You are on page 1of 19

Mechanical Systems

Technical Document
Version 0 – June 2019

R AFFLES \ ORIENT EXPRESS \ BANYAN TREE \ DEL ANO \ SOFITEL LEGEND \ FAIRMONT \ SL S \ SO \ SOFITEL \ THE ORIGINAL S

RIXOS \ MANTIS \ MGALLERY \ 21C \ ART  SERIES \ MONDRIAN \ PULLMAN \ SWISSÔTEL \ ANGSANA \ 2 5HOURS HOTEL S

H Y D E \ M ÖV EN P I C K \ G R A N D M ER C U R E \ P EP P ER S \ T H E S EB EL \ M A N T R A \ N OVOT EL \ M ER C U R E \ A DAG I O

MAMA SHELTER \ TRIBE \ BRE AKFREE \ IBIS \ IBIS S T YLES \ IBIS BUDGE T \ JO& JOE \ HOTELF 1
Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

General Requirements
Although it is understood that local codes will govern, the following internationally If the project is located in a warm climate and many of the public areas are located
recognised codes: IBC, ASHRAE, NFPA, CIBSE and EN, French Regulations in large covered open areas, provide spot air-conditioning in locations where guests
(Règlement de Sécurité) must form the basis of design and must be followed. or staff will spend lengths of time (i.e. registration desks, dining).
Work shall be completed in accordance with the latest version of standards
published by the following list of authorities ANSI/ASHRAE, NFPA, SMACNA Energy efficient appliances must be used as applicable for guest use areas or
and UL/CUL. residential style amenities.

All heating and cooling calculations are to be made using the ASHRAE or CIBSE Refer to MEP Checklist in the D&TS Library.
standards and a recognised energy analysis computer program. The design is
to consider both latent heat gain and dehumidification performance of the air
conditioning system. Humidification is required in cold climates; de-humidification
is required in hot/humid climates.

Special attention must be given to the aesthetics of all public area devices,
grilles and access panels. Special attention must also be given to space planning
requirements for service and replacement of major equipment and individual fan
coil units.

All spaces within the building except for some of the service spaces (mechanical
and electrical rooms) and underground parking facilities shall be air-conditioned,
unless required by specific regions / climates. This includes: Lobby, Public Spaces,
Guestrooms, Residential Units, Restaurants, Spa and Fitness, Heart-of-House areas,
Offices, Kitchen and Laundry.

Positive pressurisation of the entire building is required to be positive pressure


relative to outdoor temperatures.

2 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

1. Air Conditioning Systems


A centralised water-cooled chiller plant is the preferred option as it best addresses Refrigerant leak detection and leak evacuation/exhaust system are to be provided
the concerns of noise, unsightly view of rooftop condensing units, reliability and life for the chiller plant room.
cycle operating costs for a favourable initial capital cost.
1.2 Cooling Towers
Where individual residences or villas are provided, there is an option to provide
localised decentralised split systems within the footprint of each residence or villa The consultant will select the cooling tower based on reliability, service, noise,
providing the cost; acoustical requirements and appearance can be adequately cost and the available space. The cooling towers shall be arranged in a multi-cell
addressed. This option consists of separate air-cooled variable refrigerant volume configuration (one cell for each refrigeration machine) allowing each cell to be
(VRV/ VRF) heat pump systems for each residence to provide heating and cooling. operated independently of the others. Chemical treatment shall be provided for
the condenser water circuit. If cooling towers for the air conditioning plant do not
The project consultant is to evaluate the total cost of equipment, installation and operate year round, then cell capacity and arrangement shall be selected so that
energy usage to determine if sufficient capital savings justifies this system in lieu of critical cooling loads (i.e. refrigeration racks, critical electrical rooms, computer
a centralised water-cooled system for residences/villas. room, etc.) have been accounted for in the design solution.

Periodic and routine maintenance must be provided to all rotating equipment. The project acoustical consultant shall work closely with the design team to achieve
a cost-effective solution. Cooling tower vibration arises from low-frequency vibration
1.1 Centralised Chiller Plant of the relatively slow-turning propeller type fans as well as high-frequency impact
noise from falling water, therefore appropriate mechanical isolation is mandatory.
Whenever possible, vibration isolation system should be located near columns or
The equipment shall be designed to operate 24 hours a day, 7 days a week. Multiple
above load-bearing walls to achieve better structural support.
units with sufficient spare capacity (i.e. redundancy), is required to maintain guest
comfort in the event one chiller is taken out of service based on 2 x 67% or 3 x 33%
When it is not be possible to rigidly support the motor, drive shaft, gear reducer, and
of the total load serving the hotel.
propeller while having the support element isolated from the tower, large-deflection
steel springs and ribbed neoprene mounts are suggested. In cold climate locations,
The chiller capacity and selection will be determined by space requirements and
the design should use methods and materials to winterise and protect plumbing
cooling tower selection. The project consultant will verify if screw type chillers are
systems. In tropical and salt air environments, cooling towers are to be constructed
preferred over centrifugal chillers. of rust resistant stainless steel. Fibreglass structures are not permitted.

Each refrigeration machine shall be provided with a constant volume chilled water In locations where water is a premium, alternatives to evaporative cooling towers
pump and a constant volume condenser water pump. The pumps shall be piped to may be considered, including grey water collection, seawater cooling, ground source
allow cross use. The chiller refrigerant shall be a non-ozone depleting refrigerant. cooling, or dry coolers.

