Professional Documents
Culture Documents
Per Unit Calculations
Per Unit Calculations
The voltage, current, power and impedance in a power system are often expressed in per-unit or
percent of a specified base values.
Per-unit quantity is the ratio of actual quantity and base value of quantity. It is represented by pu.
Actual quantity
Per − unit quantity = (3.3.1)
Base value of quantity
For single-phase systems, or three-phase systems where the term current referes to line current, where
the term voltage referes to voltage to neutral, and where the term kilovoltamperes reerers to
kilovoltampere per phase, the following formulas reltae the various quantities:
Z =
V(
base LN
) (
2
=
base voltage, kV
LN
2) =
(
× 1000 base voltage, kV
LN
2 )
(3.2.4.2)
base S base , kVA base , MVA
base1φ 1φ 1φ
1
Base admitance, Y =G =B = (3.2.4.3)
base base base Z
base
DMAM
Base impedance, Z =R =X =
V
base LN =
V
base
(
LN
2 ) (3.2.4.1)
base base base I S
base base1φ
Z =
(
V
base LL
2) (
=
base voltage, kV / 3 × 1000
LL
2
)
base (3.2.4.2)
S ⎛ base , kVA / 3 ⎞
base3φ ⎜ 3φ ⎟⎠
⎝
Z =
(
base voltage, kV
LL
) =
(
2 × 1000 base voltage, kV
LL
2 )
(3.2.4.2)
base base , kVA base , MVA
3φ 3φ
1
Base admitance, Y =G =B = (3.2.4.3)
base base base Z
base
V (V ) V (V ) 3 ×V (V )
V = actual = actual = actual
pu V (V ) base voltage, kV ×1000 base voltage, kV ×1000
base LN LL
I ( A)
I = actual
pu I ( A)
base
Z Z ×S Z × base , kVA Z × base , MVA
actual actual base1φ actual 1φ actual 1φ
Z = = = =
pu Z
base (
V
baseLN
2) (
base voltage, kV
LN
2 × 1000) (
base voltage, kV
LN
2 )
Z Z ×S Z × base , kVA Z × base , MVA
actual actual base3φ actual 3φ actual 3φ
Z = = = =
pu Z
base V (
baseLL
2 ) (
base voltage, kV
LL
2 × 1000 )
base voltage, kV
LL
(
2 )
DMAM
Example of Generator in Per-Unit System
Example: A generator rated 1000 VA and 200 V has
internal impedance j10 Ω as shown in figure.
Considering the ratings of the generator are base
values, calculate the base current, base impedance and
per-unit of internal impedance of generator.
Solutions: Sbase=1000 VA, Vbase=200 V
Egpu = Eg/Vbase=200/200 = 1 pu
Spu = S/Sbase=1000/1000 = 1 pu
Base current, Ibase= Sbase / Vbase =1000/200=5A
Base impedance, Zbase= ( Vbase)2 / Sbase
Zbase =2002/1000= 40 Ω
Per-unit of internal impedance, Zpu= Zactual/ Zbase=j10/40=j0.25 pu
(a) Transformer impedance referred to the (b) Transformer impedance referred to the
low voltage side high voltage side
DMAM
The rated values for power and voltage are used as the bases for the calculations. It means that the
voltage base is different on each side of the transformer. Comparison of the base and the per unit value
on both sides of the tarnsformer in the following Table.
Example 6.4 [1, p.147] A single phase transformer is rated 110/440 V, 2.5 kVA. Leakage reactance
measured from the low-tension side is 0.06 Ω. Determine leakage reactance in per-unit.
Solution:
Base voltage in low-tension side, Vbase(LT) = 0.11 kV
Base kVA, Sbase = 2.5 kVA
V2
base(LT) (0.11) 2 × 1000
Base impedance in low-tension side, Z base(LT) = = = 4.84 Ω
S 2.5
base
X
actual(LT) 0.06
Leakage reactance in per-unit, X pu(LT) = = = 0.0124 pu
Z 4.84
base(LT)
If leakage reactance had been measred on the high voltage side, the actual alue would be
2
X = a2 X = ⎛⎜ 440 ⎞⎟ × 0.06 = 0.96 Ω
actual(HT) actual(LT) ⎝ 110 ⎠
V2
base(LT) (0.44) 2 × 1000
Base impedance in low-tension side, Z base(LT) = = = 77.5 Ω
S 2.5
base
X
actual(HT) 0.96
X = = = 0.0124
pu(HT) Z 77.5
base(HT)
DMAM
Example 6.5 [1, p.147] Three parts of a single-phase electrical system are designated A, B, and C and
are connected to each other through transformer, as shown in Fig. 6.19.
