "B": TIGHTENING TORQUES FOR SCREWS & BOLTS ........ ¡Error! Marcador no definido.
ATTACHMENT "C": RECORDING FORM FOR COMMISSIONING OF SWITCHGEAR...¡Error! Marcador no
definido.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 4/78

LIST OF FIGURES

FIG. 1: INSTALLATION DIAGRAM FOR THE S3C DISCONNECTOR ...............................................40


FIG. 1A: INSTALLATION DIAGRAM FOR THE S3CT DISCONNECTOR, WITH EARTHING
SWITCH ON THE RIGHT .....................................................................................................42
FIG. 1B: INSTALLATION DIAGRAM FOR THE S3CT DISCONNECTOR WITH EARTHING
SWITCH ON THE LEFT .......................................................................................................44
FIG. 1C: INSTALLATION DIAGRAM FOR THE S3C2T DISCONNECTOR............................................46
FIG. 2: MOBILE LIVE PART 1250 A.................................................................................................48
FIG. 2A: MOBILE LIVE PART 1600 - 2000 A ......................................................................................49
FIG. 2B: MOBILE LIVE PART 2500 A.................................................................................................50
FIG. 2C: MOBILE LIVE PART 3150 A.................................................................................................51
FIG. 2D: INSTALLATION OF THE BASES, INSULATORS AND LIVE PARTS ......................................52
FIG. 3: FIXED CONTACT ................................................................................................................53
FIG. 3A: ARCING-CONTACT DEVICE ...............................................................................................55
FIG. 5: LOWER PART ASSEMBLY OF THE S3C DISCONNECTOR .................................................56
FIG. 5A: LOWER PART OF THE S3C DISCONNECTOR - SECTIONS - ..............................................57
FIG. 5B: S3CT DISCONNECTOR WITH EARTHING SWITCH ON THE RIGHT: LOWER
PART ASSEMBLY ...............................................................................................................59
FIG. 5C: S3CT DISCONNECTOR WITH EARTHING SWITCH ON THE RIGHT: LOWER
PART ASSEMBLY - SECTIONS - .........................................................................................60
FIG. 5D: S3CT DISCONNECTOR WITH EARTHING SWITCH ON THE LEFT: LOWER
PART ASSEMBLY ...............................................................................................................62
FIG. 5E: S3CT DISCONNECTOR WITH EARTHING SWITCH ON THE RIGHT: LOWER
PART ASSEMBLY - SECTIONS - .........................................................................................63
FIG. 5F: LOWER PART ASSEMBLY OF THE S3C2T DISCONNECTOR .............................................65
FIG. 5G: LOWER PART OF THE S3C2T DISCONNECTOR - SECTIONS - ..........................................66
FIG.5H: BALANCING SPRING OF THE EARTHING SWITCH ............................................................68
FIG. 7: DRIVE AND VERTICAL DRIVE SHAFT ................................................................................69
FIG. 7A: DRIVE AND VERTICAL DRIVE SHAFT ................................................................................71
FIG. 8: EARTHING-SWITCH UNIT ..................................................................................................72
FIG. 9: FIXED CONTACT FOR THE EARTHING SWITCH ................................................................74
FIG. 10: LUBRICATION AND GREASING ..........................................................................................75

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 5/78

1. SAFETY INSTRUCTIONS
1.1 SPECIAL SAFETY REQUIREMENTS
Special safety requirements are incorporated in this instruction manual and are
identified as follows:

Immediate danger, possible consequences:


! Danger
Death or serious injury.

Dangerous situation, possible consequences:


! Caution Slight or minor injury,
The product or something in its vicinity may be damaged.

Important Useful information.

1.2 GENERAL SAFETY REQUIREMENTS

The operator must make sure:


- That the motor drive [operating mechanism] and the
linked equipment are installed, commissioned and
maintained only by qualified personnel or under the
! Danger direction of a supervisor qualified by AREVA and
- That during installation, commissioning and maintenance
the safety rules specified by the customer and all
applicable regulations concerning accident prevention are
observed.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 6/78

2. DESCRIPTION
2.1 GENERAL
The disconnectors AREVA of the series S3C (without earthing switches), S3CT (with
one earthing switch) and S3C2T (with two earthing switches) are of type with double
side-break with three insulators each pole and the central insulator is a rotary one.
The live part is made of a mobile part, the rotary arm, which holds on its two ends the
mobile male contacts, and of two fixed female contacts installed on the lateral fixed
insulators. The mobile part of the arm with the two mobile contacts is installed on the
central rotary insulator.
The fixed contacts are made of pairs of copper blades, each pressed by a stainless
steel spring, that ensure adequate and constant pressure on the contact-making
points.
The mobile contacts are made of copper plates fastened to the ends of the mobile
arms. The arms are made of very strong and highly conductive aluminum tubes.
With an 85° rotation of the central column, which holds the mobile arm, the contacts
close with a sliding movement. This contact-making is self-cleaning and self-
tightening and ensures, therefore, the best behavior in the case of stress due to
short-time current.
The number of the copper blades of the fixed contact, the size of the mobile contact
and of the tubes of the mobile arm depends on the electrical and mechanical features
of the equipment.
The copper contacts, both fixed and mobile ones, are silver-plated in the area where
current flows.
As far as the flow of current is concerned, there are only two gaps in the equipment:
in the disconnection contacts.
The line terminals are vertical pads located ad the ends of the two fixed female
contacts.
The lower support bases are in hot-galvanized steel, resistant to the heaviest stress
(stress on line terminals, stress due to short-time currents, etc.).
All components through which current flows have been standardized and
tested with short-circuit current.
The equipment is constructed in compliance with the following standards:
 Italy CEI EN 62271-102;
 US ANSI C37 from 30 to 37 NEMA SG 06;
 UK BS EN 62271-102;
 Europe IEC 62271-102.
The following text may refer to several types of equipment and, for better
understanding, the examination of the figures of this manual should be always
combined with the careful study of the installation drawing DIN-…, which concerns
your specific order.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 7/78
These instructions concern the disconnectors with rated voltage of 245 (252) kV.

3. PACKAGING AND SHIPMENT


All the items of the equipment are shipped in cases (crates), which must be handled
with care in accordance with the standard symbols on the sides of the containers.

3.1 TYPES OF PACKAGES


Shipment packaging is designed to fully protect the shipping units against
mechanical damage and against weather during transportation, unloading and
handling on site. It ensures that the product is not damaged and that all quality
features, that are guaranteed and tested in all stages of production, remain
unaltered.

3.1.1 Shipping cases


The shipping cases are strong, plywood-covered wooden crates, connected on the
sides and reinforced internally with wooden boards. Special-shape wood-pieces are
fastened to the bottom of the crates, and if needed to the sides too, in order to hold
the content fast; if needed the shaped pieces are lined with spongy plastic to damp
shocks to the content.
If needed, the content is wrapped in plastic film or contained in special boxes placed
on the bottom of the crate.
In order to ensure adequate ventilation, the shipping cases are equipped with
weatherproof openings.

3.2 SYSTEMATIC SHIPPING UNITS


The parts that make up the disconnectors are divided in shipping units with the
intention to reduce as much as possible the time required for installation on site,
while at the same time keeping simple the handling of the shipping units.

4. RECEIPT AND STORAGE


4.1 RECEIPT
As soon as you receive the crates, inspect the content of each package and make
sure that there is no damage and that all the items written in the packing list are
there.
Damaged items or discrepancies between content and packing list must be reported
to AREVA immediately.
If after the inspection the cases should be relocated or stored for a long time, restore
them to the original conditions.
When handling or unloading the cases, take care not to damage the equipment.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 8/78
4.2 STORAGE

4.2.1 Short-time storage (less than three months)


Place the packages in a dry and sheltered location, or if in the open-air, make sure
the area is drained well.
In the case of open-air storage, the place should be dry and ventilated and the crates
should be raised at least 10 cm from the ground with wooden beams.
If the storage is expected to last no longer than three months, the anti-condensation
heaters contained in the drives need not be energized.

4.2.2 Long-time storage (longer than three months)


In this case:
• If the equipment is stored indoors, and the warehouse is dry, the drives shall be
inspected every six months to make sure that no oxidation occurs due to
moisture inside the drives;
• If the equipment is stored outdoors or in a moist (damp) warehouse, follow the
recommendations of paragraph 4.2.1 and also connect the anti-condensation
heaters of the drive to a power supply and keep them energized.

5. UNPACKING AND LIFTING


Unpack the materials with care in order to avoid loosing or damaging any item.
Handle the complete units. Porcelain insulators should be handled with special care.
Open the shipping cases on site just before installation, in a position where the
hoisting equipment may hook the materials with ease.
Sling the material as shown in figure A and use an apparatus adequate to lift the pole
in a balanced way.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 9/78
FIG. A: LIFTING THE UNITS OF THE DISCONNECTOR

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 10/78

6. INSTALLATION AND ADJUSTMENT


6.1 CONDITIONS AND PRELIMINARY OPERATIONS BEFORE INSTALLATION
a) To install correctly the disconnectors, the connection dimensions of building
works and steel works must comply with the specific installation drawing DIN-…
of the disconnector you are going to install.
b) If needed, consult the specific instructions manuals of the drive [operating
mechanism].
c) Screws, bolts and nuts must be tightened with a torque wrench with the torque
values indicated in the Attachment "B".
d) Prepare and treat the permanent contact surfaces of live parts, through which
current will flow, (e.g. the contact surface between the terminal connection pad
or shaft and the clamp of the line conductor) as follows:
• Wipe off any trace of grease from the contact surfaces with
trichloroethylene or other non-abrasive solvent. If the surfaces are
oxidized, clean them up with a steel brush or fine emery paper;
• Cover immediately with antioxidant compound;
• Connect the surfaces as soon as possible.

e) Install the units in the following sequence:


• lower bases;
• insulators;
• fixed contacts;
• mobile arms;
• vertical drive shaft and drive of the disconnector;
• horizontal transmission rods of the disconnector.
If the earthing switches are to be installed too (disconnectors of types S3CT
and S3C2T), proceed with the following parts:
• horizontal transmission rods of the earthing switches;
• earthing switches;
• balancing springs of the earthing switches (only on driven poles);
• vertical drive shafts and drives of the earthing switches.

In order to protect them, the areas marked with  (Fig. 10) are
Important lubricated with neutral Vaseline before shipping. Before carrying
out the installation, remove the Vaseline with a dry cloth, then
apply the grease indicated in figure 10 with a brush (the quantity
required for the first greasing is included in the supply).

