Professional Documents
Culture Documents
Thomas J. Dionise, and ing process involved primary circuit switching that resulted in two voltage trans-
Robert Yanniello former (VT) failures. As a result, we conducted a comprehensive investigation
of the VT failures. As the investigation proceeded, VT ferroresonance on circuit
opening and high-frequency switching transients on closing emerged as possible
root causes of the failures. After incorporating extensive transient simulations
and three rounds of field transient measurements, we designed and implemented
a complete solution that included the sizing of snubbers to overcome excessive
switching transients and the development of a saturable reactor to protect VTs
against the effects of ferroresonance. This article describes the root causes, simu-
lations, field measurements, recommended solutions, and solution implementation
A Case Study of
Voltage Transformer Failures
©istockphoto.com/shironosov
10.0
ondaries and resulting TOVs at the line-end and bus VTs,
5.0 i.e., after mitigation was implemented.
0.0
Existing System Conditions (Baseline)
–5.0 A group of sequence operations was performed to cover
all operational scenarios of concern. These scenarios
–10.0
were opening and closing the UTS feeder breakers,
V Waveform Average AG switching between NM-A and NM-B, and UPM switching
–15.0
V Waveform Average BG
V Waveform Average CG
activities during various levels of power loading. A set of
–20.0
high-end portable power quality meters were connected to
1,000 : 1 voltage dividers to monitor three medium-volt-
0
0
64
66
68
70
72
74
.
age points of interest: NM-A line VTs, NM-B line VTs, and
35
35
35
35
35
35
0:
0:
0:
0:
0:
0:
:5
:5
:5
:5
:5
:5
17
17
17
17
17
Hours:Minutes:Seconds:Milliseconds installed on the secondary side of the NM-A line VTs and
the NM-B line VTs. The resultant waveforms were com-
FIGURE 5. The bus VT primary average. AG: phase A to ground; BG: pared for both baseline and solution testing. The wave-
phase B to ground; CG: phase C to ground. forms of interest for selected transients are d
iscussed in
the following sections.
system, including the switchgear and VTs online and bus-
side of the switchgear lineups, and performing a switching UTS Breaker Opening During Baseline Testing
transient study to quantify the transient overvoltage pro- During this scenario, a 5-kV square wave at 5–20 Hz was
duced by the 27-kV breakers at the UTS unit substations. measured during baseline testing. This is very typical
12.50 80
6.25 60
50
00
50
.0
.1
.1
V Waveform Average BN
05
05
05
0:
0:
0:
:3
:3
:3
V Waveform Average CN
17
17
17
Hours:Minutes:Seconds:Milliseconds
FIGURE 6. The primary line-to-ground voltage after the breaker is
opened, illustrating ferroresonance on phase B (from simulation). FIGURE 7. The bus VT secondary. AG: phase A to ground; BG: phase B
AN: phase A to neutral; BN: phase B to neutral; CN: phase C to neutral. to ground; CG: phase C to ground.
0
0
1
5
.6
.6
.6
.7
.7
.7
.4
.5
.5
.6
17
17
17
17
17
17
28
28
28
28
6:
6:
6:
6:
6:
6:
9:
9:
9:
9:
:2
:2
:2
:2
:2
:2
:4
:4
:4
:4
11
11
11
11
11
11
09
09
09
09
Hours:Minutes:Seconds:Milliseconds Hours:Minutes:Seconds:Milliseconds
FIGURE 9. The NM-A VT primary, from transients. AN: phase A to FIGURE 11. The bus VT primary, from baseline testing. AN: phase A to
neutral; BN: phase B to neutral; CN: phase C to neutral. neutral; BN: phase B to neutral; CN: phase C to neutral.
150,000
tured, as seen on the NM-A VT secondary (Figure 12).
100,000 The prestrike occurred during the switch closing on all
50,000 three phases, with the highest magnitude being 500 Vpk
0 at phase A. The prestrike at phase C had a magnitude
–50,000
of 135 Vpk, and the one at phase B had a magnitude of
260 Vpk. This is the line-to-ground voltage capacitively
–100,000
coupled from the primary to the secondary of the VT.
–150,000 The switch closing case was simulated by closing
–200,000 the UPM switch PD-B upstream of the NM-A VT, with a
cable length of 19 m and a pole disagreement of 0.4 ms.
