GS ABB ACS550 Inverter setting Table

Inverter Defaults Setting GS Series Defaults Setting


Item Code Name Function Setting Range
ACS550 ACS550
1 9901 LANGUAGE Language Select 0-10 ENGLISH ENGLISH
2 9902 APPLIC MACRO Application Macro 1-12 1 (ABB STANDARD) 6 (PID CTRL)
1-3(1=Vector : Speed
3 9904 MOTOR CTRL MODE Motor Control Mode 2=Vector : Torque 3 (SCALAR:Speed) 3
3=Scalar:Speed)
4 9905 MOTOR NOM VOLT Motor Nominal Voltage 200V-600V 380 V Motor Nominal Voltage
5 9906 MOTOR NOM CURR Motor Nominal Current 0.2In-2.0In 1.0*Ihd Motor Nominal Current * Motor SF Value
6 9907 MOTOR NOM FREQ Motor Nominal Frequency 10-500HZ 50 Hz Motor Nominal Frequency
7 9908 MOTOR NOM SPEED Motor Nominal Speed 50-18000rpm 1440 Motor Nominal Speed
8 9909 MOTOR NOM Motor Nominal Power 0.2-2.0Phd 1.0*Phd Motor Nominal Power * Motor SF Value
0-1(0=OFF,1=ON)
9 9910 MOTOR ID RUN Motor ID Run (0) OFF 0
1-3
10 1001 EXT1 COMMANDS External Commands 1(EXT1) 0-10 1 1 (DI1)
11 1002 EXT2 COMMANDS External Commands 2(EXT2) 0-10 1 1 (DI1)
12 1003 DIRECTION Direction 1- (3)REQUEST 1 (FORWARD)
13 1102 EXT1/EXT2 SEL EXT1/EXT2 Select 0...8,-1...-6 3 (DI3)
14 1103 REF1 SELECT Reference Setting(1) signal source 0-38 1 (AI 1) 2 (AI 2)
15 1104 REF1 MIN Reference Setting(1) Minimum Value 0~500HZ 0 Hz Parameter 1105 Setting Value 40%
16 1105 REF1 MAX Reference Setting(1) Maximum Value 0~500HZ 50 Hz Depends On Models
17 1106 REF2 SELECT Reference Setting(2)signal source 0-19 19 19 (PID1 OUT)
18 1107 REF2 MIN Reference Setting(2) Minimum Value 0~100% 0% 0%
19 1108 REF2 MAX Reference Setting(2) Maximum Value 0~100% 100% 100%
20 1201 CONST SPEED SEL Constant Speed Select 0…14,-1...-14 9 11 (DI5,6)
21 1203 CONST SPEED 2 Constant Speed 2 0~500HZ 10 Hz Parameter 1105 Setting Value 90%
22 1402 RELAY RO2 OUTPUT Relay RO2 Output 0-36 2 10 (SUPRV2 OVER)
23 1406 RO 2 ON DELAY RO2 On Delay 0~3600s 0s 20s
24 1304 MINIMUM AI2 AI2 Minimum Limits 0~100% 20% 20%
25 1305 MAXIMUM AI2 AI2 Maximum Limits 0~100% 100% 100%
26 1403 RELAY OUTPUT 3 Relay Output 3 0-34 3 (Fault-1) 4 (Fault)
27 1601 RUN ENABLE Run enable 0-7,-1~-6 0 (NOT SEL)
28 1602 PARAMETER LOCK Parameter Lock 0~2(0=Locked,1=Open,2=Not 1 1 (Note 1)
29 1603 PASS CODE Pass code 0~65535 358 358
30 1606 LOCAL LOCK Local Lock 0...8,-1...-6 0 7 (ON)
1.8*Ihd
31 2003 MAX CURRENT Maximum Current Limits 0~1.8*Ihd 1.8*Ihd
(Ihd is the Lowest Iverter Nominal Current)
32 2007 MINIMUM FREQ Minimum Frequency Limits -500~500HZ 0 Hz Parameter 2008 Setting Value 40%
33 2008 MIAXIMUM FREQ Maximum Frequency Limits 0~500HZ 50 Hz Depends On Models
34 2101 START FUNCTION Start Function 1~5(1=Auto) 1 (AUTO) 1 (AUTO)
35 2102 STOP FUNCTION Stop Function 1~2(1=Coast,2=Ramp) 1 (COAST) 2 (RAMP)
36 2201 ACC/DEC 1/2 SEL ACC/DEC Speed Curve select 0…6,-1...-6 5 0 (NOT SEL)
37 2202 ACCELER TIME 1 Acceler Time 1 0~1800s 5.0 s 30 s
5.0 s
(If Parameter 2102
38 2203 DECELER TIME 1 Deceler Time 1 0~1800s 30 s
or2103setting in 2, Parameter
2203 useful)
39 2606 SWITCHING FREQ Switching Frequency 1,4,8 kHz 4 kHz 8 kHz
40 3010 STALL FUNCTION Stall Function 0~2 0 (NOT SEL) 1 (FAULT)
41 3204 SUPERV 2 PARAM Select second supervised parameter 0104 (CURRENT)
Setting second supervised parameter
42 3205 SUPERV 2 LIM LO Parameter 3206 Setting Value * 0.9
Low Limits
Motor Nominal Current * (Motor SF
Setting second supervised parameter
43 3206 SUPERV 2 LIM HI Value+0.05) or
high Limits
the Lowest Iverter Nominal Current
44 4001 GAIN PID Gain 0.1-100 1 2,0
45 4002 INTEGRATION TIME PID Integration Time 0.0 s = NOT SEL,0.1-600 s 60 s 4s
46 4003 DERIVATION TIME PID Derivation Time 0-10s 0s 0s
47 4004 PID DERIV FILTER PID Derivation Filter Time 0-10s 1s 1s
48 4006 UNIT Unit 0-31 % 22 (bar) / 25(PSI)
49 4007 DSP FORMAT Display format 0-4 1 1
Unit and scale defined by parameter
50 4008 0% VALUE 0% Value 0 bar 0 bar
4006 and 4007
Unit and scale defined by parameter
51 4009 100% VALUE 100% Value 100 bar 16 (bar) / 232(PSI)
4006 and 4008
52 4010 SET POINT SEL Set Point Select 0-19 19 (INTERNAL)
Unit and scale defined by parameter Operating Pressure bar
53 4011 INTERNAL SETPNT Internal Set Point 40 bar
4006 and 4008 (Same as SE Controller Cut-In Pressure)
54 4016 ACT1 INPUT ACT1 Input 1-5 2 2 (AI 2)
55 4017 ACT2 INPUT ACT2 Input 1-5 2 2 (AI 2)
Over Current auto reduce speed setting wiring (Standard) Motor High Temperature Auto reduce speed setting Wiring(Option)
GS ABB ACS550 Inverter setting Table