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 11/78

6.2 INSTALLATION OF THE S3C DISCONNECTOR

6.2.1 Fixed bases (Fig. 1, 5, 5A)


Lift, as shown in figure A, the fixed bases (5.1, 5.2 Fig. 5) and, after checking that
their positions are correct, in agreement with the specific installation drawing DIN-…,
lay them down onto the support structure, with the fastening holes aligned.
Fasten them temporarily.
Remove the lifting apparatus.
With the spirit level, check that all the bases, especially the rotary discs (5.7, 5.8 Fig.
5), which support the rotary insulators (1.2 Fig. 1), are horizontal in the two
perpendicular directions. If needed shim with the C-washers on the bolts, between
the support structure and the brackets of the bases, until the bases are adequately
level.
Before fastening them finally to the structure, check that:
• The bases are aligned between themselves and with the support structure;
• The bases are horizontal;
• During final fastening no deformation has taken place that might have altered
the adjustments already carried out. If needed repeat the operations above.

6.2.2 Installation of the insulators (Fig. 1, 2D, 5)


Lift the insulators as shown in figure A and fasten the fixed insulators (1.1 Fig. 1) to
the lateral supports (5.5 Fig. 5) of the fixed bases (5.1, 5.2 Fig. 5) with the screws,
including spring washers; then fasten the rotary insulators (1.2 Fig. 1) to the central
rotary discs (5.7, 5.8 Fig. 5), as shown in figure 2D.
With the spirit level, laid on the upper ring, check that the ring is level in the two
perpendicular directions as shown in figure 2D.
Check also that during the rotation the rotary insulator (1.2 Fig. 1) turns around its
axis without describing a cone (Fig. 2D). If needed insert the C-washers (Fig. 2D)
between the ring and the rotary disc, until the system reaches the required
conditions. When you have achieved the required conditions, tighten the fastening
bolts. Take into account that any C-washers should be inserted as shown in Figure
2D, so that slanted supporting surfaces are created for the bolts, in order to avoid
stress to the rings of the insulators.
Finally check that the distances between the centers of the insulators are as
indicated in the installation drawing DIN-…

6.2.3 Fixed contacts (Fig. 1,3)

See the layout drawing (Fig. 1) for the correct positions of the
Important
fixed contacts (3.0 Fig. 3).

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 12/78
Fasten the fixed contacts (3.0 Fig. 3) to the external insulators with the screws (3.4
Fig. 3), including plain and spring washers, and - before tightening the bolts - make
sure that:
• The fixed contacts are aligned and perpendicular to the axes of the supports
(5.5 Fig. 5);
• The contact blades (3.2 Fig. 3) are horizontal. If needed insert the special C-
washers between the upper flanges of the external insulators (1.1 Fig. 1) and
the fixed contacts (3.0 Fig. 3).

6.2.4 Mobile live parts (Fig. 1, 2, 2A, 2B, 2C, 2D)


The figures 2, 2A, 2B and 2C show the live parts for rated
currents of 1250, 1600-2000, 2500 and 3150 A respectively. The
! Caution
installation procedure described hereafter can be applied to all
kinds of live parts.
Set the rotary discs (5.7, 5.8 Fig. 5) to the OPEN positions.
Fasten the live part (2.0 Fig. 2, 2A, 2B, 2C) to the central rotary insulator (1.2 Fig. 1)
with the screws, including spring washers.
Turn the base by hand, to check that - on each side of the arm - the mobile contacts
(2.3 Fig. 2, 2.12 Fig. 2A, 2.22 Fig. 2B and 2.32 Fig. 2C) are centered when they
couple with the respective fixed contacts (3.0 Fig. 3).
If the mobile contact is lower than the fixed contacts, insert the special C-washers
between the upper flange of the rotary insulator (1.2 Fig. 1) and the support of the
mobile arm (2.2 Fig. 2, 2.11 Fig. 2A, 2.21 Fig. 2B and 2.31 Fig. 2C). On the contrary,
when the fixed contacts are lower than the mobile contacts, the C-washers should be
inserted between the upper flanges of the lateral insulators (1.1 Fig. 1) and the fixed
contacts (3.0 Fig. 3).
Turn the mobile arm (2.1 Fig. 2, 2.10 Fig. 2A, 2.20 Fig. 2B and 2.30 Fig. 2C) to the
open position and check that its axis is at an angle of around 85° with the axis of the
base.

6.2.5 Vertical drive shaft and drive of the disconnector (Fig. 7, 7A)

Before carrying out the installation, check that the serial number
Important of the drive is the same as the serial number of the
disconnector.

Concerning the lifting of the drive, see the instruction


manual on the specific installation and maintenance
! Danger procedures for the device.

Lift the drive; take the back of the device toward the support structure and take care
that the holes (7.11 Fig. 7) on the drive match those on the structure. Fasten
temporarily two bolts diagonally; do not tighten them.
Remove the lifting apparatus.
AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 13/78
With reference to Fig. 7A, measure the distance "L" between the center of the hole of
the pin (7.13 Fig. 7A), on the driving shaft of the lower base (5.1 Fig. 7A), and the
upper surface of the support (7.15 Fig. 7A) of the clamp of the drive; subtract 15 mm
from this distance. Such distance is called "La":
La=L-15 (with "L" and "La" in mm)
Measure the vertical drive shaft (7.3 Fig. 7) supplied with the disconnector and, if it is
longer than "La", cut it to the exact size and then deburr the edges and reinstate the
surface protection by cold galvanizing.
Make sure that the drive is in the OPEN position.
In order to ensure the best grip, before installing the drive shaft
of the switchgear, polish with abrasive paper the lower part of
Important the shaft for a length of about 150 mm.
Check also that the internal surface of the clamp is free from
any trace of grease or other impurities.
Remove the lower fastening bolt installed previously and, by pivoting on the other
bolt still installed, tilt the drive to permit the installation of the vertical drive shaft (7.3
Fig. 7).
Insert the top of the vertical drive shaft (7.3 Fig. 7) into the hub of the driving base
(5.1 Fig. 5) and lock it in the correct position with the lock pin and cotter pins (7.13
Fig. 7).
While keeping the drive at a slant, insert the bottom of the vertical drive shaft (7.3
Fig. 7) into the clamp (7.12 Fig. 7).
Bring back the drive to the correct position and fasten the others fastening bolts to
the support structure.
If needed, loosen the bolts that fasten the drive to the structure, raise or lower the
drive and then tighten the bolts again, in order to get - when the adjustment is
complete - the exact dimensions shown in the specific installation drawing DIN-….
Check also that the drive is horizontal in two perpendicular directions, if needed shim
the fastening devices.
Fasten temporarily the clamp (7.12 Fig. 7), but do not tighten the screws (7.10 Fig.
7).
Check that the drive shaft (7.3 Fig. 7) is vertical in the two perpendicular directions.
Now you can tighten the clamp (7.12 Fig. 7) with the screws (7.10 Fig. 7) to lock the
shaft (7.3 Fig. 7), with a torque of around 80 Nm. In order to assist in this operation,
apply some normal grease on the bolts.

6.2.6 Installation of the horizontal transmission rods of the disconnector (Fig. 5)


With reference to figure 5, measure the distance "X" between the bases: add 200
mm to this distance. This distance is indicated by "Xb":
Xb = X + 200 (with "X" and "Xb" in mm)
Measure the horizontal transmission rods (5.3 Fig. 5) supplied with the disconnector
and, if they are longer than "Xb", cut them to size, then deburr the edges and
reinstate the surface protection by cold galvanizing.
AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 14/78
Loosen the U-bolts (5.9 Fig. 5) already installed on the rotary discs (5.7, 5.8 Fig. 5).
Insert the rods (5.3 Fig. 5) into the loose clamps (5.9 Fig. 5), make sure that the ends
of the rods protrude for about 50 mm.
Tighten the clamps.

6.2.7 Arcing-contact device (IEC 62271-102 Att. B) (Fig. 3A)


In figure 3A, you can see a special device called "arcing-contact device" which is
supplied on request.
This device is already installed and adjusted in our workshop, so it does not require
additional assembly.
You should only check with a manual closing operation of the mobile arm that the
male and female arcing contacts (3.31, 3.22 Fig. 3A) get in touch earlier than the
male and female contacts of the disconnector.

6.3 INSTALLATION OF THE S3CT DISCONNECTOR

6.3.1 Fixed bases (Fig. 1A, 1B, 5B, 5C, 5D, 5E)
Lift, as shown in figure A, the fixed bases (5.1, 5.2 Fig. 5B, 5D) and, after checking
that their positions are correct, in agreement with the specific installation drawing
DIN-…, lay them down onto the support structure, with the fastening holes aligned.
Fasten them temporarily.
Remove the lifting apparatus.
With the spirit level, check that all the bases, especially the rotary discs (5.7, 5.8 Fig.
5B, 5D), which support the rotary insulators (1.2 Fig. 1A, 1B), are horizontal in the
two perpendicular directions. If needed shim with the C-washers on the bolts,
between the support structure and the brackets of the bases, until the bases are
adequately level.
Before fastening them finally to the structure, check that:
• The bases are aligned between themselves and with the support structure;
• The bases are horizontal;
• During final fastening no deformation has taken place that might have altered
the adjustments already carried out. If needed repeat the operations above.

6.3.2 Installation of the insulators (Fig. 1A 1B, 2D, 5B, 5D)


Lift the insulators as shown in figure A and fasten the fixed insulators (1.1 Fig. 1A,
1B) to the lateral supports (5.5 Fig. 5B, 5D) of the fixed bases (5.1, 5.2 Fig. 5B, 5D)
with the screws, including spring washers; then fasten the rotary insulators (1.2 Fig.
1A, 1B) to the central rotary discs (5.7, 5.8 Fig. 5B, 5D), as shown in figure 2D.
With the spirit level, laid on the upper ring, check that the ring is level in the two
perpendicular directions as shown in figure 2D.
Check also that during the rotation the rotary insulator (1.2 Fig. 1A, 1B) turns around
its axis without describing a cone (Fig. 2D). If needed insert the C-washers (Fig. 2D)
between the ring and the rotary disc, until the system reaches the required

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 15/78
conditions. When you have achieved the required conditions, tighten the fastening
bolts. Take into account that any C-washers should be inserted as shown in Figure
2D, so that slanted supporting surfaces are created for the bolts, in order to avoid
stress to the rings of the insulators.
Finally check that the distances between the centers of the insulators are as
indicated in the installation drawing DIN-…

6.3.3 Main fixed contacts with fixed contacts for the earthing switches
(Fig. 1A, 1B, 3, 8, 9)
See the layout drawings (Fig. 1A, 1B) for the correct positioning
Important of the main fixed contacts (3.0 Fig. 3) and of the fixed contacts
(9.0 Fig. 9) for the earthing switches (8.0 Fig. 8).

