Professional Documents
Culture Documents
ICE RINKS
Applications ............................................................................ 34.1 General Rink Floor Design ..................................................... 34.6
Refrigeration Requirements .................................................... 34.1 Building, Maintaining, and Planing Ice Surfaces ................... 34.8
Ice Rink Conditions ................................................................. 34.4 Rink Fog and Ceiling Dripping .............................................. 34.8
Equipment Selection ............................................................... 34.4 Imitation Ice-Skating Surfaces ................................................ 34.9
Latent heat of freezing water = 334 kJ/kg Table 2 Ice Rink Heat Loads, Indoor Rinks
Building and pumping heat load = 170 kW of refrigeration Approx. Max. Max. Reduction
System losses = 15% Percentage of through Design
Mass of water = 1500 m2 0.025 m 1000 kg/m3 = 37 500 kg Load Sources Total Loada and Operation,%
Mass of concrete = 1500 m2 0.150 m 2400 kg/m3 = 540 000 kg
Then: Conductive loads:
Ice resurfacing 12 60
qR = (Sys. losses)(qF + qC + qSR + qHL) System pump work 15 80
Ground heat 4 80
where Header heat gain 2 40
qR =refrigeration requirement Skaters 4 0
qF =water chilling and freezing
qC =concrete chilling load Convective loads:
qSR =refrigeration to cool secondary coolant Rink air temperature 13 50
qHL =building and pumping heat load Rink humidity 15 40
37 500 kg { 4.18 ( 11 – 0 ) + 334 kJ ⁄ kg + 2.04 [ 0 – ( – 4 ) ] } Radiant loads:
qF = ----------------------------------------------------------------------------------------------------------------------------------------
24 h × 3600 s/h Ceiling radiation 28 90
=168.5 kW Lighting radiation 7 40
540 000 × 0.67 [ 2 – ( – 6 ) ] Total 100
qC = ------------------------------------------------------------- = 33.5 kW
24 × 3600 aLoad distribution for basic rink without insulation below rink floor.
14 000 × 3.5 [ 5 – ( – 9 ) ]
qSR = ------------------------------------------------------- = 7.9 kW Table 3 Ice Rink Heat Loads, Outdoor Rinks
24 × 3600
qR =1.15(168.5 + 33.5 + 7.9 + 170) = 437 kW Approx. Max. Max. Reduction
Percentage of through Design
When no time restrictions apply, the estimated refrigeration is Load Sources Total Loada and Operation,%
the amount needed to offset the usage loads plus the coincidental Conductive loads:
heat loads during the most severe operating conditions. Table 1 lists Ice resurfacing 9 50
approximate refrigeration requirements for various rinks with con- System pump work 12 80
trolled and uncontrolled atmospheric conditions. Table 1 should Ground heat 2 40
only be used to check the calculated refrigeration requirements. Header heat gain 1 30
Table 2 shows the distribution of various load components for basic Skaters 1 0
construction and the estimated potential load reductions that may be
obtained when energy-conserving design and operating techniques Convective loads:
are used. Air velocity 0 to 15 10
Air temperature 0 to 15 0
Table 1 Range of Ice Rink Refrigeration Humidity 0 to 15 0
appropriate controls. Proprietary variable motor speed controls are because the large ice slab tends to maintain a lower than normal dry-
also available. The coolant flow should be sufficient at all times for bulb temperature.
acceptable chiller operation and to maintain a balanced flow Radiant Loads. Indoor ice rinks create a unique condition where
through the piping grid. a large, relatively cold plane (the ice sheet) is maintained beneath an
The refrigeration system auxiliaries, such as condenser pumps, equally warm plane (the ceiling). The ceiling is warmed by conduc-
condensers, cooling tower or evaporative condensers, and con- tive heat flow from the outside and by normal stratification of arena
denser fans consume substantial electrical energy. Appropriate air. Up to 35% of the heat load on the ice sheet comes from radiant
design and control of the system and good equipment selection sources. On outdoor rinks radiant sources are the sun or a warm
should keep these auxiliary electric loads reasonable. cloud cover. Vertical hanging cloth suspended from east-west hori-
Ice resurfacing represents a significant operating heat load. zontal overhead wires has been used to reduce the winter sun load.
