Professional Documents
Culture Documents
DEP 32.32.00.11-Gen.
September 2012
(Amendment A01 has been incorporated - February 2013)
ECCN EAR99
This document contains information that is classified as EAR99 and, as a consequence, can neither be exported nor re-exported to any country which is under an
embargo of the U.S. government pursuant to Part 746 of the Export Administration Regulations (15 C.F R. Part 746) nor can be made available to any national of such
country. In addition, the information in this document cannot be exported nor re-exported to an end-user or for an end-use that is prohibited by Part 744 of the Export
Administration Regulations (15 C.F.R. Part 744).
PREFACE
DEP (Design and Engineering Practice) publications reflect the views, at the time of publication, of Shell Global Solutions
International B.V. (Shell GSI) and, in some cases, of other Shell Companies.
These views are based on the experience acquired during involvement with the design, construction, operation and
maintenance of processing units and facilities. Where deemed appropriate DEPs are based on, or reference international,
regional, national and industry standards.
The objective is to set the standard for good design and engineering practice to be applied by Shell companies in oil and
gas production, oil refining, gas handling, gasification, chemical processing, or any other such facility, and thereby to help
achieve maximum technical and economic benefit from standardization.
The information set forth in these publications is provided to Shell companies for their consideration and decision to
implement. This is of particular importance where DEPs may not cover every requirement or diversity of condition at each
locality. The system of DEPs is expected to be sufficiently flexible to allow individual Operating Units to adapt the
information set forth in DEPs to their own environment and requirements.
When Contractors or Manufacturers/Suppliers use DEPs, they shall be solely responsible for such use, including the
quality of their work and the attainment of the required design and engineering standards. In particular, for those
requirements not specifically covered, the Principal will typically expect them to follow those design and engineering
practices that will achieve at least the same level of integrity as reflected in the DEPs. If in doubt, the Contractor or
Manufacturer/Supplier shall, without detracting from his own respons bility, consult the Principal.
The right to obtain and to use DEPs is restricted, and is typically granted by Shell GSI (and in some cases by other Shell
Companies) under a Service Agreement or a License Agreement. This right is granted primarily to Shell companies and
other companies receiving technical advice and services from Shell GSI or another Shell Company. Consequently, three
categories of users of DEPs can be distinguished:
1) Operating Units having a Service Agreement with Shell GSI or another Shell Company. The use of DEPs by these
Operating Units is subject in all respects to the terms and conditions of the relevant Service Agreement.
2) Other parties who are authorised to use DEPs subject to appropriate contractual arrangements (whether as part of
a Service Agreement or otherwise).
3) Contractors/subcontractors and Manufacturers/Suppliers under a contract with users referred to under 1) or 2)
which requires that tenders for projects, materials supplied or - generally - work performed on behalf of the said
users comply with the relevant standards.
Subject to any particular terms and conditions as may be set forth in specific agreements with users, Shell GSI disclaims
any liability of whatsoever nature for any damage (including injury or death) suffered by any company or person
whomsoever as a result of or in connection with the use, application or implementation of any DEP, combination of DEPs
or any part thereof, even if it is wholly or partly caused by negligence on the part of Shell GSI or other Shell Company. The
benefit of this disclaimer shall inure in all respects to Shell GSI and/or any Shell Company, or companies affiliated to these
companies, that may issue DEPs or advise or require the use of DEPs.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual arrangements, DEPs shall
not, without the prior written consent of Shell GSI, be disclosed by users to any company or person whomsoever and the
DEPs shall be used exclusively for the purpose for which they have been provided to the user. They shall be returned after
use, including any copies which shall only be made by users with the express prior written consent of Shell GSI. The
copyright of DEPs vests in Shell Group of companies. Users shall arrange for DEPs to be held in safe custody and Shell
GSI may at any time require information satisfactory to them in order to ascertain how users implement this requirement.
All administrative queries should be directed to the DEP Administrator in Shell GSI.
TABLE OF CONTENTS
1. INTRODUCTION ........................................................................................................ 5
1.1 SCOPE........................................................................................................................ 5
1.2 DISTRIBUTION, INTENDED USE AND REGULATORY CONSIDERATIONS ......... 5
1.3 DEFINITIONS ............................................................................................................. 5
1.4 CROSS-REFERENCES ............................................................................................. 7
1.5 SUMMARY OF MAIN CHANGES ............................................................................... 7
1.6 COMMENTS ON THIS DEP ....................................................................................... 8
1.7 DUAL UNITS ............................................................................................................... 8
2. COMMON SYSTEM REQUIREMENTS ..................................................................... 9
2.1 INTRODUCTION ........................................................................................................ 9
2.2 REQUIREMENT HIERARCHY ................................................................................... 9
2.3 AGREEMENTS ........................................................................................................... 9
2.4 MEASUREMENT STANDARD SELECTION.............................................................. 9
2.5 ENGINEERING UNITS ............................................................................................... 9
2.6 BASE CONDITIONS ................................................................................................. 10
2.7 RESPONSIBILITIES ................................................................................................. 10
3. SYSTEM DESIGN .................................................................................................... 11
3.1 INTRODUCTION ...................................................................................................... 11
3.2 APPROVALS ............................................................................................................ 11
3.3 MEASUREMENT UNCERTAINTY ........................................................................... 12
3.4 GENERAL DESIGN REQUIREMENTS .................................................................... 12
3.5 SYSTEM AVAILABILITY........................................................................................... 13
3.6 RANGEABILITY ........................................................................................................ 13
3.7 DYNAMIC VS. STATIC CUSTODY TRANSFER MEASUREMENTS ...................... 14
3.8 TRACEABILITY ........................................................................................................ 14
3.9 DEVICE VALIDATION CAPABILITY ........................................................................ 14
3.10 OPERATING ENVELOPE ........................................................................................ 15
3.11 MATERIALS .............................................................................................................. 16
3.12 ELECTRICAL ............................................................................................................ 16
3.13 ENVIRONMENTAL PROTECTION .......................................................................... 17
3.14 SKID, STRUCTURAL AND BASEPLATE................................................................. 17
3.15 PIPING AND VALVING ............................................................................................. 18