Fasten the fixed contacts (3.0 Fig. 3) to the external insulators (1.1 Fig. 1A, 1B) with
the special screws, including plain and spring washers.
On the side where the fixed contact (9.0 Fig. 9) of the earthing switches (8.0 Fig. 8) is
to be installed, install the support plate (9.2 Fig. 9) together with the main fixed
contact (3.0 Fig. 9), use the same two screws (3.4 Fig. 9) as shown in figure 9.
Complete the installation of the fixed contact of the earthing switch by installing the
contact holding clamp (9.1 Fig. 9), with the fixed contact (9.3 Fig. 9) already
assembled, with the special bolts (9.4 Fig.9).
Before tightening the bolts make sure that:
• The fixed contacts (3.0 Fig. 3) are aligned and perpendicular to the centerlines
of the supports (5.5 Fig. 5B, 5D);
• The contact blades (3.2 Fig. 3) are horizontal. If needed, insert the special C-
washers between the upper flanges of the external insulators (1.1 Fig. 1A, 1B)
and the fixed contacts (3.0 Fig. 3).

6.3.4 Mobile live parts (Fig. 1, 2, 2A, 2B, 2C, 2D)


The figures 2, 2A, 2B and 2C show the live parts for rated
currents of 1250, 1600-2000, 2500 and 3150 A respectively.
Important
The installation procedure described hereafter can be applied
to all kinds of live parts.
Set the rotary discs (5.7, 5.8 Fig. 5B, 5D) to the OPEN positions.
Fasten the live part (2.0 Fig. 2, 2A, 2B, 2C) to the central rotary insulator (1.2 Fig. 1A,
1B) with the screws, including spring washers.
Turn the base by hand, to check that - on each side of the arm - the mobile contacts
(2.3 Fig. 2, 2.12 Fig. 2A, 2.22 Fig. 2B and 2.32 Fig. 2C) are centered when they
couple with the respective fixed contacts (3.0 Fig. 3).
If the mobile contact is lower than the fixed contacts, insert the special C-washers
between the upper flange of the rotary insulator (1.2 Fig. 1A, 1B) and the support of
the mobile arm (2.2 Fig. 2, 2.11 Fig. 2A, 2.21 Fig. 2B and 2.31 Fig. 2C). On the
contrary, when the fixed contacts are lower than the mobile contacts, the C-washers

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 16/78
should be inserted between the upper flanges of the lateral insulators (1.1 Fig. 1A,
1B) and the fixed contacts (3.0 Fig. 3).
Turn the mobile arm (2.1 Fig. 2, 2.10 Fig. 2A, 2.20 Fig. 2B and 2.30 Fig. 2C) to the
open position and check that its axis is at an angle of around 85° with the axis of the
base.

6.3.5 Vertical drive shaft and drive of the disconnector (Fig. 7 and 7A)

Before carrying out the installation, check that the serial number
Important of the drive is the same as the serial number of the
disconnector.

Concerning the lifting of the drive, see the instruction


manual on the specific installation and maintenance
! Danger procedures for the device.

Lift the drive; take the back of the device toward the support structure and take care
that the holes (7.11 Fig. 7) on the drive match those on the structure. Fasten
temporarily two bolts diagonally; do not tighten them.
Remove the lifting apparatus.
With reference to Fig. 7A, measure the distance "L" between the center of the hole of
the pin (7.13 Fig. 7A), on the driving shaft of the lower base (5.1 Fig. 7A), and the
upper surface of the support (7.15 Fig. 7A) of the clamp of the drive; subtract 15 mm
from this distance. Such distance is called "La":
La=L-15 (with "L" and "La" in mm)
Measure the vertical drive shaft (7.3 Fig. 7) supplied with the disconnector and, if it is
longer than "La", cut it to the exact size and then deburr the edges and reinstate the
surface protection by cold galvanizing.
Make sure that the drive is in the OPEN position.
In order to ensure the best grip, before installing the drive shaft
of the switchgear, polish with abrasive paper the lower part of
Important the shaft for a length of about 150 mm.
Check also that the internal surface of the clamp is free from any
trace of grease or other impurities.
Remove the lower fastening bolt installed previously and, by pivoting on the other
bolt still installed, tilt the drive to permit the installation of the vertical drive shaft (7.3
Fig. 7).
Insert the top of the vertical drive shaft (7.3 Fig. 7) into the hub of the driving base
(5.1 Fig. 5B, 5D) and lock it in the correct position with the lock pin and cotter pins
(7.13 Fig. 7).
While keeping the drive at a slant, insert the bottom of the vertical drive shaft (7.3
Fig. 7) into the clamp (7.12 Fig. 7).

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 17/78
Bring back the drive to the correct position and fasten the others fastening bolts to
the support structure.
If needed, loosen the bolts that fasten the drive to the structure, raise or lower the
drive and then tighten the bolts again, in order to get - when the adjustment is
complete - the exact dimensions shown in the specific installation drawing DIN-….
Check also that the drive is horizontal in two perpendicular directions, if needed shim
the fastening devices.
Fasten temporarily the clamp (7.12 Fig. 7), but do not tighten the screws (7.10 Fig.
7).
Check that the drive shaft (7.3 Fig. 7) is vertical in the two perpendicular directions.
Now you can tighten the clamp (7.12 Fig. 7) with the screws (7.10 Fig. 7) to lock the
shaft (7.3 Fig. 7), with a torque of around 80 Nm. In order to assist in this operation,
apply some normal grease on the bolts.

6.3.6 Installation of the horizontal transmission rods of the disconnector


(Fig. 5B, 5D)
With reference to figures 5B and 5D, measure the distance "X" between the bases:
add 200 mm to this distance. This distance is indicated by "Xb":
Xb = X + 200 (with "X" and "Xb" in mm)
Measure the horizontal transmission rods (5.3 Fig. 5B, 5D) supplied with the
disconnector and, if they are longer than "Xb", cut them to size, then deburr the edges
and reinstate the surface protection by cold galvanizing.
Loosen the U-bolts (5.9 Fig. 5B, 5D) already installed on the rotary discs (5.7 and 5.8
Fig. 5B, 5D).
Insert the rods (5.3 Fig. 5B, 5D) into the loose clamps (5.9 Fig. 5B, 5D), make sure
that the ends of the rods protrude for about 50 mm.
Tighten the clamps.

6.3.7 Installation of the horizontal transmission rods of the earthing switches


(Fig. 5B, 5C, 5D, 5E)
The horizontal transmission rod of the earthing switches (5.4 Fig. 5B, 5D) is sent in
two sections for shipping reasons.
Locate the longer section, insert it into the supports (5.20 Fig. 5B, 5C, 5D, 5E) of one
of the lateral driven bases (5.2 Fig. 5B, 5D) and of the central driving base and lock it
in position with the lock rings (5.22 Fig. 5B, 5D).
Insert the other section of the horizontal transmission rod (5.4 Fig. 5B, 5D) of the
earthing switch into the supports (5.20 Fig. 5B, 5C, 5D, 5E) of the other driven base
and lock it in position with the lock rings (5.22 Fig. 5B, 5D).

During the insertion of the horizontal transmission rods of the


Important earthing switches, the balancing springs (5.31 Fig. 5B, 5D) must
be installed too in the driven poles only (see section 6.3.9).

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 18/78
Connect the two sections of the horizontal transmission rod (5.4 Fig. 5B, 5D) of the
earthing switch by means of the joining clamp (5.23 Fig. 5B, 5D) using the U-bolts
(5.24 Fig. 5B, 5D) and the nuts (5.25 Fig. 5B, 5D) to fasten it.
Cut both end of the rod (5.4 Fig. 5B, 5D) to size, then deburr the edges and reinstate
the surface protection by cold galvanizing.
Install the adjustable control lever (5.14 Fig. 5B, 5C, 5D, 5E) of the earthing switch
with the U-bolts (5.15 Fig. 5C, 5E) and fastening nuts (5.16 Fig. 5B, 5C, 5D, 5E), use
the angles indicated in the figures 5C and 5E and the distance from the centerline of
the lower base indicated in the figures 5B and 5D.
Take care that the adjustable control levers (5.14 Fig. 5B, 5C,
5D, 5E) are positioned correctly, since their rotation in the wrong
Important
direction may break the ball joints of the thrust linkages (5.13
Fig. 5B, 5C, 5D, 5E).

6.3.8 Earthing switches (Fig. 5B, 5C, 5D, 5E, 8)


With reference to Fig. 5B, 5C, 5D, 5E and 8, set the control lever (5.12 Fig. 5B, 5D)
of the earthing switch to the OPEN position; the adjustable control lever (5.14 Fig.
5C, 5E) of the earthing switch will then make an angle of about 30° in relation to the
horizontal axis.
While keeping the control lever (5.12 Fig. 5B, 5D) in the position above, install the
earthing switches (8.0 Fig. 8) while keeping them in almost horizontal positions
(OPEN) and resting on the stop bolts (5.18 Fig. 8).
The mobile arm (8.1 Fig. 8) of each earthing switch is fastened to the horizontal
transmission rod (5.4 Fig. 5B, 5D) by means of the U-bolts (8.7 Fig. 8) and nuts (8.8
Fig. 8).
Before tightening the fastening nuts (8.8 Fig. 8), the driving and
driven earthing switches must be adjusted and synchronized, in
Important
accordance with the procedure described in the sections 6.5.2
and 6.5.3.
Connect the stranded conductors (8.9 Fig. 8) to the lower bases (5.1, 5.2 Fig. 5C,
5E) with the bolts (5.21 Fig. 5C, 5E).
Please see the photo below for the correct connection of the earthing stranded
conductors.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 19/78

Connection of the earthing stranded conductors to the fixed base of the earthing switch

6.3.9 Installation of the balancing springs of the earthing switches (Fig. 5H)

The balancing springs (5.31 Fig. 5B, 5C, 5D, 5E, 5H) must be
! Caution
installed only on the driven poles of the earthing switch.

While the mobile arm of the earthing switch is in the open position, install on the
horizontal transmission rod (5.4 Fig. 5H) of the earthing switch the clamp (5.32 Fig.
5H) with the U-bolt (5.33 Fig. 5H) without tightening the bolts.
Insert the balancing spring (5.31 Fig. 5H) on the specific holes of the block (5.30 Fig.
5H), already fastened to the fixed base (5.2 Fig. 5H), and of the clamp (5.32 Fig. 5H).
Bring the mobile arm to the closed position and pre-load the balancing spring for
about 15°, as shown in figure 5H.
Fasten finally the clamp (5.32 Fig. 5H) by tightening the bolts of the U-bolt (5.33 Fig.
5H).

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 20/78

Balancing spring of the earthing switch

6.3.10 Vertical drive shaft and drive of the earthing switches (Fig. 7 and 7A)

Before carrying out the installation, check that the serial number
Important of the drive is the same as the serial number of the
disconnector.

Concerning the lifting of the drive, see the instruction


manual on the specific installation and maintenance
! Danger procedures for the device.