Water is flooded onto the ice surface, normally at temperatures In indoor and covered rinks, lighting is the major source of radi-
between 55 and 80°C, to restore the ice surface condition. The heat ant heat to the ice sheet. The actual quantity depends on the type of
load resulting from the flood water application may be calculated as lighting and how the lighting is applied. The direct radiant heat
follows: component of the lighting can be as much as 60% of the kilowatt rat-
ing of the luminaires. A radiant heating system can be another
Qf = 1000Vf [4.2(tf – 0) + 334 + 2.0(0 – ti)] source of radiant heat gain to the ice. If radiant heat is used to main-
tain the comfort level in the promenade or spectator area, the radiant
where heaters should be located and directed to avoid direct radiation to
Qf = heat load per flood, kJ the ice surface. The infrared components of the lighting can be esti-
Vf = flood water volume (typically 0.4 to 0.7 m3 for a 30 m by 60 m mated from manufacturers’ data.
rink), m3 The infrared heat gain component from the ceiling and building
tf = flood water temperature, °C structure, which is warmer than the ice surface, can be calculated by
ti = ice temperature, °C applying the Stefan-Boltzmann equation as follows:
The resurfacing water temperature affects the load and time 4 4
required to freeze the flood water. Maintaining good water quality q r = Afci σ ( T c – T i )
through proper treatment may permit the use of lower flood water Ac 1 –1
fci = ------- + ---- – 1 + ----- ---- – 1
temperature and less volume. 1 1
Convective Loads. The convective load from the air to the ice F ci ε c Ai ε i
may represent as much as 28% or more of the total heat load to the
ice (Tables 2 and 3). The convective heat load is affected by air tem- where
perature, relative humidity, and air velocity near the ice surface. qr = radiant heat load, W/m2
Precautions should be taken to minimize the influence of air move- Ac = ceiling area, m2
ment across the ice surface in the design of the rink heating and Ai = ice area, m2
dehumidification air distribution system. The convection heat load e = emissivity
may be estimated using the procedure from Appendix 5 in the pub- fci = gray body configuration factor, ceiling to ice surface
lication, “Energy Conservation in Ice Skating Rinks” (DOE 1980). Fci = angle factor, ceiling to ice interface (from Figure 1)
The estimated convective heat transfer coefficient can be calculated T = temperature, K
s = Stefan-Boltzmann constant = 5.67 10
-8 W/(m2 ·K4)
using the formula:
The effective heat load (including the latent heat effect of con-
vective mass transfer) is given by the following equation:
where
Qcv = convective heat load, W/m2
K = mass heat transfer coefficient
ta = air temperature, °C
ti = ice temperature, °C
Xa = mole fraction of water vapor in air, kg mol/kg mol
Xi = mole fraction of water in saturated ice, kg mol/kg mol
Ceiling radiating area: 28 m 60 m = 1680 m2 however, condensation can occur on the ceiling or roof structure due
Ceiling mid-height: 7.6 m to radiation from the building structure to the ice. Low relative
Ceiling temperature: 16°C (289 K), ec = 0.90 humidity is needed to reduce this condition when a high emissivity
x/d = 28/7.6 = 3.6 ceiling is exposed to the ice surface.
y/d = 60/7.6 = 7.9 Ventilation should be the minimum required for the building
occupancy so that the humidity introduced with outdoor air is kept
From Figure 1, Fci = 0.68 as low as is feasible; but enough outdoor air must enter to maintain
–1
acceptable indoor air quality (see ASHRAE Standard 62). Gas
f ci = ---------- + ---------- – 1 + ------------ ---------- – 1
1 1 1680 1 engine resurfacing machines should be equipped with catalytic
= 0.610
0.68 0.90 1560 0.95 exhaust convertors to reduce carbon monoxide emissions. The
Then: makeup air or ventilation air in humid climates should be dehumid-
ified prior to being supplied to the arena.
–8 4 4 Carbon monoxide and nitrogen dioxide are pollutant emissions
q r = 1680 × 0.610 × 5.67 × 10 ( 289 – 269 ) ⁄ 1000
from gasoline- or propane-fueled ice resurfacers. The concentration
= 101 kW of these chemicals can reach dangerously high levels if they are not
The ceiling radiant heat load can be reduced by lowering the tem- controlled or eliminated. In some areas, regulations require sensors
perature of the ceiling, keeping warm air away from the ceiling, to detect and alarm at unsafe chemical concentrations. Check the
increasing the roof insulation, and, more significantly, by lowering health regulations for local requirements.
the emissivity of the ceiling material to shield the ice from the build- Each rink user group has its own preference for the type of ice
ing structure. used. Hockey players and curlers prefer hard ice; figure skaters pre-
Ceiling and roof materials and exposed structural members have fer softer (i.e., warmer) ice so they can clearly see the tracings of
an emissivity that may be as high as 0.9. Special aluminum paint can their skates; and recreational skaters prefer even softer ice, which
lower the emissivity to between 0.5 and 0.2. Polished metal such as minimizes the buildup of shavings and scrapings.
