You are on page 1of 12

REMOTE CONTROLLED CIRCUIT BREAKER (RCCB)

Single Pole Three Phase


• 28 VDC • 115/200 VAC 400 Hz
• 115/200 VAC 400 Hz • Three Phase Only

Qualified
PERFORMANCE DATA
Qualified to demanding perfor-
mance parameters of MIL- PRF Rupture Levels 3600 A (115 VAC or 28VDC for 1 Pole and 115VAC for 3 Pole)
- 83383 standard. Endurance 50,000 Cycles
(Resistive & Inductive (Motor)
Use as a Relay, Circuit Breaker, Or
Both Endurance (Motor) 5-50A: 50,000 cycles; 60-100A: 25,000 cycles
Endurance (Lamp) 5-25A: 50,000 cycles; 35-50A: 25,000 cycles; 60-100A: no rating
RCCBs combine the best attri-
butes of a circuit breaker and a Dielectric Strength 1500V, 60 Hz, MIL-STD-202, method 301, 0.5 MA max
relay. Automatically protects the Insulation Resistance 100 mega ohm min, MIL-STD-202, method 302
wires and the load device dur- Thermal Temperature Range -54°C to 71°C (-65°F to 160°F). MIL-STD-202, Method 107
ing circuit/load breakdown, but
allows the flight deck control of Vibration 10G's to 2000 Hz. Exceeds MIL-STD-202, Method 204, Condition
the load during normal opera- C, 10 microseconds max. chatter
tion. Shock 25G's. MIL-STD-202, Method 213, 10 microseconds max. chatter
Altitude 50,000 ft.
Weight and Cost Savings
EMI Requirements MIL-STD-461, Requirements CS114 and RE102 over the frequency
In distributed-load applications, range of 14 kHz to 400 MHz and RE102 limits for Aircraft and
RCCBs are a more efficient Space Systems.
power distribution solution pro-
moting cost and weight savings EMI/RFI Susceptibility MIL-STD-461, Class 1D
and Generation
through the elimination of long
runs of heavy cables associ- Moisture Resistance MIL-STD-202, method 106
ated with the conventional relay Salt Spray Resistance MIL-STD-202, method 101, Condition B
- flight deck circuit protector Sand and Dust Resistance MIL-STD-202, method 110, Condition A
method. Control of the RCCB
requires only one #22 AWG Fungus Resistance MIL-HDBK-454, Guideline 4
control wire from the ICU on the Explosion Proof MIL-STD-202, method 109
flight deck to the RCCB. Weight (Single Pole) 5-25A: 318 grams (0.703 lbs.); 35-50A: 325 grams (0.719 lbs.); 60-
100A: 332 grams (0.734 lbs.)
Cockpit Space Savings
An RCCB system removes the Weight (w/ Auxiliary Contacts) 5-25A: 332 grams (0.734 lbs.); 35-50A: 339 grams (0.750 lbs.); 60-
100A: 346 grams (0.766 lbs.)
presence of large circuit break-
ers from the cockpit while per- Weight (Three Phase) 2.0 lbs. max.
mitting remote On/Off operation
from the flight deck. Combine
3AFRAN%LECTRICAL0OWERRCCB OVERLOAD CALIBRATION DATA
with Indicator Control Unit (ICU)
model #1500-052-05. @ 25°C @ +71°C @ -54°C

Specification MIN MAX MIN MAX MIN MAX


Test Time
Table Parameters
Must Hold 115% 115% 115% % for 1 Hour
Must Trip 138% 138% 150% % Within 1 Hour

4"'3"/&-&$53*$"-108&3 9

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE CONTROLLED CIRCUIT BREAKER (RCCB)

Engineering Data

Single Pole Single Throw (Double Break Contacts)

Rated Contact Load (Amperes)


28 Vdc 115/200 V 400 Hz
Catalog MIL-PRF-83383 Maximum
NumberM Res. Ind. Motor Lamp Res. Ind. Motor Lamp Part Number Weight Oz/gm
SM600BA5A1 5 5 5 5 5 5 5 5 M83383/02-01 11.75/332
SM600BA5N1 M83383/01-02 11.25/318
SM600BA10A1 10 10 10 10 10 10 10 10 M83383/02-03 11.75/332
SM600BA10N1 M83383/01-03 11.25/318
SM600BA15A1 15 15 15 15 15 15 15 15 M83383/02-04 11.75/332
SM600BA15N1 M83383/01-04 11.25/318
SM600BA20A1 20 20 20 20 20 20 20 20 M83383/02-05 11.75/332
SM600BA20N1 M83383/01-05 11.25/318
SM600BA25A1 25 25 25 25 25 25 25 25 M83383/02-06 11.75/332
SM600BA25N1 M83383/01-06 11.25/318
SM600BA35A1 35 35 35 35 35 35 35 35 M83383/02-07 12.00/339
SM600BA35N1 M83383/01-07 11.50/325
SM600BA40A1 40 40 40 40 40 40 40 40 M83383/02-08 12.00/339
SM600BA40N1 M83383/01-08 11.50/325
SM600BA50A1 50 50 50 50 50 50 50 50 M83383/02-09 12.00/339
SM600BA50N1 M83383/01-09 11.50/325
SM600BA60A1 60 60 60 — 60 60 60 — M8338/02-10 12.25/346
SM600BA60N1 M83383/01-10 11.75/332
SM600BA75A1 75 75 75 — 75 75 75 — M83383/02-11 12.25/346
SM600BA75N1 M83383/01-11 11.75/332
SM600BA100A1 100 100 100 — 100 100 100 — M83383/02-13 12.25/346
SM600BA100N1 M83383/01-13 11.75/332