3.16 FLOW CONDITIONING ............................................................................................ 20
3.17 STRAINERS.............................................................................................................. 20
3.18 AIR/VAPOUR ELIMINATORS .................................................................................. 22
3.19 FLUID COMPOSITION DETERMINATION .............................................................. 24
3.20 COMPUTATIONAL DEVICES .................................................................................. 24
4. SPECIFIC APPLICATION REQUIREMENTS .......................................................... 25
4.1 MASS MEASUREMENT ........................................................................................... 25
4.2 VOLUMETRIC MEASUREMENT ............................................................................. 25
4.3 ENERGY MEASUREMENT ...................................................................................... 25
4.4 TRUCK LOADING .................................................................................................... 26
4.5 TRUCK UNLOADING ............................................................................................... 26
4.6 LNG ........................................................................................................................... 27
4.7 LEASE AUTOMATIC CUSTODY TRANSFER (LACT) ............................................ 27
4.8 MARINE UNLOADING .............................................................................................. 27
4.9 PIPELINE MEASUREMENT SYSTEMS .................................................................. 27
4.10 VISCOUS FLUIDS .................................................................................................... 27
5. METER REQUIREMENTS ....................................................................................... 27
5.1 GENERAL REQUIREMENTS ................................................................................... 27
5.2 MULTI-PATH ULTRASONIC METERS .................................................................... 28
5.3 CORIOLIS ................................................................................................................. 28
5.4 POSITIVE DISPALCEMENT (PD) ............................................................................ 29
5.5 TURBINES ................................................................................................................ 29
5.6 ORIFICE.................................................................................................................... 30
APPENDICES
APPENDIX A BLACK AND WHITE LIST .............................................................................. 57
APPENDIX B COMMON ENGINEERING UNITS .................................................................. 61
APPENDIX C BASE CONDITIONS ....................................................................................... 62
APPENDIX D TYPICAL SINGLE METER RUN CTM APPLICATION EXAMPLE ............... 63
APPENDIX E TYPICAL MULTI METER RUN WITH PIPE PROVER/MASTER METER
(SINGLE PRODUCT) ...................................................................................... 64
APPENDIX F “Z” MASTER METER CONFIGURATION EXAMPLE ................................... 65
APPENDIX G CTM SYSTEM ARCHITECTURE EXAMPLE – PART 1 ................................ 66
APPENDIX H CTM SYSTEM ARCHITECTURE EXAMPLE – PART 2 ................................ 67
APPENDIX I FLOW COMPUTER DETAILED REQUIREMENTS ....................................... 68
1. INTRODUCTION
1.1 SCOPE
This DEP specifies requirements and gives recommendations for the design, fabrication,
installation and commissioning of custody transfer measurement systems. Application of
this DEP is limited to single phase homogenous Newtonian fluids which are liquids or super
critical (dense phase) fluids at the measurement conditions such as LPGs, refined products
(e.g., gasoline, diesel, kerosene), crude oils, ethane, CO2, NGLs, LNG and chemicals (e.g.,
ethylene, benzene, styrene, glycols).
Custody transfer measurement systems associated with pipeline, marine vessel and truck
(un)loading applications with some exceptions as detailed below are included in the scope
of this DEP. Custody transfer measurement systems at the retail level of trade (e.g.,
gasoline dispensers) are outside the scope of this DEP as are weight scales.
Metering requirements associated with allocation meters upstream of the sales meters are
outside the scope of this DEP, see DEP 32.00.00.12-Gen.
This DEP encompasses mass, volumetric and energy measurement.
This DEP shall be used in conjunction with requisition sheet DEP 32.32.00.94-Gen.
This is a revision of the DEP of the same number dated September 2002; see (1.5)
regarding the changes.
1.3 DEFINITIONS
1.3.1 General definitions
The Contractor is the party that carries out all or part of the design, engineering,
procurement, construction, commissioning or management of a project or operation of a
facility. The Principal may undertake all or part of the duties of the Contractor.
The Manufacturer/Supplier is the party that manufactures or supplies equipment and
services to perform the duties specified by the Contractor.
The Principal is the party that initiates the project and ultimately pays for it. The Principal
may also include an agent or consultant authorised to act for, and on behalf of, the
Principal.
Term Definition
Custody Custody transfer measurement provides highest accuracy quantity and
Transfer quality information used for the physical and fiscal documentation of a
change in ownership and/or a change in responsibility for feed stocks, fuel,
products etc. Synonymous with fiscal measurement with the exclusion of
government taxation and possible lack of change of ownership.
Fiscal Measurement pertaining to income and revenues of parties concerned,
Measurement including government taxation.
Validation In jurisdictions where API MPMS terminology is utilized, measurement
equipment performance assurance is denoted by the terms verification
(i.e., assessment of the as-found state of the device relative to a reference
standard) and calibration (i.e., device output adjustment to conform to
reference standard value).
In jurisdictions where OIML/ISO terminology is utilized, measurement
equipment performance assurance is denoted by the terms calibration (i.e.,
verification as defined above) and adjustment (i.e., calibration as defined
above).
In this document the term “validation” shall be used to denote the process of
verification followed by calibration if required.
Meter validation is typically termed meter proving.
1.3.3 Abbreviations
Term Definition
AMS Asset Management System
API American Petroleum Institute
ATEX European Union directives describing explosive atmosphere equipment
requirements
BPCS Base Process Control System
CCR Central Control Room
CTM Custody Transfer Measurement
D Nominal Pipe Internal Diameter
TM
FF FOUNDATION FIELDBUS
FGS Fire and Gas System
GC Gas Chromatograph
GPA Gas Processors Association
HART® Highway Addressable Remote Transducer
HPIMS Hydrocarbon Production Information Management System
HFE Human Factors Engineering
IPS Instrument Protective System
ISO International Organization for Standardization
IUPAC International Union of Pure and Applied Chemistry
LACT Lease Automatic Custody Transfer
Term Definition
LCR Local Control Room
LPG Liquefied Petroleum Gas
MESC Materials, Equipment, Standards and Code
MID Measuring Instruments Directive
MPMS Manual of Petroleum Measurement Standards
NGL Natural Gas liquid
NIST National Institute of Standards and Technology
OIML International Organization of Legal Metrology or Organisation Internationale
de Métrologie Légale
PD Positive Displacement
PEFS Process Engineering Flow Scheme
P&ID Piping and Instrumentation Diagram
RTD Resistance Temperature Detector
PLC Programmable Logic Controller
SCADA Supervisory Control and Data Acquisition
STP IUPAC Standard Temperature and Pressure
TCoO Total Cost of Ownership
UL Underwriters Laboratories Inc.
1.4 CROSS-REFERENCES
Where cross-references to other parts of this DEP are made, the referenced section
number is shown in brackets ( ). Other documents referenced by this DEP are listed in (15).
Comments on this DEP may be submitted to the Administrator using one of the following
options:
Feedback that has been registered in the DEP Feedback System by using one of the above
options will be reviewed by the DEP Custodian for potential improvements to the DEP.