polished aluminum or aluminum foil have an emissivity of 0.05. Since ice surface temperature can not be measured easily, the
Also because a low-emissivity ceiling is cooled very little by ice condition is customarily controlled either from a predeter-
radiant loss, most of the time its temperature remains above the dew mined coolant average temperature or from the ice temperature
point of the rink air. Thus, condensation and dripping is substan- measured by a themocouple embedded beneath the ice surface.
tially reduced or eliminated. With approximately 7°C air temperature and one 25-mm ice
Low emissivity fabric or tiled ceilings are frequently incorpo- thickness, ice at -6.5 to -5.5°C is satisfactory for hockey, -4 to
rated into new and existing rinks to reduce radiation loads, decrease -3°C for figure skating, and -3 to -2°C for recreational skating.
condensation problems, and reduce the overall lighting required. A 0.5 K higher ice temperature may be feasible when water with a
Radiant heat gain to the ice, especially in outdoor rinks, can be low mineral content is used for resurfacing. To achieve these ice
further controlled by painting the ice about 25 mm below the surface temperatures, the coolant temperature is maintained about 3 to 6
with whitewash or slaked lime. Commercial paints with a low solar K lower than the ice temperature. The temperature of the coolant
absorptivity, which are generally water based, are also available. must be lowered to maintain the same ice conditions when there
are higher wet-bulb temperatures or abnormally high loads, such
ICE RINK CONDITIONS as when television lighting is used.
Properly designed indoor rinks, as well as properly designed ren-
ovated rinks, can be operated year-round without shut down. How- EQUIPMENT SELECTION
ever, some indoor rinks operate from 6 to 11 months and shut down
for various reasons including maintenance, rink construction, Compressors
inability to control indoor conditions, or unprofitable operation dur- Two or more refrigeration compressors should be used in an ice
ing part of the year. Outdoor, uncovered rinks generally operate rink system. When two compressors are used, one compressor
from early November to mid-March above 40° North latitude. How- should be specified with ample capacity to maintain the ice sheet
ever, if sufficient refrigeration capacity is provided, the ice can be under normal load and operating conditions. When greater capacity
maintained for a longer period. is required during the initial ice freezing or under high heat loads,
Indoor rinks are operating successfully even in warm tropical cli- the second compressor picks up the load. In multiple compressor
mates. Relative humidity, temperature, and ceiling radiant losses installations, a multistage thermostat microprocessor control and/or
must be controlled in these climates to prevent fog, ceiling dripping, a motorized sequence control may be used to control the operation
and high operating cost. of the compressors. The multiple compressors serve as backups;
Steel frame, brick, concrete, and various forms of plastic have they maintain the ice in the event of compressor failure or a service
been used to enclose ice skating rinks. Rinks have also been built requirement.
under air-supported structures for seasonal use and are usually over Compressors and evaporators should operate at a suction pres-
a multipurpose surface. sure corresponding to a 6 K mean temperature difference between
Arena heating is frequently provided for skater and/or spectator the coolant and primary refrigerant in systems operating with sec-
comfort and can be provided in conjunction with a dehumidification ondary coolants, or between the ice and the refrigerant in direct
system. Heat recovery from the refrigeration system may be used refrigerant rinks.
for limited heating, supplementing the heating system, or dehumid-
ification reheat. Ice rink temperatures are usually maintained
Condensers and Heat Recovery
between 5 and 15°C; however, for skater or spectator comfort,
higher temperatures are sometimes preferred. The relative humidity Wells, lakes, or rivers can be good sources of condenser cooling
maintained in the arena depends on factors such as building con- water, if they are available. Capacity is easy to regulate and the low
struction, indoor temperature, and outdoor wet bulb. coolant temperature maintains low condensing pressures, which
The system should be designed to reduce fogging and ice surface saves energy. But, condensers require high quality water, which
condensation. Relative humidity at or below 80% with rink temper- may need treatment to prevent scale formation, fouling, or corrosion
atures between 5 and 15°C is usually sufficient to eliminate fogging; in the condenser tubes.