Lift the drive; take the back of the device toward the support structure and take care
that the holes (7.11 Fig. 7) on the drive match those on the structure. Fasten
temporarily two bolts diagonally; do not tighten them.
Remove the lifting apparatus.
With reference to Fig. 7A, measure the distance "L" between the center of the hole of
the pin (7.13 Fig. 7A), on the driving shaft of the lower base (5.1 Fig. 7A), and the
upper surface of the support (7.15 Fig. 7A) of the clamp of the drive; subtract 15 mm
from this distance. Such distance is called "La":
La=L-15 (with "L" and "La" in mm)
Measure the vertical drive shaft (7.3 Fig. 7) supplied with the disconnector and, if it is
longer than "La", cut it to the exact size and then deburr the edges and reinstate the
surface protection by cold galvanizing.
Make sure that the drive is in the OPEN position.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 21/78
In order to ensure the best grip, before installing the drive shaft
of the switchgear, polish with abrasive paper the lower part of
Important the shaft for a length of about 150 mm.
Check also that the internal surface of the clamp is free from any
trace of grease or other impurities.
Remove the lower fastening bolt installed previously and, by pivoting on the other
bolt still installed, tilt the drive to permit the installation of the vertical drive shaft (7.3
Fig. 7).
Insert the top of the vertical drive shaft (7.3 Fig. 7) into the hub of the driving base
(5.1 Fig. 5B, 5D) and lock it in the correct position with the lock pin and cotter pins
(7.13 Fig. 7).
While keeping the drive at a slant, insert the bottom of the vertical drive shaft (7.3
Fig. 7) into the clamp (7.12 Fig. 7).
Bring back the drive to the correct position and fasten the others fastening bolts to
the support structure.
If needed, loosen the bolts that fasten the drive to the structure, raise or lower the
drive and then tighten the bolts again, in order to get - when the adjustment is
complete - the exact dimensions shown in the specific installation drawing DIN-….
Check also that the drive is horizontal in two perpendicular directions, if needed shim
the fastening devices.
Fasten temporarily the clamp (7.12 Fig. 7), but do not tighten the screws (7.10 Fig.
7).
Check that the drive shaft (7.3 Fig. 7) is vertical in the two perpendicular directions.
Now you can tighten the clamp (7.12 Fig. 7) with the screws (7.10 Fig. 7) to lock the
shaft (7.3 Fig. 7), with a torque of around 80 Nm. In order to assist in this operation,
apply some normal grease on the bolts.

6.3.11 Mechanical interlocking device (Fig. 5B, 5C, 5D, 5E)


The interlocking device between the disconnector and the earthing switch, driven by
different drives, is installed on the fixed driving base (Fig. 5B, 5C, 5D, 5E) and is
made of:
• Connection plate with locking peg (5.28 Fig. 5B, 5C, 5D, 5E);
• Disconnector interlocking disc (5.26 Fig. 5B, 5C, 5D, 5E);
• Earthing-switch interlocking disc (5.27 Fig. 5B, 5C, 5D, 5E).

6.3.12 Arcing-contact device (IEC 62271-102 Att. B) (Fig. 3A)


In figure 3A, you can see in detail a special device called "arcing-contact device"
which is supplied on request.
This device is already installed and adjusted in our workshop, so it does not require
additional assembly.
Check with a manual CLOSING operation of the mobile arm that the male and
female arcing contacts (3.21, 3.22 Fig. 3A) get in touch earlier than the male and
female contacts of the disconnector.
AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 22/78
6.4 INSTALLATION OF THE S3C2T DISCONNECTOR

6.4.1 Fixed bases (Fig. 1C, 5F, 5G)


Lift, as shown in figure A, the fixed bases (5.1, 5.2 Fig. 5F) and, after checking that
their positions are correct, in agreement with the specific installation drawing DIN-…,
lay them down onto the support structure, with the fastening holes aligned.
Fasten them temporarily.
Remove the lifting apparatus.
With the spirit level, check that all the bases, especially the rotary discs (5.7, 5.8 Fig.
5F), which support the rotary insulators (1.2 Fig. 1C), are horizontal in the two
perpendicular directions. If needed shim with the C-washers on the bolts, between
the support structure and the brackets of the bases, until the bases are adequately
level.
Before fastening them finally to the structure, check that:
• the bases are aligned between themselves and with the support structure;
• the bases are horizontal;
• During final fastening no deformation has taken place that might have altered
the adjustments already carried out. If needed repeat the operations above.

6.4.2 Installation of the insulators (Fig. 1C, 2D, 5F)


Lift the insulators as shown in figure A and fasten the fixed insulators (1.1 Fig. 1C) to
the lateral supports (5.5 Fig. 5F) of the fixed bases (5.1, 5.2 Fig. 5F) with the screws,
including spring washers; then fasten the rotary insulators (1.2 Fig. 1C) to the central
rotary discs (5.7, 5.8 Fig. 5F), as shown in figure 2D.
With the spirit level, laid on the upper ring, check that the ring is level in the two
perpendicular directions as shown in figure 2D.
Check also that during the rotation the rotary insulator (1.2 Fig. 1C) turns around its
axis without describing a cone (Fig. 2D). If needed insert the C-washers (Fig. 2D)
between the ring and the rotary disc, until the system reaches the required
conditions. When you have achieved the required conditions, tighten the fastening
bolts. Take into account that any C-washers should be inserted as shown in Figure
2D, so that slanted supporting surfaces are created for the bolts, in order to avoid
stress to the rings of the insulators.
Finally check that the distances between the centers of the insulators are as
indicated in the installation drawing DIN-…

6.4.3 Main fixed contacts with fixed contacts for the earthing switches
(Fig. 1C, 3, 8, 9)
See the layout drawings (Fig. 1C) for the correct positioning of
Important the main fixed contacts (3.0 Fig. 3) and of the fixed contacts (9.0
Fig. 9) for the earthing switches (8.0 Fig. 8).

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 23/78
Install the main fixed contacts (3.0 Fig. 9) on the external insulators (1.1 Fig. 1C)
together with the support plates (9.2 Fig. 9) of the fixed contacts (9.0 Fig. 9) of the
earthing switches, use the same screws (3.4 Fig. 9) as shown in figure 9.
Complete the installation of the fixed contacts of the earthing switches by installing
the contact holding clamp (9.1 Fig. 9), with the fixed contact (9.3 Fig. 9) already
assembled, with the special bolts (9.4 Fig.9).
Before tightening the bolts make sure that:
• The fixed contacts (3.0 Fig. 3) are aligned and perpendicular to the centerlines
of the supports (5.5 Fig. 5F);
• The contact blades (3.2 Fig. 3) are horizontal. If needed, insert the special C-
washers between the upper flanges of the external insulators (1.1 Fig. 1C) and
the fixed contacts (3.0 Fig. 3).

6.4.4 Mobile live parts (Fig. 1, 2, 2A, 2B, 2C, 2D)


The figures 2, 2A, 2B and 2C show the live parts for rated
currents of 1250, 1600-2000, 2500 and 3150 A respectively. The
! Caution
installation procedure described hereafter can be applied to all
kinds of live parts.
Set the rotary discs (5.7, 5.8 Fig. 5F) to the OPEN positions.
Fasten the live part (2.0 Fig. 2, 2A, 2B, 2C) to the central rotary insulator (1.2 Fig.
1C) with the screws, including spring washers.
Turn the base by hand, to check that - on each side of the arm - the mobile contacts
(2.3 Fig. 2, 2.12 Fig. 2A, 2.22 Fig. 2B and 2.32 Fig. 2C) are centered when they
couple with the respective fixed contacts (3.0 Fig. 3).
If the mobile contact is lower than the fixed contacts, insert the special C-washers
between the upper flange of the rotary insulator (1.2 Fig. 1C) and the support of the
mobile arm (2.2 Fig. 2, 2.11 Fig. 2A, 2.21 Fig. 2B and 2.31 Fig. 2C). On the contrary,
when the fixed contacts are lower than the mobile contacts, the C-washers should be
inserted between the upper flanges of the lateral insulators (1.1 Fig. 1C) and the
fixed contacts (3.0 Fig. 3).
Turn the mobile arm (2.1 Fig. 2, 2.10 Fig. 2A, 2.20 Fig. 2B and 2.30 Fig. 2C) to the
open position and check that its axis is at an angle of around 85° with the axis of the
base.

6.4.5 Vertical drive shaft and drive of the disconnector (Fig. 7 and 7A)

Before carrying out the installation, check that the serial number
Important of the drive is the same as the serial number of the
disconnector.

Concerning the lifting of the drive, see the instruction


manual on the specific installation and maintenance
! Danger procedures for the device.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 24/78
Lift the drive; take the back of the device toward the support structure and take care
that the holes (7.11 Fig. 7) on the drive match those on the structure. Fasten
temporarily two bolts diagonally; do not tighten them.
Remove the lifting apparatus.
With reference to Fig. 7A, measure the distance "L" between the center of the hole of
the pin (7.13 Fig. 7A), on the driving shaft of the lower base (5.1 Fig. 7A), and the
upper surface of the support (7.15 Fig. 7A) of the clamp of the drive; subtract 15 mm
from this distance. Such distance is called "La":
La=L-15 (with "L" and "La" in mm)
Measure the vertical drive shaft (7.3 Fig. 7) supplied with the disconnector and, if it is
longer than "La", cut it to the exact size and then deburr the edges and reinstate the
surface protection by cold galvanizing.
Make sure that the drive is in the OPEN position.
In order to ensure the best grip, before installing the drive shaft
of the switchgear, polish with abrasive paper the lower part of
Important the shaft for a length of about 150 mm.
Check also that the internal surface of the clamp is free from any
trace of grease or other impurities.
Remove the lower fastening bolt installed previously and, by pivoting on the other
bolt still installed, tilt the drive to permit the installation of the vertical drive shaft (7.3
Fig. 7).
Insert the top of the vertical drive shaft (7.3 Fig. 7) into the hub of the driving base
(5.1 Fig. 5B, 5D) and lock it in the correct position with the lock pin and cotter pins
(7.13 Fig. 7).
While keeping the drive at a slant, insert the bottom of the vertical drive shaft (7.3
Fig. 7) into the clamp (7.12 Fig. 7).
Bring back the drive to the correct position and fasten the others fastening bolts to
the support structure.
If needed, loosen the bolts that fasten the drive to the structure, raise or lower the
drive and then tighten the bolts again, in order to get - when the adjustment is
complete - the exact dimensions shown in the specific installation drawing DIN-….
Check also that the drive is horizontal in two perpendicular directions, if needed shim
the fastening devices.
Fasten temporarily the clamp (7.12 Fig. 7), but do not tighten the screws (7.10 Fig.
7).
Check that the drive shaft (7.3 Fig. 7) is vertical in the two perpendicular directions.
Now you can tighten the clamp (7.12 Fig. 7) with the screws (7.10 Fig. 7) to lock the
shaft (7.3 Fig. 7), with a torque of around 80 Nm. In order to assist in this operation,
apply some normal grease on the bolts.