DMAM
Z
actual, A 12
Per-unit impedanc of load referred to circuit A: Z pu, A = = = 0.63 Ω
Z 19
base, A
From above calculation, it is clear that the per-
unit impedance of the load referred to any part of
the system is same since the selection of base in
various parts of the system is determined by the
tns ratio of the transformer.
Fig. 6.20 is the required impedance diagam with
impedances marked in per-unit.
DMAM
2 2
⎛ 38.1 ⎞ ⎛ 66 ⎞
Z = 0.6⎜ ⎟ = 0.6⎜ ⎟ = 60 Ω
HT ⎝ 3.81 ⎠ ⎝ 6.6 ⎠
2
⎛ 66 ⎞
For Fig. 6.22(a) Z = 0.6⎜ ⎟ = 180 Ω
HT ⎝ 3.81 ⎠
2
⎛ 38.1 ⎞
For Fig. 6.22(b) Z = 0.6⎜ ⎟ = 180 Ω
HT ⎝ 2.2 ⎠
Example 6.6 [1, p.151] The transformers rated 25 MVA, 38.1/3.81 kV are connected Y-∆ as shown in
Fig. 6.22(a) with the balanced load of three 0.6 Ω, Y-connceted resistors. Choose a base of 75 MVA,
66 kV for high tension side of the transformer and specify the base for the low tension side. Determine
the per-unit resistance of the load on the base for the low-tension side. Then determine the load
resistance RL referred to high-tention side and the per-unit value of this resistance on the chosen base.
Solution: therating of the transformer as a three-phase bank is 75 MVA, 66Y/3.81∆ kV. So base for
the low-tension side is 75 MVA, 3.81 kV.
2
⎡base KV ⎤
Base impedance on the low-tension side, Z
⎢
=⎣
LL( LT ) ⎥⎦
=
(3.81)2 = 0.1935 Ω
base (LT) base MVA 75
R
L, actual (LT) 0.6
Load resistance in per-unit, R = = = 3.1 pu
L, pu(LT) R 0.1935
base (LT)
DMAM
2
⎡base KV ⎤
Base impedance on the high-tension side, Z =⎣
⎢ LL( HT ) ⎥⎦
=
(66)2 = 58.1 Ω
base (HT) base MVA 75
Actual load resistance in high-tension-side,
2
⎛V ⎞ 2
⎜ HT(LL) ⎟ ⎛ 66 ⎞
R =R = 0.6⎜ ⎟ = 180 Ω
L, actual (LT) L, actual (LT) ⎜⎜ V ⎟
⎟ ⎝ 3.81 ⎠
⎝ LT(LL) ⎠
R
L, actual (HT) 180
Load resistance in per-unit, R = = = 3.1 pu
L, pu(HT) R 58.1
base (HT)
Z Z Z
actual pu, old base, old
Z = = (3.3.10)
pu, new Z Z
base, new base, new
2
⎛V ⎞ ⎛S ⎞
⎜ base, old ⎟ ⎜ base, new ⎟
Z = Z pu,old ⎜
pu, new ⎜ Vbase, new ⎟⎟ ⎜⎜ S ⎟⎟
⎝ ⎠ ⎝ base, old ⎠
⎛S ⎞
⎜ base, new ⎟
If Vbase,old = Vbase,new then Z = Z pu,old ⎜ (3.3.11)
pu, new ⎜ S base, old ⎟⎟
⎝ ⎠
⎛V ⎞
⎜ base, old ⎟
If S base,old = S base,new then Z = Z pu,old ⎜
pu, new ⎜ Vbase, new ⎟⎟
⎝ ⎠
2
⎛ base voltage, kV ⎞ ⎛ base voltage, kVA ⎞
Z = Z pu,old ⎜ old ⎟ ⎜ new ⎟
pu, new ⎜ base voltage, kV ⎟ ⎜ base voltage, kVA ⎟
⎝ new ⎠ ⎝ old ⎠
2 (2.52)
⎛ base voltage, kV ⎞ ⎛ base voltage, MVA ⎞
Z = Z pu,old ⎜ old ⎟ ⎜ new ⎟
pu, new ⎜ base voltage, kV ⎟ ⎜ base voltage, MVA ⎟
⎝ new ⎠ ⎝ old ⎠
Example 2.5: The reactance of a generator is given as 0.25 pu based on the generator nameplate rating
of 18 kV, 500 MVA. Calculate the new pu of the reactance if the new base are as 20 kV, 100 MVA.
