Professional Documents
Culture Documents
The analyst uses this checklist to assess the laboratory, this helps the analyst to have an
idea of how to improve the laboratory.
Lighting Uniformity
We measure the brightness lux level by using the lux meter, and then we can get the figure so
certain zones. It is unlikely to measure the parameter by a single device there is no uniformity of
the data. It is because lighting uniformity is defined as the ratio between minimum to average
lux, or minimum to maximum lux. Lux is the unit of illuminance, indicating the actual brightness
received on the ground. This uniformity ratio is extremely useful as it allows us to determine how
the lights evenly distribute light onto the ground. If the difference between average and
minimum lux is not high, the ratio would be high. It indicates better light uniformity. Shown below
summary of the lux in different zones.
Value Lux
Minimum 122
Average 264
Maximu
m 341
The analyst also configures the sides of each zone where they find out that the area of
every zone is 3.9688m2 so that we could be able to find out the acceptable illuminance.
According to IESNA, a school laboratory should have a light level of 50-75 FC or 500 to 750 lux.
Zone 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Average 25 28 24 24 28 27 25 25 30 29 27 22 26 26 22 27
Lux 2 8 7 6 5 0 8 9 3 1 7 8 4 4 8 3
Table __ Average Lux of Each Zone
The zone that is greater than or equal by 277 lux is Zone 2, 5,9,10, and 11 it means that
the zone that is said is the only zone that conforms to the needed lumens.
There are eight luminaires in the laboratory with 2 fluorescent lamps for every luminaire
there are also buffers and diffusers in each luminaire. The total number required for the
laboratory according to the lumen method is 8.07 or eight, so the total number of luminaires in
the current laboratory is in the standard. The ratio of the distance between adjacent luminaires
(center to center) to their height above the working plane is 1.26 meters. And the distance
between the luminaire and its adjacent wall is 1.95 meters and the distance between two
adjacent luminaires is 2.255 meters and the distance between the parallel luminaires is 3.52
meters.
The distribution of luminaires is shown below.
The table below provides acceptable sound levels for various room types. This table covers a
majority of the space types that an architect may be interested in.
The analyst took a sound reading in the same zones as seen in figure __ the analyst took the
average of the three groups and after that the analyst took the average of the 16 zones as
shown below.
Zone dBA
1 69
2 71
3 69
4 67
5 68
6 65
7 61
8 62
9 67
10 71
11 65
12 65
13 64
14 65
15 64
16 62
Overall
Average 66