6.4.6 Installation of the horizontal transmission rods of the disconnector (Fig. 5F)
With reference to figure 5F, measure the distance "X" between the bases: add 200
mm to this distance. This distance is indicated by "Xb":
AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 25/78
Xb = X + 200 (with "X" and "Xb" in mm)
Measure the horizontal transmission rods (5.3 Fig. 5F) supplied with the disconnector
and, if they are longer than "Xb", cut them to size, then deburr the edges and
reinstate the surface protection by cold galvanizing.
Loosen the U-bolts (5.9 Fig. 5F) already installed on the rotary discs (5.7, 5.8 Fig.
5F).
Insert the rods (5.3 Fig. 5F) into the loose clamps (5.9 Fig. 5F), make sure that the
ends of the rods protrude for about 50 mm.
Tighten the clamps.

6.4.7 Installation of the horizontal transmission rods of the earthing switches


(Fig. 5F, 5G)
The horizontal transmission rod of the earthing switches (5.4 Fig. 5F) is sent in two
sections for shipping reasons.
Locate the longer section, insert it into the supports (5.20 Fig. 5F, 5G) of one of the
lateral driven bases (5.2 Fig. 5F) and of the central driving base and lock it in position
with the lock rings (5.22 Fig. 5F).
Insert the other section of the horizontal transmission rod (5.4 Fig. 5F) of the earthing
switch into the supports (5.20 Fig. 5F, 5G) of the other driven base and lock it in
position with the lock rings (5.22 Fig. 5F).

During the insertion of the horizontal transmission rods of the


Important earthing switches, the balancing springs (5.31 Fig. 5F) must be
installed too in the driven poles only (see section 6.4.9).

Connect the two sections of the horizontal transmission rod (5.4 Fig. 5F) of the
earthing switch by means of the joining clamp (5.23 Fig. 5F) using the U-bolts (5.24
Fig. 5F) and the nuts (5.25 Fig. 5F) to fasten it.
Cut both end of the rod (5.4 Fig. 5F) to size, then deburr the edges and reinstate the
surface protection by cold galvanizing.
Install the adjustable control lever (5.14 Fig. 5F, 5G) of the earthing switch with the
U-bolts (5.15 Fig. 5G) and fastening nuts (5.16 Fig. 5G), use the angles indicated in
the figure 5G and the distance from the centerline of the lower base indicated in the
figure 5G.
Take care the adjustable control levers (5.14 Fig. 5F, 5G) are
positioned correctly, since their rotation in the wrong direction
Important
may break the ball joints of the thrust linkages (5.13 Fig. 5F,
5G).

6.4.8 Earthing switches (Fig. 5F, 5G, 8)


With reference to figure 5F, set the control lever (5.12 Fig. 5F) of the earthing switch
to the OPEN position; the adjustable control lever (5.14 Fig. 5F) of the earthing
switch will then make an angle of about 30° in relation to the horizontal axis.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 26/78
While keeping the control lever (5.12 Fig. 5F) in the position above, install the
earthing switches (8.0 Fig. 8) while keeping them in almost horizontal positions
(OPEN) and resting on the stop bolts (5.18 Fig. 8).
The mobile arm (8.1 Fig. 8) of each earthing switch is fastened to the horizontal
transmission rod (5.4 Fig. 5F) by means of the U-bolts (8.7 Fig. 8) and nuts (8.8 Fig.
8).
Before tightening the fastening nuts (8.8 Fig. 8), the driving and
driven earthing switches must be adjusted and synchronized, in
Important
accordance with the procedure described in the sections 6.5.2
and 6.5.3.
Connect the stranded conductors (8.9 Fig. 8) to the lower bases (5.1 and 5.2 Fig. 5F)
with the bolts (5.21 Fig. 5F).
Please see the photo below for the correct connection of the earthing stranded
conductors.

Connection of the earthing stranded conductors to the fixed base of the earthing switch

6.4.9 Installation of the balancing springs of the earthing switches (Fig. 5H)

The balancing springs (5.31 Fig. 5F, 5G, 5H) must be installed
Important
only on the driven poles of the earthing switch.

While the mobile arm of the earthing switch is in the open position, install on the
horizontal transmission rod (5.4 Fig. 5H) of the earthing switch the clamp (5.32 Fig.
5H) with the U-bolt (5.33 Fig. 5H) without tightening the bolts.
Insert the balancing spring (5.31 Fig. 5H) on the specific holes of the block (5.30 Fig.
5H), already fastened to the fixed lower base (5.2 Fig. 5H), and of the clamp (5.32
Fig. 5H).

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 27/78
Bring the mobile arm to the closed position and pre-load the balancing spring for
about 15°, as shown in figure 5H.
Fasten finally the clamp (5.32 Fig. 5H) by tightening the bolts of the U-bolt (5.33 Fig.
5H).

Balancing spring of the earthing switch

6.4.10 Vertical drive shaft and drive of the earthing switches (Fig. 7 and 7A)
Before carrying out the installation, check that the serial number
Important of the drive is the same as the serial number of the
disconnector.

Concerning the lifting of the drive, see the instruction


manual on the specific installation and maintenance
! Danger procedures for the device.

Lift the drive; take the back of the device toward the support structure and take care
that the holes (7.11 Fig. 7) on the drive match those on the structure. Fasten
temporarily two bolts diagonally; do not tighten them.
Remove the lifting apparatus.
With reference to Fig. 7A, measure the distance "L" between the center of the hole of
the pin (7.13 Fig. 7A), on the driving shaft of the lower base (5.1 Fig. 7A), and the
upper surface of the support (7.15 Fig. 7A) of the clamp of the drive; subtract 15 mm
from this distance. Such distance is called "La":
La=L-15 (with "L" and "La" in mm)

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 28/78
Measure the vertical drive shaft (7.3 Fig. 7) supplied with the disconnector and, if it is
longer than "La", cut it to the exact size and then deburr the edges and reinstate the
surface protection by cold galvanizing.
Make sure that the drive is in the OPEN position.
In order to ensure the best grip, before installing the drive shaft
of the switchgear, polish with abrasive paper the lower part of
Important the shaft for a length of about 150 mm.
Check also that the internal surface of the clamp is free from any
trace of grease or other impurities.
Remove the lower fastening bolt installed previously and, by pivoting on the other
bolt still installed, tilt the drive to permit the installation of the vertical drive shaft (7.3
Fig. 7).
Insert the top of the vertical drive shaft (7.3 Fig. 7) into the hub of the driving base
(5.1 Fig. 5F) and lock it in the correct position with the lock pin and cotter pins (7.13
Fig. 7).
While keeping the drive at a slant, insert the bottom of the vertical drive shaft (7.3
Fig. 7) into the clamp (7.12 Fig. 7).
Bring back the drive to the correct position and fasten the others fastening bolts to
the support structure.
If needed, loosen the bolts that fasten the drive to the structure, raise or lower the
drive and then tighten the bolts again, in order to get - when the adjustment is
complete - the exact dimensions shown in the specific installation drawing DIN-….
Check also that the drive is horizontal in two perpendicular directions, if needed shim
the fastening devices.
Fasten temporarily the clamp (7.12 Fig. 7), but do not tighten the screws (7.10 Fig.
7).
Check that the drive shaft (7.3 Fig. 7) is vertical in the two perpendicular directions.
Now you can tighten the clamp (7.12 Fig. 7) with the screws (7.10 Fig. 7) to lock the
shaft (7.3 Fig. 7), with a torque of around 80 Nm. In order to assist in this operation,
apply some normal grease on the bolts.

6.4.11 Mechanical interlocking device (Fig. 5F, 5G)


The interlocking device between the disconnector and the earthing switch, driven by
different drives, is installed on the fixed driving base (Fig. 5F, 5G) and is made of:
• Connection plate with locking peg (5.28 Fig. 5F, 5G);
• Disconnector interlocking disc (5.26 Fig. 5F, 5G);
• Earthing-switch interlocking disc (5.27 Fig. 5F, 5G).

6.4.12 Arcing-contact device (IEC 62271-102 Att. B) (Fig. 3A)


In figure 3A, you can see in detail a special device called "arcing-contact device"
which is supplied on request.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 29/78
This device is already installed and adjusted in our workshop, so it does not require
additional assembly.
Check with a manual CLOSING operation of the mobile arm that the male and
female arcing contacts (3.21 and 3.22 Fig. 3A) get in touch earlier than the male and
female contacts of the disconnector.

6.5 ADJUSTMENT OF THE S3C / S3CT / S3C2T DISCONNECTORS


In the following sections you can find the procedures for the adjustment and fine
tuning of the equipment.

6.5.1 Adjustment of the live parts of the disconnector (Fig. 2, 2A, 2B, 2C, 3)
With the lever or crank of the drive of the disconnector, carry out slowly a few
OPENING and CLOSING operations and check that the three poles of the
disconnector reach the final OPEN and CLOSED positions at the same time.
This condition is satisfied also if, when the mobile contacts (2.3 Fig. 2, 2.12 Fig. 2A,
2.22 Fig. 2B and 2.32 Fig. 2C) of the driving pole reach the end stops (3.6 Fig. 3) of
the respective fixed contacts, the distances of the mobile contacts (2.3 Fig. 2, 2.12
Fig. 2A, 2.22 Fig. 2B and 2.32 Fig. 2C) of the driven poles from the end stops (3.6
Fig. 3) of the respective fixed contacts (3.0 Fig. 3) do not exceed 20 mm.
Adjustments may be effected by changing the positions of the tube clamps (5.9 Fig.
5, 5B, 5D, 5F) on the horizontal transmission rods (5.3 Fig. 5, 5B, 5D, 5F).
You can avail yourself also of the freedom of positioning on the holes for fastening of
the insulator, either the upper or lower ones.
Tighten the fastening screws fully and carry out a few manual operations to check the
adjustment.
If needed, repeat the operations above.

6.5.2 Adjustment of the earthing switches (Fig. 8 and 9)


Carry out a few OPENING/CLOSING operations of the earthing switch and check
that, in the CLOSED position, each mobile arm is vertical and that the mobile contact
(8.2 Fig. 8) is correctly centered on the fixed contact (9.3 Fig. 8).
If needed, loosen the nuts (8.8 Fig. 8) that fasten the U-bolts (8.7 Fig. 8) and let the
mobile arm (8.1 Fig. 8) slide along the horizontal transmission rod (5.4 Fig. 5B, 5D,
5F) of the earthing switch.
You can synchronize the three mobile arms by loosening the nuts (8.8 Fig. 8) that
fasten the U-bolts (8.7 Fig. 8) and letting the mobile arm (8.1 Fig. 8) rotate clockwise
or counterclockwise on the horizontal transmission rod of the earthing switch.
Check also that, in the OPEN positions, the mobile arms (8.1
Fig. 8) of the earthing switches do not interfere with the
horizontal transmission rods (5.4 Fig. 5B, 5D, 5F) of the
Important
disconnector.
In this configuration, the mobile arms (8.1 Fig. 8) should be
almost horizontal with a slight upward slant.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 30/78
Check also that, in the OPEN positions, the end plates (5.18 Fig. 8) are in contact
with the mobile arms (8.1 Fig. 8) without forcing on them. If needed adjust the
positions of the end stops (5.18 Fig. 8) by loosening the bolts that fasten them to the
lower bases (5.1, 52.2 Fig. 8) and using the freedom of positioning of the bolts in the
holes.