2.1 INTRODUCTION
Custody transfer measurement systems are designed to provide accurate, equitable and
reliable measurements. This intent is achieved by pre-establishing and then meeting the
regulatory, contractual and the Principal’s due diligence requirements. This mitigates the
risk of breach of contract, financial loss or non-compliance. The use of industry
measurement standards lays the foundation for appropriate custody transfer measurement
system design.
2.3 AGREEMENTS
The measurement sections of contracts (e.g., tariffs, connection agreements, sales and
purchase agreements) should refer to general custody transfer measurement requirements.
Measurement requirements should be expanded in an addendum (i.e., exhibit, attachment)
to the contract thus avoiding undue revision of the contract if only technical requirements
change. Measurement details such as procedures should be addressed in a Measurement
Manual. The “Black and White List” (Appendix A) should be reviewed when preparing the
contract.
2.7 RESPONSIBILITIES
The Contractor’s scope of work shall include system design, equipment selection, and
documentation of the measurement system and oversight of the Supplier. The Supplier’s
scope of work shall include fabrication, inspection, testing, delivery, and the initial
calibration of the complete liquid metering system.
The Contractor shall assume full system responsibility. This means that the Contractor shall
have, as a minimum, single point responsibility for the following:
a) designing the custody transfer measurement system in accordance with this DEP
and all applicable codes and standards,
b) the operability, accuracy and quality of all components including those of sub-
suppliers,
c) obtaining written approvals from the Principal, regulatory authorities and all
interested parties for the design prior to procurement and fabrication
d) all performance based testing (e.g., water injection test for crude oil samplers)
e) obtaining all permits, certifications and calibrations (e.g., prover water draw)
f) demonstrating satisfactory system performance via a FAT, SAT and site
commissioning
g) timely notification of upcoming shop and field testing to permit witnessing (Principal,
authorities, interested parties)
h) providing appropriate documentation,
i) fabrication, delivery and installation oversight.
The Supplier shall prepare a preliminary design with appropriate documentation (14.2) for
approval by the Principal in writing prior to equipment procurement.
Where applicable, the Supplier shall be required to liaise with the main data acquisition
system Supplier (to be advised by the Principal) to arrange the data links and protocols
necessary for monitoring and control of the metering system.
The Supplier shall immediately inform the Contractor and the Principal if there is doubt
regarding the specified requirements. The Supplier shall not proceed with any aspect of the
work until the Principal gives the necessary written approval.
3. SYSTEM DESIGN
3.1 INTRODUCTION
The measurement system shall be designed to meet all applicable agreements, codes and
standards using field proven methods and devices (i.e., no prototypes). Products shall be
technically qualified to the satisfaction of the Principal and shall be sourced from
Manufacturers acceptable to the Principal.
NOTE: For this purpose, Shell Companies may use the list of Technically Acceptable Manufacturers and
Products (i.e., TAMAP) maintained by Shell.
The total life cycle costs of ownership (TCoO) of the measurement station shall be
optimised against the requirements stated below. A method for calculating the TCoO is
given in DEP 32.31.09.31-Gen.
Prior to the design of custody transfer measurement systems, the following shall be defined
and documented (14):
a) target uncertainty for measurement system,
b) applicable codes, regulations, agreements and standards,
c) ownership of measurement equipment,
d) responsible party for measurement system,
e) measurement basis (mass, volume or energy),
f) acceptable meter types,
g) range of process conditions (e.g., fluid types, fluid contaminants, density,
pressures, temperatures, flow rate range, etc.),
h) acceptable validation techniques (e.g., in-situ or remote),
i) reference conditions for volumetric techniques, mass or weight (4.1),
j) target system availability,
k) third party data transfer connection requirements,
l) engineering units,
m) fluid quality specifications.
n) load factor (3.6), and,
o) measurement system operational control philosophy (consistent with the facility
operational control philosophy).
It should be noted that selecting the industry measurement standards to be applied in
combination with defining what validation techniques are to be applied will largely
determine the potential measurement uncertainty (3.3).
3.2 APPROVALS
Custody transfer metering installations are usually subject to approval by local authorities or
other interested parties (e.g., JV partners, other producers or refiners, pipeline companies).
These approvals typically extend from the design stage through to final installation and
eventually to the operating stage. Those authorities/interested parties shall be consulted at
the earliest possible stage and thereafter, in order to gain acceptance of the metering
philosophy, approval of the system design (where required) and to simplify final approval of
the installation.
In some cases, local authorities require that devices (e.g., meters, flow computers,
transmitters) have individual approvals (e.g., NMI, MID). However, the fact that a device
has such an approval does not negate the necessity to ensure the devices suitability for the
application under consideration.
The preliminary design shall be submitted to the Principal for approval prior to detailed
engineering (2.7).
The design shall meet the process control domain security requirements as detailed in
DEP 32.01.20.12-Gen.
3.5 SYSTEM AVAILABILITY
The required system availability and load factor shall be defined prior to design and
specified in DEP 32.32.00.94-Gen. The design shall incorporate the degree of redundancy
to meet the defined system availability considering the documented reliability of the system
components and subsystems based on the Principal’s experience with similar devices or
Manufacturer’s reliability data. Local availability of spares and expertise to repair
equipment failures in a timely manner shall be considered a part of the availability
assessment.
When 100 % availability is required, the metering system shall be arranged in such a way
that a single device failure does not result in a complete loss of measurement. This means
that:
a) The power supply of the measuring station up to and including the field
instrumentation shall be redundant. However, failure of the power supply in
combination with a failure of the back-up supply need not be assumed in the design.
b) The pressure measurement and temperature measurements shall be redundant.
c) In a multi-meter run design, at least the flow meter with the highest range shall be
redundant. For equal range flow meters the design shall be N+1 (i.e., 2 x 100 %, 3 x
50 %, etc.).
d) Redundant flow computers shall be provided.
e) A spare instrument or an alternative method shall be available to determine physical
properties of the liquid.
f) The change out of failed equipment shall not interrupt measurements.
g) Redundant meter provers are not required.
Although selection of components with a high inherent availability may reduce the level of
redundancy required, such selections do not negate the requirement for redundant devices,
adequate spares or repair expertise.
The Manufacturer shall with his proposal include a description of how the target availability
is to be met.
3.6 RANGEABILITY
The design capacity of the metering system is determined by the maximum flow rate that
can be measured at the required uncertainty (excluding any spare meter runs provided for
reliability purposes).