3 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

1.3 Chilled Water Distribution static deflection of 12mm (0.5”) should be initially selected. For pumps supported on
floors above grade, steel spring isolators with 25mm (1”) static deflection should be
initially selected.
Primary-secondary-tertiary pumping shall be utilised to distribute the chilled water
throughout the hotel and outlying buildings.
The project acoustical consultant shall verify all mounting conditions and advise the
design team on the appropriate mounting system on a case-by- case basis.
Secondary and tertiary chilled water loops should be provided with VFD operation
for energy conservation.
1.4 Special Systems
Large pumps are to be horizontally split case, double suction type.
Computer, PBX and similar rooms shall be provided with independent air
Smaller pumps are to be vertically spit case, end suction type. conditioning systems on emergency power. Allow for 100% system redundancy.

All pumps shall have shut off valves and strainers in the suction side and check Water-cooled kitchen refrigeration equipment shall be served from either the
valves and throttling valves on the discharge side. The design pressure for each chilled water or refrigeration plant condenser water systems and shall be on
pump must be at least equal to 1.5 times their working pressure. emergency power.

Widespread use of VFDs on pumps and fans is required. VFDs should be utilised for Ice machines shall be served from the return loop of the chilled water system.
the cooling tower fans, the condenser water pumps, the chilled water secondary Speciality areas such as wine cellar coolers, chocolate prep rooms, pastry shops,
pumps on the air-handling units. recycling and trash rooms etc. will have independent refrigeration systems specified
by the food service consultant.
Do not use PVC-based insulation wrap; specify aluminium or similar product.
Provide manual domestic cold water by-pass for water-cooled condensers in the
Separate distribution loops shall be provided to supply, isolate and meter the hotel event of chilled water/condenser water failure.
from the residences (if applicable). For campus style layouts consider separate loops
for guest rooms and the main building.

The distribution piping shall be insulated steel piping within the building with a
vapour barrier. Distribution piping outside the main building shall be underground,
prefabricated insulated piping with joints and prefabricated fittings.

Field fabricated fittings are not allowed.

Chilled water shall be available year round. Chilled water piping systems are to be
designed with balancing capability. All chiller pumps shall be mounted on inertia
bases on vibration isolators. For pumps on floors or grade, neoprene mounts with a

4 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

2. Steam And Hot Water Boiler Plants

2.1 Centralised Boiler Plant All equipment must be acoustically treated and vibration insulated to meet industry
standards (45NC, STC-55).
Direct fired hot water boilers are the preferred choice of equipment and system for
If boilers are to be oil fired, then the capacity should be based on the delivery
meeting the hotel heating water requirements. The hotel boiler plant equipment is
service of fuel with a minimum of five days. In cold climates, the fuel storage
to be designed to meet the specific requirements based on the following criteria:
facilities shall be designed to accommodate a two-week supply.
— Boiler plant expansion tanks
Steam pressure reducing valve stations are to be provided wherever high-pressure
— Chemical treatment for water
steam needs to be reduced to a lower pressure. The reducing valves may be
— Dependability and quality of local fuel supply either self-contained or air pressure operated, designed for the highest steam
— Daily and seasonal variations of the load inlet pressure. The station should consist of two reducing valves in parallel, one sized
at 1/3 the total capacity and one sized at 2/3 the total capacity. Provide a manual
— Operator skill, hours and license requirements by-pass valve, inlet strainers, safety relief valve and pressure gauges with alarm
— The need for winter heating and utilisation of steam during cooling season and contacts.
air conditioning refrigeration plant.
Where properties consist of buildings scattered around the site, partially
The boilers are to be sized to meet the anticipated peak load and must be selected decentralised boiler plants may be considered. This approach involves a centralised
to provide sufficient excess capacity to permit one unit to be removed from service boiler plant for the hotel and smaller boiler plants serving a cluster of buildings such
for repairs and maintenance without seriously affecting the operations of the hotel. as guest rooms, fractional units and residences. Boiler plants serving the clusters
Centralised boiler plants are to be based on either 2 x 67% or 3 x 33% of the total would be integrated near service spaces such as housekeeping/service rooms
load serving the hotel. Boilers are to be insulated to reduce heat loss and must have where the guests experience will not be impacted due to aesthetics and noise.
their own circulating pump.
The decentralised option such as a centralised boiler plant for the hotel and
Where steam is required for the laundry and kitchens, separate steam boilers fractional with VRV heat pumps to private residences/villas is preferred. The
should be located as close to the operating areas as possible. The steam boiler VRV heat pump unit selection in the decentralised approach requires further
plant is to be based on 2x100% of the total load required. In cold climates or where investigation by the Project Consultant to ensure satisfactory heating for outdoor
humidification is required, the steam boiler plant may be used to distribute steam winter design conditions and a complete cost benefit analysis of the total capital
to the air-handling units. and operating costs.

The project acoustical consultant shall verify boundary conditions and selected Boiler plant shall be properly ventilated, well-lit and provided with building
equipment to advise the design team on the appropriate airborne and structure- automation and alarm devices, as required.
borne noise isolation measures.