6.5.3 Horizontal transmission rods of the earthing switches (Fig. 5B, 5C, 5D, 5E, 5F,
5G)
Carry out a few OPENING/CLOSING operations to check that the three poles of the
earthing switch reach the final OPEN and CLOSED positions at the same time.
You can synchronize the three mobile arms by loosening the nuts (8.8 Fig. 8) that
fasten the U-bolts (8.7 Fig. 8) and letting the mobile arm (8.1 Fig. 8) rotate clockwise
or counterclockwise on the horizontal transmission rod (5.4 Fig. 5B, 5C, 5D, 5E, 5F,
5G) of the earthing switch.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 31/78

7. CONNECTIONS, FINAL CHECKS AND FINE-TUNING

! Danger

7.1 CONNECTIONS
Connect to the station earthing system all earthing points.
Connect electrically the drive in accordance with the wiring diagrams supplied.
Connect adequately the high-voltage conductors to the line connection terminals.
Check that acceptable mechanical loads on the disconnector, as indicated on the
installation drawing, are not exceeded.

7.2 FINAL CHECKS AND FINE-TUNING


Carry out some manual and motor operations and check that:
• In the fully closed and fully open positions, the indicators (plates) located on
disc hub reach exactly the reference marks provided on the plate fixed on the
top of the drive;
• During CLOSING, the coupling of the male and female contacts occurs
correctly;
• At the rated voltage, the current consumption of the motor does not exceed the
value indicated in the wiring diagram.
Measure the resistance of the main circuit. The values measured between the
terminal connections of the S3C / S3CT / S3C2T disconnectors must be as in the
following table:

1250 A 1600-2000 A 2500 A 3150 A


S3C / S3CT / S3C2T 160 µΩ 102 µΩ 90 µΩ 65 µΩ
VALUES AT 20° C TOLERANCE ± 20%

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 32/78

8. MAINTENANCE PLAN
The switchgears not require special maintenance. We recommend, however, in order
to ensure the correct operation of the equipment, to carry out routine checks and
maintenance actions, especially on the component parts which are most sensitive or
subject to wear.
The frequency of checks and maintenance actions depends on the number of
operations (1,000, 2,000, 3,000 or 10,000) that have been guaranteed for the
equipment supplied.
In order to keep the guarantee of the equipment in force, routine checks and
maintenance operations must comply with the following NTC-1955/E table.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 33/78

TABLE NTC-1955/E
FREQUENCY OF ACTIONS
CONDITION TYPE OF ACTION TO PERFORM IN
OF COMPLIANCE WITH THE RELEVANT Guaranteed Guaranteed Guaranteed Guaranteed
SWITCHGEAR INSTALLATION INSTRUCTIONS operations: operations: operations: operations:
1,000 2,000 3,000 10,000
A: MINOR INSPECTION: During site During site During site During site
SWITCHGEAR Verify: inspection inspection inspection inspection
IN SERVICE A.1) That the mechanical parts of the switchgear or, in any or, in any or, in any or, in any
and of the protection surfaces are not dam- case, every case, every case, every case, every
aged; 2 years 2 years 3 years 4 years
A.2) That the sheaths of the low voltage cables
and of the earthing cables are not damaged;
A.3) That the insulators are not damaged and that
there is no deposit or fouling on their sur-
faces;
A.4) That the drive (operating mechanism) is in
working order.
OPTIONAL:
Verify heating with a thermal detector.

B: INSPECTION OF SWITCHGEAR: Every 5 Every 5 Every 6 Every 8


SWITCHGEAR B.1) Carry out the checks A.1 – A.2 – A.3; years or years or years or years or
OUT OF every 500 every 1000 every 1500 every 5000
SERVICE B.2) Verify that the live parts are clean; operations operations operations operations
B.3) Measure the resistance of the live parts;
B.4) Check that bolts are tight;
B.5) The operation of local controls;
B.6) Check manual operation;
B.7) The correct coupling of the main contacts;
B.8) Check the condition of the surfaces of the
contacts;
B.9) Check that the mechanical parts are ade-
quately lubricated (Fig. 10).

INSPECTION OF THE DRIVE:


B.10) Verify that all mechanical and electrical
components, cables and earthing connec-
tions are not damaged;
B.11) Verify the correct operation of the following
electrical components:
• anti–condensation and heating resis-
tance (if any);
• motor protection automatic switch;
• electromechanical interlocking device.
C: MAJOR INSPECTION: Every 10 Every 10 Every 12 Every 15
SWITCHGEAR C.1) Full check of the switchgear as per section years or years or years or years or
OUT OF B; every 1000 every 2000 every 3000 every 10000
SERVICE operations operations operations operations
C.2) Check the condition and the wear of the main
components, the condition of the insulators
and the mechanical adjustments performed
during the first installation (see installation
manual). Verify that the mechanical parts
are adequately lubricated (Fig. 10). If you
find any deviation, restore the required condi-
tions. If replacement of units or components
is required, comply with the procedures in
the installation manual. In case of troubles
or doubts on how to restore correctly the re-
quired conditions, contact AREVA.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 34/78
PREVENTIVE MAINTENANCE PLAN OF SWITCHGEARS
GUARANTEED UP TO 1,000 OPERATIONS

PREVENTIVE MAINTENANCE PLAN OF SWITCHGEARS


GUARANTEED UP TO 2,000 OPERATIONS

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 35/78
PREVENTIVE MAINTENANCE PLAN OF SWITCHGEARS
GUARANTEED UP TO 3,000 OPERATIONS

PREVENTIVE MAINTENANCE PLAN OF SWITCHGEARS


GUARANTEED UP TO 10,000 OPERATIONS

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 36/78

9. DISASSEMBLING THE APPARATUS AND REPLACEMENT OF MAIN


PARTS
9.1 DISASSEMBLING THE APPARATUS

! Danger

WARNING: before carrying out any of the following operations, make sure that:
a) The disconnector is in the OPEN position;
b) Both the incoming and outgoing high-voltage conductors are visibly connected
to earth;
c) The drive is disconnected from all low-voltage conductors.

9.1.1 Disconnection
• Disconnect all high-voltage conductors from the line terminals.
• Disconnect all low-voltage conductors from the drive.

9.1.2 Disassembly
With the same tools used during the installation, but in a sequence reverse to that of
Section 6, remove the parts in the following sequence:

S3C DISCONNECTORS:
• horizontal transmission rods of the disconnector;
• vertical drive shaft and drive of the disconnector;
• mobile arms;
• fixed contacts;
• insulators;
• lower bases.

S3CT / S3C2T DISCONNECTORS:


• vertical drive shaft and drive of the earthing switches;
• balancing springs of the earthing switches;
• earthing switches;
• horizontal transmission rod of the earthing switches;
• horizontal transmission rod of the disconnector;
• vertical drive shaft and drive of the disconnector;
• mobile arms;
• fixed contacts;
• insulators;

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 37/78

• lower bases.
When disassembly is complete, store correctly all components.

9.2 DISASSEMBLING THE EQUIPMENT AND REPLACEMENT OF MAIN PARTS

! Danger

WARNING: before carrying out any of the following operations, make sure that:
a) The disconnector is in the OPEN position;
b) Both the incoming and outgoing high-voltage conductors are visibly connected
to the earth.

9.2.1 Mobile contacts of the disconnector (Fig. 2, 2A, 2B, 2C)


To replace the male mobile contact (2.3, 2.12, 2.22 and 2.32), proceed as follows:
• Remove the contacts (2.3, 2.12, 2.22 and 2.32) after unscrewing the screws
(2.4, 2.13, 2.23 and 2.33);
• Clean the contact surfaces of the new contacts and apply on them a layer of
antioxidant paste.
• Install the new contacts (2.3, 2.12, 2.22 and 2.32) with the reverse procedure.

9.2.2 Fixed contacts (Fig. 3)


To replace the female fixed contacts (3.8) proceed as follows:
With the disconnector in the OPEN position:
• Remove the fixed contacts (3.2 Fig. 3) after unscrewing the screws (3.3 Fig. 3)
that fasten them to the supports [ATTENTION: the pressure springs (3.5 Fig. 3)
are removed too].
• Clean the contact surfaces and those of the new contacts and apply on them a
layer of antioxidant paste;
• Install the new contact (3.2 Fig. 3) and the pressure springs (3.5 Fig. 3) and
fasten it with the screws (3.3 Fig. 3) removed previously.

9.2.3 Drive (operating mechanism) (Fig. 7)


If the drive needs to be replaced, proceed as follows:
• Set the disconnector to the OPEN position;
• Disconnect the flexible conductor from the vertical drive shaft and disconnect all
electric connections;
• Uncouple the vertical drive shaft;
• Sling the drive and lift it slightly to put the sling in tension;
• Remove the four bolts that fasten the cabinet to the support structure with their
spring washers and plain washers;

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 38/78

• Pull out the drive horizontally and move it to the required place.
To install the new drive, proceed as indicated in Section 6.

9.2.4 Ball joints of the adjustable thrust linkages


Check that the ball joints move freely, that they are not slack, and that their surfaces
are not corroded.
Take into account that, in the case of replacement, any adjustment carried out in our
factory is lost.
Before replacing the ball joints, measure carefully the distance between the axes of
the two joints and, after the replacement, adjust the length of the linkages to reinstate
the original distance between the axes of the two joints.

10. LIST OF TOOLS


Common tools should be adequate for the installation and maintenance of these
disconnectors such as box wrenches, open-end wrenches, socket wrenches, torque
wrenches with torque up to 200 Nm, screwdrivers, pliers, hammers, spirit level,
mason's rule, tape measure, etc. Therefore, no special tools are required.
To lift the units, a truck crane equipped with adequate ropes (slings) with eyes as
shown in figure A is required.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 39/78

11. SPARE PARTS


Send any order for spare parts to:
AREVA T&D S.A. de C.V.
Calle 4 Norte #101, Parque Industrial Toluca 2000
Toluca Edo. De México. México
C.P. 50200
(Tel. 01 722 276 2000)
State:
• The number and the revision of the manual that you can find on the cover page;
• The number of the figure and the number of the item in the figure;
• The customer's order number, the type of disconnector and its serial number.

