ASSESSMENT REPORT

Introduction

Description of Equipments
Equipment Details
Quantity: 1
Manufacturer: Sinvac
Status: Good
Existence: Yes

Main Control Panel

Quantity: 1
Manufacturer: Sinvac
Status: Good
Existence: Yes

Chlorine dosing tank


Quantity: 1
Manufacturer: Sinvac
Status: Good
Existence: Yes

Causatic dosing tank

Quantity: 1
Manufacturer:
Status: Good
Existence: Yes

Ferric tank

Quantity: 2
Manufacturer: Grundfoss
Status: Good
Existence: Yes

Raw water pump


Quantity: 2
Manufacturer: Rapid Alweir
Status: Dismantled
Existence: No

Semi-treated water pump

Backwash pump Quantity: 2


Manufacturer: Rapid Alweir
Status: Unknown
Existence: No

Air blower Quantity: 1


Manufacturer: Sowerby
Status: Unknown
Existence: No

Equipment is being used at different site.

Quantity: 1
Manufacturer: Etatron
Status: Good
Existence: Yes

Ferri/Flocculent dosing pump


Quantity: 1
Manufacturer: Tekna ACL 602 ASP
Status: Good
Existence: Yes

Chlorine dosing pump

Quantity: 1
Manufacturer: Etatron
Status: Good
Existence: Yes

Caustic dosing pump

Quantity: 2
Manufacturer: Rapid Alweir
Status: Defective Solenoid
Existence: Yes

Valves

In-line mixer Quantity: 1


Manufacturer: VWS
Status: Unknown
Existence: No
Quantity: 4
Status: Unknown
Existence: Yes

Flow indicator

Quantity: 1
Manufacturer: E+H
Status: Good
Existence: Yes

Equipment has a blur screen which needs replacement

Flow transmitter

Quantity: 1
Manufacturer:
Status: Defective
Existence: Yes

pH transmitter
Quantity: 1
Manufacturer: E+H
Status: Defective
Existence: Yes

Turbidity transmitter

Quantity: 1
Manufacturer:
Status: Defective
Existence: Yes

Free chlorine transmitter

Quantity: 6
Manufacturer:
Status: Unknown
Existence: Yes (Only 2)

Level switch
Quantity: 4
Manufacturer:
Status: Defective
Existence: Yes

Differential pressure switch

Flow switch Quantity: 2


Manufacturer:
Status: Unknown
Existence: No

Quantity: 2
Manufacturer: Telemechanique (Zelio)
Status: One in good condition, one defective
Existence: Yes

PLC base
Status: Good
Existence: Yes

The existing pipping has been replaced with new ones,


however instrumentation points/sources were not
considered.

Pipping

Status: Defective
Existence: Yes

Cable tray used are of sub-standard.

Cable tray arrangement

Status: Defective
Existence: Yes

Control cables to be replaced.


Power cable to be redressed.

Scattered Cables
Status: Good
Existence: Yes

Dosing point to be cleaned.


Manual valve to be replaced.

Chemical dosing point

Status: Bad
Existence: Yes

Rubber tubes to be connected to source.

Status: Bad
Existence: Yes

Rubber tubes to be connected to source.


Summary

Recommendations
Quotation of Equipments
Item Lead
No Code Description Time UoM Qty Unit Price Total
1 17219 Endress+Hauser Electromagnetic 4 weeks Ea 1 8,840.00 8,840.00
Flowmeter Promag W400, DN10

Approval: Non-hazardous area Design:


Fixed flange Power Supply:100-
240VAC/24VAC/DC Output; Input:4-
20mA HART, pulse/freq., switch output
Housing: Compact, alu, coated Cable,
Remote Version: Not used Electrical
Connection: Gland M20 Liner:
Polyurethane Process Connection:PN16,
carbon steel, flange EN1092-1
Electrodes:1.4435/316L Calibration
Flow:0.5% Operation Language Display:
English Application Package: Heartbeat
Verification + Monitoring

2 17219 Endress+Hauser Electromagnetic 4 weeks Ea 1 8,432.00 8,432.00


Flowmeter Promag W400, DN80

Approval: Non-hazardous area Design:


Fixed flange Power Supply:100-
240VAC/24VAC/DC Output; Input:4-
20mA HART, pulse/freq., switch output
Housing: Compact, alu, coated Cable,
Remote Version: Not used Electrical
Connection: Gland M20 Liner:
Polyurethane Process Connection:PN16,
carbon steel, flange EN1092-1
Electrodes:1.4435/316L Calibration
Flow:0.5% Operation Language Display:
English Application Package: Heartbeat
Verification + Monitoring

3 17211 Endress+Hauser Multiparameter 4 weeks Ea 1 22,440.00 22,440.00


Liquiline CM448

Approval: Non-hazardous area Digital


Communication: HART Digital Sensor;
Output; Input: 8x; 8x 0/4..20mA, 4x
relay; none Power Supply:100...230VAC
(50/60Hz) Cable Entry Housing, Sensor:
Metric, Metric Female Jack Fieldbus
Communication: W/o Cable Entry
Set+female Jack: Mounted Presetting
Operation Language: English Software:
Heartbeat Verification+Monitorin

4 17208 Endress+Hauser Turbidity Sensor 4 weeks Ea 1 13,600.00 13,600.00


Turbimax CUS52
Approval: Non-hazardous area
Measuring Method: ISO 7027, IR
Process Connection: Clamp 2" Adaption
Cable: Fixed cable, M12 plug Cable
Length:15m

5 17208 Endress+Hauser Turbidity Sensor 4 weeks Ea 1 4,352.00 4,352.00


Assembly Flowfit CUA252

Approval:Non-hazardous area Process


Connection: Male thread G1 1/4
Material, Wetted Parts: PE100 Seal,
Wetted Parts: EPDM

6 17210 Endress+Hauser Free Chlorine Sensor 4 weeks Ea 1 8,024.00 8,24.00


Memosens CCS51D

Approval: Non-hazardous area


Application: Process water, drinking
water Measuring Range:20 mg/l
Calibration solution: Zero-point gel
COY8

7 17210 Endress+Hauser Free Chlorine Sensor 4 weeks Ea 1 4,532.00 4,532.00


Assembly FLOWFIT-W CCA250

Process Connection; Adapter:G1/2; w/o


Proximity Switch:Installed, INS

8 17206 Endress+Hauser pH Sensor Memosens 4 weeks Ea 1 1,700.00 1,700.00


CPS31D

Version: Basic version Application


Range:1-12pH; 0-80oC; 3 diaphragm
Shaft Length:120 mm Approval: Non-
hazardous area

Technical buffer solution CPY2

9 17206 Endress+Hauser pH Sensor Memosens 4 weeks Ea 1 1,700.00 1,700.00


CPS11D

Version: Basic version Application


Range:1-12pH; -15...80oC, 6 bar Shaft
Length:120 mm Approval: Non-
hazardous area

Technical buffer solution CPY20

10 17206 Endress+Hauser pH Sensor Assembly 4 weeks Ea 1 5,236.00 5,236.00


Cleanfit W CPA450

Immersion depth max.; Material:100mm;


316L Process connection: thread G 1-
1/4" male, 316L Material; seal: EPDM
Equipment; Cable protection: w/o, with

11 17206 Endress+Hauser Memosens Cable 4 weeks Ea 3 1,360.00 4,080.00


CYK10

Approval: Non-hazardous area Cable


Length:15m Cable Connection:M12 plug

Subtotal 82,936.00

VAT 2,488.08

Total 85,424.08