The minimum design capacity is the minimum flow rate of the smallest single meter run at
the required uncertainty.
Minimum and maximum flow rate design shall consider the limitations of all components
such as the meter, static mixer, strainer, prover, etc. The system design shall incorporate
sufficient parallel meter runs to:
• permit the maximum and minimum system flow rates to be measured at the specified
uncertainty,
• achieve the specified availability including validation exercises when one of the
meter runs is removed for remote validation.
Where required by agreement or regulation, provision shall be made to stop the flow at
rates below a preset minimum value.
When determining the maximum flow rate required, peak as well as average flow rates
shall be considered. For example, the average throughput of a jetty would not represent the
average meter flow rate required because the product is typically unloaded or loaded as
quickly as possible to reduce vessel demurrage. To properly size meters a load factor
would be determined by dividing the average quantity to be measured by the time it is to be
measured in.
3.8 TRACEABILITY
The system shall be designed in a manner to permit traceability to the required national
metrological standards. At the design stage this requires:
• selecting equipment types that are inherently traceable, and,
• providing appropriate means (e.g., access, provers, process taps) for the required
field verifications and calibrations.
The equipment used for determining fluid and process properties shall be traceable to
national and international standards through a system of analytical procedures, reference
materials, sampling and calibration procedures.
devices and to provide suitable software to utilize such functions for performance
monitoring and troubleshooting.
For the purposes of validation and troubleshooting, suitable electronic connections shall be
provided for computational devices and field devices.
3.9.3 Meter proving
As part of the preliminary design, the flow meter validation practice shall be selected.
Specifically, an assessment shall be performed to determine which of the following meter
validation options meet the application requirements:
a) off site calibrations (availability of suitable proving facilities in terms of geographic
proximity, uncertainty and capacity)
b) on site calibrations using a portable prover (local availability of suitable portable
provers in terms of geographic proximity and capacity),
c) on site calibrations using a permanently installed prover,
d) on site calibration using a master meter (either permanently installed in series or
periodically brought in-line).
Such assessments shall consider the total cost of ownership of the various meter validation
options, meter performance characteristics, fluid properties and the risk associated with
increased uncertainty or loss of use associated with master meter or off site calibrations.
3.11 MATERIALS
All pressure retaining components such as piping, valves, strainers, air eliminators and
meter bodies shall comply with the piping classes specified in DEP 32.32.00.94-Gen. and
with requirements of DEP 31.38.01.11-Gen., DEP 31.38.01.12-Gen.,
DEP 31.38.01.15-Gen. and DEP 39.01.10.11-Gen.
All instruments shall comply with the materials requirements as specified in
DEP 32.32.00.94-Gen.and as specified in DEP 32.31.00.32-Gen.
3.12 ELECTRICAL
All electrical devices shall be approved (e.g., ATEX, CSA, UL) and so marked for the area
classification and jurisdiction in which they are to be installed. See DEP 32.31.00.32-Gen.,
Section 2.5 for electrical certification requirements.
3.12.1 Measurement device outputs
In addition to the primary element signals (3.12.2) and secondary instrument signals
(3.12.3), all measurement devices shall output a fault condition (3.12.4).
Where available, device diagnostics shall be provided (but not necessarily on a real-time
basis).
With the exception of communications downstream of the flow computer, wireless shall not
be utilized in custody transfer measurement systems.
Barriers to achieve intrinsically safe designs shall not be utilized for measurement devices
analog outputs.
For custody transfer measurement devices, meter wiring design shall utilize a minimum
number of connections (e.g., junction boxes). Continuous conductors shall be utilized
between field devices and the skid junction box and between the skid junction box and the
computational device. Other wiring practices are as per DEP 32.31.00.32-Gen.
3.12.2 Primary element outputs
Linear meters shall output pulses where each pulse represents a discrete volume or mass.
Specifically, analog signals (e.g., 4-20 mA) or digital communications such as
TM
FOUNDATION FIELDBUS (FF) shall not be utilized for linear custody transfer meters.
3.12.3 Secondary device signals
Where practical and provided compatibility has been proven through interoperability testing,
secondary instruments such as static pressure, differential pressure, temperature and QMIs
shall utilize a digital communications such as FF. With the exception of gas
chromatographs, Modbus shall not be used for secondary device signals. Where digital
communications are not practical, analogue outputs shall be 4-20 mA.
The square root function of differential pressure meters shall be applied in the computing
device.
Temperature measurements may utilize one of the following:
• a fully characterized temperature transmitter combined with an RTD, or,
• a 4 wire RTDs interfaced directly to the computing device (i.e., avoid temperature
transmitters).
3.12.4 Diagnostics/fault signals
In addition to the required measurement output, where practical measurement devices shall
output common (i.e., grouped) warning and fault status signals to the BPCS or SCADA.
Detailed diagnostic capability/screens shall be provided by equipment specific software and
need not be programmed into the BPCS or SCADA.
The fault status may be transmitted utilizing a set of dry contacts, over/under range analog
signals or via a digital protocol such as Modbus or digital communications such as FF.
Fault status via analog 4-20 mA type output signals shall comply with NAMUR NE-43
recommended values for abnormal signal levels. In such designs the computational device
inputs shall also comply with NAMUR NE-43. The field device shall not drive the signal
through the alarm condition to reach the fault condition value.
Contacts used for fault status shall be normally closed, open on fault detection and shall be
self resetting.
Measurement systems shall be designed to provide the capability to connect to field and
flow computation devices digitally (e.g., Modbus over Ethernet) for the purpose of
performance validation and troubleshooting utilizing fit for purpose software.
Where asset management systems are employed, the analogue output devices shall be
HART® or FF compatible to enable enhanced diagnostic data to be collected. The
associated analogue input modules shall support HART® or FF without the need for
additional hardware.
Subject to (2.2) the action upon fault detection shall be documented (e.g., measurement
manual, control narrative).
For the specification of the painting, refer to DEP 30.48.00.31-Gen. The painting schedule
shall be as specified in DEP 32.32.00.94-Gen. Colour schemes shall be as specified in
DEP 32.32.00.94-Gen. and may be governed by local regulations and customs.
The metering system manufacturer shall provide foundation loading drawings/calculations
for the metering skid prior to fabrication.
The inlet and outlet piping of parallel metering devices with common inlet and outlet
headers shall have sufficient flexibility to cope with differences in thermal expansion when
one device is not in operation and to facilitate component removal. The manufacturer shall
complete piping stress analysis on the metering skid piping to ensure adequate strength
during the various stream online configurations, varying process conditions and external
termination point loads. Calculations shall be made available to Principal for review and
approval prior to start of fabrication.
