SPECIFICATION
SETTING PROTECTION
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
PROTECTION RELAY
EARTH
OVER CURRENT
FAULT
INST P.U (Ii) RELAY
LTD (s) STD (s) RELAY
(…xIr) I = 100 - 120%
I = 15%
T = 2.5 Sec
T = 5 sec
114%
91%
73%
57%
50%
OTECTION RELAY
REVERSE POWER
RELAY CURRENT
Turbin = 4% TRANSFORMER
Genset = 8%
4% 4000/5A.
4% 5000/5
8% 1600/5
8% 1600/5
8% 800/5
GENERATOR
SPECIFICATION
MAGNAPLUS
Genset 320kW MARATHON 433CSI6220 320 608
ELECTRIC
MAGNAPLUS
Genset 300kW MARATHON 433PSL1371 300 570
ELECTRIC
0.4
0.04
0.06
0.16
0.32
0.98 0.85
ACB / MCCB
SETTING PROTECTION
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
0.13
PROTECTION RELAY
EARTH
OVER CURRENT
FAULT
INST P.U (Ii) RELAY
LTD (s) STD (s) RELAY
(…xIr) I = 100 - 120%
I = 15%
T = 2.5 Sec
T = 5 sec
91%
91%
85%
71%
95%
OTECTION RELAY
REVERSE POWER
RELAY CURRENT
Turbin = 4% TRANSFORMER
Genset = 8%
3000/5A
3000/5
800/5
800/5
800/5
1200/5
GENERATOR
SPECIFICATION
MERLIN
4000 1.05 50 2 x Ir
GERIN
SETTING PROTECTION
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
PROTECTION RELAY
EARTH
OVER CURRENT
FAULT
INST P.U (Ii) RELAY
LTD (s) STD (s) RELAY
(…xIr) I = 100 - 120%
I = 15%
T = 2.5 Sec
T = 5 sec
REVERSE POWER
RELAY CURRENT
Turbin = 4% TRANSFORMER
Genset = 8%
4% 4000/5A
4% 2000/5A
4% 2000/5A
8% 400/5A
8% 1000/5A
8% 1000/5A
8% 1000/5A
GENERATOR
SPECIFICATION
LSA 47.1L10
Genset 400kW LEROY SOMER
C6/3
400 760
ACB
MERLIN
4000 0.91 50 2 x Ir
GERIN
MERLIN
1000 0.64 50 2 x Ir
GERIN
MERLIN
1000 0.91 50 2 x Ir
GERIN
ACB / MCCB
SETTING PROTECTION
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
2 x Ir 1 x Ir 50 0.3 2 x Ir
PROTECTION RELAY
EARTH
OVER CURRENT
FAULT
INST P.U (Ii) RELAY
LTD (s) STD (s) RELAY
(…xIr) I = 100 - 120%
I = 15%
T = 2.5 Sec
T = 5 sec
REVERSE POWER
RELAY CURRENT
Turbin = 4% TRANSFORMER
Genset = 8%
4% 4000/5A
4% 3000/5A
8% 1000/5A
8% 1000/5A
GENERATOR
SPECIFICATION
Ir (…xIn)
POM TURBIN/GENSET KW A In Long Time Current
Setting
EARTH
OVER CURRENT REVERSE POWER
FAULT
RELAY RELAY
RELAY CT
I = 100 - 120% Turbin = 4%
I = 15%
T = 2.5 Sec Genset = 8%
T = 5 sec