5 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

2.2 Hot Water Distribution pressure of 12 psi (0.8 Bar) and a maximum of 30 psi (2.06 Bar). The kitchen
consultant shall review electric versus steam in this equipment.
Primary-secondary pumping shall be utilised to distribute heating water throughout
the hotel building. Separate distribution loops shall be provided for hotel air handling 2.4 Humidification
units, hotel guest room fan coil units, fractional, residences and estates, as applicable.
The project consultant is to evaluate if humidification is required to maintain 30%
The distribution piping shall be insulated steel piping within the building with relative humidity. Humidification control is essential for comfort and to protect
a vapour barrier. Distribution piping outside the main building shall be interior finishes.
underground, prefabricated, insulated steel piping with welded joints for high
temperature distribution. Gas fired steam humidification is recommended. Where multiple air handing units
are located, a decentralised steam boiler is recommended.
Heating water for the hotel shall be available year round. Testing and balancing
units should be provided as required to ensure a properly balanced heating system. 2.5 Central Air-Compressor Plant
Provide VFD on secondary heat pumps.
The plant will consist of at least two compressors, a receiver, water cooler, moisture
2.3 Steam Boiler Plant Laundry and oil elimination and reducing station. Discharge air pressure is to be a minimum
of 100 psi (7 kgf/cm2). A separate air compressor is to be designed and installed for
A high-pressure steam plant shall supply steam to the laundry and possibly to the the laundry and valet shop.
hotel air handling unit’s humidifiers. The design of the steam plant should be sized
with fire tube or water tube type steam boilers and 100% standby. 2.6 Heat Exchangers
The boiler plant shall include a condensate receiver and pump set, de-aerator, feed Heat exchangers are to be either shell and tube type or plate and frame depending
water pump set, flash tank and blow down tank. on the system operating conditions. Heat exchangers are to be mounted on
concrete pads where possible.
A water softener shall be provided to supply the feed water system.
2.7 Water-side Economiser
Laundry and valet equipment, unless otherwise specified by the equipment
manufacturer is to be supplied with a steam pressure of 150 psi (10.34 Bar). Pressure Utilise plate and frame heat exchangers for water-side economiser and/or all other
reducing valves (PRV) will be required for equipment using lower steam pressure. required applications.

Kitchen Consider a fouling factor of 0.001 for the selection of the heat exchanger. Provide
glycol heat exchangers and fill stations in cold weather locations.
If steam is used for the kitchen and dishwashing equipment, unless otherwise
specified by the equipment manufacturer is to be supplied with a minimum

6 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

3. HVAC Guidelines

3.1 General Air Handling Units and HVAC Criteria — Provide flexible couplings at suction and discharge pipe connections to pumps
and chillers.
The hotel building shall be generally maintained under positive pressure to — Electrical connections to mechanical equipment shall use flexible electrical cables.
prevent infiltration.
— Wall and floor penetrations shall be isolated from the building structure to
Ductwork (excluding kitchen exhaust ductwork) shall be provided in accordance prevent transmission of vibration, and to prevent leakage of sound through
with SMACNA– Sheet Metal and Air Conditioning Contractors National Association. cracks around the penetrations.
Kitchen exhaust ductwork must be NFPA 96 or equivalent compliant. Ductwork
— Provide thrust restraints on vane-axial fans with TSP greater than 9cm (3.5 in)
outside of the kitchen shall be enclosed in a fire enclosure or if approved by the
Authority, provided with a 2-hour fire rated, UL listed or approved 2-hour rated duct — All roof-mounted equipment subject to wind loading may require special
assembly and labelled wrap. If approved by the Authority, ductwork downstream of vibration isolation mounts. The lateral and vertical anchored restraints must
the ecology unit may be HVAC grade ductwork. be selected carefully and installed so that the vibration isolation system is not
short- circuited
All visible ductwork in display kitchens or guest visible areas shall be stainless
steel.Unless advised on the contrary by the project acoustical consultant, sound — The project acoustical consultant shall develop parametric specifications for
attenuators (silencers) shall be provided on supply and return air ductwork to air acoustical requirements and isolation systems as necessary to meet local
handling units and on dedicated exhaust system ductwork. Return air ductwork industry standards.
shall be extended to within 15m (50 feet) of the furthest return air grill, when
the ceiling spaces are used as a return air plenum. Grilles shall be ducted in Dehumidification process and controls shall be provided to ensure that the humidity
smoking areas. level with the building does not exceed these standards.

The following vibration isolation criteria shall apply to all HVAC equipment and Pumps or glycol heating coils are required to circulate water to prevent a chance of
associated ductwork and piping: coil freezing in cold weather climate.
— Vibration isolators with static deflection shall support
Consider using multiple supply fan arrangements (duplex/fan wall) for possible
— Ductwork and piping and type equal to those used for the associated equipment
energy efficiency and redundancy.
for the first three support points either side of the equipment. Beyond this,
provide vibration isolators with static deflection equal to one-half the first three
Mechanical rooms shall be located as close as possible to the areas that are being
support points for a minimum of 12m (40 feet).
served to avoid long duct runs, shafts and lowered ceilings.
— Provide 5cm flexible canvas connectors (2 inches long minimum) between
fans/air handler units and ductwork.

7 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

Specifications for acoustical requirements and isolation pads must be developed by Return and exhaust fans shall be SWSI centrifugal or tubular type with backward
qualified consultants and included in the project scope. Provide vibration isolation inclined air foil type wheels and complete with 200,000 hour L50 rated bearings
as required to meet North American or European industry standards (depending on with extended grease lines, high efficiency electric motor and adjustable v-belt
hotel location). drive secured to a structural steel base on a spring type vibration isolators selected
by project acoustical engineer.
Linear diffusers shall be provided in all public spaces and shall be carefully
coordinated with the interior designer. All mechanical devices such as variable air Consider using direct drive plug/plenum fans instead of belt-drive forward curved/air
volume boxes, drainage cleanouts and isolation valves shall be provided with access foil fans for reduced noise, reduced cabinet size and improved system performance.
that has been coordinated with the interior designer. Individual temperature control
shall be provided for all areas with varying usage profile or exposure. Consider using multiple supply fan arrangements (duplex/fan wall) for possible
energy efficiency and redundancy.
Unless otherwise advised by the project acoustical consultant, there shall be no
rotary equipment located in the ceiling spaces or on the roof above any function Central air conditioning systems shall have high efficiency; high capacity bag type
room (Ballrooms, Meeting Rooms, Boardrooms, etc.). filters with pre-filters. Use MERV 13 filters on all air handling equipment.

