A B C D E F G H I J

All content, drawings, templates shall be used for reference and shall not be
circulated without prior approval from Owner. All content herewith is considered
as property of Owner. Please obtain rightful approval from Owner prior to
usage of materials for presentation usage to third parties.

1
< Site Image > 1

2 2
2 x 4mm sq/1c UV STABILIZED

2 x 4mm sq/1c UV STABILIZED


1 x 4mm sq/1c (from strings to earthing system) Using grounding clip between pv panels 1 x 6mm sq/1c (from strings to earthing system) Using grounding clip between pv panels

X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26
R < 4 Ohm

R < 4 Ohm
S1(1/1) S2(2/1) S3(3/1) S4(4/1) S5(5/1) S6(6/1) S7(7/1) S8(8/1) S1(1/1) S2(2/1) S3(3/1) S4(4/1) S5(5/1) S6(6/1) S7(7/1) S8(8/1)
DC CABLE

DC CABLE
AS - BUILT DRAWING D

DC
SPD
4 x 95 sq.mm/1C XLPE/PVC
+ 50 sq.mm PVC
DC
SPD
ISSUE FOR EPC CONTRACT C
MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6 MPPT 7 MPPT 8 MPPT 9 MPPT 10 MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6 MPPT 7 MPPT 8 MPPT 9 MPPT 10
2 x 2.5 sq.mm/ XLPE/CV
DC SWITCH + 2.5 sq.mm CV WATER PUMP UPS DC SWITCH
HUAWEI 100KTL
INVERTER 10 AC
HUAWEI 100KTL
INVERTER 14 AC
ISSUE FOR CONSTRUCTION B
Com. Port Com. Port
SPD SPD
E E
ISSUE FOR TENDER A
3P+N 45KA 385V
3 type 1 3
2 x 4mm sq/1c UV STABILIZED

SURGE ARRESTER
DATE REMARKS REV

2 x 4mm sq/1c UV STABILIZED


1 x 6mm sq/1c (from strings to earthing system) Using grounding clip between pv panels 1 x 6mm sq/1c (from strings to earthing system) Using grounding clip between pv panels
MCCB - 4P MCCB - 4P MCCB - 4P MCCB - 4P MCCB - 4P MCCB - 4P MCCB - 4P MCCB - 4P MCB - 2P RCBO - 2P
X26 X MCCB - 100A - 4P X 200A - 25kA X 200A - 25kA X 200A - 25kA X 200A - 25kA X 200A - 25kA X 200A - 25kA X 200A - 25kA X 200A - 25kA X 25A - 25kA X 25A - 25kA
X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26
R < 4 Ohm

R < 4 Ohm
S1(1/1) S2(2/1) S3(3/1) S4(4/1) S5(5/1) S6(6/1) S7(7/1) S8(8/1) S1(1/1) S2(2/1) S3(3/1) S4(4/1) S5(5/1) S6(6/1) S7(7/1) S8(8/1)
1 2 3 4 5 6 7 8 9 10
COPPER BUSBAR 2000A
6A MCB
DC CABLE

L1 L2 L3

DC CABLE
X PV SUPPLY INDICATING LIGHT

MCT 3x2000/5A AMI REVENUE METER


AMI
CL 0.5
6A MCB
X

SHT OC GF PCT 3x2000/5A


DC DC
SPD SPD
MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6 MPPT 7 MPPT 8 MPPT 9 MPPT 10 Trip relay
ACB - 4P MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6 MPPT 7 MPPT 8 MPPT 9 MPPT 10
X
DC SWITCH 2000A - 65kA DC SWITCH
HUAWEI 100KTL HUAWEI 100KTL
INVERTER 11 Com. Port AC INVERTER 15 AC
SPD Com. Port
AC DISTRIBUTION BOARD 1 SPD
E (TO BE LOCATED ON GROUND NEAR INVERTERS) E
Modbus RTU
E
4 4
2 x 4mm sq/1c UV STABILIZED

2 x 4mm sq/1c UV STABILIZED


1 x 4mm sq/1c (from strings to earthing system) Using grounding clip between pv panels R < 4 Ohm 1 x 6mm sq/1c (from strings to earthing system) Using grounding clip between pv panels