Three Pole Single Throw (Double Break Contacts)


Rated Contact Load
(Amperes)

115/200 V 400 Hz
Catalog MIL-PRF-83383
NumberM Res. Ind. Motor Lamp Part Number
SM601BA10A1 10 10 10 10 M83383/04-03
SM601BA15A1 15 15 15 15
SM601BA20A1 20 20 20 20 M83383/04-05
SM601BA25A1 25 25 25 25
SM601BA35A1 35 35 35 35 M83383/04-07
SM601BA40A1 40 40 40 40 M83383/04-08
SM601BA50A1 50 50 50 50
SM601BA60A1 60 60 60 60 M83383/04-10

M Contact factory on alternate amperage, trip times, control configurations,


grounding, auxiliary switches, and mounting systems.

10 4"'3"/&-&$53*$"-108&3

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE CONTROLLED CIRCUIT BREAKER (RCCB)

ORDERING INFORMATION

Single Pole Single Throw (Double Break Contacts) Three Pole Single Throw (Double
Break Contacts)
Standard w/ Auxiliary Contacts w/ Auxiliary Contacts
AMPERE MS P/N 3AFRAN%LECTRICAL MS P/N 3AFRAN%LECTRICAL MS P/N 3AFRAN%LECTRICAL
RATING 0OWER P/N 0OWER P/N 0OWER P/N
5 M83383/01-01 SM600BA5N1 M83383/02-01 SM600BA5A1 **
7.5 ** ** **
10 M83383/01-03 SM600BA10N1 M83383/02-03 SM600BA10A1 M83383/04-03 SM601BA10A1
15 M83383/01-04 SM600BA15N1 M83383/02-04 SM600BA15A1 SM601BA15A1
20 M83383/01-05 SM600BA20N1 M83383/02-05 SM600BA20A1 M83383/04-05 SM601BA20A1
25 M83383/01-06 SM600BA25N1 M83383/02-06 SM600BA25A1 SM601BA25A1
35 M83383/01-07 SM600BA35N1 M83383/02-07 SM600BA35A1 M83383/04-07 SM601BA35A1
40 M83383/01-08 SM600BA40N1 M83383/02-08 SM600BA40A1 M83383/04-08 SM601BA40A1
50 M83383/01-09 SM600BA50N1 M83383/02-09 SM600BA50A1 SM601BA50A1
60 * M83383/01-10 SM600BA60N1 M83383/02-10 SM600BA60A1 M83383/04-10 SM601BA60A1
75 * M83383/01-11 SM600BA75N1 M83383/02-11 SM600BA75A1
80 ** **
*
100 M83383/01-13 SM600BA100N1 M83383/02-13 SM600BA100A1
*
All Ampere Ratings equal to Rated Contact Loads (Resistive, Inductive, Motor, and Lamp) except as noted.
* No Lamp Load Rating
** Contact Factory
Note: Contact factory on alternate amperage, trip times, control configuations, grounding, auxilary switches, mounting systems, etc.

SINGLE POLE TRIPLE POLE

OVERLOAD CALIBRATION DATA OVERLOAD CALIBRATION DATA

Ratings Percent Ambient Temperature Tripping Time Ratings Percent Ambient Temperature Tripping Time
Rated Current Degrees C. ± 5° Rated Current Degrees C. ± 5°

All 115% 25°C & 71°C No Trip All 115% 25°C & 71°C No Trip
138% 1 Hour Max.* 138% 1 Hour Max.*
115% -54°C No Trip 115% -54°C No Trip
150% 1 Hour Max.* 150% 1 Hour Max.*
* Must trip in one hour. * Must trip in one hour.