2
⎛ 18 ⎞ ⎛ 100 ⎞
X = 0.25⎜ ⎟ ⎜ ⎟ = 0.0405
pu, new ⎝ 20 ⎠ ⎝ 500 ⎠
Solution:
Vbase,1 = 13.8 kV − − − − − − − − Region 1
110
Vbase, 2 = Vbase,1 = 110 kV − − − − − − − − Region 2
13.8
14.4
Vbase,3 = Vbase, 2 = 13.2 kV − − − − − − − − Region 3
120
DMAM
2
VLL ,base (13.8kV ) 2
Z base,1 = = = 1.904 Ω − − − − − − − − Region 1
S 3φ ,base 100MVA
2
VLL ,base (110kV ) 2
Z base, 2 = = = 121Ω − − − − − − − − Region 2
S 3φ ,base 100MVA
2
VLL ,base (13.2kV ) 2
Z base,3 = = = 1.74 3Ω − − − − − − − − Region 3
S 3φ ,base 100MVA
Base impedance calculation in region 1 is not required, since the rated value of region 1 is considered
as base value and resistance and reactance values are given in pu.
For G1: R = 0.1 pu, Xs = 0.9 pu
For T1: R = 0.01 pu, Xs = 0.05 pu
15 75
For L1: RL1 = = 0.124 pu ; X L1 = = 0.62 pu
121 121
Base impedance calculation in region 3 is not required, since the given data in this region is given in
pu. Thus, the values of pu are needed to update.
⎛V ⎞⎛ S ⎞
⎜ base, old ⎟⎜ base, new ⎟
For T2: Z = Z pu,old ⎜
pu, new ⎜ Vbase, new ⎟⎟⎜⎜ S base, old ⎟⎟
⎝ ⎠⎝ ⎠
⎛ 14.4 ⎞⎛ 100 ⎞ ⎛ 14.4 ⎞⎛ 100 ⎞
R = 0.01⎜ ⎟⎜ ⎟ = 0.238 pu ; X = 0.05⎜ ⎟⎜ ⎟ = 0.119 pu
pu, new ⎝ 13.2 ⎠⎝ 50 ⎠ pu, new ⎝ 13.2 ⎠⎝ 50 ⎠
⎛ 13.8 ⎞⎛ 100 ⎞ ⎛ 13.8 ⎞⎛ 100 ⎞
For M2: R = 0.01⎜ ⎟⎜ ⎟ = 0.219 pu ; X = 1.1⎜ ⎟⎜ ⎟ = 2.405 pu
pu, new ⎝ 13.2 ⎠⎝ 50 ⎠ pu, new ⎝ 13.2 ⎠⎝ 50 ⎠
DMAM
Example 6.10 [1, p.159] A 300 MVA, 20 kV three-phase generator has a subtransient reactance of
20%. The generator supplies a number of synchronous motors over a 64 km (4- mi) transmission line
having transformers at both ends, as shown on the one-line diagram of Fig. 6.29. The motors, all rated
13.2 kV, are represented by just two equivalent motors. The neutral of one motor M1 is grounded
through reactance. The neural of the second motor M2 is not connected to the ground (an unusual
condition). Rated inputs to the motors are 200 MVA and 100 MVA for M1 and M2, respectively. For
both motors X” =20%. The three-phase transformer T1 is rated 350 MVA, 230/20kV with the leakage
reactance of 10%. Transformer T2 is composed of three single-phase transformer each rated 127/13.2
kV, 100 MVA with leakage reactance of 10%. Series reactance of the transmission line is 0.5 Ω/km.
Draw the reactance diagram with all reactance marked in per-unit. Select the generator rating as base
in the generator circuit.
Solution:
Base MVA, Sbase, 3φ = 300 MVA
Base kV, VbaseLL = 20 kV
Generator:
Given, A 300 MVA, 20 kV three-phase generator has a subtransient reactance of 20%
Base MVA, Sbase, 3φ = 300 MVA
Base kV, VbaseLL = 20 kV
Transformer T1:
Given, transformer T1 is rated 350 MVA, 230/20kV with the leakage reactance of 10%
Base MVA, Sbase, 3φ = 300 MVA
Base kV, VbaseLL = 20 kV
2
⎛ base voltage, kV ⎞ ⎛ base voltage, MVA ⎞
X =X ⎜ old ⎟ ⎜ new ⎟
pu, new pu,old ⎜ base voltage, kV ⎟ ⎜ base voltage, MVA ⎟
⎝ new ⎠ ⎝ old ⎠
2
⎛ 230 ⎞ ⎛ 300 ⎞
X = 0.1⎜ ⎟ ⎜ ⎟ = 0.0857 pu
⎝ 230 ⎠ ⎝ 350 ⎠
Transmission Line:
Given, series reactance of the transmission line is 0.5 Ω/km.
Transformer T2:
Given, transformer T2 is composed of three single-phase transformer each rated 127/13.2 kV, 100
MVA with leakage reactance of 10%
The three-phase rating is 3×100 = 300 MVA
2
⎛ 13.2 ⎞ ⎛ 300 ⎞
X = 0.1⎜ ⎟ ⎜ ⎟ = 0.0915 pu
⎝ 13.8 ⎠ ⎝ 300 ⎠
Motor M1:
Given, the neutral of one motor M1 is grounded through reactance.