X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X26 X24 X24 X24 X24 X24
R < 4 Ohm

R < 4 Ohm
S1(1/1) S2(2/1) S3(3/1) S4(4/1) S5(5/1) S6(6/1) S7(7/1) S8(8/1) 3x(4x240) + 1x(2x240) sq.mm Cu/XLPE/PVC S1(1/1) S2(2/1) S3(3/1) S4(4/1) S5(5/1) S6(6/1) S7(7/1) S8(8/1) S9(9/1)
+ 120 sq.mm PVC
DC CABLE

DC CABLE
DC
Tủ MSB - 2
DC
SPD SPD
MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6 MPPT 7 MPPT 8 MPPT 9 MPPT 10 MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6 MPPT 7 MPPT 8 MPPT 9 MPPT 10
COPPER BUSBAR 2000A
DC SWITCH DC SWITCH
HUAWEI 100KTL MCT 3x3200/5A HUAWEI 100KTL
INVERTER 12 Com. Port AC INVERTER 16 AC
MCCB 3P-36KA MCCB 3P-36KA CL 0.5 Com. Port

E
SPD
125AF/125AT 125AF/125AT AMI
E
SPD
Approved by
6A MCB
X
1 2 8 9
ACB
5 3P-65kA 5
2 x 4mm sq/1c UV STABILIZED

2 x 4mm sq/1c UV STABILIZED


CONTACTOR CONTACTOR CONTACTOR CONTACTOR
1 x 4mm sq/1c (from strings to earthing system) Using grounding clip between pv panels 3P - 125A 3P - 125A 3P - 125A 3P - 125A MCB 2P-16A 2000AF/2000AT 1 x 6mm sq/1c (from strings to earthing system) Using grounding clip between pv panels
APFC

X26 X26 X26 X26 X26 X26 X26 X26 X24 X24 X24 X24 X24 X24 X24 X24 X24
R < 4 Ohm

R < 4 Ohm
S1(1/1) S2(2/1) S3(3/1) S4(4/1) S5(5/1) S6(6/1) S7(7/1) S8(8/1) S1(1/1) S2(2/1) S3(3/1) S4(4/1) S5(5/1) S6(6/1) S7(7/1) S8(8/1) S9(9/1)
DC CABLE

DC CABLE
50KVAR 50KVAR ... 50KVAR 50KVAR

TỤ BÙ HỆ SỐ CÔNG SUẤT (9 BƯỚC) 550KVAR

CT 3x2000/5A I> kW kWh PF A

MCB 3P-16A AS 0-2000A

VS
A

0-500A
Client: Approved by:
U> U<
DC 3x2A DC
SPD R Y B SPD
MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6 MPPT 7 MPPT 8 MPPT 9 MPPT 10 MPPT 1 MPPT 2 MPPT 3 MPPT 4 MPPT 5 MPPT 6 MPPT 7 MPPT 8 MPPT 9 MPPT 10

DC SWITCH MCT 3x2000/5A DC SWITCH


HUAWEI 100KTL HUAWEI 100KTL
INVERTER 13 Com. Port AC INVERTER 17 AC
SPD Com. Port
6A MCB SPD
E X E

6 Al/XPLE/PVC 3x(6x1C-300mm2) + N(3x1C-300mm2) 6


Weather station

Smart Logger 2x1.0 sq.mm/CV


3000
SMART METER
EPC Contractor: Approved by:
2x2.5 sq.mm/CV ROUTER - MODEM
E + 1x2.5 sq.mm/CV
SMART LOGGER 3000
4G Router
SOCKET

E UPS 3000 VA
220VAC/ 50 Hz
SOCKET
CÔNG TY TNHH TERU DENSO
22/0.4KV - 50HZ
1250 KVA
MÁY BIẾN ÁP- TBA
UPS 3000VA RACK 12U CABINET DETAILS
VIET NAM
2x2.5 sq.mm/CV
+ 1x2.5 sq.mm/CV
Power from AC solar cabinet
7 7
Project:

TOYODA GOSEI
Drawing Title:

Designed by:

Checked by:

Approved by:
8 8
1 of 1 Date: Scale: NTS

Revision: A Sheet
Drawing No: Size

A3

A B C D E F G H I J
DANH MỤC BẢN VẼ