OVERLOAD CALIBRATION DATA — SINGLE POLE OVERLOAD CALIBRATION DATA — THREE POLE
200% Trip Times 400% Trip Times 1000% Trip Times 200% Trip Times
400% Trip Times 1000% Trip Times
AMPERE AMPERE
-54°C to +71°C -54°C to +71°C -54°C to +71°C -54°C to +71°C
-54°C to +71°C -54°C to +71°C
RATING RATING
MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX
AMPERES SECONDS SECONDS SECONDS SECONDS SECONDS SECONDS AMPERES SECONDS SECONDS SECONDS SECONDS SECONDS SECONDS
5 7 40 1.2 6.4 0.3 1.2 10 12 80 2.8 11 0.42 1.3
7.5 11 40 2.4 6.8 0.33 1.1 15 13 80 1.7 10 0.35 1.2
10 12 42 2.8 8.5 0.42 1.05 20 14 80 2.9 9.6 0.4 1.15
15 13 45 1.7 8.3 0.35 1.2 25 15 80 2.6 10 0.4 1.3
20 14 46 2.9 7.6 0.4 1.15 35 16 80 2.8 11 0.35 1.3
25 15 50 2.6 8.7 0.4 1.3 40 16 80 2.6 10 0.36 1.3
35 16 55 2.8 8.3 0.35 1.3 50 13 80 2.9 10 0.4 1.25
40 16 55 2.9 9.2 0.36 1.3 60 13 80 2.4 16 0.26 1.8
50 13 55 2.9 10 0.4 1.25
60 13 60 2.6 13 0.26 1.8
75 13 60 2.5 13 0.26 1.8
80 14 60 2.7 12.5 0.3 2
100 17 63 3.5 13 0.38 1.9

TRIP CURVE
Contact business unit for trip curve.

4"'3"/&-&$53*$"-108&3  11

“Safran Electrical & Power Proprietary Information


Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE CONTROLLED CIRCUIT BREAKER (RCCB)

Engineering Data
Application Note
Without RCCB With RCCB Distributed Load Concept
1/2 AMP
C8 SWITCH SWITCH
1/2 AMP 100 AMPS
B RCCB
U
C8 S
S L
O
100 AMPS A
RELAY D
B L MS22073-1/2 OR
C8 100 AMPS U O
S A MS26574-1/2
S D
FLIGHT DECK FLIGHT DECK

Typical Wiring Diagrams


Integrated Wire Termination Module
(MIL-STD-1549)

LOAD A2 A1 LINE
LOAD LINE

3 4 5A 5B 6
LOAD LINE
S3 S1 S2
LOAD LINE
To Indicator/ Auxiliary Contacts When Applicable
3 4 5A 5B
Control Unit
Circuit Breaker Internal Connection S3 S1 S2
Type MS22073-
1/2 OR MS26574- To Indicator/ Auxiliary Contacts
1/2 Backup Control Power (when used) Control Unit Internal Connection
115 V 400 Hz or 28 Vdc Backup Control
Circuit Breaker Power (when
(Must be same AC Phase as the Type MS22073-
“Line” Power) used) 28 Vdc
1/2 OR MS26574-
1/2

Contacts and Coil Wiring for Multiple


Circuits Only Line Protection
3 4 5A 5B 6 Contacts and Coil
S2 Circuits Only
Auxiliary Contacts
S1 3 4 5A 5B 6
S2
S3
3 4 5A 5B 6
S1
A2 A1 S3

A2 A1
B2 B1
Intermittent Duty
C2 C1
Coils Current Cut-
Off Controlled
Electronically Intermittent Duty
Coils Current Cut-Off
Controlled Electronically

Single Pole

NOTE: Terminals 5A and 5B internally grounded to the mounting leg (s). Integrated Wire
Termination (IWT) module accepts pin contacts P/N M39029/1-100 or -101. Use with
insertion/extraction tool M81969/14-02.
Three Pole
12 4"'3"/&-&$53*$"-108&3

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE CONTROLLED CIRCUIT BREAKER (RCCB) — 1 POLE AND 3 POLE

Engineering Data

Approximate Dimensions - 1 Pole


Typical Placement of .172/4.37 DIA.
R. 20
Rating on Top Plane 2 MTG. HOLES Options
5.08 • Special application auxiliary
switches
LOAD A2

.688/
LINE A1

17.48
50
• Unique grounding
2.940 Mtg. Flanges
• Power sources
74.68 Main Contact Mate As Shown • Other current ratings
Position Indicator
3.250
82.55
Red: Closed; Green: Open
1.200
• Control via systems other
2.250
30.48 than I/CU
57.15 .350
.42
• Low level auxiliary contacts
1.530 8.89
38.86
.07
1.778
10.67 .056
1.42
available
.500 - .610
• Data Bus/Interface capability
12.70 - 15.24 available
.180 • Electronically held coil
Name 4.57 • Moisture resistant sealing
Plate 4.26
108.20
3.42
86.87

.084
2.13

Three Pole
Main Contact 3.69
Position Indicator 93.73
2.28
LOAD A2

.07 3.29
LINE A1

Red: Closed; 57.91


.350 1.78 83.57
Green: Open 1.50 2.03
38.86 8.89 51.56
.77
2.526 19.56
LOAD B2

64.16
LINE B1

.05
2.526 1.27
64.16 4.26
LOAD C2

LINE C1

108.20
Location of
3.43
NamePlate
87.12
.130
50

3.30

2.940
74.68
3.250
82.55

Coil Operate Current/Set And Trip Time RCCB

Circuits Nominal I/CU Set Set Coil MAX. Set Time *I/CU. Trip Current Nominal MAX.
System Current Current Nominal Most Adverse 71°C & -54°C & Room Temp. 71°C & -54°C & Standby
Voltage @ Nom @ Nom Voltage & Condition - MIN. Nominal Nominal Nominal Nominal Nominal Current
Voltage Voltage Room Temp. Voltage 71°C. Voltage Voltage Voltage Voltage Voltage Milliamp
(Mulliamp) Pulse Ambient