Rated inputs to the motors (M1 and M2) are 200 MVA and 100 MVAwith X” =20%.
Motor M2:
Given, the neutral of one motor M2 is not grounded.
Rated inputs to the motors (M1 and M2) are 200 MVA and 100 MVA with X” =20%.
Fig. 6.30 Reactance diagram for Example 6.10. Reactances are in per unit n the specified base.
DMAM
Example 6.11 [1, p.160] If the motors M1 and M2 of Example 6.10 have inputs of 120 and 60 MW
respectively at 13.2 kV, and both opeate at unity power facto, find the voltage at the terminal of the
generator.
Solution:
Together the motors take 180 MW. Or (180/300) = 0.6 pu
Therefore with V and I at the motors in pu |V||I| = 0.6 pu
13.2
And since V= = 0.9565∠0° pu
13.8
0.6
I= = 0.6273∠0°
0.9565
At the generator
V = 0.9565 + 0.6273( j 0.0915 + j 0.1815 + j 0.0857) = 0.9565 + j 0.2250 = 0.9826∠13.2° pu
The generator terminal voltage is
V = 0.9826 × 2019.65 kV
t
Example 3: Prepare a per phase schematic of the system shown in the figure and show all impedances
in per unit on a 100 MVA, 132 kV base in the transmission line circuit
G1 : 100 MVA, 11 kV, X= 0.15 p.u
G2 : 200 MVA, 13.8 kV, X= 0.2 p.u
T1 : 120 MVA, 11/132 kV, X= 0.1 p.u
T2: 250 MVA, 13.8/161 kV, X= 0.1 p.u
Load: 250 MVA, 0.8 Lagging, operating at 132 kV
Determine the per unit impedance of the load for the following cases: (i) load modeled as a series
combination of resistance and reactance, and (ii) load modeled as a parallel combination of resistance
and reactance.
Solution:
Transmission Line: Base kV in the transmission line =132 kV
Base impedance in the transmission line is = (132)2 / 100 = 174.24 Ω
Actual quantity
Per − unit quantity =
Base value of quantity
Ztransmission-line = (50+j100) / 174.24 = 0.287 + j1.1478
Ztransmission-line = (25+j100) / 174.24 = 0.1435 + j0.5739
DMAM
Transformer T1:
X = 0.1 × (11/11)2 × (100/120) = 0.0833 p.u
Load: The base impedance in the load circuit is same as the base impedance in the base impedance in
the transmission line.
Load is specified as: 250 MVA, 0.8 p.f lagging, 132 kV
cosθ = 0.8; θ = cos-1 (0.8) = 36.87o ; sinθ = 0.6
So the load is S = VI( cosθ + jsinθ) = 250 × (0.8 + j0.6) = 200 + j150
Series Connection:
S = VI* = V(V*/Z* ) = V2/ Z*
Z* =V2/S
Zload* =(132)2/ (200+j150) = 55.7568 - j41.8176Ω
Zload = 55.7568 + j41.8176 Ω
Zload,pu = (55.7568 + j41.8176 )/ 174.24 =0.32 + j0.24 p.u
Parallel Connection:
As it is parallel, the impact effect on the load is going to be separated
Rload =V2/P= (132)2/200 = 87.12 Ω;
Xload =V2/Q= (132)2/150 = 116.16 Ω;
DMAM
Practice Math
Element of Power System Analysis 4th Edition (Stevenson):
Example: 6.4; 6.5; 6.6; 6.10; 6.11
Exercise: 6.13; 6.15; 6.16
Power System Analysis and Design (Glover and Sharma):
3rd Edition
Example: 3.3; 3.4; 3.7
Exercise: 3.18; 3.19; 3.29; 3.30; 3.33; 3.34
4th Edition
Example: 3.3; 3.4; 3.7
Exercise: 3.23; 3.24; 3.28; 3.41; 3.42; 3.45; 3.46
References
[1] Willaim D. Stevenson, Elements of Power System Analysis, Fouth Edition, McGraw-Hill
International Editions, Civil Engineering Series, McGraw-Hill Inc.
[2] John J. Grainger, William D. Steevnson, Jr., Power System Analysis, McGraw-Hill Series in
Electrical and Conputer Engineering, McGraw-Hill Inc.
[3] J. Duncan Glover, Mulukutla S. Sharma, Thomas J. Overbye, Power System Analysis and Design,
Fouth Edition (India Edition), Course Technology Cengage Learning
[4] V. K. Mehta, Rohit Mehta, Principles of Power System, Multicolor Illustrative Edition, S. Chand
and Company Limited
DMAM