85
90
95
00
05
.8
.8
.8
.9
.9
32
32
32
32
:
:
39
39
39
39
39
:
11
11
11
11
11
0.00
150
100 –6.25
50
0 –12.50
–50
–100 –18.75
–150
–200 –25.00
–250 0 4 8 12 16 *10–3 20
Time (s)
0
0
8
0
.8
.8
.8
.8
.9
3
:0
:0
:0
:0
:0
7
7
:2
:2
:2
:2
:2
V Waveform Average AN
11
11
11
11
11
●● cable circuits
●● equivalent stray capacitance at the switchgear and VTs Recorded Volts/Amperes/Hertz Zoomed Detail:
27 February 2014 11:39:10–27 February 2014 11:39:10
●● VTs (parameters that include saturation characteristics)
50
These are common circuit parameters represented in the
0
EMTP model and are usually available from manufacturers,
although equivalent stray capacitance across circuit vacuum –50
breaker contacts is difficult to obtain. When the vacuum
–100
interrupter contacts are fully parted inside the vacuum bot-
tle, a capacitance can be measured across the open contacts. –150
Although very small, it will have an effect on the transient –200
response following the opening of the breaker; this was
0
50
55
60
65
70
34
34
.3
.3
.3
.3
.3
0.
0.
10
10
10
10
:1
:1
9:
9:
9:
9:
39
39
39
:3
:3
:3
:3
:
11
11
11
11
11
11
11
11:39:10.288
11:39:10.266
Primary VT Voltage (V)
–2,338 V
200,000 ing circuit is needed, all of which were preferred by the
–170 V
150,000 owner of this data center. The simulations show that,
100,000
50,000 with small-reactor resistance, high-speed ferroresonance
0 damping is achieved much faster than the conventional
–50,000
–100,000 solution of damping resistors.
–150,000
–200,000 The proposed and effective solution for mitigating
–250,000 the ferroresonance is a saturable reactor, as shown in
–300,000
–350,000 Figure 16. After the upstream circuit breaker opens, there
will be a dc trapped voltage on the open line. With the VT
0
0
6
9
.2
.2
.2
0
:1
:1
:1
:1
9
:3
:3
:3
11
11
11
11
1,000
VT Saturable Reactor
PT
Current (mA)
100
100 Ω
Noninductive
22-kV Peak SA
17.5 kJ 10
0.25 µF at 27 kV
1
0.01 0.1 1 10
Voltage (V)
FIGURE 17. The snubber solution for mitigating transient overvoltage FIGURE 18. A custom saturable reactor designed to mitigate
at the VT. SA: surge arrestor. ferroresonance.
V Waveform Average BG
15.0 V Waveform Average CG 10.0
Primary VT Voltage (kV)
10.0 5.0
5.0 0.0
–5.0
0.0
–10.0
–5.0
–15.0
–10.0
–20.0
–15.0
0
0
32
34
36
38
–20.0
.
.
56
56
56
56
7:
7:
7:
7:
:5
:5
:5
:5
50
00
12
12
12
12
:5
:6
Hours:Minutes:Seconds:Milliseconds
54
54
5:
5:
:0
:0
V Waveform Average AG
13
13
FIGURE 19. The NM-A incoming feeder UTS opening. AG: phase A to FIGURE 21. The NM-B primary switchgear voltage. AG: phase A to
ground; BG: phase B to ground; CG: phase C to ground. ground; BG: phase B to ground; CG: phase C to ground.
100
Recorded Volts/Amperes/Hertz Zoomed Detail:
3 September 2014 12:58:09– 3 September 2014 12:58:09 75
10.0 0
5.0
–25
0.0
–50
–5.0
–75
–10.0
–15.0 –100
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35
–20.0 Time (s)
(file Cell3_inductor_H_Design.pl4; x-var t )
00
50
:1
:1
09
09
V Waveform Average AN
8:
8:
:5
:5
V Waveform Average BN
12
12
FIGURE 24. The NM-A secondary voltage after UTS opening (from
FIGURE 22. The bus primary voltage after UTS opening. AG: phase A simulation). AN: phase A to neutral; BN: phase B to neutral; CN:
to ground; BG: phase B to ground; CG: phase C to ground. phase C to neutral.
60
Primary VT Voltage (kV)
20
40
0
20
0 –20
–20 –40
–40 –60
–60 V Waveform Average AG –80
–80 V Waveform Average BG V Waveform Average AG
–100
V Waveform Average CG V Waveform Average BG
–100 –120 V Waveform Average CG
–140
00
50
00
.3
.3
.4
0
55
55
55
35
36
37
5:
5:
5:
9.
9.
9.
:0
:0
:0
:2
:2
:2
14
14
14
06
06
06
:
Hours:Minutes:Seconds:Milliseconds
13
13
13
Hours:Minutes:Seconds:Milliseconds
FIGURE 23. The NM-A secondary voltage after UTS opening. AG: FIGURE 25. The NM-A primary VT voltage. AG: phase A to ground;
phase A to ground; BG: phase B to ground; CG: phase C to ground. BG: phase B to ground; CG: phase C to ground.