28 Vdc 2 3.0 AMP 20 Millisec 35 Millisec 1.4 AMP 1.9 AMP 1.6 AMP 0.9 AMP 2.1 AMP 10
(18 volts MIN.) MAX ***
1 Pole 115 Vac
400 Hz (104 V. 2 10 AMP 15 Millisec 30 Millisec 6.8 AMP 6.3 AMP 8.6 AMP 6.1 AMP 7.0 AMP 10
MIN. MAX ** ** ** ** **
28 Vdc
(18 volts MIN.) 2 7.0 AMP 20 Millisec 35 Millisec 1.5 AMP 2.0 AMP 1.7 AMP 0.9 AMP 2.2 AMP 10
3 Pole 115 Vac MAX ***
400 Hz (104 V. 13.0 AMP 15 Millisec 30 Millisec 4.3 AMP 3.3 AMP 4.5 AMP 4.0 AMP 3.1 AMP 10
MIN.) 2 MAX ** ** ** ** **
* MAX. I/CU. Line Impedance 7.5 Current Decreases w/Time so that I2t
** Average Half-Wave Rectified DC Current ***Absolute Min. Value from -54° to +71°C

4"'3"/&-&$53*$"-108&3 13

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE CONTROLLED CIRCUIT BREAKER (RCCB) — 1 POLE AND 3 POLE

Engineering Data
Description by a command from the
The Remote Control Circuit Indicator/Control Unit (I/CU) (a ½
Breakers (RCCB) concept, as ampere fast trip, thermal circuit
load controllers in distributed- breaker).
load applications, provides for a With power available to terminal
more efficient power distribution #4 and/or terminal A1 (28 Vdc or
system with less line loss at a 115 V 400 Hz) on 1PST RCCB:
lower cost and with less weight to terminal #4 (28 Vdc) and/
than the conventional relay-flight or both terminals B1 and C1
deck circuit protector method. (115 V 400 Hz) on 3PST RCCB,
the RCCB will assume the
Designed to meet the state requested/indicated by
requirements of MIL-PRF-83383, the I/CU. If power is removed
the RCCB's capability and from terminal #4 and A1 on
advantages include: 1PST or from terminal #4 and
both B1 and C1 on 3PST, the
• Fusible link fail safe RCCB will remain in the state it
• Explosion-proof. MIL-
was in prior to power removal.
• Remote on/off operation from STD-202, Test Method 109
When power is reapplied to
the flight deck
the terminals, the RCCB will • Thermal Temperature Range.
• Visual indicators for open assume the state indicated by -54°C to 71°C (-65°F to
(green) and closed (red) on the I/CU. 160°F). MIL-STD-202, Test
top surface Method 107
• Substantial reduction in With the RCCB closed, an • Insulation Resistance. MIL-
weight and size overload or fault current on any STD-202, Test Method 302,
line or lines will cause the RCCB 100 Megohms minimum
• Most direct route from power to trip and in turn will cause a
source to load controlled overload of the I/CU, • Aircraft Electrical Power. MIL-
• Single wire control line from causing it to trip also. A fault or STD-704
I/CU to RCCB overload on any power contact • Vibration. 10 g's to 2000 Hz.
will cause the RCCB to trip open MIL-STD-202, Test Method
• Double-break power contact
within the time limits specified 204. Condition C (-54°C,
assembly
regardless of the availability of 25°C, and 71°C). Maximum
• Indication of trip or set by coil power. To reclose the RCCB, duration of contact transfer to
position of the ½ ampere circuit the I/CU line (line 3 to ground) uncommanded state: 10x10-6
breaker on the flight deck must be opened by the I/CU or seconds.
• Elimination of long runs of series switch and reconnected
• Shock. 25 g's. MIL-TD-202,
heavy and costly cables to ground.
Test Method 213. Maximum
• Magnetically latched coils duration of contact transfer to
(low power consumption) uncommanded state: 10x10-6
Other Performance seconds.
• Use as a relay or circuit Parameters For MIL-
breaker or both • Altitude. 50,000 feet
PRF-83383
• Flanges mate for in-line or • EMI, MIL-STD-461, Class 1D
• Coordination. An overload
side-by-side mounting • Moisture Resistance. MIL-
applied to two devices in
• 1PST for DC or single phase AC series with a 2 to 1 current STD-202, Test Method 106
• 3PST for three phase AC only rating will result in only the • Fungus Resistance. MIL-STD-
lower rated device opening. 454, Guideline 4
• Rupture capability to 3600A • Sand and Dust Resistance.
Application
(115 Vac rms or 28 Vdc for MIL-STD-202, Test Method
The Remote Control Circuit SM600BA and 115 Vac rms 110, Test Condition A
Breaker (RCCB) is a combination for SM601BA series)
relay and circuit breaker which • Salt Spray Resistance. MIL-
can be released or set by • Dielectric. 1500 V, 60 Hz, STD-202, Test Method 101,
applying a release or set coil MIL-STD-202, Test Method Test Condition B
current electronically controlled 301, 0.5 MA maximum

