INSTRUCTIVO DE PRUEBA
Rev. 01
ALTO VOLTAJE (HIGH POT) 10 /06/ 2014
C.H. HUANZA
5. Test procedure
High voltage output of test equipment connection to the Single-phase of generator stator,
short connecting the other two、shell and grounding connection.
The connecting cable, ensure each point for good contact. The shortest distance between a
contact of grounding and divider.
Test steps
1 according to the various connection method of samples, ensure each point for good contact,
one point grounding, and recently of divider.
2 ensure that the connection is correct after electrify.
3 open the switch of host power will display the main menu
System parameter setting Test operation
Test parameter setting Main menu wiring help
4 Move the cursor to ‘test of parameter settings’; press confirm key. Modifies various
parameters, use the up and down and confirm key to execute.
5: Move the cursor to ‘system parameter setting’: press confirm key. Modifies time
parameters , use the up and down and confirm key to execute.
If choose manual test, test process through the test manual adjusting
frequency、voltage
If choose automatic test , test process will be according to the following parameters
7. Now connected to the IGBT input voltage for selection of test methods, test of samples,
use the confirm key to execute.
8 .Select the manual test, first is to find the resonance point of samples, using the up and
down key, make the test voltage at the highest point; please follow the pressure adjusting
button of panel with about the left or right key displacement ,the up key to increase the
excitation power , the right key move the cursor to after the decimal point and slowly increase
the power to prevent the samples breakdown when approaching the test voltage, the host
start automatic timing until to exit test after rated voltage . (You)don't need these
operations when select automatic test as long as the press confirm key
9. Pay attention to the safety distance of samples before entering the test, ensure the life
safety.
10 .Please do not arbitrarily change the main menu test operation,and the two coefficients
should be recorded in the instructions , prevent for missing.