Ice Rinks 34.5
Cooling towers used with water-cooled condensers, evapora- one end. Small-diameter tubing rinks generally run crosswise, with
tive condensers, or air-cooled condensers are alternatives. When the supply and return headers along one side. Direct refrigerant
selecting a cooling tower or evaporative condenser, not only the rinks generally run lengthwise, with the supply header at one end
maximum expected wet-bulb temperature during the skating and the return header at the opposite end in a balanced system. The
season should be considered, but also suitable controls to cover header must be sized to assure an even distribution of coolant
the wide range in capacities and protection against freezeup through every pipe. The systems are generally designed with low
needed in cold weather. A water treatment specialist should also coolant velocities, which do not need balancing valves. If at all
be consulted. possible, the return header should be placed at the same elevation
Air-cooled condensers are used in northern climates, particularly as the rink piping, with a minimum of two air vents to eliminate
where the rink is used only in the winter. They can be economically the trapping of air.
sized and require no water, so that the possibility of freezeup is elim- The three-pipe reversed return header and distribution arrange-
inated. This type of condenser, however, is not economical for year- ment (Figure 2) is commonly used. However, a properly sized two-
round operation, and for seasonal operation it must have wide-range pipe header system (Figure 3) is frequently applied and gives nearly
capacity control. Heat rejected by the condensers can be recovered uniform circuit flow with no discernible differences in the ice sur-
and used with water or air-cooled condensing systems. face. To allow for thermal contraction and expansion, headers and
When a cooling tower system is selected, heat from condensers main piping should be free to move without producing excessive
can be used for such energy-saving applications as arena heating, stress.
subfloor heating, domestic water heating, and snow melting. This is Polyethylene distribution headers should only be used with
generally done either by circulating the condenser cooling water proper allowances for expansion and contraction. The coefficient of
through heat exchangers or with fan coil units. The circulated cool- thermal expansion for steel is relatively low and very close to that of
ing water can also be used in conjunction with a heat pump as a heat concrete, while the polyethylene pipe expansion coefficient is much
sink/source for heating or cooling various areas within the rink higher. Pipe clamp connections must remain accessible for inspec-
building and for water heating. tion and tightening. Clamps are not considered permanent joints.
A closed secondary coolant system requires an expansion tank to
Ice Temperature Control safely accommodate the expansion and contraction of the coolant
Ice temperature may be controlled by various methods. Thermo- resulting from fluid temperature changes. The expansion tank must
stats that sense the return coolant temperature or the differential be installed so that it cannot be isolated from the system.
temperature between the supply and return coolant can be used to
control the refrigeration system. They may also be used in control-
ling operation of the coolant pump. To be effective, a differential
sensor should sense a small temperature difference. The return cool-
ant temperature can be sensed by multistage sensors that sense a
larger temperature difference. Another strategy varies coolant flow
by controlling the pump with a temperature sensor buried in the ice.
Direct refrigerant systems can be controlled by regulating compres-
sor operation with a sensor in the ice. This method has been used
with a direct refrigerant impulse pumping system. Compressor
capacity and pump operation may be controlled from the low-pres-
sure receiver when refrigerant pumps are used to circulate the
refrigerant.
develop. Once started, the pouring of each course of the concrete The sprinkler has an adjustable valve to control the quantity of
floor should be continuous with interruptions not to exceed 15 min. water, which is sprayed into a terry cloth bag that wipes the fine
General-purpose rink floors should not be defrosted too fre- snow off the ice surface and fills the crevices cut by the skaters. In
quently. When a rink constructed with a general-purpose floor is to this manner, the least amount of water is added, reducing the ice
be used during the ice season for purposes that require an ice-free buildup and refrigeration load.
floor, it is preferable to place an insulated portable-section wood By far the most common method is the use of automatic resur-
floor over the ice for each occasion. facing machines. Mounted on four-wheel drive chassis, the
machines plane the ice, pick up the snow, and lay down a new ice
All-Purpose Floors surface using hot or cold water. Hot water generally gives harder
If a rink floor as used in sports arenas is to withstand both the ice, since air bubbles are removed, but high energy costs have led
expansion and contraction of frequent frosting and defrosting and many rinks to alternate hot and cold water resurfacings. Rink cor-
thermal shock because of the circulation of very low-temperature ners should be at least a 6.1-m, preferably 8.5-m, radius for effective
coolant, then extra precautions must be taken in its construction, use of this equipment. Smaller equipment is available for studio and
such as provisions for the free movement of the freezing slab with small rinks.
respect to the subfloor. Because of inattentive ice making, improper sprinkling equip-
ment, or deep cutting of the ice during public skating, the ice may
Header Trench become uneven and excessively thick. There may be a fairly slight
A well-constructed header trench of sufficient size to house the variation in the ice thickness across the rink, but more serious is the
headers and connections and the subfloor heating system, if appli- resulting variation in the condition of the ice. In any case, the low
cable, is essential unless the steel distribution headers are cast into spots on the ice must be built up, increasing the thickness and refrig-
the concrete slab as part of the rink. Provisions for movement of eration requirements.