14 4"'3"/&-&$53*$"-108&3

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE CONTROLLED CIRCUIT BREAKER (RCCB)

Single Pole Design Concept BI-METAL


LOAD-L2 LOAD-L1

• 28 VDC
Introduction K
• 115/200 VAC 400 Hz J
E-PIVOT
Part of the weight of the STATIONARY
CONTACTS
modern jet aircraft comes from G-PIVOT N MOVEABLE
H-LATCH
Three Phase the electrical wires and power I L-LEVER
CONTACT
BRIDGE
control systems needed to LATCH
• 115/200 VAC 400 Hz distribute the electrical energy. BAR M C
D
• Three Phase Only As these aircraft increase
ARMATURE
their passenger carrying
capability, the electrical power
Qualified management system becomes TRIP
B
SET
more complex and could A
(CLOSED)
(OPEN)
Meets MIL-PRF-83383 become heavier. Wire runs of COIL
COIL
T1 T2
more than 300 feet from the
flight deck circuit breakers to S1 S2
Weight and Cost Savings the load become common. PERMANENT MAGNET

Saves fuel by eliminating long Utilization of 3AFRAN%LECTRICAL DOUBLE THROW


runs of heavy, costly cables 0OWERgSRemote Controlled TOGGLE SWITCH
Circuit Breakers (RCCB) close to
the load or power source will SET TRIP
Space Savings eliminate much of these long, POSITION POSITION
heavy, and expensive wire/
Keeps larger breakers out of cable. Control of the RCCB Figure 1
cockpit requires only one #22 AWG
control wire from the flight deck Single Pole RCCB magnet itself. Its path now,
to the RCCB. however, is through the right leg
RCCB System for Remote Motor Operation of the electro-magnet. The flux
Weight reduction, directly from generated by the electro-magnet
Operation wire use and indirectly from Figure 1 depicts a simplified increases in magnitude as
To form an RCCB system (generator) line heat loss, and presentation of the RCCB. power is applied, and as the flux
enabling remote On/Off opera- installation and maintenance builds up in the path through
cost reductions becomes Figure 2 describes the "motor",
tion from the flight deck, com- the right leg of the electro-
significant. which when "energized", will
bine the 3AFRAN%LECTRICAL magnet, the flux tending to latch
result in typical armature
The RCCB combines the the armature in the left leg of
0OWERRCCB with Indicator transfer operation.
best attributes of a circuit the electro-magnet becomes
Control Unit (ICU) model The magnetic circuit utilizes very small in comparison. The
breaker and a relay. The RCCB
#1500-053-05 on pg. 13. a permanent magnet as a armature then "transfers" and
automatically protects the wires
and the load device during fulcrum and latch for the rocking seals at the pole face of the
circuit/load breakdown, but armature and uses electro- right leg of the electro-magnet.
Single Wire from Flight allows flight deck control of the magnets (coils) at each end of
The cutthroat contact B in series
Deck load during normal operation. the armature stroke for transfer
purpose. In the set position with coil T1 -T2 is opened by
Control of the RCCB requires (Figure 2), the flux generated by mechanical actuation due to
only one #22 AWG control wire Operation the permanent magnet follows the armature movement. In
from the ICU on the flight deck a patch from the top of the Figure 2, a "dotted extension"
The RCCB is basically a relay of the armature represents
to the RCCB. and a circuit breaker and allows permanent magnet through the
armature, through the left leg of the mechanical actuator of the
the utilization of each identity cutthroat contacts. In actual
singularly or in combination, the electro-magnet and back to
the permanent magnet. design, this is accomplished
Use as a Relay, Circuit depending upon the application. more conveniently through only
Breaker, or Both All of the RCCB's capabilities When the coil T1 -T2 is one armature extension and
apply in either application. energized, the flux generated
Combines the best attributes of an appropriate actuator which
It can be employed as a relay is such that it "flows" through drives both contacts B and A.
a circuit breaker and a relay. the permanent magnet in the
Automatically protects the located adjacent to its load and
remotely operated much like same direction as the flux
wires and the load device relays are today through control generated by the permanent
during circuit/load breakdown, wiring and a switching device in
but allows the flight deck the flight deck.
control of the load during
It can also be utilized as a S B
normal operation. TRIP
circuit breaker and mounted SET
A (OPEN)
adjacent to the load, the power (CLOSED)
COIL
N
source, or even the flight deck. COIL T1 T2