Verifiable isolation utilizing double block and bleed (DB&B) valves shall be provided as
required to preclude the possibility of measurement error due to unmetered fluids (i.e.,
bypass around meters), undelivered fluids (i.e., diversion downstream of meters) or meter
proving errors (i.e., inflow or outflow between meter and prover). This requires DB&B
valves as follows:
• between parallel or redundant meter runs,
• on all permanently piped drain valves downstream of the meter including those
between the meter and prover.
Single body type rotating plug valves are preferred for DB&B service.
The bleed port of DB&B valves shall allow visual or electronic means of seal verification.
Double block-and-bleed valve body relief valves shall not discharge into the line between
the prover and the meter being proved.
Unless required for HSSE reasons, vent valve connections through which leakage is clearly
visible do not require DB&B valves.
Facilities shall be designed to minimize hard-piped pressure relief and vent connections
through which flow would cause measurement error. If hard piped relief, vent or DB&B
bleed connections are necessary, the outlet of potential bypasses shall be routed to a
continuously monitored sump or surge tank. Where such sumps or tanks are impractical,
redundant, monitored electronic flow detection shall be provided.
If vents, drains, and relief valves that discharge to the downstream side of the flow meter
absolutely cannot be avoided, associated discharge lines shall include a visual or electronic
means of determining leakage.
3.15.2 Thermal relief
Thermal expansion relief valves are required in liquid-full systems if the system can be
blocked in and subjected to heat input from atmosphere or process. For the application of
thermal expansion relief valves, see DEP 80.45.10.11-Gen.
In no case shall a thermal relief valve be located between the meter and the prover or
between the sampling system and meter.
3.15.3 Prover piping
Prover valving/manifolds shall be provided for applications requiring in-situ proving.
Prover valving/manifolds shall be:
• sized to allow meter proving over the full operating range expected for the meter.
• be located downstream of the flow meters.
Where in-situ meter proving is required, DB&B valves shall be provided as follows:
• as the meter run prover bypass (i.e., divert) valve to divert the flow through the
prover for a single meter run application,
• as the meter run prover bypass (i.e., divert) valve to divert the flow to the prover
supply header for a multi meter run application, and,
• to isolate individual meter runs from the prover supply header when meter proving
other meters,
• to isolate individual meter runs the prover return header when meter proving other
meters.
For multi-product, single meter run applications such a pipeline transporting multiple
products, a stationary prover or master meter may be shared between different products
(e.g., gasoline and diesel).
For multi-meter run single product applications, a stationary prover or master meter should
be shared between different products.
Sharing a prover between multi meter run, multi-product applications shall not be applied.
3.15.4 Flow control valves
Flow control valves shall be utilized where required to:
• control the flow rate through a meter to ensure the measured flow rate is within the
calibrated portion of the meter range, and,
• create sufficient backpressure to preclude flashing.
With the exception of truck (un)loading applications, flow control valves are normally not
required for single meter run applications. For multi-run flow measurement systems, one
flow control valve shall be provided per meter run to balance flow rates during operation
and when proving (where applicable).
Flow control valves associated with meter runs shall be installed outside the downstream
straight length required by a meter (i.e., typically 5D downstream).
Flow control valves shall be selected, sized and installed as per the requirements of
DEP 32.36.01.17-Gen.
3.17 STRAINERS
Strainers shall be provided for turbine meter, PD meter and displacement prover
applications.
head for that pump when the storage tank is at its minimum level and at any pump
operating condition.
g) The pump is equipped at its inlet with a tap and valve to accommodate a
pressure/vacuum gauge during inspection.
h) If the installation necessitates piping bridges, these bridges are equipped with
manual high point bleed valves for system priming.
i) The piping is installed so that there is no possibility of air leaks if a vacuum condition
occurs.
j) The installation has an automatic control valve installed downstream of the meter,
which opens only after the pump has been energized and sufficient time has elapsed
for any vapour to be compressed into liquid (10 seconds minimum).
k) Where the installation contains control or automatic valves, the sequence of valve
openings begins at the control valve nearest to the storage tank and ends at the
control valve downstream of the meter.
l) There is no common piping between the installation intended for the delivery of
product through the meter and the installation intended for the receipt of product into
the storage tank.
m) Means are provided to ensure that the level of liquid in the storage tank is such that
no air or vapour can be drawn into the piping to the measuring system, and that the
delivery is inhibited and cannot be initiated unless the tank contains sufficient
product. These means may consist of:
• low level sensors interlocked to the pump, and/or
• an automatic tank gauging system, and/or
• an automation system which monitors inventory in real-time and has
automatic daily reconciliation against product receipts and sales, and which is
further backed by manual tank gauging.
Air eliminators shall be sized for the highest expected velocity and viscosity.
For truck and marine unloading applications, air eliminators shall be provided with level
detection device(s) to respond to air/vapour entrainment detection as follows:
• upon first detection of air, reduce the flow rate by approximately 50 % (field
adjustable) to facilitate air elimination and open solenoid valve to vent entrained
air/vapour,
• halt flow if air is detected by lower level switch to prevent air from passing through
meter.
The above flow control functionality requires a single level transmitter with two set points or
two level switches installed at the correct levels in the vessel. For applications utilizing
level switches, ultrasonic gap or vibrating type level switches shall be specified (i.e.,
mechanical float switches are not acceptable).
Air eliminators for truck unloading applications should be vertical with internal baffling to
improve efficiency.
The air eliminator shall be located at the highest point between the pump and the
sampling/metering system.
The air eliminator shall be equipped with a positive seat check valve on the vapour
discharge line. The check valve shall be close-coupled to the air eliminator discharge and
be installed to allow vapour discharge while preventing air from entering the system.
If a block valve is installed in the discharge line, the block valve shall be located
downstream of the check valve and sealed in the open position.
The discharge piping shall provide a view space or other means for detecting leakage or
malfunctions.
For applications associated with high vapour pressure fluids such as LPGs, the system
shall be designed in such a manner to established and maintain the fluid in the liquid state
(4.4.3) which should preclude subject to (2.2) the need for air eliminators in such
applications provided non-condensables (e.g., ethane in propane) are absent.
Truck load rack meters are typically proved using the loading arm so divert valves for meter
proving are not normally required. For side stream blending, a proving connection is
required for the minor blend component.
For volumetric measurements, temperature measurement shall be as per (7.2).
Flow rates shall meet the limitations in Section 2.3 of DEP 31.06.11.11-Gen.
