Professional Documents
Culture Documents
Department of Education
Region IV-A CALABARZON
Division of Rizal
I. LEARNING OBJECTIVES
Content Standard
The learners demonstrate an understanding of the Service Entrance Installation
Objectives
At the end of this lesson, the learners will be able to:
• Familiarize themselves with the parts of a service entrance installation
• Install a typical service entrance installation
• Observe safety precautions while performing the activity.
It also refers to the conductor and equipment for delivering energy from the
electricity supply system to the wiring system of the premises served.
1. Service drop – Lines from local power company supplying electricity to the
consumers. The overhead service conductors between the last pole or
other aerial support and the first point of attachment to the building.
2. Secondary rack or wire holder insulator – where the service drop and
service entrance wires are inter-connected.
3. Service entrance conductors – service conductor between the terminals
of the service equipment and a point usually outside the building, clear or
building, clear or building walls, where joined by tap or splice to service
drop. Encloses the service wires, as required by the power company in the
municipality. The consumer’s main lines, the size of which is based on the
connected loads.
4. Service meter or kilowatt-hour meter – indicates the total amount of
electric power consumed during the given time. It is furnished and installed
by the power company and is sealed against tampering by consumer.
5. Service head or entrance cap – consists of three parts; the body which
as attached to the conduit; an insulating block, to keep the wires apart
where they emerge; the cover, that keeps the rain out and holds the parts
together. Entrance cap protects the wires and prevents water from entering
the service entrance conduit.
6. Service Equipment – the necessary equipment, usually consisting of a
circuit breaker or switch and fuses, and their accessories, located near
point of entrance of supply conductors to a building and intended to
constitute the main control and means of cut off for the supply to that
building.
7. Distribution panel – where the electric power is distributed to the branch
circuits. It is also consisting of the circuits disconnecting mean and over
current protection.
8. Disconnecting means – is a device or group of devices whereby the
conductors of a circuit can be disconnected from the electrical power
source.
9. Branch circuit – are conductors originating from the distribution panel to
the electric load. They supply power to the connected load (lightning,
convenience outlet etc.)
1. Only cooper conductor shall be used for the service entrance wire.
2. The line sides portion of the service entrance (from the entrance cap to the
meter socket) should never be concealed or embedded except if the size of
the service entrance wires or conductors is NO. 1/0AWG or bigger.
3. Insulators for supporting the service drop wires where they reach the
building must be provided. They must be kept a minimum distance of 6 inches
apart.
4. Point of connection of the service entrance wires to the service drop wires
should be lower than the service head. A difference of a foot or so is difficult.
5. At the top of the service conduit, the code requires a fitting that will prevent
rain from entering the conduit.
6. An entrance tells is used at the bottom of the conduit, where it enters the
building.
7. Location of the meter is usually about 5 to 6 ft. above ground level. (some
power suppliers have specified heights for meters, so check before deciding
where to locate it.)
8. Service entrance conduit shall be properly strapped to the wall of the
building.
9. The drip loop (wire protruding at the entrance cap for to the service wire)
shall be shorter than two (2) feet.
10. The line side portion shall always be of rigid metallic electrical conduit.
Plastic (PVC) conduit and BX cable are not allowed.
11. Joints and splices inside conduits are not allowed.
12. Service entrance shall be installed (0.91 M (3 ft.) away from open window
and close to the point of service drop attachment to the building.
13. Meter Socket shall be installed facing the street in the clean place, free
from the vibration on the outside wall of a building or on the private pole within
1.6 meters to 2.15 meters from the ground.
14. In the case of single-phase, three-wires 115/230 volts service, the
identified neutral conductor of the service entrance shall always be grounded
to an existing water system or its equivalent driven ground rods.
15. Line side and load side wire or conductor shall not be contained together
in the conduit junction box, accessory box, and wire gutter or wire trough.
Service Entrance Installation
(The teacher will be presenting a video of an actual installation of a service
entrance)
C. ANALYSIS
1. Give one part of a service entrance and describe its function/use
2. Would you rather use an overhead service entrance or an underground service
entrance?
D. ABSTRACTION
(The teacher will ask the students about what they learned on the discussion)
IV. ASSESSMENT
Directions: Analyze the picture provided and label all the parts correctly.
REMINDER: all answers must be in CAPITAL LETTERS
1. SERVICE DROP
2. DRIP LOOP
3. SERVICE HEAD / ENTRANCE CAP / WEATHERHEAD / WEATHER CAP
4. SERVICE ENTRANCE CONDUCTOR
5. SERVICE METER / KILOWATT HOUR METER
IV. ASSIGNMENT
Direction:
Draw an Overhead service entrance and label each part.
Use the picture provided as a reference.
Prepared by:
Checked by:
SENNEN ALEJANDRO
Cooperating Teacher