NOTE: When replacing live parts through which current will flow, the surfaces that
are permanently in contact must be treated as follows (e.g. the contact surface
between the terminal pad and the fixed-contact support):
• Wipe off any trace of grease from the contact surfaces with trichloroethylene or
other non-abrasive solvent. If the surfaces are oxidized, clean them up with a
steel brush or fine emery paper;
• Cover immediately with antioxidant compound;
• Connect the surfaces as soon as possible.
Surfaces through which wiping-contact current flows (e.g. mobile contact blades)
must be covered with a thin layer of grease NYOGEL 760G (to be restored at each
inspection).

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 40/78
FIG. 1: INSTALLATION DIAGRAM FOR THE S3C DISCONNECTOR

N.B.: See the Table 1 and the specific installation drawings DIN-… for the dimensions A, B, H, X.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 41/78
Key of the installation diagram for the S3C disconnector (Fig. 1)

1.1 POST INSULATOR


1.2 ROTARY INSULATOR
2.0 LIVE PART ASSEMBLY
3.0 FIXED CONTACT
5.1 LOWER DRIVING BASE
5.2 LOWER DRIVEN BASE
5.3 HORIZONTAL TRANSMISSION ROD OF THE DISCONNECTOR
7.1 MOTOR DRIVE
7.2 MANUAL DRIVE
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 42/78
FIG. 1A: INSTALLATION DIAGRAM FOR THE S3CT DISCONNECTOR, WITH EARTHING
SWITCH ON THE RIGHT

N.B.: See the Table 1 and the specific installation drawings DIN-… for the dimensions A, B, H, X.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 43/78
Key of the installation diagram for the S3CT disconnector with earthing switch on the
right (Fig. 1A)

1.1 POST INSULATOR


1.2 ROTARY INSULATOR
2.0 LIVE PART ASSEMBLY
3.0 FIXED CONTACT
5.1 LOWER DRIVING BASE
5.2 LOWER DRIVEN BASE
5.3 HORIZONTAL TRANSMISSION ROD OF THE DISCONNECTOR
5.4 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
7.1 MOTOR DRIVE
7.2 MANUAL DRIVE
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
7.4 VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
8.0 EARTHING-SWITCH UNIT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 44/78
FIG. 1B: INSTALLATION DIAGRAM FOR THE S3CT DISCONNECTOR WITH EARTHING
SWITCH ON THE LEFT

N.B.: See the Table 1 and the specific installation drawings DIN-… for the dimensions A, B, H, X.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 45/78
Key of the installation diagram for the S3CT disconnector with earthing switch on the
left (Fig. 1B)

1.1 POST INSULATOR


1.2 ROTARY INSULATOR
2.0 LIVE PART ASSEMBLY
3.0 FIXED CONTACT
5.1 LOWER DRIVING BASE
5.2 LOWER DRIVEN BASE
5.3 HORIZONTAL TRANSMISSION ROD OF THE DISCONNECTOR
5.4 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
7.1 MOTOR DRIVE
7.2 MANUAL DRIVE
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
7.4 VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
8.0 EARTHING-SWITCH UNIT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 46/78
FIG. 1C: INSTALLATION DIAGRAM FOR THE S3C2T DISCONNECTOR

N.B.: See the Table 1 and the specific installation drawings DIN-… for the dimensions A, B, H, X.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 47/78
Key of the installation diagram for the S3C2T disconnector (Fig. 1C)

1.1 POST INSULATOR


1.2 ROTARY INSULATOR
2.0 LIVE PART ASSEMBLY
3.0 FIXED CONTACT
5.1 LOWER DRIVING BASE
5.2 LOWER DRIVEN BASE
5.3 HORIZONTAL TRANSMISSION ROD OF THE DISCONNECTOR
5.4 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
7.1 MOTOR DRIVE
7.2 MANUAL DRIVE
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
7.4 VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
8.0 EARTHING SWITCH

TABLE 1

Rated current (A) BIL A ±10 (mm) B (mm)


1250 950 2460 2800
1250 1050 2660 2800
1600-2000 950 2460 2800
1600-2000 1050 2660 2800
2500 950 2460 2800
2500 1050 2660 2800
3150 950 2460 2800
3150 1050 2660 2800

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 48/78
FIG. 2: MOBILE LIVE PART 1250 A

2.0 LIVE PART ASSEMBLY


2.1 MOBILE ARM
2.2 MOBILE ARM SUPPORT
2.3 MALE MOBILE CONTACT
2.4 SCREWS FASTENING THE MALE MOBILE CONTACT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 49/78
FIG. 2A: MOBILE LIVE PART 1600 - 2000 A

2.0 LIVE PART ASSEMBLY


2.10 MOBILE ARM
2.11 MOBILE ARM SUPPORT
2.12 MALE MOBILE CONTACT
2.13 SCREWS FASTENING THE MALE MOBILE CONTACT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 50/78
FIG. 2B: MOBILE LIVE PART 2500 A

2.0 LIVE PART ASSEMBLY


2.20 MOBILE ARM
2.21 MOBILE ARM SUPPORT
2.22 MALE MOBILE CONTACT
2.23 SCREWS FASTENING THE MALE MOBILE CONTACT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 51/78
FIG. 2C: MOBILE LIVE PART 3150 A

2.0 LIVE PART ASSEMBLY


2.30 MOBILE ARM
2.31 MOBILE ARM SUPPORT
2.32 MALE MOBILE CONTACT
2.33 SCREWS FASTENING THE MALE MOBILE CONTACT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 52/78
FIG. 2D: INSTALLATION OF THE BASES, INSULATORS AND LIVE PARTS

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 53/78
FIG. 3: FIXED CONTACT

FIXED CONTACT FOR RATED CURRENT OF 1250 A

FIXED CONTACT FOR RATED CURRENT OF 1600-2000-2500 A

FIXED CONTACT FOR RATED CURRENT OF 3150 A

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 54/78
Key of the fixed contact (Fig. 3)

3.0 FEMALE FIXED CONTACT UNIT


3.1 FEMALE FIXED-CONTACT SUPPORT
3.2 FEMALE CONTACT BLADES IN COPPER
3.3 SCREWS FASTENING THE BLADES OF THE FEMALE CONTACT
3.4 SCREWS FOR FASTENING TO THE INSULATOR
3.5 PRESSURE SPRINGS OF THE FEMALE CONTACT
3.6 END STOP BOLT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 55/78
FIG. 3A: ARCING-CONTACT DEVICE

3.20 ARCING-CONTACT DEVICE


3.21 FIXED ARCING CONTACT
3.22 MOBILE ARCING CONTACT
3.23 RETURN SPRING
3.24 SUPPORT FOR THE FIXED ARCING CONTACT
3.25 FASTENING SCREWS

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 56/78
FIG. 5: LOWER PART ASSEMBLY OF THE S3C DISCONNECTOR

B B

A A

B B

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 57/78
FIG. 5A: LOWER PART OF THE S3C DISCONNECTOR - SECTIONS -

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 58/78
Key of the lower part of the S3C disconnector (Fig. 5 and 5A)

5.1 LOWER DRIVING BASE


5.2 LOWER DRIVEN BASE
5.3 HORIZONTAL TRANSMISSION ROD OF THE DISCONNECTOR
5.5 INSULATOR LATERAL SUPPORT
5.6 AREA FOR FASTENING TO THE STRUCTURE
5.7 DRIVING ROTARY DISC
5.8 DRIVEN ROTARY DISC
5.9 TUBE FASTENING CLAMP
5.10 DISCONNECTOR CONTROL LEVER
5.11 DISCONNECTOR THRUST LINKAGE
5.19 SUPPORT OF THE VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 59/78
FIG. 5B: S3CT DISCONNECTOR WITH EARTHING SWITCH ON THE RIGHT: LOWER
PART ASSEMBLY

D D

C C

D D

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 60/78
FIG. 5C: S3CT DISCONNECTOR WITH EARTHING SWITCH ON THE RIGHT: LOWER
PART ASSEMBLY - SECTIONS -

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 61/78
Key of the lower part of the S3CT disconnector with earthing switch on the right
(Fig. 5B and 5C)

5.1 LOWER DRIVING BASE


5.2 LOWER DRIVEN BASE
5.3 HORIZONTAL TRANSMISSION ROD OF THE DISCONNECTOR
5.4 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.5 INSULATOR LATERAL SUPPORT
5.6 AREA FOR FASTENING TO THE STRUCTURE
5.7 DRIVING ROTARY DISC
5.8 DRIVEN ROTARY DISC
5.9 TUBE FASTENING CLAMP
5.10 DISCONNECTOR CONTROL LEVER
5.11 DISCONNECTOR THRUST LINKAGE
5.12 EARTHING-SWITCH CONTROL LEVER
5.13 EARTHING-SWITCH THRUST LINKAGE
5.14 ADJUSTABLE CONTROL LEVER OF THE EARTHING SWITCH
5.15 CLAMP FOR FASTENING OF THE ADJUSTABLE LEVER
5.16 NUTS FASTENING THE ADJUSTABLE LEVER
5.17 SUPPORT OF THE VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
5.18 END STOP OF THE EARTHING SWITCH
5.19 SUPPORT OF THE VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
5.20 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.21 EARTHING BOLT (WITH EARTHING SIGN)
5.22 LOCKING RING
5.23 CLAMP JOINING THE HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.24 U-BOLT FASTENING THE HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.25 NUTS FASTENING THE HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.26 DISCONNECTOR INTERLOCKING DISC
5.27 EARTHING-SWITCH INTERLOCKING DISC
5.28 INTERLOCKING-DEVICE CONNECTION PLATE
5.30 BLOCK FOR THE BALANCING SPRING
5.31 BALANCING SPRING
5.32 FASTENING CLAMP
5.33 FASTENING U-BOLT
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
7.4 VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
8.0 EARTHING-SWITCH UNIT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 62/78
FIG. 5D: S3CT DISCONNECTOR WITH EARTHING SWITCH ON THE LEFT: LOWER
PART ASSEMBLY

F F

E E

F F

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 63/78
FIG. 5E: S3CT DISCONNECTOR WITH EARTHING SWITCH ON THE LEFT: LOWER
PART ASSEMBLY - SECTIONS -

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 64/78
Key of the lower part of the S3CT disconnector with earthing switch on the left
(Fig. 5D and 5E)