0
–20
–3
–40
–60 –14
–80
–100 –25
V Waveform Average AG 0 5 1015 20 25 30
*10–3
–120 V Waveform Average BG Time (s)
V Waveform Average CG (file NM-1-Close-PD.pl4; x-var t )
–140
V Waveform Average AN
90
95
00
05
.3
.3
.4
.4
V Waveform Average BN
56
56
56
56
0:
0:
0:
0:
V Waveform Average CN
:4
:4
:4
:4
13
13
13
13
Hours:Minutes:Seconds:Milliseconds
FIGURE 28. The NM-A primary VT voltage after closing the UPM
FIGURE 26. The NM-B primary voltage. AG: phase A to ground; BG: switch (from simulation). AN: phase A to neutral; BN: phase B to
phase B to ground; CG: phase C to ground. neutral; CN: phase C to neutral.
25.00
*103 Recorded Volts/Amperes/Hertz Zoomed Detail:
18.75 3 September 2014 14:37:35–3 September 2014 14:37:35
100
Primary VT Voltage (V)
12.50
6.25 50
Secondary VT Voltage (V)
0.00
0
–6.25
–12.50 –50
–18.75
–100
–25.00
0 5 10
15 20 25 30
*10–3
–150 V Waveform
Time (s)
(file NM-1-Close-PD.pl4; x-var t ) Average AB
–200
V Waveform Average AN
20
30
40
50
.6
.6
.6
.6
V Waveform Average BN
34
34
34
34
7:
7:
7:
7:
V Waveform Average CN
:3
:3
:3
:3
14
14
14
14
Hours:Minutes:Seconds:Milliseconds
FIGURE 27. The NM-A primary VT voltage after closing the UPM
switch using a snubber (from simulation). AN: phase A to neutral;
BN: phase B to neutral; CN: phase C to neutral. FIGURE 29. The bus VT secondary voltage after UPM switching.
50
100
50 0
0
–50
–50
–100
0 5 10 15 20 25 30
*10–3
–100
Time (s)
–150 (file NM-1-Close-PD.pl4; x-var t )
V Waveform Average AN
90
95
00
V Waveform Average BN
.2
.2
.3
15
15
15
V Waveform Average CN
2:
2:
2:
:4
:4
:4
14
14
14
Hours:Minutes:Seconds:Milliseconds
FIGURE 32. The NM-A secondary VT voltage after closing the UPM
FIGURE 30. The secondary bus voltage after closing the NM-B. AG: switch. AN: phase A to neutral; BN: phase B to neutral; CN: phase C
phase A to ground; BG: phase B to ground; CG: phase C to ground. to neutral.
100 initiate transients in the other phases for which the pole
has not yet opened. In both phases A and B, there is a sig-
50 nificant TOV followed by a damped oscillation. The peak
as well as the rate of change of voltage can damage the VT
0 primary winding insulation.
This case was simulated by closing the UPM switch
–50 PD-B upstream. The TOV magnitude is 120.01 V with a
frequency of 3,300 Hz, as shown in Figure 31. Note that
–100 the case was initially simulated with a 30-X resistor and
*10–3
0 5
15 20 10 25 30
Time (s) a 0.125-µF capacitor, but repeated using a fine-tuned
(file NM-1-Close-PD.pl4; x-var t ) snubber (100 X and 0.25 µF). This analysis shows a
reduced TOV of 125.52 V, with a frequency of 2,500 Hz,
V Waveform Average AN
as shown in Figure 32. There is a reduction in the TOV
V Waveform Average BN
by using the fine-tuned snubber, but it still damped to
V Waveform Average CN
an acceptable level.
FIGURE 31. The NM-A secondary VT voltage after closing the UPM Conclusions and Observations
switch using an off-shelf snubber (from simulation). AN: phase A to
The “Existing System Conditions (Baseline)” and “Solution
neutral; BN: phase B to neutral; CN: phase C to neutral.
Testing” sections have shown the resultant waveforms dur-
ing the UTS breaker opening and closing with and without
a frequency of 3,300 Hz, as shown in Figure 27. Note that the saturable reactor as a solution to the ferroresonance
the case was initially simulated in EMTP with a 30-X resis- problem and with and without custom snubbers as a
tor and 0.125 µF capacitor. The case was repeated using solution to the switching transient problem. The effective-
a fine-tuned snubber (100 X and 0.25 µF). This showed a ness of the implemented solution has been verified through
reduced TOV of 26.14 kV, with a frequency of 2,500 Hz, as field testing and simulation. During baseline testing, the
shown in Figure 28. measured waves showed significant 5–20-Hz ferroresonance
Figures 29 and 30 show the VT secondary voltage when at the VT on opening and even worse prestrike/reignition
closing the UPM PD-B switch. In Figure 30, notice that transients on closing. After the installation of saturable reactors,