You are on page 1of 3

INSULATORS

Safety Considerations Favour


Safety and reliability are increasingly 3. The joint can separate into two parts in quite a
important considerations for power This is the adhesive joint between the catastrophic manner. Therefore, such
utilities and are therefore becoming tube and the metal flanges. designs should be avoided.
one of the most important advantages

Hollow Composite Insulators on offered by composite insulators


in place of porcelain housings on
pressurized substation equipment.
4. The flange
The metal flange transfers mechanical
loads to other parts of the assembly.
Failure in the adhesive joint is another
undesirable failure mode. For this
reason, this joint should be designed to

High Voltage Apparatus


have a greater safety margin than the
Insulators filled with compressed gas The insulator norm does not specify other insulator components. To verify
can store great amounts of energy which modes of failure are or are not that insulators have safe behaviour,
(typically anywhere from 100 to acceptable during a pressure test. even if loaded to failure, one optional
1000 kJ depending on size and Still, for safety reasons it is preferable test to consider is to pressurize to
pressure). To reduce the risks associated that the failure mode is by leakage failure once type tests have been
with explosive failure, current completed. Such failure should then
international standards prescribe ideally occur only by leakage through
minimum requirements for materials, the tube wall.
design and construction as well as
validation of these by full-scale testing Modeling can also be used to optimize
and routine manufacturing inspection. design of the tube and adhesive joint
The selection of hollow composite insulators prior to manufacturing prototypes and
to replace porcelain on HV equipment such Typically, all such vessels must be verifying by means of type tests. Stress
as bushings, surge arresters, breakers subject to a routine pressure test to analysis is performed to determine the
(both live & dead tank) and instrument verify structural performance prior local stress state in a single layer of the
transformers is increasing worldwide. Indeed, to delivery. In the case of composite composite and adhesive as a function
for certain applications where reduced insulators, this routine test pressure of applied thermal and mechanical
is twice the highest pressure expected loads. The margin of safety is then
weight or superior pollution performance are
in service, i.e. the design pressure assessed using conservative failure
the key decision criteria, the majority of such
or maximum service pressure (MSP). criteria given the strength parameters
apparatus is now being ordered equipped The failure or burst pressure of these of the particular raw materials and
with this type of insulator. vessels is generally required to be at manufacturing process.
least twice the test pressure.
Hollow core composite insulators are also a It is important that these properties
prerequisite in the move toward UHV DC since There are four different parts of a are determined for the material
420 kV disconnecting circuit breakers at
they permit creepage distances to be reduced typical modern design hollow core combination and manufacturing
substation in Sweden.
compared to porcelain. This makes production composite insulator that will govern process of each particular supplier.
of very long insulators more feasible given the mode of failure due to an internal This is because certain properties
mechanical needs, especially in areas with pressure overload: may prove sensitive to design details
seismic activity. through the tube wall or by excessive of the manufacturing equipment and
But a growing requirement that also makes 1. The inner barrier layer (or liner) deformations of the flange that lead to process. In other words, material
them the preferred option is safety – not only This protects the load-carrying leakage. These are clearly better than properties determined to be relevant
for personnel but also for nearby substation composite in the tube from corrosive e.g. failure of the adhesive joint. for insulators produced by one supplier
equipment that could be destroyed in the event of degeneration products from the For insulators whose tube fibers cannot be expected to be valid for those
failure. For example, the explosive shattering of insulating gas, e.g. SF6. A new are wound either in or close to the produced by all other suppliers. For
an old circuit breaker at a insulator must be able to sustain an circumferential direction, axial strength this same reason, the performance of
400 kV near Geneva during the mid 1990s internal pressure of at least 4 times is very low and sensitive to variations similar-looking composite tubes can
caused such extensive damage to the substation the MSP with no visible damage to during manufacturing. In the event of also differ significantly among different
that it plunged the entire city into a blackout. this liner. excess pressure loading, such insulators manufacturers.