Variable air volume systems shall be provided with variable speed drives (VSD) and Ventilation systems serving utility areas are to have disposable filters. Where
VSD duty fan motors. Utilise premium efficiency or ECM motors, if feasible. Where disposable or replaceable type filters are used, one set of spare filters is to be
power quality is a concern, a full voltage bypass shall be provided. provided in addition to the new filter being installed.

Cartridge type filters shall be provided for VAV systems. Fusible link fire, combination fire and smoke, or smoke dampers shall be provided
where ductwork passes through fire rated construction. The position of the fusible
Multi-zone dampers shall be low leakage type, double skin air foil type complete with link must be visible to clearly show the position of the damper. Access doors shall
jamb seals and blade edge seals, maintenance free bearings and internal linkage. be provided immediately upstream or downstream of each smoke and fire damper.
Dampers and access doors shall be built to meet local code requirements or the
All air-handling units shall be provided with economiser features to provide airside above detail - whichever is stricter.
free cooling when the outdoor air enthalpy is lower than the indoor air enthalpy.
Incorporate air-side economiser on all air handling units or as required based on Public washrooms shall be provided with air conditioning in addition to exhaust.
climatic conditions. A minimum of 10.11 l/s/m2 (2 cfm per square foot) shall be exhausted. An exhaust grille
shall be provided for each full height stall within public washrooms. High-rise hotels to
Air handlers shall be factory-assembled units of G90 galvanised steel panels with be provided with toilet exhaust remote or centralized fans. Consideration to be given
factory applied rigid insulation on the interior and a rigid steel frame. Coils shall to limiting the speed or shutting off fans during midday and night-time periods
be corrosion resistant aluminium fin, copper tube construction suitable for both
normal and salty conditions. Coils shall be designed with corrosion resistant finish A separate exhaust system for a paint booth(s) shall be provided in the maintenance
fans and should be a DWSI backward inclined air foil blade type. Filter sections area (NFPA compliance or equivalent requirement).
shall be complete with filter racks, 30% efficient pre-filters and 85% efficient
cartridge type filters. Adequate maintenance access shall be provided for air
handling unit servicing.

8 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

3.2 Miscellaneous Operating Equipment Criteria The following areas must be air conditioned when outside design criteria for
summer is above 75° dry bulb and 65° wet bulb:

The following criteria shall apply to all circulating pumps: — Kitchen shall have a required temperature of 27° C (80° F) dry bulb at 60%

— Motor driven, centrifugal type — Bake shop, pastry shop, laundry and valet shall have a required operational
maximum temperature of 27° C (80° F)
— Large pumps shall be horizontally split case, double suction type
— Garde Manger, chocolate shop, butcher shop and beverage stores to have a
— Smaller pumps shall be vertically split case, end suction type
required temperature of 18° C (65° F)
— All pumps s hall have shut off valves and strainers in the suction side and check
— Computer room shall have a required temperature of 22° C (72° F)
valves and throttling valves on the discharge side
— Telephone equipment room (Server Room) shall have a required temperature of
— The design pressure for each pump shall be at least equal to 1.5 times their
21°C (69° F) 50% RH.
working pressure

— Pumps shall be installed on spring-isolated concrete inertia blocks, etc, to ensure The VAV systems are to be designed using the following criteria:
that noise and vibration are not be transmitted to the building structure
— Maintain absolute minimum total system static
— Chilled water and condenser water pumps shall have factory mechanical
— Maintain minimum duct velocities in accordance with applicable codes industry
seals installed
standards. These services as per guidelines must be verified by the mechanical
— Each chiller shall have a minimum of one chilled water pump and one condenser consultant - for the hotel bedroom and general offices – 5.08 mps (1000 FPM);
water pump and shall be piped to allow cross-use Boardrooms – 6.1mps (1200 FPM)
— Each boiler shall have one circular pump. — Meeting rooms, ballrooms and pre-function areas – 4mps (800 FPM);
Restaurants – 7.62mps (1500 FPM); Spa and Fitness – 6.1mps (1200 FPM)
— Provide flexible couplings at suction and discharge pipe connections to all
pumps. — Unless otherwise advised by the project acoustical consultant, ducting layout
shall avoid components such as mitred elbows, conventional and acoustical
— All pumps shall be mounted on inertia bases on vibration isolators.
turning valves, bullhead tees, etc. in order to ensure that noise is kept to a
— For pumps on floors on grade, neoprene mounts with a static deflection of minimum.
1.25cm (0.5 inch) shall be initially selected.
— The air distribution ductwork shall be sized on the basis of the Static Regain
For pumps supported on floors above grade, steel spring isolators with 2.5cm (1 Method (SRM)
inch) static deflection should be initially selected. The project acoustical consultant
— Pressure-independent low-pressure VAV regulators shall be selected to serve
shall verify all mounting conditions and advise the design team on the appropriate
each occupied space
mounting system on a case-by-case basis.

