Relion® 670 series

Your best choice for transmission applications

REC670 Bay control IED


REL670 Line distance protection
RED670 Line differential protection
RET670 Transformer protection
REG670 Generator protection
REB670 Low impedance busbar protection
RES670 Phasor measurement unit

Unmatched flexibility in the form of


functional integration!
Relion® 670 series
REL670
RED670

RET670 REC670

REB670 REG670 Generator protection IED for


Busbar protection IED for Medium to large sized generators

Autotransformers
Shunt Reactors
Shunt Capacitors
Relion® 670 series
Features

Up to 24 analogue inputs
Expandable I/O
½ 19” case, ¾ 19” case, full 19” case
Extensive communication facilities
IEC 61850-8-1 (redundant; PRP)
IEC61850-9-2 (process bus)
IEC 60870-5-103
LON
SPA
DNP 3.0
TCP/IP communication to the
PCM 600 tool
ANSI C37.94 for teleprotection
Graphical HMI
Functionality
High speed operation
Multiple instances of same function
Multi-terminal (<5) Line diff
GPS time synch
Large installed base (approx. 65,000 units)
Platform
Relion® 670 series
Hardware
SOM
(max 3)

MIM
(max 3)

IOM
(max 3)

BOM
1/2 Case (max 3)
12 binary outputs
•1TRM BIM and 8 binary inputs
(max 3)
•< 3 I/O modules
24 binary outputs
max

16 binary inputs

Available I/O-modules ½ 19” case


Platform
Relion® 670 series
Hardware
11*CAN 3*PCI

PSM

TRM1
TRM2

I/O GSM NUM ADM2 ADM1


Platform
Relion® 670 series
Hardware

With RTXP 24 Test Switch


Platform
Relion® 670 series
Main Application Functions in the 670 Series
Five Zone full scheme distance protection
Five terminal line differential protection
Six input transformer differential protection
High impedance and restricted EF differential
Ultra High Speed bus differential protection
Phase segregated directional comparison
Adaptive Breaker Failure Protection
Four step Dir/Undir overcurrent protection
Four step Dir/Undir earthfault protection
Over Excitation & Over Load Protection
Multi bay & Multi breaker Control, AR & SC
Multi input measurement (24 AI)
High accuracy fault locator
Platform
Relion® 670 series
Software AFL
Base software Line Distance Protection
Application Function Library ZCOM
ZCAL L3D
The IEC 61850 standard allows an THL BFP
open structure with free allocation ZM TEF
of functions AR
TOC TOV OEX
Gives the user the freedom of SYN T2D
choice to design his protection and TTR
control solution exactly as needed
Transformer Protection
Protection, control and monitoring
functions can be integrated or
distributed in any IED, exactly
according to the user’s architecture
and redundancy requirement
Relion® 670 series
Your best choice for transmission applications

REC670 Bay control IED


REL670 Line distance protection
RED670 Line differential protection
RET670 Transformer protection
REG670 Generator protection
REB670 Low impedance busbar protection
RES670 Phasor measurement unit
Relion® 670 series
REC670 Bay controller Apparatus control of up to 30 apparatus
Multi-object (CB) and Multi-bay control
capability for handling several bays with a
single IED
Modeled according to IEC 61850
Select before operate with enhanced
security
Ready to use interlocking modules for
different switchgear arrangements
Integrates comprehensive back-up
protection functionality
Capacitor bank protection available
Autorecloser and Synchrocheck
Binary signal transfer to remote
Monitoring functions
Pre-configured or customized
Relion® 670 series
Your best choice for transmission applications

REC670 Bay control IED


REL670 Line distance protection
RED670 Line differential protection
RET670 Transformer protection
REG670 Generator protection
REB670 Low impedance busbar protection
RES670 Phasor measurement unit
Relion® 670 series
REL670 Line distance protection
Main Applications:
All voltage levels
OH-lines
Cables
Multi-breaker arrangements
Double circuit lines
Directly earthed or resonantly
earthed networks
Single-, two- or three pole trip
Series compensated lines

Main
Technology Summary REL670
Most Important Protection Functions

Distance protection
5 zone full-scheme high-speed line
distance protection with quadrilateral,
Mho- or series compensation
characteristics, and with scheme
communication logic and load
encroachment discrimination
Selective phase selection and automatic
switch on to fault logic
Current reversal and weak end infeed
logic
Power swing detection and blocking
Phase preference logic
Pole slip protection
Relion® 670 series
REL670 Summary

