You are on page 1of 8

TRAMO CAUDAL (Lt/s)

DE HASTA UC

- PO
P0 P1 456
P1 P2 228
P2 P3 114
P3 P4 76
P4 P5 38
P5 P5' 38
P5' P6 19
P6 P7 10
P6 P8 9
P8 P9 3
P8 P10 6
CAUDAL (Lt/s)
PLACA DE TANQUES

ALTUR
PROVEED ϕ int LV LH
Q L/S UC fluxor Q fluxor ϕ (in) RDE V (m/s) A REF
OR (mm) (m) (m)
PISO(m)

7.32 0.00 0.00 PAVCO 3.00 21.00 82.42 1.37 6.90 0.00 1.81
4.86 0.00 0.00 PAVCO 2.50 21.00 66.07 1.42 6.90 0.00 9.90
3.02 0.00 0.00 PAVCO 2.00 21.00 54.58 1.29 6.90 0.00 1.53
2.28 0.00 0.00 PAVCO 1.50 21.00 43.68 1.52 6.90 0.00 7.00
1.42 0.00 0.00 PAVCO 1.00 21.00 30.20 1.98 6.90 0.00 3.74
1.42 0.00 0.00 PAVCO 1.00 21.00 30.20 1.98 3.45 3.45 10.00
0.88 0.00 0.00 PAVCO 1.00 21.00 30.20 1.23 3.45 0.00 0.25
0.57 0.00 0.00 PAVCO 1.00 21.00 30.20 0.79 3.45 0.00 4.00
0.53 0.00 0.00 PAVCO 1.00 21.00 30.20 0.74 3.45 0.00 2.30
0.25 0.00 0.00 PAVCO 0.50 13.50 18.18 0.95 3.45 0.00 1.00
0.40 0.00 0.00 PAVCO 0.50 13.50 18.18 1.54 3.45 1.50 4.20
PÉRDIDAS PRESIÓN

∑h
L total
J (m/m) ∑hf (m) Km total P salida (m)
(m)
(m)

ALTURA
Presión
TANQUE Total
Hidro(m)
(m)
8.26 28 36.26
1.81 0.02 0.03 1.20 0.14 29.22
9.90 0.02 0.22 0.50 0.27 28.95
1.53 0.02 0.04 0.50 0.08 28.87
7.00 0.04 0.29 0.50 0.35 28.52
3.74 0.10 0.39 0.50 0.49 28.02
13.45 0.10 1.41 1.10 1.63 29.84
0.25 0.05 0.01 0.40 0.04 29.80
4.00 0.02 0.08 1.80 0.14 29.66
2.30 0.02 0.04 0.20 0.05 29.75
1.00 0.06 0.06 1.10 0.11 29.65
5.70 0.13 0.72 2.00 0.96 27.29
VERIFICACION

P ssalida Verificacionde
psi velocidad

PAVCO
20.54 OK
20.35 OK RDE ϕ (in)
20.29 OK 13.5 1/2
20.05 OK 21 3/4
19.70 OK 21 1
20.98 OK 21 1 1/4
20.95 OK 21 1 1/2
20.85 OK 21 2
20.92 OK 21 2 1/2
20.84 OK 21 3
19.18 OK
ACCESORIOS
Entrada
Codo 45°
Codo 90°
Reducción
Salida
Tee lateral
Tee directo
PAVCO

ϕ int (mm)
18.18
23.63
30.2
38.14
43.68
54.58
66.07
82.42

Km's
1
0.5
0.9
0.3
1
0.2
0.15
PROVEED
DE HASTA Q L/S ϕ (in) ϕ int (mm)
OR
B PISO 2 12.62 HD 4 100
PISO 2 GABINETE 6.31 HD "2-1/2" 75
Caracteristica de la bomba
ADT(m) 20.0
Q(m3/s) 12.62
NPSH disponible 6.906
NPSH requerido Max 8.28697248
Potencia aproximada(no menor) 5
L
ϕ int (mm) V (m/s) LH (m) LV (m) L total (m) J (m/m) ∑h total (m)
equivalente
100 1.60682831 205 5 210 252 0.0483856981 12.1931959
75 1.42829183 5 0.5 5.5 6.6 0.0544832702 0.35958958
Verificacion EFICIENCI POTENCIA
Perdidas ADT
de velocidad A HP
17.2 OK
1.9 OK 0.65 19.1 5