9 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

— Supply duct connection shall be either galvanized rigid metal or a maximum of — Where temperatures fall below freezing, preheat coils are to have a minimum of
155cm of bonded aluminium flex with no more than a 45° bend. Flex ductwork two steam traps
shall be avoided wherever possible
— Each section of preheat coils is to have an individual control
— Terminal ceiling diffusers or booted-plenum slots shall be specifically designed
for VAV air distribution from the standpoint of minimum “dumping” action at Water-cooling and heating coils are to be designed and specified to meet the
reduced air volumes and from the standpoint of sound levels at maximum cfm following criteria:
delivery shall be selected.
— Water heating and cooling coils are to be of the continuous tube type with
— Unless otherwise approved by the project acoustical consultant, there shall be no vertical fins, tested to 21.1 kgf/cm2 (300 psi) pneumatic pressure and provided
VAV boxes located in the ceiling spaces or on the roof above any function room with positive methods of draining and venting
(ballrooms, meeting rooms, boardrooms, etc.)
Electric heating coils are to have finned tubular heating elements and are to be
Quiet operating centrifugal fans are to be designed as follows: resistance wire centred in copper plated steel tubes.

— Rated in accordance with AMCA or equivalent procedure and shall bear the — Direct expansion coils are to have fins copper bonded to the tubes by hydraulic
AMCA or equivalent seal expansion of the tubes and tested to 21.1 kgf/cm2 (300 psi) pneumatic pressure.

— Class I, II or III as recommended by AMCA or equivalent based upon both


Electric motors are to be designed and specified to meet the following criteria:
operating pressures and maximum tip speed
— All motors are to be of the quiet operating type and preferably should be from
— Blades continuously welded to hub and inlet rim are to be backward inclined
one manufacturer
from the direction of the rotation for non- overloading power characteristic
— All motors and accessories are to comply in all aspects with NEMA or equivalent
— Bearings are to be precision anti-friction, pillow-block, either ball or roller type
standards, are to include a service factor and to be energy efficient
with an average minimum life of 60,000 full load hours
— Exhaust fans for dishwashers are to be wired so that the fan only works when
— Vibration isolators are to be provided as per the guidelines from the project
the dishwasher is in operation
acoustical consultant

With cabinet type air supply units, design and specify the fans to be centrifugal Ductwork are to be designed and specified to meet the following criteria:
non-overloading silent type with double-inlet, multi-blades. Also, allow for
— Kitchen range hood exhaust ducts are to be manufactured from 16 gauge black
maintenance access.
iron and are to be provided with clean-outs at each bend, every 3.0m (10’ 0” feet)
horizontally and every 6.0m (20’ 0”) vertically and shall be installed to the latest
Steam coils are to be designed and specified to meet the following criteria:
version of NFPA or equivalent standard.
— Coils to be of the steam distributing type, within a tube construction with heated
— Dishwashers and laundry flat ironers are to be manufactured from stainless steel
return headers
for a minimum distance of 7.6m (25 feet) from the equipment
— Coils are to be provided with an outlet for complete drainage of condensation
— For gas operated equipment, verify equipment ducting specification.

10 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

— Horizontal ducts from dishwashers are to pitch toward the equipment at 25mm
3.3 HVAC for the Guest Unit
per 3m (1 inch per 10 feet)

— Swimming pool supply and exhaust air ducts are to be manufactured from Horizontal four-pipe fan coil units (FCU) are required in the guest rooms and
aluminium. residential units for heating, cooling and air distribution. In tropical environments
where heating is rarely required and energy consumption justifies, a two-pipe
— Laundry dryer exhaust ducts are to be manufactured from galvanized steel with
system with electric reheat may be considered.
watertight joints and the interiors are to be smooth and free from any intrusions

— The inside of supply and return ducts and plenums in public areas are to be If vertical FCU’s are considered, the unit will need to be fully ducted sound
painted matte black for any portion visible through the grille. Any exterior dampening and air supply location at the bulkhead over the entry.
ducting, if seen through any grilles, shall be painted matte black.
For 4-pipe FCU’s, the system will directly control a 3-speed line-voltage fan motor
Sound levels due to air conditioning and ventilation equipment, pipes, ducts, etc. with rating of up to 0.3 Kw (½ HP). The system will also control two line-voltage
are to be designed to not exceed the following criteria: valves that regulate the cold and hot water flow. The system will provide automatic
switchover from heating to cooling operation at each room. Provision shall be made
— Boardrooms, meeting rooms – NC25~30 or RC25~30 (N)
to prevent the system from switching repeatedly from cooling to heating and back
— Ballrooms, executive offices, massage rooms – NC30~35 or RC30~35 (N) while attempting to maintain a constant target temperature.

— Public spaces, pre-function corridors, lobby lounge, main dining and general
The HVAC Control Strategies are as follows:
offices – NC35~40 or RC35~40 (N)

— Guest rooms, suites and residential units – NC 30 (N) night-time with FCU on Humidity Control
low speed — The system in the room shall have the option to be equipped with a humidity
— Staff cafeteria, swimming pool and health club – NC40~45 or RC40~45 (N) sensor and logic capable of maintaining a set level of humidity through
activation of the room air conditioning unit on a pre-defined duty cycle.
— Kitchen and laundry – NC 50 or RC40.
— Both humidity control and refresh cycle will activate in unoccupied rooms only.
Unless otherwise advised by the project acoustical consultant, neoprene or vinyl
coated fibreglass of 0.6kg (1.5 pounds) density acoustic duct lining of at least 25mm Fan Speed Control
(1”) thickness is to be provided and installed to the following areas: — Fan speed shall be selected automatically by the system to match the heat gain/
— Discharge and intake ducts of every low-pressure handling unit for a minimum loss in the room. Fixed-fan operation shall also be available to the guest.
distance of 4.6m (15’0”) or provide an acoustic silencer — Fan coil unit selections shall be based on the fan operating a medium speed
— Insulating materials shall be provided and installed to all piping, mechanical with NC levels of 35 for medium and low speed with NC levels of 30 for night-
equipment, ductwork, etc. time operation.