2. The load-bearing composite in


This article, based on a contribution by Anders the tube. TABLE 1: TEST OBJECT DATA
Bypass breaker at
Holmberg and Mattias Lundborg at ABB and The tube must be able to a carry
± 800 kV converter
Dan Windmar (now at STRI), reviews this issue Test object
station in China pressure of at least twice the MSP
of safety as it applies to hollow composite without damage and at least 4 times Description Live tank circuit breaker 245kV
insulators. MSP without rupture during validation Filling gas Helium
tests under ambient conditions.
The tube must also be designed to Filling pressure 15 bar (abs)
withstand all relevant mechanical, Insulator test object 1 Porcelain (brown)
thermal and electrical loads over the
entire service life. Insulator test object 2 Composite insulator with silicone rubber sheds (grey)

13 INMR® Q2 2010 Safety Considerations Favour Hollow Composite Insulators on High Voltage Apparatus Safety Considerations Favour Hollow Composite Insulators on High Voltage Apparatus Q2 2010 INMR® 14
Shatter Test of HV Breakers Data for the two test objects are effects caused by typical real-life
To compare the failure mode provided in Table 1. events such as: A B A
of pressurized porcelain versus
composite housings, a shatter test The methodology selected to • internal fault/over-pressure in the
was performed on live tank circuit investigate the different failure equipment
breakers equipped with both types of modes was by shooting with a 7.62 • external shock during transport,
insulators. The different failure modes mm caliber hunting rifle (Figure 2) installation or maintenance
were then carefully investigated. at a distance of 100 m from the test • environmental influences e.g.
object. This simulated the possible earthquake, landslide, tornado

TABLE 3: COMPARISON BETWEEN PORCELAIN AND COMPOSITE INSULATOR


Porcelain Insulator Composite Insulator
Time after impact for pressure release << 1 s > 150 s
Maximum weight of fragment 31.3 kg Not applicable
Maximum distance of fragment from test object 57 m Not applicable
Mechanical intact (load bearing) after impact No Yes

Figure 1: Live tank circuit breaker tested. C D


B
A B

Figure 2: Shatter test of insulator by rifle shot. Figure 4: ABB composite insulator, a) before shatter test, b) after shatter test, c) 6 ms Figure 5: a) Puncture of composite insulators,
after impact, d) 12 ms after impact. b) jagged porcelain fragment
TABLE 2: DISTRIBUTION OF
PORCELAIN FRAGMENTS
• vandalism e.g. rock throwing, By contrast, test object 2 (the live tank The composite insulator, by contrast,
Distance from test Weight of shooting breaker with composite insulators) remains mechanically intact and with
object [m] fragment [kg] remained mechanically intact after the only a small puncture from the bullet.
57 m 3.0 kg The live tank breaker having porcelain impact of the bullet. A small puncture
35 m 14.3 kg C D insulators experienced failure with a occurred at the point of entrance, In the event of an internal fault/inner
violent explosion. The upper breaking which was the upper breaking chamber. over-pressure or external influence such
35 m 9.5 kg chamber where the impact of the bullet There was no launching of destructive as vandalism, a porcelain insulator will
35 m 16.0 kg occurred was completely destroyed and fragments in the air. experience violent failure (explosion)
sharp porcelain fragments were ejected with dangerous fragments thrown about
30 m 6.1 kg at high speeds. Figure 3 illustrates the Figure 4 shows the results before and at high speed.
29 m 11.0 kg results before and after the impact. after impact and includes high speed
High speed photos of the event are also photos of the event. The time needed The failure mode of a composite
25 m 10.0 kg
shown. to release the overpressure through the insulator, however, is by de-lamination/
40 m 4.1 kg puncture was >2.5 minutes. puncture without launching of any
23 m 11.4 kg The main concentration of porcelain dangerous fragments. There is therefore
fragments landed in the range of 23 to Conclusions no possible damage to surrounding
30 m 31.3 kg 57 m from the test object and had a The photos in Figure 5 above show equipment and no danger for persons
35 m 20.3 kg weight of between 3.0 and 31.3 kg (see these different failure modes. The in the vicinity. This assures maximum
Figure 3: Porcelain insulator, a) before shatter test, b) after shatter test, c) 6 ms after Table 2). porcelain insulator explodes into sharp safety for both personnel and other
40 m 11.4 kg fragments spread over a wide area. equipment at the substation. 
impact, d) 12 ms after impact.

15 INMR® Q2 2010 Safety Considerations Favour Hollow Composite Insulators on High Voltage Apparatus Safety Considerations Favour Hollow Composite Insulators on High Voltage Apparatus Q2 2010 INMR® 16

You might also like