4.4.2 Blended products
Product blending applications require special consideration. For example, ethanol shall be
blended prior to the custody transfer meter. To maximize the growth potential from ethanol
blending, it is recommended the ethanol injection point be located 60D upstream of the
custody blend meter and a static mixer be provided. If 60D of line length cannot be
achieved, the application of a static mixer alone is acceptable. Where static mixers are
utilized, their pressure drop should be considered.
4.4.3 LPGs
Custody transfer dynamic measurement systems for LPGs shall be designed, installed,
calibrated and operated to meet the minimum requirements of API MPMS 14.8.
See (6) for LPG measurement using tank gauging.
Coriolis meters are recommended for LPG truck loading applications.
Vapour return lines should not be used. If a vapour return line is not used, the meter
indicates directly the transferred quantity. Where vapour return lines downstream of the
meter, a correction has to be made for the returned vapour.
In the design and operation of LPG metering systems, care shall be taken to ensure that
sufficient back-pressure is kept on the meter to reduce the probability of vapour formation.
This will reduce or eliminate partial vaporization which impairs the accuracy of metering and
may cause meter over speeding and/or cavitation which would cause damage to meters.
The use of over pressure is effective provided non condensables (e.g., ethane, fixed gases)
are absent. See (3.15.1) for computation of required back pressure.
The size of the truck unloading header vent line should be a minimum of 18 mm (3/4 in)
diameter to ensure proper venting.
In a drain dry system, a large vertical air eliminator located downstream of the unloading
pumps shall be utilized. The small 356 mm (14 in) face to face truck loading type air
eliminators shall not be utilized for truck unloading. See (3.18) for air eliminator
requirements.
Operability of system (e.g., location of proving valves, snow removal, spill containment
pads, etc.) shall be considered.
Coriolis meters should be utilized for truck off loading.
For volumetric measurements, temperature measurement shall be as per (7.2).
For truck off loading measurement systems, meter proving valves shall be provided for
applications utilizing turbine and PD meters and may be required for Coriolis meter
applications subject to (2.2). When required, proving connections shall be downstream of
the air eliminator.
4.6 LNG
Custody transfer LNG measurements shall be made according to The GIIGNL LNG
Custody Transfer Handbook. Currently this requires the use of level, temperature and
composition measurements associated with shore storage tanks or marine vessel
compartments.
LNG shall be sampled according to The GIIGNL LNG Custody Transfer Handbook.
LNG composition shall be measured using a gas chromatograph (7.4.4).
5. METER REQUIREMENTS
At a minimum, subject to (2.2) and the individual meter requirements in (5), multipath
ultrasonic, Coriolis, turbine and PD meters shall comply with OIML R117 accuracy class 0.3
or better at normal operating conditions over the specified turndown ratio.
NOTE: In OIML R117 the accuracy is defined as the Maximum Permiss ble Error (MPE). The MPE is not
equal to 2 sigma.
Additionally subject to (2.2), all meters used for custody transfer applications shall be
capable of delivering a meter proving precision uncertainty (i.e., repeatability) of +/-0.027 %
as per API MPMS 4.8.
NOTE: API MPMS 4.8 details various combinations of number of runs and repeatability to deliver a 0.027 %
uncertainty (e.g., a maximum repeatability of 0.05 % for five consecutive runs).
All meters shall be installed so that they are well supported (i.e., adjacent piping shall not
exert any stress on the meter body).
Adequate filtering and degassing shall be provided where necessary.
5.3 CORIOLIS
Coriolis meters used for liquid custody transfer metering shall be selected, sized, installed,
calibrated and operated to meet the requirements of:
• API MPMS 5.6 or,
• ISO 10790.
Coriolis meters are acceptable for uni-directional and bi-directional volumetric or mass flow
measurement applications.
Coriolis meters shall have an uncertainty of ± 0.15 % of reading or better at normal
operating conditions over the specified turndown ratio.
Due to the sensitive nature of Coriolis meters to flow disturbances which occur during the
prover pre-run time (e.g., poppet valve closing, ball launch), proving repeatability difficulty
may be observed. In such situations, high speed Coriolis electronics, a prover with
increased pre-run time, a larger prover or a master meter shall be considered. Prover
sizing shall be confirmed with the prover Manufacturer.
Coriolis meters are acceptable for applications with significant viscosity and/or density
variations.
5.5 TURBINES
Turbine meters used for liquid custody transfer metering shall be selected, sized, installed,
calibrated and operated to meet the requirements of:
• API MPMS 5.3 or,
Amendment A01
• ISO 2715
Exceptions: Tube bundle type flow straighteners shall not be utilized.
Turbine meters are acceptable for uni-directional volumetric or inferred mass flow
measurement applications.
Turbine meters shall have a linearity of ± 0.15 % of reading or better at normal operating
conditions over the specified turndown ratio.
Turbine meters shall only be used within the Manufacturer’s published viscosity limits. The
use of bladed (i.e., standard) turbine meters is normally limited to products with relatively
2
low viscosities, typical maximum 10 mm /s (10 cSt). Helical turbine meters may be used
2
for relatively high viscosity up to 1000 mm /s (1000 cSt) with lower turndown ratio. The
Manufacturer shall be consulted in both cases to verify that the meter in question is suitable
for the viscosity range adjusted for the minimum credible flowing temperature.
Additional requirements are as follows:
a) Be sized to operate at a flow rate between 40 % – 100 % of meter capacity.
b) Be equipped with dual pick-up coils, 90 degrees out of phase, for pulse verification.
One pick-up coil is used for the pulse train to the flow computer for accumulation
while the second coil is used for pulse fidelity checking.
c) The body material shall be carbon steel with stainless steel internals, unless the
application requires other materials as specified by the Principal.
d) Preamplifiers shall be utilized.
e) Bearings shall be made of hardened material, e.g., tungsten carbide. Bearing
dimensions shall be such that a permanent liquid film is maintained (e.g., by having a
longer axis and/or a larger diameter).
The meters shall be protected against damage due to over-speeding or hydraulic shock,
(e.g., caused by the quick opening and closing of valves).
Turbine meters shall meet the straight run requirements (3.17).
The meter calibration factor (K-factor) for each turbine meter shall be determined initially by
tests carried out by the Manufacturer and stamped on the meter body or a permanently
affixed name plate.
For applications without provision for in-situ proving, the meters shall be calibrated initially
by an independent authority utilizing a liquid with a viscosity comparable to the process fluid
for which the system is designed. This calibration shall be performed at the minimum and
maximum flow and at evenly distributed flow rates within the specified 10:1 range.