S1 S2
PERMANENT MAGNET
Figure 2
4"'3"/&-&$53*$"-108&3 15

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE CONTROLLED CIRCUIT BREAKER (RCCB) — DESIGN CONCEPT

The opening of contact B occurs especially when vehicles LOAD-L2 LOAD-L1


BI-METAL
in the last several thousandths sophistication requires use
of an inch travel of the armature of a significant number K
J
movement. After coil opening, of these devices. Also, it E-PIVOT
STATIONARY
the armature movement must be remembered that G-PIVOT N
CONTACTS MOVEABLE
continues (until it seats i.e. power utilized by relay coils H-LATCH CONTACT
seals), due in some degree to generate heat which must I
LATCH
L-LEVER BRIDGE

the inertia of the armature, but be dissipated. The necessary BAR M C


D
mostly due to the magneto- elimination of this heat, in
ARMATURE
motive force of the permanent turn, requires the use of
magnet in conjunction with the additional energy from the SET TRIP
decreasing air gap at the right main power source. (CLOSED) S (OPEN) B
A COIL COIL T2
pole face. 4. As indicated, the cutthroat S2 U1 BUCKING BUCKING V1
T1
N
contacts are opened by the U2
COIL COIL V1
The device now is again in a armature mechanically during
S1

stable position, but the armature the last several thousandths PERMANENT MAGNET
has transferred and the following of an inch travel of armature
conditions exist: Figure 3
movement. Note: In actual
RCCB, the cutthroat contacts
Contact A is closed and contact function is replaced by BI-METAL
LOAD-L2
LOAD-L1
B is open, and the armature electronic control of coil on
is sealed and latched at the time. J
E-PIVOT
right leg of the electro-magnet.
To transfer the armature to its G-PIVOT N
H-LATCH
STATIONARY
CONTACTS
K

original position, energizing the RCCB Operation As A Relay I C


coil S1-S 2 allows the process LATCH
L-LEVER
MOVEABLE
CONTACT
described above to occur in the To examine the RCCB operation
BAR M
BRIDGE
opposite direction. as a relay, refer to Figure 3 and ARMATURE
4. The device is shown in the D

There are a number of set position in Figure 3 and in SET TRIP


advantages to this design the tripped position in Figure 4. (CLOSED) S (OPEN) B
approach of the "motor." The circuit path is from L2, A COIL COIL
T1
T2
V1
through the bimetal to one of S2 U1 BUCKING
COIL
N
BUCKING
COIL
1. The coils open upon transfer the stationary contacts. L1 is S1 U2 V1

of the armature; hence, the connected directly to the other


actual "on time" or duty cycle stationary contact. PERMANENT MAGNET

approximately equals the Figure 4


operate time of the relay. The movable bridge closes the
Accordingly, the coil can circuit by bridging between the LOAD-L2
be driven hard without fear two stationary contacts. BI-METAL LINE-L1
of burnout. The "hot coil"
with the low timer constant As can be seen, movement of J E-PIVOT
results, in turn, in fast operate the armature about its fulcrum
times. will determine the position of G-PIVOT
N H-LATCH STATIONARY
CONTACTS
K

2. Using intermittent duty the contacts. When coil S1-S I


coils (smaller coils with less 2 has been energized such LATCH M L-LEVER MOVEABLE

copper) results in less weight that the armature seals on the BAR CONTACT
BRIDGE
and smaller sizes. left-hand pole face (Figure 3), D
the mechanical linkage system ARMATURE
3. Power is conserved. This is closes the contacts. Conversely,
important for two reasons. when coil T1-T 2 has been S
If a relay is to use power, it energized, such that the A
SET TRIP
(OPEN)
B
(CLOSED)
must be available. In some armature seals on the right- COIL N
COIL
of the present day and future hand pole face (Figure 4), the
vehicles, power remains an relay contacts will open due
S1 S2 T1 T2

expensive commodity, and to the spring forces exerted by PERMANENT MAGNET


elimination of coil power compression spring K. Figure 5
drawing (10-35 watts) in
power devices can add up Note: there is an "upward force" directed on the lever L through the linkage tying into the armature
at point D. During operation as a relay, point C (interface between lever L and latch bar I) is "fixed"
in place, and the lever L actually rotates about point C when moving the contact structure from the
opening to the closed, and from the closed to the open position.