pipes due to thermal expansion and contraction should be incorpo- For example, under assumed conditions, where -8°C coolant
rated into the design. This trench should be equipped with remov- would be cold enough to hold a 38 mm thickness of ice, calculations
able covers and be well-drained to facilitate drying out. The headers show that -21°C coolant would be required if the ice were permit-
and piping in the trench are not usually insulated, which allows for ted to build up to 150 mm, with a corresponding decrease in effec-
periodic inspection and painting of the piping. However, unless a tive refrigeration capacity and an increase in operating costs. In
large trench is provided, consideration should be given to insulating other words, every additional 25 mm of ice thickness required from
the headers on rinks that operate year-round because of the massive the refrigeration system increases 8 to 15%, depending on system
buildup of frost. Provision must be made for purging air from the heat load (DOE 1980).
rink piping and header system. Since ice of 13 to 25 mm thickness is satisfactory for skating and
is the most economical thickness to freeze and hold, the ice should
Snow Pit be periodically planed to maintain this desired thickness.
A snow-melting pit should be provided at a suitable point,
usually at one end of the rink. It should be of sufficient size to Water Quality
handle the scraped off snow and the ice accumulated during plan- The quality of the water affects energy consumption and ice
ing, or it may be made large enough to accommodate the com- quality. Water contaminants, such as minerals, organic matter, and
plete ice removal. dissolved air, can affect both the freezing temperature and the ice
Discharge water from shell-and-tube condensers, a waste heat thickness necessary to provide satisfactory ice conditions. Propri-
recovery system, or some other heat source should be provided to etary treatment systems for arena flood water are available. When
melt the snow and ice. An average load for a snow melting pit from these treatments are properly applied, they reduce or eliminate the
a mechanical ice resurfacer is between 40 and 50 kW for a 1500 m2 effects of contaminants and improve ice conditions.
rink. A large drain with overflow, as well as a large removable
screen to filter out trash, should be provided.
RINK FOG AND CEILING DRIPPING
BUILDING, MAINTAINING, AND During mild weather, particularly in early fall and late spring in
PLANING ICE SURFACES the northern United States and Canada, condensation often drips
Regardless of the type of rink floor used, when the plant is first from the roofs and roof supports of rinks (especially curling rinks),
placed in operation, the equipment should be operated long enough due to construction, internal conditions, or insufficient internal heat
for a sharp frost to appear on the surface. Then the entire surface loads. The condensate dropping on the ice ruins the curling surface
should be uniformly covered with a fine spray. This process should and the fog obstructs the view. These conditions cannot be solved by
be repeated until a 13 mm thickness of ice is built, or until the sur- ventilation because the introduction of outdoor air only aggravates
face is level. After applying a layer of water base white paint, the problem when the weather is mild and humid. Insulating the roof
another 10 mm thick layer of ice is built before painting the red and also aggravates the drip during mild outside weather conditions.
blue lines. Red and blue lines are available in plasticized paper; Low-emissivity ceilings stay warmer and thus reduce condensation
however, they need to be covered with a minimum of 13 mm of ice and drip.
to protect against damage. It is essential that sand floors be thor- Under these conditions, to prevent condensation in the roof space
oughly wet before freezing because dry sand has poor conductivity. and to clear the fog, a six-sheet curling rink, with 1160 m2 of ice,
The surface should not be frozen any colder than required after this would require the removal of 15 kg of moisture per hour, necessi-
buildup so as to allow the ice to temper before it is used for skating tating about 21 kW of refrigeration.
and also to deter cracking. Units using the coolant from the rink piping as a cooling medium
To maintain an ice surface, it is customary to scrape off the snow avoid frosting by recirculating with a small bypass pump to keep coil
after each skating session or hockey period. In all but the smallest inlet brine above 0°C. Reheat coils are often included and frequently
rinks, this is done by a motorized resurfacer. On small rinks, the use back waste heat from condenser cooling water to counter the
scraping is done manually with a wide hardened-steel scraper blade. cooling effect of the dehumidifier coil. Self-contained, air-cooled,
The most satisfactory method of resurfacing the ice between ses- compressor-type packaged dehumidifying units, as well as desiccant
sions is to wheel a sprinkler tank filled with hot water over the ice. drier types with gas or electric regeneration, are available.
Ice Rinks 34.9