— Fan coil units — The make-up air shall be humidity controlled in balance with the
air-conditioned supply.

11 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

Energy Conservation Guest room bathrooms shall be provided with one exhaust grille for the shower and
one exhaust grille for the water closet. Guest toilet exhaust fans are to be designed
The system shall provide optimised energy conservation measures with minimum
to maintain negative pressure with respect to adjacent rooms and positive pressure
inconvenience to the guest.
with respect to outside air. Make up air for toilet rooms and other exhaust systems
Consider an option of an “energy mode or eco option” button or environmental should be designed to be continuously conditioned air and not filtrating outside air,
awareness function to allow the guest to activate a variety of hotel defined energy or natural ventilation. Toilet exhaust systems for each water closet shall exhaust 75
conservation and eco-friendly practices. The button shall be available on the cfm directly to the outdoors.
thermostat or as a switch in the room connected to the system.
The system shall be capable of supporting multi-room suites, where the rooms are
The quantity of make-up air supply must be sufficient to offset the toilet exhaust not separated by a door, yet each room has its own FCU. The System shall be able to
while maintaining the guest room and / or residential units at negative pressure link the thermostats and bedside panel in these rooms so that they track.
relative to the corridor. The corridors shall be positively pressurised relative to the
guest room and the guest room shall be slightly positive relative to the outdoors. 3.4 Digital Thermostat for Guest rooms
Outdoor air shall be supplied from the make-up air unit in the immediate vicinity of
each fan coil unit intake for delivery throughout the guest suite. Outdoor air shall
The thermostat controlling the guest room HVAC system shall be a multi-purpose
also be supplied into the enclosed corridors.
thermostat with the capability for integration as part of a centrally controlled
“intelligent guest room” with built-in presence detection.
The supply air diffusers within the guest room and / or residential units shall be
located in the room wall so that the supply air stream is directed away from the bed.
Supply air diffusers shall be double deflection grilles with no visible screws; finish The system shall be a wall-mounted illuminated digital thermostat that will be able
specified by interior designer. Return air grilles or slots shall be provided. Return air to display the following:
grilles shall have no visible screws; finish to be specified by interior designer. — Current room temperature and target temperature in °C and °F.

Unless otherwise advised by the project acoustical consultant, acoustic lining for a — Clear indication of system status with guest operated On / Off button
minimum of 1.5m (5’ 0”) length shall be provided on the discharge ductwork of all
— Three fan speeds that may be manually adjusted separately from the
fan coil units.
temperature control.
Access doors for each fan coil unit shall be coordinated with the interior designer.
— Heat and Cool options
The unit is to be located over the entry vestibule or in the closet. The location of the
unit must allow for adequate space to access and service filters, pans, drain and The thermostat should have the capability of humidity monitoring and control.
water connections, valves and controls.
For acquisition properties and major renovation projects, if (and only if) the
Valves and controls must be located directly over the pan. Provide galvanised FCU or heating system does not allow for the integration with “intelligent
condensate pan under FCU with pan extension below chilled water valves and guest room” technology, provide a thermostat with the minimum features
controls. FCU shall be provided with spring isolation system to de determined by noted above.
the project acoustical consultant.
Refer to AccorHotels preferred suppliers for GSRM Systems

12 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

To the extent that the system includes another temperature setting panel motion sensors coupled with timing logic. (Multi-point lighting including
(i.e. bedside controller) in the guest room, changes to the target temperature master scene control, welcome light scenes based on PMS check-in)
made on the other panel shall be displayed on the digital thermostat. Likewise,
­— Integrated “Make up Room”, “Do Not Disturb”, and doorbell functions -
changes to target temperature made on the digital thermostat shall be
both to alert staff and guest in the hall as well/remotely as well as provide
displayed on the panel.
data for reporting.

­— Mini-bar / Mini-Fridge control message reports - detailed daily reports on


3.5 Networked Energy Management System
which mini-bars are actually opened.

Each guest room system will communicate in real-time with a central ­— Green qualifications to support hotel acquiring “LEED” or other equal
computer interfaced to provide the following minimum functionality: sustainable status.

­— Guest room Un-rented and Staff Occupied: ­— Centralised control system in order to provide not only the room status,
The thermostat shall allow the temperature to drift up or down within room temperature, light status, capability of upgrade to include (but
a programmable setback band to reduce energy consumption when not limited to) any of the following integrated room automation options
the guest room is unsold/un-rented. An additional provision shall be including Multi-Point Lighting Control, Dimming and Scene Control,
incorporated for a secondary temperature control level for staff cleaning electronic “Do Not Disturb” / “Make up room”, door chime system drape
and maintenance. control. Bedside console control of guest room and interface to the PMS for
reporting (and control) of energy usage and guest trends, (service request
­— Guest room Occupied and Unoccupied: reporting, service request performance tracking alarming), etc.
The thermostat shall have an integral occupancy sensor and wired or
wireless magnetic door switch to identify when the guest room is rented The system panel shall be easy to use, with 3-dimensional colour graphic
and unoccupied; to allow the temperature to drift within a programmable display of room information.
set point to reduce energy consumption. All room-related parameters such as target temperature upon Check-in,
setback temperatures, and the like shall reside in non-volatile memory in
Additional minimum requirements for in-room automation are as follows:
each room and shall be programmable from the central computer.
­— Ability to manage the temperature of the room for the benefit of both The application program shall be changeable through the central computer,
the guest as well as cost savings, leveraging the information provided by without the need to visit the room. The program stored in each room shall not
the Property Management System and Thermostat in the room as well as be affected by the temporary loss of power regardless of the duration of the
motion sensors and timing logic (in-room occupancy based control). power outage.
­— Ability to manage the lighting of the room for the benefit of both the guest After a power outage, the system throughout the hotel shall start up automatically
as well as cost savings, leveraging both controls within the room as well as and will be fully operational within 5 minutes after restoration of power.