5.6 ORIFICE
Unless ultrasonic, Coriolis, PD and turbine meters are not suitable, orifice meters shall not
be used for new liquid custody transfer meter applications. When orifice meters are used
for liquid custody transfer, meters shall be selected, sized, installed, calibrated and
operated to meet the requirements of:
a) ISO 5167–1
b) ISO 5167-2
c) API MPMS 14.3.1
d) API MPMS 14.3.2
e) API MPMS 14.7
f) API MPMS 14.8
6.1 INTRODUCTION
Volumetric and inferred mass static measurements can be one of the following types:
storage tank, rail car or marine vessel. In all cases, volume determination consists of
measuring the level and temperature of the product and taking a sample for density
(gravity) determination. The level is then converted to a gross volume using a volume
capacity table (i.e., strapping table). The gross volume is then converted to a mass or to a
net standard volume. Static measurement can also be made using weigh scales which are
outside the scope of this DEP.
As stated in (3.7), the use of storage tanks, marine vessels or rail car or trucks for custody
transfer measurement shall only be used where dynamic measurement is not practical or
cost effective or precluded by agreements, codes, etc.
The premise for storage tank/vessel custody transfer measurements is that the level and
temperature measurements and sampling and analysis shall be performed manually by
approved inspectors (i.e., surveyors/gaugers) according to Industry standards such as
API MPMS 3.1A, API MPMS 3.2, API MPMS 3.4 or API MPMS 17.1. Automatic tank
gauges and temperature measurement devices shall only be used for custody transfer
measurements with the agreement of local authorities and all interested parties.
To facilitate periodic validations of the automatic tank gauge level and temperature
measurement devices, these devices shall be installed along the circumference of the tank
in the vicinity of the manual gauging point which shall meet applicable HSSE requirements
(e.g., safe access, railings).
e) tank floors, shells, or roofs have been altered enough to suspect a change in tank
volume,
f) significant unanswered volume discrepancies arise.
Tank re-calibration should be considered whenever tank maintenance/gas freeing (e.g.,
API 653 internal inspection) is scheduled and the tank is approaching the 10 year elapsed
time since the last tank strapping.
Tank (re)calibration or (re)computation authority and interested party witnessing and
approval requirements shall be as detailed in DEP 32.32.00.94-Gen.
Tank re-computation is the process of developing a revised capacity table based on
previously established tank dimensions. Capacity tables shall be re-computed when
significant changes have occurred in operating variables such as temperature, product
service - API gravity (density), reference gauge height, floating roof weight, leg position, or
when unexplained significant stock variations have occurred. Examples include:
• addition or removal or change of floating suction line or swivel,
• addition or change of a roof seal for a floating roof,
• installation, replacement or change to the datum plate,
3
• a change in density (gravity) greater than 50 kg/m (+/-10°API) from the density
(gravity) stated on the capacity table (e.g., from gasoline to diesel service).
After review by the Principal, initial/revised tank strapping tables shall be updated in the
tank gauging computation device (e.g., BPCS).
7. SECONDARY INSTRUMENTS
7.1 INTRODUCTION
Temperature, pressure and differential pressure transmitters shall be selected and installed
as per the requirements of DEP 32.31.00.32-Gen.
7.2 TEMPERATURE
Temperature measurement shall be performed using RTDs mounted in flanged
thermowells (refer to Standard Drawing S 38.113). Meter skin or meter body temperature
measurements may only be used to correct for temperature effects on the meter body but
not to compute physical properties or correct volumes.
A pair of thermowells, one for the measurement RTD and one for validation purposes shall
be provided at the following locations:
• For each displacement meter or Coriolis meter, first device downstream of the meter
within 300 mm (12 in ) from the meter outlet flange;
• For each turbine, ultrasonic and orifice meters, first device downstream of the meter
downstream straight length provision (i.e., typically from 5D to 10D from the meter
outlet flange);
• At the prover inlet, within the lesser of 5D or 600 mm (24 in) of the prover inlet
flange;
• At the prover outlet, within the lesser of 5D or 600 mm (24 in) of the outlet flange.
Test thermowells shall have a 10 mm to 13 mm (3/8 in to 1/2 in) internal bore.
The two thermowells shall be installed on different radial axes to minimise vibration fatigue
of the downstream well by vortex shedding from its upstream partner.
Insertion depth shall be middle third of pipe or 75 mm (3 in) maximum into pipe subject to
the vibration failure avoidance constraints and length requirements detailed in
DEP 32.31.00.32-Gen. For pipe sizes 50 mm (2 in) and smaller, the pipe size shall be
7.3 PRESSURE
Pressure transmitters shall be provided at the following locations:
• For each meter, adjacent to or downstream of the temperature transmitter, within
450 mm (18 in) of the temperature transmitter location;
• At the prover inlet and outlet, adjacent to or downstream of the temperature
transmitters, within 450 mm (18 in) of the temperature transmitter location.
To facilitate calibration, a dedicated impulse line connection to the transmitter manifold
block shall be available to allow calibration of the transmitter without the transmitter being
removed from the field.
Local pressure gauges shall be applied only by exception and shall be selected and
installed according to DEP 32.31.00.32-Gen. Indicating pressure transmitters should be
used rather than permanently mounted pressure gauges.
8. COMPUTATIONAL DEVICES
Signal transmission between the meter and secondary devices and the flow computer shall
be as per (3.12).
See (Appendix I) for detailed flow computer requirements.
8.2 COMPUTATIONS
8.2.1 Introduction
Computations shall be made to meet the requirements of the applicable standards,
regulations and agreements.
8.2.2 Dynamic measurement
At a minimum the computations shall meet the requirements of the API MPMS Chapters
associated with the different meter types (5) and of the following:
• API MPMS 21.2
• API MPMS 21.2 - Addendum to Section 2 – Flow Measurement, Inferred Mass
For the purposes of this DEP, API MPMS 21.2 shall apply to Coriolis and ultrasonic meter
applications including proving requirements as well as PD and turbine meter applications.
Computations for linear meters such as ultrasonic, PD, turbine and Coriolis (in volume
mode) including aspects such as rounding, order or operations and significant figures shall
be as per:
• API MPMS 12.2.1
• API MPMS 12.2.2
• API MPMS 12.2.3
For similar computations associated with orifice meters shall be as per:
a) API MPMS 21.1
b) API MPMS 14.3.1, Part 1, (AGA Report No. 3), (ANSI/API 2530, Part 1), and,
c) API MPMS 14.3.2, Part 2, (AGA Report No. 3, Part 2, GPA 8185-00, Part 2),
(ANSI/API 14.3, Part 2-2000) and,
d) API MPMS 14.8, or,
e) ISO 5167–1, and,
f) ISO 5167-2.