16 4"'3"/&-&$53*$"-108&3

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE CONTROLLED CIRCUIT BREAKER (RCCB) — DESIGN CONCEPT

Note that the coil U1-U2 is bar I counter-clockwise around ØB


connected in parallel with T1-T2. its pivot point G. This allows the
It is wound on the left-hand main lever L to rotate clockwise
core of the electro-magnet such around point D (where it is
1Ø AC
that when energized along with engaged with the armature) due
T1-T2, the force it generates will to the "contact return" spring
be in a direction opposing the (compression spring) force
latching force generated in that K acting upon the moveable
core by the permanent magnet. contact bridge.
2.5 MILLISECONDS
The utilization of a permanent Note that when this overload
magnet and intermittent duty occurs, the armature is not
coils, in conjunction with transferred to the "off" (tripped)
cutthroat contacts, allows a position, but instead remains
considerable reduction in copper in the latched position normally
and iron from that normally associated with the "on" (set) 1.0 RECTIFIED AC
required in electro-magnets for position of the device.
continuous duty operation.
To "reset" the device after the 1.25 MILLISECONDS OFF TIME
RCCB Operation as a fault or overload clears could ØB ØC
Circuit Breaker be readily accomplished by
energizing the "trip" coil (T1-
To examine the operation of T2) through a toggle or push-
the device as a breaker, refer to button switch (see Figure 1)
2Ø AC
Figures 3, 4, and 5. located in the flight deck. The
armature would then transfer
In Figure 3, the device is shown and seal on the right-hand core
in the closed contact position of the electro-magnet, which
(presumably) carrying rated is the "open" position shown in
current. Should an overload Figure 4. At that time, springs
occur, currents greater than M and N (tension springs)
rated currents now "flow" would reposition latch bar I and
through the device "entering" latch H to the position shown
through L2, passing through the in Figure 4, providing that
bimetal, through the connection the bimetal has now cooled
of the bimetal to one stationary sufficiently and returned to
contact, through the bridging its original position as shown 2Ø RECTIFIED AC
moveable contact structure, to in Figure 4. At this stage,
the other stationary contact, and the RCCB is still in an "open APPROXIMATELY
"out" through L1. position" i.e. (the contacts are 0.4 MILLISECONDS OFF TIME
open), but as outlined above, Figure 6
Depending upon the size of the the fault or overload has been
overload, the bimetal will begin to cleared through action and
deflect as shown in Figure 5 until operation of the device through
the actuating end of the bimetal bimetallic activity, i.e. "Circuit
engages latch H at point J. Breaker" operation.

Motion and force due to the To re-close the contacts, it is


deflection of the bimetal moves now only necessary to energize
latch H such that it rotates in coils S1-S2 and re-establish a
a counter-clockwise direction mechanism position similar to
around its pivot point E. that shown in Figure 3. If the
fault of overload condition is still
When latch H has moved an in existence, the device would
adequate distance, the upward again trip through bimetallic
force of lever L, applied at point activity as just described.
C to latch bar I, will rotate latch

4"'3"/&-&$53*$"-108&3 17

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE CONTROLLED CIRCUIT BREAKER (RCCB) — DESIGN CONCEPT

Three Pole RCCB phases. The "off" time between the single pole devices. logic circuit. Should AC power
current pulses during coil be lost, the DC connection
The design principles employed energization is approximately The difference is the addition would automatically take over
in the 3-pole RCCB have 0.4 milliseconds. In comparison, of a power junction area in the the control function.
followed many of the same the "off" time for single-phase electronics. (see Figure 7).
paths utilized in the 1-pole power is approximately 1.25 The 3-pole RCCB is designed for The other differences between
RCCB. Differences other milliseconds. See Figure 6. use in 3-phase circuits and is a 1-phase and 3-phase control
than the obvious, such as 400 Hz AC load controller. The circuitry, i.e. timer addition, is
size, weight, shape, etc., are The timing circuit establishes power junction is designed to directly related as described
explained below. a coil "on" time longer than use AC power only. DC operate in the above Motor Operation
the actual transfer time of the (coil) power may be used even section.
armature. The operation of the though AC loads are to be
Motor Operation
3-pole RCCB is identical to the controlled. This connection is
1-pole. made at terminal 4 of the IWTS
The principles of motor
connector. In Figure 7, two
operation and construction
Control Circuit separate power junctions are
of the three pole devices are
shown: one for AC and one for
similar to those employed in the
Refer to Figure 7. There is one DC. In the event both AC and
single pole RCCB. In the 3-pole
minor difference in operating DC are connected to the RCCB,
device, the AC operating power
principles and parameters from only AC would be utilized by the
is drawn from two of the three

ØB
LINE POWER EMERGENCY
115 V 400 Hz (BACK-UP)
ØC POWER
* 28Vdc
POWER
DC
JUNCTION TRIP COIL
Set Coil

LOGIC
POWER
SUPPLY

SET TRIP
SWITCH LOGIC SWITCH
(FET) (FET)

TIMER
1/CU
(1/2 AMP C.B.)