13 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

In the rooms, all loads controlled by the system will be returned to their designed to handle the entire heating load, while in conditioned spaces they
previous states, including target temperature, selected fan speed operation are sized to operate in conjunction with the air conditioning system. Hot water
and lights, regardless of the duration of the power outage. is preferred as a source of heat.

The project consultant is to confirm final capacities and equipment selection


3.6 Corridor Air Conditioning and Pressurisation
once lighting design and interior design is complete.

To restrict smoke migration in the event of fire and for odour control, corridor
All public areas shall have tamper-proof temperature sensors placed
airflow is to be positively pressurised with airflow from the corridors into
discreetly in the each zone. The operator from the monitor system shall
guest rooms.
define all set points.

3.7 Public Areas Heating and Cooling 3.8 Spa HVAC


Public spaces, including large volume living rooms, shall be ventilated and air-
The Spa will be conditioned with a centralised VAV air handling system.
conditioned by means of individual air handling units. Conditioning of multiple
Each treatment room will be on its own zone, independently controlled. The
rooms or zones from a common AHU should be equipped with zone dampers
coed lounge and the private lounges will also be on their own zonal control.
and variable fan speed controls. The heating and cooling system for public
Individual design requirements shall apply for heating, cooling, ventilation and
areas shall be connected to the building automation system to allow the units
humidity control for all unique conditions, i.e. wet treatment, sauna, steam, and
to switch to an energy conservation mode based on occupancy and demand.
inhalation and relaxation rooms.
Low-pressure air handling equipment, ducted air distribution systems and
linear diffusers should be used. Perforated false ceilings with a pressurised
The cooling load from the exercise area is to be calculated on a basis of the
plenum above are not accepted.
room being fully occupied with guests doing a vigorous workout.

The amount of outside air ventilation shall be demand-controlled based on


indoor air quality and CO2. Where return air is used, an economizer system
with outside exhaust and return air dampers for free cooling shall be provided.
Centrifugal blower type heaters are to be used at entrances.

Propeller type heaters are to be used at loading docks and equipment rooms.
Base radiators and convectors are to be designed for full height windows in
cold weather environments. Heating units in unconditioned spaces are to be

14 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

3.9 Kitchen HVAC 3.10 Underground Parking / Loading Dock

Kitchens shall have a dedicated make-up air system complete with heating Underground parking areas shall be ventilated at a rate of 0.043m3/min (1.5
and cooling to maintain the desired space temperature. Kitchen areas shall be cfm/ft²) in accordance with the requirements of the International Building
maintained under a negative pressure to ensure there is no migration of doors Code or local building code requirements. Exhaust fans will be located such
to adjacent areas. Only conditioned outside air shall be supplied at a rate not to that the arrangement shall provide cross ventilation to the entire area unless
exceed 90% of the exhaust air rate. Supply air should be provided to the space ducting is required per local code. Carbon monoxide and nitrogen dioxide
by means of grilles or linear diffusers on the side opposite the exhaust hoods. concentration monitoring systems shall initiate exhaust fan operations in the
Total airflow depends on input from the food service consultant for heat gain garage to maintain the CO and N2O levels within acceptable limits.
and exhaust loads. I
f free air movement to remove car exhaust gases is not guaranteed at the
The kitchen consultant shall provide the design for the stainless steel exhaust Loading Dock then a separate air system controlled by a carbon monoxide
hoods. All exhaust hoods; ducts and ventilation systems shall meet NFPA or control system must be provided.
equivalent requirements. The consultant shall determine special requirements
for grease filters, extractors and UV oxidation lamps, as required. Where 3.11 Mechanical and Service Areas
exhaust discharge above the roof is not feasible or where doors are a nuisance,
a kitchen ecology unit shall be provided with a high efficiency filter systems The boiler room shall be supplied with a sufficient amount of outdoor air to
and grease/odour reducing module. Spot cooling shall be provided for hot maintain proper combustion and set point temperature. Transformer and
cooking areas as required. switchgear rooms shall be adequately ventilated to maintain a maximum
temperature of 30° C (85° F). Carbon Monoxide detectors are to be provided in
A separate, stainless steel exhaust system shall be provided for the all fuel burning locations (Boiler Rooms, Generator rooms etc.)
dishwashers.
Elevator machine rooms shall be air conditioned as required to maintain a
The project consultant will prepare a cost/ benefit analysis for the addition of maximum temperature of 30°C (85° F).
UV hoods to minimize grease accumulation, reduce doors, fire hazard and to
the lower the operational costs for periodic cleaning of the duct and ecology If air cooled condensers are used for refrigeration, the room shall have a
unit grease filters. sufficient amount of air supply and exhaust air movement to dissipate the heat
emitted by machinery. Air-cooled condensers should be installed outside the
building in a location that does not impact the guest.

