Professional Documents
Culture Documents
1.1 Introduction
This section discusses the various types of methods that cables can be protected against
mechanical damages. It is because of the complexity and hazards involved in the
installation of cables in the many types of buildings and their surroundings, there are
quite a number of different types of cables and wiring systems in use. Each is designed
to meet and withstand the elements encountered and at the same time, fit in with the
overall building construction in terms of convenience and appearance.
• Three types of conduit: metal, flexible (metal) and non-metallic (PVC). See
Figure 1.2 (a).
Points to note
i) The conduit system for each circuit of an installation must be completely erected
before any cables are drawn in.
iii) All conduits system must be properly supported. In the case of rigid PVC
conduits, allowance must also be made for longitudinal expansion.
iv) Supports for conduit system must be purpose made saddles or clamps as shown
in Figure 1.2 (b). The spacing between supports is as per recommended in
Appendix 11, CP5: 1988, Table 11 C.
v) When conduit is bent, the radius of the bent must not be less than 2.5 times the
outside diameter of the conduits. See Figure 1.2 (c). The bending radius may
have to be increased to allow for the bending radius of cables as specified in
Table 52 C, CP5:1988.
Table 52C
Minimum Internal Radii of Bend in Cables for Fixed Wiring
Exceeding 25mm 6
Armoured Any 6
P.V.C. Armoured or Non- Any 8
(solid aluminium or armoured
shaded copper
conductors)
Impregnated paper Lead sheath Any 12
Mineral Copper or Aluminium Any 6
sheath with or without
p.v.c covering
+
For flat cables the factor is to be applied to the major axis
* The figure in brackets relates to single-core circular conductors of stranded construction installed in
conduit, ducting or trunking.
vi) Non-inspection solid conduit elbows or tees are allowed only at:
• not more than 500 mm from a fitting which will allow permanent access,
provided that the total run of conduit between 2 points of permanent access
is 10 m or less and there is not more than 1 right angle ( or 2 45°) bend in the
run in addition to the solid elbow. See Figure 1.2 (d).
Figure 1.2 (d) Illustration of the Limitation in the use of solid elbows
vii) The number of cables drawn into a conduit may be determined by selecting the
size of conduit using the tables shown in Appendix 12, CP5:1998.
viii) The ends of conduit must be reamed and entries to boxes and accessories must be
bushed in order to prevent damage to cables.
ix) Conductor carrying current has a magnetic field around it. The a.c. current causes
the field to change direction continually and the field will cut across any metal
close to it. As a result e.m.f. is induced in the metal and give rise to eddy currents
(heating) in that metal. Running another conductor close to the first with its
current flowing in the opposite direction will cancel out the fields. Hence, cables
of a.c. circuits installed in steel conduit should have all phases and neutral
bunched in the same conduit.
xi) Drainage points should be provided at the lowest point of a metallic conduit
installation to allow moisture due to condensation to drain away.
xi) Where conduits pass through floors or walls the opening through which they pass
must be made good to the full thickness and to give the required degree of the
fire resistance. See Figure 1.2 (e).
• The trunking can be classified in to two types. They are ordinary wiring trunking
and bus-duct trunking. The ordinary trunking system is available in either metal
or PVC. See Figure 1.3 (a).
• There are 2 main types of busbar trunking, the overhead type used for
distribution in industrial area, and rising-main trunking. See Figure 1.3 (b).
Points to note
• Where trunking passes through floors, wall or ceilings a fire barrier must be
provided. Additionally fire internal barriers must be fitted within the trunking in
which cables or conductors are installed, where these pass through fire
compartment walls or floors. See Figure 1.3 (d).
Figure 1.3 (d) internal fire barrier to prevent the spread of fire
• The size of trunking may be determined from the guidance notes as outline in
Appendix 12, CP5:1998, or can be obtained by allowing a space factor of 45%.
Category 1: all low-voltage circuits and supplied directly from the mains
supply (other than fire alarm or emergency lighting circuits).
• All phases and neutral (if any) of a.c. circuits must be contained in the same
metal trunking.
Trunking of this type is installed directly onto the structural slab of new
buildings, and screed is poured over it until it is completely submerged. Access is
obtained only at junction boxes or where the trunking rises up the wall to go to a
distribution board or join up with skirting trunking. Figure 1.4.1 (a)
• System with total access throughout its entire length to enable easy installation
and maintenance of cables is known as the trench duct system. Figure 1.4.1 (b)
• Duct should extend into the telephone riser and link to the floor trench (Figure
1.4.1 (c) and 1.4.1 (d)
Figure 1.4.1 (c) Under floor duct extended to the telephone riser
• Should be designed with the main junction boxes along the common corridor
area or passageway. Figure 1.4.1 (e)
Figure 1.4.1 (e) Main junction boxes along common corridor area or passageway
• Should be free from internal roughness, sharp edges, moisture and dirt.
• Should be provided with floor outlets to lead the telephone cables out of the
ducts. Figure 1.4.1 (f)
• For an underfloor duct system with junction box access, the thickness of the
floor screed on top of the ducts should not exceed 40 mm for ease in carrying
out cabling work.
• The size of the underfloor duct should be such that the cross-sectional area of
all the cables accommodated within a duct does not exceed 30% of the cross-
sectional area of the duct.
• Underfloor duct should be made of either high impact rigid PVC or galvanized
metal or steel of welded construction and of sufficient thickness.
• The duct should have a minimum internal height of 25mm.
• Nylon draw wire should be provided in the duct between every adjacent
junction box.
• Junction boxes should be provided at all junctions and bends. The distance
between 2 junction boxes in a straight run should preferably not exceed 6 m
Figure 1.4.1 (g)
• Junction box cover should be secured to the junction box by means of screws
or other acceptable means. Figure 1.4.1 (h)
• All junction boxes and telephone outlets should be readily accessible at all
times. Wall or partitions should not be constructed on the top of them.
Figure 1.4.1(i)
• For carpeted floors, appropriate slits should be made on the carpet at all
junction boxes and floor outlets to enable access to the floor ducts. Figure
1.4.1 (j) illustrates one method of providing the access to the junction box for
carpeted floors.
• Usually used in computer rooms and offices with high number of telephones.
• The raised floor panels should be supported on pedestals that are of a height
sufficient to ensure a clear working space of at least 25mm below the floor panel.
Distribution Cells
These are mainly constructed of steel but concrete distribution calls can
also be used.
• The system basically has two-level system with the distribution cells on the
lower level and header duct or trench header on the upper level.
• The layout of the distribution system and the design of the structural floor and its
supported members should be integrated.
• Header duct is installed on top of the distribution cell. It provides permanent and
ready access to distribution cells which run at right angle to it.
• Since the header duct is the link between the distribution calls and the telephone
riser, it is important that adequate capacity be provided.
• Trench header is a metallic trough that is flushed with the finished floor. It
provides permanent and ready access to distribution calls that run at right angles
to it.
• Trench header is equipped with removable steel cover plates for its entire length.
• The main trench header or header duct should be installed along the common
corridor of the building and made accessible at all times.
• No partition shall be constructed on top of the trench header or the duct junction
box of the header duct.
• Cable tray consists of perforated metal channel which allow cables to be fastened
to it by means of cleats or cable ties. See Figure 1.5.