Figure 7

*Indicates In 3 Phase Electronics

18 4"'3"/&-&$53*$"-108&3

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE POWER CONTROLLERS — WITH ELECTRONIC CURRENT SENSING

PERFORMANCE DATA
Rupture Levels 2500 A (28VDC)
Endurance (Resistive) 50,000 Cycles
Endurance (Inductive and Motor) 25,000 cycles
Endurance (Lamp) No Rating
Mechanical Life 100,000 cycles
Single Pole
• 28 VDC Dielectric Strength Sea Level - VRMS .2-3 seconds: Coil to Case - 1250 initial. 1,000
After Life, All other Points 1,800 Initial, 1350 After Life
Electronic Current Sensing 50,000 ft - VRMS 1 Minute: Coil to Case 500 Initial & After Life.
All other Points 700 Initial & After Life
The electronic over current
sensing of these devices offer Insulation Resistance 1100 Megaohms initial, 50 Megohms after Life, MIL-STD-202,
several advantages over the method 302, test condition B
bi-metal sensing RCCB. Trip
Thermal Temperature Range -55°C to 85°C (-67°F to 185°F).
current levels can be closely
controlled, for better protection Vibration Sinusoidal 5 to 10 Hz: 0.08 DA; 10 TO 55 Hz: 0.06 DA; 55 to 2000
of sensitive loads, trip times are Hz: 10G's
faster, and both can be custom-
ized for specific applications. Shock 50G's. (1/2 sine, 10-12 ms)
Other advantages included less Altitude 50,000 ft. Maximum
heat buildup, and higher current EMI Requirements MIL-STD-461, Requirements CS114 and RE102 over the frequency
capabilities in the same small
package. range of 14 kHz to 400 MHz and RE102 limits for Aircraft and
Space Systems
Moisture Resistance MIL-STD-202, method 106
Use as a Relay, Circuit
Breaker, Or Both Salt Spray Resistance MIL-STD-202, method 101, Condition B
Sand and Dust Resistance MIL-STD-202, method 110, Condition A
RPCs, like RCCBs, combine the
best attributes of a circuit break- Fungus Resistance MIL-HDBK-454, Guideline 4
er and a relay. Automatically Explosion Proof MIL-STD-202, method 109
protects the wires and the load Weight (Standard) 425.017 grams (0.937 lbs.)
device during circuit/load break-
down, but allows the flight deck
control of the load during nor-
mal operation.
OVERLOAD DATA
Weight and Cost Savings % Rated Trip in Seconds
Current -55°C to +85°C
In distributed-load applications,
RPCs are a more efficient power 100% No Trip
distribution solution promoting 125% 45 Sec. Trip
cost and weight savings through 200% 0.22 Sec. Trip
the elimination of long runs of 400% 0.095 Sec. Trip
heavy cables associated with
the conventional relay - flight
deck circuit protector method.
Control of the RPC requires only ORDERING INFORMATION
one #22 AWG control wire from Single Pole Single Throw (Double Break Contacts)
the ICU (model #1500-053-05)
on the flight deck to the RPC.
Rated Contact Load (Amperes)
AMPERE 28 VDC
3AFRAN%LECTRICAL
RATING 0OWER P/N Res. Ind. Motor Min.
125 SM600BA125A1 125 125 125 5
150 SM600BA150A1 150 150 150 5
175 SM600BA175A1 175 150 175 5
200 SM600BA200A1 200 150 175 5
Notes:
• One auxiliary contact included on each unit
• Contact Business Unit on Alternate Amperages, Trip Times, Control Configurations, Grounding, Auxiliary Switches, Mounting Systems, etc.

4"'3"/&-&$53*$"-108&3 19

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”
REMOTE POWER CONTROLLER (RPC)

Engineering Data
Approximate Dimensions - 1 Pole
Typical Integrated
Placement Wire Module
of Rating .172/4.37 DIA.
on Top 2 MTG. HOLES
Plane
LOAD A2

.688/
LINE A1

17.48
.256/6.50 125

.150 2.940
3.81 74.68 Position Indicator
Red: Closed
3.250 Green: Open
82.55 1.200
2.250
30.48
Barrier Black 57.15 .350
Nylon Per 8.89 .42
1.530 .07 .056
MIL-M- 10.67
38.86 1.778 1.42
20693A Type
I. General
Purpose .05/1.27

Terminal .180
Pad .6 DIA. 4.57
4.26
Name 108.20
Plate 3.42
86.87
R.06
1.52

Typical Wiring Diagram


Approximate Dimensions Auxiliary
Contacts
S2
S1
S3
A2 A1
5A 5B
Over Current Detector

LOAD A2 A1 LINE
Module: Integrated wire termination. Terminals
3 A2 A2 A2 3 will accept PIN contact per M39029/1 - 101. Use
insertion/extraction tool M81969/14 - 02.
To Indicator / 5A 4 3
Control Unit Circuit
Breaker Type 28 VDC
MS22073 - 1/2 Or Back Up
MS26574 - 1/2 Power 4 5B S3 S2 S1

COIL OPERATE CURRENT/SET AND TRIP TIME

Nominal I/C Set Set Coil MAX. Set Time *I/CU. Trip Current Nominal
System Current @ Current Nominal Most Adverse 71°C and -54°C and Room Temp Max.
Voltage Nom. Voltage @Nom Voltage @ Condition-Min. Nominal Nominal and Nominal Standby
Room Temp Voltage 71°C Voltage Voltage Voltage Current
(milliamp) Voltage
Ambient (milliamp)
Pulse

28 VDC 2 3.7 Amp 20 Millisec 35 Millisec 1.76 Amp 1.25 Amp 1.89 Amp 30
(18 volts
Min)
* MAX I/CU. LINE IMPEDANCE 7.5 Ohms CURRENT DECREASES W/TIME SO THAT I2t >= 2

20 4"'3"/&-&$53*$"-108&3

“Safran Electrical & Power Proprietary Information. Information contained in this document is Safran Electrical & Power Proprietary Information and is disclosed in confidence. It is the property
of Safran Electrical & Power and shall not be used, disclosed to others, or reproduced without the express written agreement of Safran Electrical & Power. If consent is given for reproduction in
whole or in part, this notice set forth on each page of this document shall appear in any such reproduction in whole or in part. Unauthorized export or re-export is prohibited.”

You might also like