15 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

3.12 Laundry — Condensing units

— Exhaust and Supply fans


The laundry consultant shall provide requirements for cooling and ventilation.
— Lift stations
Single zone air handling unit for heating and cooling is acceptable. Separate
exhaust ducts must be provided for dryers and ironer. Tumbler exhausts shall — Miscellaneous Alarms
be equipped with efficient lint filters. Careful review of termination location is
— Pool equipment Etc.
required to avoid unfavourable effects to guests and equipment. Untreated
make-up air may be used for dryers. — Air handling units

— Pumping systems
In cold climates provide a booster coil to heat the make-up air. Spot cooling in
— Critical mechanical systems (per consultant’s recommendations)
valet and ironer is required. A separate air compressor is to be designed and
installed for the laundry and valet shop. Vacuum piping is to be provided that — Electrical equipment
will supply the laundry and valet.
— High Voltage Switchboards

3.13 Building Management System (BMS) — ATS

— Main Low voltage panels


The project shall include a building management system to allow the operator
to overview and interface to the entire system including: — Emergency Generators

— Performing energy management functions — UPS

— Printing (immediate) and recording of alarms and reports The system shall include:

— Visualisation of all installation — Distributed data gathering panels located in mechanical room

— Changing set points based on project, client or location requirements — Third party integration devices for connection to manufacturers control panels,

— Maintaining historical trend data — Application specific controllers coupled with a building management server,
graphics packages, printer and web.
The areas to control as a minimum are as follows:
— A Separate network on its own dedicated backbone.
— Guest room HVAC system / intelligent room system; as an integrated
system or a standalone system (refer to section above for specifics)

— Chiller and boiler plants

16 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

3.14 Cold Climate Design

In cold climates, additional provisions must be provided to achieve comfort,


safety and protection of property.

Comfort

— Perimeter heating at exterior façades;

— Radiant floor heating;

— Overhead radiant heating at exterior spaces i.e. Porte Cochere, outdoor


patio seating etc.

Safety

— Snow and Ice melting of public circulation spaces, ramps, roofs, eves etc.

Property

— Heat tracing on all piping systems susceptible to freezing.

— Surface conditioning to all areas susceptible to condensation,


i.e. exterior glazing.

17 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

4. Sustainable Initiatives
The intent of the concepts identified below is to expand the boundaries for
4.2 Hot Water Reheat Heat Recovery
sustainable projects. While we aim to offer comprehensive sustainable design
initiatives into our hotel brand design requirements, we realise that we cannot
Standard chillers reject all heat to cooling towers and gas fired boilers are used to
respond to all of the organisations, methodologies and innovations that will be ever
produce hot water for reheat of dehumidification systems. Install condenser heat
evolving in this ever-changing methods of construction.
recovery bundle on one chiller to produce reheat hot water.

These and other ideas and innovations merit consideration if important to the
Consider that the energy model may show a better payback with more efficient
project vision.
chillers (magnetic drive), in lieu of a less efficient heat recovery chiller.

Many of these different sustainable “best practice” concepts focus or emphasise


4.3 Condensate Recovery
slightly different aspects of the sustainability design including but not limited
to site issues, water, energy, materials, and indoor environmental quality. These
Recover waste water from condensate drains for use as makeup water for cooling
will vary based on project scope and location, climatic variations and local codes;
tower or irrigation.
incorporating these concepts shall be considered on a case-by-case basis.
4.4 Cogeneration
An environmental consultant shall be required if the project proposes to seek these
sustainable design alternatives as part of the accreditation process.
Consider use of waste heat from electricity generation for hot water heating.

4.1 Chiller Plant - Variable Primary Flow (VPF) Plant 4.5 Solar Hot Water Heating
VPF eliminates the constant flow chiller pumps and uses the variable flow pumps to
Prepare cost/benefit analysis to determine whether this is a viable option. Provide
circulate water throughout the entire chilled water loop. The chiller is outfitted with
utility cost information, cost for system and projected cooling loads. There shall also
a variable speed drive that allows for infinite ramping of the chiller based on actual
be an aesthetic consideration if these are on visible roofs.
load conditions.
4.6 Tri-Gen
Special care must be taken to ensure the incorporation of a control system with
fast-acting control valves. This system may not be recommended for some
Where feasible, consider use of Tri-Gen for the simultaneous generation of
regions worldwide.
Electricity, Heating energy and cooling energy.

18 Accor Technical Document | Version 0 | June 2019


Mechanical Systems | Technical Document
1. Air Conditioning Systems | 2. Steam & Hot Water Boiler Plants | 3. HVAC Guidelines | 4. Sustainable Initiatives

4.7 Thermal Comfort


Meet the latest version of ASHRAE 55 2009 or similar equivalent system for
humidification requirements and provide controls. Design ventilation systems and
controls to comply.

4.8 Building Systems Commissioning


Hire Commissioning (Cx) agent before end of Design Development phase.
Incorporate Cx requirements into specs.

Minimum Indoor Air Quality (IAQ) Performance: Meet latest version of ASHRAE
6-2009 or similar equivalent system requirements.

4.9 Environmental Tobacco Smoke (ETS) Control


No smoking in hotel and or in any indoor public areas or within 7.6m (25ft) of any
building entrance (also consider International/local smoking policies and customs).

4.10 Indoor Pollutant Source Control


Isolate air and water pollutants. Properly ventilate areas where hazardous gases
or chemicals may be present or used (including conditioned garages and
housekeeping/laundry areas and HOH copy rooms, if any).

4.11 Thermal Ice Storage


Consider the production of ice at night to use for cooling during the day to avoid
energy demand during peak periods. Prepare cost/benefit analysis to determine
whether this is a viable option.

19 Accor Technical Document | Version 0 | June 2019

You might also like