5.1 LOWER DRIVING BASE


5.2 LOWER DRIVEN BASE
5.3 HORIZONTAL TRANSMISSION ROD OF THE DISCONNECTOR
5.4 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.5 INSULATOR LATERAL SUPPORT
5.6 AREA FOR FASTENING TO THE STRUCTURE
5.7 DRIVING ROTARY DISC
5.8 DRIVEN ROTARY DISC
5.9 TUBE FASTENING CLAMP
5.10 DISCONNECTOR CONTROL LEVER
5.11 DISCONNECTOR THRUST LINKAGE
5.12 EARTHING-SWITCH CONTROL LEVER
5.13 EARTHING-SWITCH THRUST LINKAGE
5.14 ADJUSTABLE CONTROL LEVER OF THE EARTHING SWITCH
5.15 CLAMP FOR FASTENING OF THE ADJUSTABLE LEVER
5.16 NUTS FASTENING THE ADJUSTABLE LEVER
5.17 SUPPORT OF THE VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
5.18 END STOP OF THE EARTHING SWITCH
5.19 SUPPORT OF THE VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
5.20 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.21 EARTHING BOLT (WITH EARTHING SIGN)
5.22 LOCKING RING
5.23 CLAMP JOINING THE HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.24 U-BOLT FASTENING THE HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.25 NUTS FASTENING THE HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.26 DISCONNECTOR INTERLOCKING DISC
5.27 EARTHING-SWITCH INTERLOCKING DISC
5.28 INTERLOCKING-DEVICE CONNECTION PLATE
5.30 BLOCK FOR THE BALANCING SPRING
5.31 BALANCING SPRING
5.32 FASTENING CLAMP
5.33 FASTENING U-BOLT
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
7.4 VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
8.0 EARTHING-SWITCH UNIT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 65/78
FIG. 5F: LOWER PART ASSEMBLY OF THE S3C2T DISCONNECTOR

H H

G G

H H

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 66/78
FIG. 5G: LOWER PART OF THE S3C2T DISCONNECTOR - SECTIONS -

Key of the lower part of the S3C2T disconnector (Fig. 5F and 5G)
AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 67/78

5.1 LOWER DRIVING BASE


5.2 LOWER DRIVEN BASE
5.3 HORIZONTAL TRANSMISSION ROD OF THE DISCONNECTOR
5.4 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.5 INSULATOR LATERAL SUPPORT
5.6 AREA FOR FASTENING TO THE STRUCTURE
5.7 DRIVING ROTARY DISC
5.8 DRIVEN ROTARY DISC
5.9 TUBE FASTENING CLAMP
5.10 DISCONNECTOR CONTROL LEVER
5.11 DISCONNECTOR THRUST LINKAGE
5.12 EARTHING-SWITCH CONTROL LEVER
5.13 EARTHING-SWITCH THRUST LINKAGE
5.14 ADJUSTABLE CONTROL LEVER OF THE EARTHING SWITCH
5.15 CLAMP FOR FASTENING OF THE ADJUSTABLE LEVER
5.16 NUTS FASTENING THE ADJUSTABLE LEVER
5.17 SUPPORT OF THE VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
5.18 END STOP OF THE EARTHING SWITCH
5.19 SUPPORT OF THE VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
5.20 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.21 EARTHING BOLT (WITH EARTHING SIGN)
5.22 LOCKING RING
5.23 CLAMP JOINING THE HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.24 U-BOLT FASTENING THE HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.25 NUTS FASTENING THE HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.26 DISCONNECTOR INTERLOCKING DISC
5.27 EARTHING-SWITCH INTERLOCKING DISC
5.29 INTERLOCKING-DEVICE CONNECTION PLATE
5.30 BLOCK FOR THE BALANCING SPRING
5.31 BALANCING SPRING
5.32 FASTENING CLAMP
5.33 FASTENING U-BOLT
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
7.4 VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
8.0 EARTHING-SWITCH UNIT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 68/78
FIG.5H: BALANCING SPRING OF THE EARTHING SWITCH

5.2 DRIVEN LOWER BASE


5.4 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCHES
5.30 BLOCK FOR THE BALANCING SPRING
5.31 BALANCING SPRING
5.32 FASTENING CLAMP
5.33 FASTENING U-BOLT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 69/78
FIG. 7: DRIVE AND VERTICAL DRIVE SHAFT

MOTOR DRIVE

7.10 7.14
7.13
7.12

7.3 7.10
7.4
7.14
7.15
7.10
7.12
150
7.11
7.15

7.1

7.16

MANUAL DRIVE

7.13

ZONA DA CARTEGGIARE
CON CARTA ABRASIVA 7.3
AREA TO CLEAN BY 7.4
SANDPAPER
7.14

150 7.12
7.11
7.15

7.2 7.16

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 70/78
Key of the drive with vertical drive shaft (Fig. 7)

7.1 MOTOR DRIVE


7.2 MANUAL DRIVE
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
7.4 VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
7.10 SHAFT FASTENING BOLTS (SCREW, PLAIN WASHER, NUT)
7.11 HOLES FOR FASTENING TO THE STRUCTURE
7.12 CLAMP
7.13 LOCK PIN AND COTTER PINS FOR FASTENING
7.14 EARTHING STRANDED CABLE
7.15 CLAMP SUPPORT
7.16 EARTHING BOLT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 71/78
FIG. 7A: DRIVE AND VERTICAL DRIVE SHAFT
5.1

7.13

7.3
7.4

7.12
7.15

7.1
7.2

5.1 LOWER DRIVING BASE


7.1 MOTOR DRIVE
7.2 MANUAL DRIVE
7.3 VERTICAL DRIVE SHAFT OF THE DISCONNECTOR
7.4 VERTICAL DRIVE SHAFT OF THE EARTHING SWITCH
7.12 CLAMP
7.13 LOCK PIN AND COTTER PINS FOR FASTENING
7.15 CLAMP SUPPORT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 72/78
FIG. 8: EARTHING-SWITCH UNIT

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 73/78
Key of the earthing switch (Fig. 8)

3.0 FIXED CONTACT WITH CONTACT FOR THE EARTHING SWITCH


5.1 LOWER DRIVING BASE
5.2 LOWER DRIVEN BASE
5.4 HORIZONTAL TRANSMISSION ROD OF THE EARTHING SWITCH
5.18 MOBILE ARM END STOP
8.0 EARTHING-SWITCH UNIT
8.1 MOBILE ARM OF THE EARTHING SWITCH
8.2 CONTACTS OF THE MOBILE ARM
8.3 SCREW FASTENING THE CONTACTS
8.4 PLATE FOR FASTENING OF THE MOBILE ARM
8.5 SCREWS FOR FASTENING OF MOBILE-ARM
8.6 SUPPORT FOR FASTENING TO THE HORIZONTAL TRANSMISSION ROD
8.7 FASTENING U-BOLT
8.8 NUTS FOR FASTENING TO THE HORIZONTAL TRANSMISSION ROD
8.9 EARTHING STRANDED CABLES
9.3 FIXED CONTACT OF THE EARTHING SWITCH

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 74/78
FIG. 9: FIXED CONTACT FOR THE EARTHING SWITCH

3.0 FIXED-CONTACT UNIT OF THE DISCONNECTOR


9.0 FIXED-CONTACT UNIT OF THE EARTHING SWITCH
9.1 CONTACT-HOLDING CLAMP
9.2 MOUNTING BRACKET
9.3 FIXED CONTACT FOR THE EARTHING SWITCH
9.4 BOLTS FASTENING THE CONTACT-HOLDING CLAMP
9.5 CORONA CAP AND ICE SHIELD
9.6 BOLTS FASTENING THE MOUNTING BRACKET

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 75/78
FIG. 10: LUBRICATION AND GREASING

NYOGEL 760G (alternatively: RHEOLUBE 365, ASEOL Sylitea 3 0-365.2)


 The contact areas are protected with neutral Vaseline before shipment. Before installing the
equipment, remove the Vaseline with a dry cloth and then apply the grease indicated above with
a brush (the quantity required for the first greasing is included in the supply).

MULTI-F-S (alternatively: SILAN)


 These parts have already been lubricated in our workshop. The following lubrications should be
carried out as directed in Section 8.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 76/78

ATTACHMENT "A": SPECIFICATIONS FOR THE S3C / S3CT / S3C2T DISCONNECTORS

Rated Voltage [ Ur ] kV 245 (252)

(*)
Rated Current [ Ir ] A 1250 - 3150

(*)
Rated Short-Time withstand Current [ Ik ], up to… kA x s 50 x 3
(*)
Rated Peak withstand Current [ Ip ], up to… kA 125

Rated Power Frequency Withstand voltage [ Ud ]


(*)
- To ground and between poles kV 395 - 460
(*)
- Across the insulating distance kV 460 - 530

Rated Lightning Impulse Withstand Voltage [ Up ]


(*)
- To ground and between poles kV 950 - 1050
(*)
- Across the insulating distance kV 1050 - 1200

Rated Switching Impulse Withstand Voltage [ Us ]

- To ground and between poles kV N.A.


- Across the insulating distance kV N.A.

(*) = see specific installation drawing.


See the instruction manual of the drive for the technical data of the drive.

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 77/78

ATTACHMENT “B”: TIGHTENING TORQUES FOR SCREWS & BOLTS


STAINLESS STEEL HOT-ZINCED STEEL
Nominal diameter SCREWS BOLTS SCREWS BOLTS
Nm Nm Nm Nm
M4  1.5  
M5  3  
M6 4.5 5  
M8 11 12  
M10 19 23  
M12 32 40 58 65
M14 50 63 90 105
M16 78 95 140 160
M18  126 190 220
M20  175 270 300
M22  240 360 400
M24  320 470 520

WARNING: in the case of connections of stainless steel with hot-zinced steel,

comply with the stainless steel values

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
D0496-04-EN 78/78

ATTACHMENT “C”: RECORDING FORM FOR COMMISSIONING OF SWITCHGEARS

Customer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S/S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type of switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Serial No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring diagram DIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation drawing DIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1) CHECKS:
Remarks or
Sign after test measured values
1.1 Dimensional check according to installation drawing
1.2 Verification of verticality of installed insulators
1.3 Verification of correct installation of drive
1.4 Verification of alignment and coupling of fixed and mobile
contacts
1.5 Verification of correct installation of shafts and transmission
components

2) TEST OF OPERATION:
Remarks or
Sign after test measured values
2.1 Perform 5 manual operations and check that the opening and
closing movements are correct
2.2 Perform 5 motor operations and check that the end positions
are correctly reached
2.3 Verify the correct signaling of the auxiliary contacts

3) CURRENT CONSUMPTION OF MOTOR (maximum value excluding the starting peak):


3.1 Perform 5 operations and write the average value of the measures:
EARTHING SWITCH EARTHING SWITCH
POLE DISCONNECTOR VOLTAGE
(mobile contact side) (fixed contact side)
CLOSING OPENING CLOSING OPENING CLOSING OPENING
A (A) (A) (A) (A) (A) (A) (V)
B (A) (A) (A) (A) (A) (A) (V)
C (A) (A) (A) (A) (A) (A) (V)

4) CONTACT RESISTANCE OF MAIN CIRCUIT:


POLE RESISTANCE ENV. TEMP. CURRENT

A (µW) (°C) (A)


4.1 Reference value . . . . . . . . . µW at 20°C ±20% B (µW) (°C) (A)
C (µW) (°C) (A)
After the above verifications we declare that, as far as we are concerned, the switchgear is suitable to be put in service.

Signature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Date: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art.2359 of the Italian Civil Code.

You might also like