FAT procedure
Purchase Order No: 75000…. Material Req.No: 3844-..-MR-…..
THIS DOCUMENT IS INTENDED FOR USE BY ADCO AND ITS NOMINATED CONSULTANTS, CONTRACTORS, MANUFACTURERS AND SUPPLIERS.
CONTRACTOR:
Rated voltage: 36 kV
Operating voltage: 33 kV
Rated lightning impulse withstand voltage: 170 kV
Rated power frequency withstand voltage: 70 kV
Rated frequency 50 Hz
Rated short-time withstand current: 25 kA
Rated duration of short-circuit: 3s
Rated peak withstand current: 63 kA
Rated busbar current: 1250 A
Participants
The tests could carry out on each panel, which the inspector will select. All panels are
final tested.
Our Ref.: 243311443 Rev. 0
Date: 18.04.2016
Page 2 of 8
Our Ref.: 243311443 Rev. 0
Date: 18.04.2016
Page 3 of 8
Our Ref.: 243311443 Rev. 0
Date: 18.04.2016
Page 4 of 8
Our Ref.: 243311443 Rev. 0
Date: 18.04.2016
Panel Busbar L1 L2 L3
BB ...µohm ...µohm ...µohm
Page 5 of 8
Our Ref.: 243311443 Rev. 0
Date: 18.04.2016
1.1Un/1.1Un/V3 = 100/10pC
Page 6 of 8
Our Ref.: 243311443 Rev. 0
Date: 18.04.2016
Items :
ABB commitment Industrial and application knowledge
Ability to manage complexity
Partnering for mutual benefit
Easy doing of business