High speed and reliable line protection functions


Excellent for series compensation and in HVDC
vicinity
Multi-object and multi-terminal capability
Autorecloser and synchrocheck
Apparatus control able to be integrated in the line
protection
Full compatibility in scheme communications
between 670 series and 650 series
Full IEC 61850 compatibility
Full engineering capability to the customer needs
Relion® 670 series
Your best choice for transmission applications

REC670 Bay control IED


REL670 Line distance protection
RED670 Line differential protection
RET670 Transformer protection
REG670 Generator protection
REB670 Low impedance busbar protection
RES670 Phasor measurement unit
Line differential protection RED670
670 series

The IED for simple and complex


networks with phase-segregated line
differential protection
Multi-terminal lines with communication
for up to 4 remote line ends
Transformer in the protected zone
Tapped lines, also with transformer
included
Short lines
Long lines with charging current
compensation

© ABB Group
November 2010
Slide 62
Relion® 670 series
Line Data Communication Module

LDCM modules
mount on
A/D module

LDCM modules available for short range, medium


range and long range optical connections, as well
as X.21 galvanic
Relion® 670 series
RED670 Line differential protection
LDCM with direct fiber (multi mode max 3 km)

LDCM with direct fiber (single mode max 30 / >100 km)

Remote communication
Relion® 670 series
RED670 Line differential protection

Single or redundant
channels

Single or 1½
breaker

With or without
transformer

Master-master or
Master-slave com. system
Relion® 670 series
Your best choice for transmission applications

REC670 Bay control IED


REL670 Line distance protection
RED670 Line differential protection
RET670 Transformer protection
REG670 Generator protection
REB670 Low impedance busbar protection
RES670 Phasor measurement unit
Relion® 670 series
RET670 Transformer differential protection

Power transformers, including


autotransformers, reactors,
generator transformer blocks
Phase shifting transformers
Two or three winding transformers
Single or multi circuit breaker
arrangements
Up to six stabilized 3-phase current
inputs
Relion® 670 series
RET670 Transformer differential protection
Single and multiple circuit breaker arrangements
Two-winding transformer Three-winding transformer
Up to 4 three-phase CT inputs Up to 6 three-phase CT inputs
Relion® 670 series
RET670 Transformer differential protection

Integrated breaker control available (30


apparatus)
Capacitor bank protection available
Four-zone full scheme distance protection
Protect and control of the transformer
and a line with a singe IED
Back-up protection for faults within the
transformer
Versatile overcurrent and thermal overload
protection
Extensive back-up protection
Breaker failure protection
Relion® 670 series
Functional integration examples
(Multi object capability)

Protect transformer and line with


one RET670

Transformer 1

Protect two transformers, each


with its own differential
RET670
protection, with one RET670

Transformer 2
Relion® 670 series
Functional integration examples
(Multi object capability)
Line differential protection with
RED670 RED670
integrated distance protection and
control functionality
87L

RET670
RET670
Transformer protection with
communication for line differential
87T
and control functionality
Relion® 670 series
Your best choice for transmission applications

REC670 Bay control IED


REL670 Line distance protection
RED670 Line differential protection
RET670 Transformer protection
REG670 Generator protection
REB670 Low impedance busbar protection
RES670 Phasor measurement unit
Relion® 670 series
REG670 Generator protection

REG670 provides extensive protection


and monitoring functionality for
generators
Stator Earth Faults
Rotor Earth Faults
Stator Short Circuits
Stator/Rotor Interturn faults
External faults
Abnormal Operation

© ABB Group
November 2010
Slide 75
Generator protection REG670
670 series
Up to 24 analog inputs per IED permit
integration of main and back-up
protection in one IED and/or additional
objects
REG 670 enables full duplication of the
protection in main one and main two
and at the same time reducing the
number of IEDs
The protection is used for all type/sizes
of generators from 2 to 1200MW
The combination of generator and
G transformer protection in one IED is
unique on the world market.