(Option setting fot Motor High Temperature Auto reduce speed)


56 1001 EXT1 COMMANDS External Commands 1(EXT1) 0-10 1 1 (DI1)
57 1002 EXT2 COMMANDS External Commands 2(EXT2) 0-10 1 1 (DI1)
58 1102 EXT1/EXT2 SEL EXT1/EXT2 Select 0-8,-1...-6 3 (DI3)
59 1201 CONST SPEED SEL Constant Speed Select 0~-2 11 (DI5,6)
60 1202 CONST SPEED 1 Constant Speed 1 0~500HZ 5 Hz Parameter 1105 Steeing value 70%
61 1204 CONST SPEED 3 Constant Speed 3 0~500HZ 15 Hz Parameter 1105 Setting Value70%
62 1401 RELAY RO1 OUTPUT Relay RO1 Output 0-36 8 (SUPRV1 OVER)
63 1404 RO 1 ON DELAY RO 1 On Delay 0~3600s 0s 20s
64 3201 SUPERV 1 PARAM Select First supervised parameter 0145 (MOTOR TEMP)
Setting First supervised parameter
65 3202 SUPERV 1 LIM LO 125℃
Low Limits
Setting First supervised parameter
66 3203 SUPERV 1 LIM HI 135℃
High Limits
67 1501 AO1 CONTENT AO1 Content 99-199 100 (EXCITE = PT100)
68 3501 SENSOR TYPE Motor temperature sensor type 0-4 1 (1 x PT100)
69 3503 ALARM LIMIT Motor temperature alarm limits -10~200 140℃
70 3504 FAULT LIMIT Motor temperature fault limits -10~200 150℃
Note 1:ACS550 Model:Parameter[1602] need to input value in "1",then could be madify and save the parameter.
After parameter setting or modified. Please setting the parameter[1602] to "0" to lock the parameter setting for protect the user adjust it without any authorizationthe.
When the parameter need to change again.
First into the parameter [1603], input the passcode 358.
Then into the parameter [1602] input to "1" to open the parameter setting eable.

Note2:Parameter[1602] "parameter lock" will (need to) lock after maunfacture test running.

Note3:The item 56 (parameter [1001]) to item 70 (parameter [3504]) are for moter high temperature reducing speed setting.
If customer option the temperature sensor "RTD PT100" for motor protect.
For standard model do not need to setup parameter item 56~70.