87G 87T

87O
21G

51/27
51V
© ABB Group
November 2010
Slide 76
Protection Concept: Overlapping Principle
670 series
87G 87T

System A

87G 87T
87GT 21G

87GT 51/27
21G
System B

51/27

Overlapping Principle used for small Generators:


Main and back-up functional scheme
System A for main protection, System B for back-up protection
Different algorithms in main and back-up to cover the same type of fault,
e.g. 87G – 21, 87T – 87GT
Protection Concept: Duplication Principle
670 series
87G 87T

Relay A

87G 87T
87G 87T

87G 87T Relay B

Duplication Principle used for normal and big Generators:


Main1 and Main2 functional scheme
Protection functions are duplicated in System A and System B e.g. 87G.1 –
87G.2 , 87T.1 – 87T.2
Both systems have the same availability and selectivity
Relion® 670 series
Your best choice for transmission applications

REC670 Bay control IED


REL670 Line distance protection
RED670 Line differential protection
RET670 Transformer protection
REG670 Generator protection
REB670 Low impedance busbar protection
RES670 Phasor measurement unit
Busbar protection REB670
670 series

Features complete
protection and monitoring for
Busbars
T-connectors
Meshed corners

Provides selective, reliable


and fast fault clearance
Continues ABB’s strong
track record in busbar
protection

Very fast and stable busbar protection

© ABB Group
November 2010
Slide 81
Relion® 670 series
REB670 Busbar differential protection
Two busbar differential protection zones
Overall check zone
Integrated, software driven zone selection (i.e. disconnector
replica)
Breaker failure protection
Selective tripping for busbar and breaker failure protection
Four-step, non-directional, phase overcurrent protection with
definite and inverse time characteristics
Autoreclosing function for busbar restoration after IED operation
Configurable logic blocks
Disturbance recording
Relion® 670 series
REB670 for single buses
ZA ZB
ZA

Single Busbar Single Bus with bus tie CB


up to 4/8 feeder bays up to 3/7 feeder bays on each side

ZA
ZA ZB

ZB
H type station with bus-section CB
or sectionalizing disconnector
Alternative CT Location
T connections
Relion® 670 series
REB670 1-ph for single buses

ZA
.. . ZA
.. . .. .
ZB

Single Bus
Single Bus with bus-section disconnector
up to 12/24 feeder bays
up to 12/24 feeder bays (i.e. 12+12; 16+8 etc.)

ZA ZB ZA ZB
.. . .. . .. . .. .

Single Bus with bus-section CB, up to Single Bus with bus-section CB


11/23 feeder bays (i.e. 12+11; 10+13 etc.) up to 11/23 feeder bays on each side
Relion® 670 series
Your best choice for transmission applications

REC670 Bay control IED


REL670 Line distance protection
RED670 Line differential protection
RET670 Transformer protection
REG670 Generator protection
REB670 Low impedance busbar protection
RES670 Phasor measurement unit
Phasor measurement unit RES670
670 series
RES670 provides extensive
protection, monitoring and control
functionality
Overcurrent protection
Phase
Residual
Negative sequence
Overvoltage protection
Undervoltage protection
Frequency protection
Over frequency
Under frequency
Rate of change
Configurable logic

© ABB Group
November 2010
Slide 88
Relion® 670 series
Your best choice for transmission applications

REC670 Bay control IED


REL670 Line distance protection
RED670 Line differential protection
RET670 Transformer protection
REG670 Generator protection
REB670 Low impedance busbar protection
RES670 Phasor measurement unit

Unmatched flexibility in the form of


functional integration!
Where to use PCM600?
Protection and Control IED Manager PCM600

IED configuration Communication


configuration

PCM600

Application
configuration

Monitoring

Display
configuration
Protection and Control IED Manager PCM600
Intuitive and familiar user environment

541 / 543 / 545 series

SPACOM series *)
REF542plus
670 series

650 series

630 series

615 series

610 series

REX521
PCM600 Selection Table
Signal matrix tool x x x x
Parameter setting x x x x x x x x x

PCM600 Engineering

PCM600 Engineering Pro


Communication management x x x x

PCM600
Disturbance handling x x x x x x x x
Signal monitoring x x x x x x x x
Event viewer x x x x x
Creating/Handling projects x x x x x x x x x
IED user management x x x x x
Graphical application configuration x x x
Graphical display editor x x x
Hardware tool x x x
IEC 61850 communication configuration, incl.
GOOSE x x x x
*) SPAD 346 C, SPAJ 140 C, SPAJ 141 C, SPAJ 142 C, SPAJ 144 C, SACO 16D1, SACO 16D3 and SACO 64D4