8.2.3 Static measurement
Computations for converting levels to volumes and gross volumes to net volumes shall be
as per the following:
• API MPMS 12.1.1
• API MPMS 12.1.2
The gross volume, density, mass and energy of LNG shall be computed using The GIIGNL
LNG Custody Transfer Handbook.
8.2.4 Physical properties and volume correction
The recommended algorithms for computing volumes at base conditions or computing
corrected density are detailed below but are not intended to supersede the requirements of
applicable agreements, local codes and regulations and Industry standards.
Computations for density and volume correction factors should be as per API MPMS
Chapter 11 and ASTM D1250 using the appropriate subchapter based on fluid type as
summarized in the following table.
10.1 GENERAL
Proving systems shall be designed and installed in accordance with one or more of the
following:
a) API MPMS 4.1
b) API MPMS 4.2
c) API MPMS 4.5
d) API MPMS 4.6
10.2 PROVERS
10.2.1 Prover selection
For applications requiring in-situ validations, ball or sphere type provers or displacement
provers with a captive piston type displacer and external switches (i.e., captive displacer
provers) shall be utilized. Piston provers shall not be utilized.
NOTE: Provers with a captive piston type displacer and external switches were formerly referred to as small
volume or ballstic provers.
Where practical and when field proven for similar applications, captive displacement type
provers should be utilized.
For multipath ultrasonic meter applications where a captive displacer prover has been
selected, master meter proving shall be utilized.
10.2.2 Prover sizing
Provers shall be sized so that:
• operating velocity falls within permitted range,
• required repeatability can be achieved,
• sufficient pre-run is provided so the 4 way valve, interchange valve, or poppet valve
can seat properly before displacer reaches first switch.
For PD and turbine meter applications without pulse interpolation, 10,000 unaltered whole
pulses per pass are required. For design purposes for PD and turbine meter applications
which utilize pulse interpolation, at least 900 unaltered whole pulses per pass are required.
The actual number of pulses collected per run during prover operation is not restricted with
pulse interpolation provided the required repeatability can be achieved.
For some Coriolis meter applications, the maximum operating flow rate of captive displacer
provers must be reduced to achieve target repeatability. In such cases, the meter and
prover Manufacturers shall be consulted.
Provers shall be designed to operate within the following displacer velocity ranges:
• For bi-directional sphere provers, the sphere velocity shall operate between 0.15 m/s
and 1.5 m/s (0.5 ft/s and 5.0 ft/s).
• For unidirectional sphere provers, the sphere velocity shall operate between
0.15 m/s and 3 m/s (0.5 ft/s and 10.0 ft/s).
• For captive displacer provers, the piston velocity shall operate within the
manufacturer’s recommendations.
For ease of water draw calibration, sphere provers should be designed to 200 litre (50 US
3
gal) increments, within 1000 ml (50 in ).
10.2.3 Prover fabrication
Pipe provers shall be designed and fabricated in accordance with the following
requirements:
a) The prover pre-run and calibrated sections shall be fabricated with seamless pipe.
b) All weld surfaces in the pre-run and calibrated sections shall be ground smooth and
flush with the internal pipe surfaces.
c) The calibrated section shall be without side connections or taps.
d) Flanges shall be provided in the calibrated section for full visual inspection of the
internal coating and surface.
e) Flanges in the calibrated section shall be machine-matched bored, centered, and
pinned or suitably designed to ensure alignment. Alignment pins, where required,
shall be uniquely arranged to prevent incorrect mating of flanges.
Sphere provers shall have two detector switches at each end of the calibrated volume in
order to prevent the loss of the prover function in case of a faulty detector switch.
NOTE: The use of two pairs of detector switches requires that two water draw volumes be established during
prover calibrations.
Detector switches shall be the non-adjustable type and shall be equipped with wire seals.
Temperature and pressure measurements shall be provided in the inlet and outlet sections
of the prover for use during proving. See (7.2) and (7.3).
In addition to the prover system valving requirements detailed in (3.15.3), the following shall
be provided:
• Vent valves at the highest point of the prover piping outside of the pre-run and
calibrated sections to assure that air or vapour is completely vented before proving.
• Drain valves on the receive chamber upstream and downstream of the eccentric
reducer (both outside calibrated section) to allow the prover to be drained without the
sphere being drawn back into the prover pipe work due to drainage suction pressure.
• 50 mm (2 in) or greater water draw connections. For bi-directional provers, the
connections shall be located between the 4-way valve flanges and the prover
chambers.
• Stainless steel spectacle blinds shall be located between the four-way valve and
water draw connections.
The prover 4-way or interchange valve shall have sufficient torque for positive sealing
during operation at maximum flow rate. This shall occur before the displacer actuates the
first detector switch.
The prover 4-way or interchange valve shall be equipped with a means at the valve to allow
visual verification of sealing. Indicating differential pressure transmitters should be used for
this purpose.
A quick-opening closure equipped with a pressure actuated locking device shall be
provided for sphere loading and unloading.
The launching and receiving chambers shall be designed (angled) to accelerate and
decelerate the sphere without damage to the sphere or prover. The chamber angle shall
be such that the sphere can be removed without having to drain the complete prover.
Guide bars or tees should be carefully designed to avoid damage to spheres. Appropriate
access shall be provided for sphere removal and replacement. For ball provers > 250 mm
(10 in), sphere removal piping orientation shall provide for:
a) the weight of the sphere,
b) the access level of the sphere relative to operator access
c) the means of removing the sphere (hoisting arrangements, etc.);
d) the suitability of the letdown area;
e) depressuring, decontamination and handling considerations, and the layout of the
immediate area (noting that sphere removal can be a messy activity);
f) isolation (e.g., double block and bleed facilities, blinding), depressuring, and lock-out
tagging. The need for protective functions may have to be addressed in some
circumstances.
Transition reducers located between the launching and receiving chambers and the
calibrated section or pre-run shall be the eccentric type and oriented to provide a flat invert
in the transition section for horizontal positioned launch chambers.
Carbon steel provers shall be internally coated.
The internal coating of the prover shall have a uniform bore and a durable and smooth
surface. The Manufacturer shall provide full details of the coating, maximum allowable fluid
temperature and methods of surface preparation, application, and repair. The lining shall be
non-porous and not prone to explosive decompression.
For general applications, an acceptable epoxy phenolic type internal coating approved by
the Principal shall be applied by the coating Manufacturer or an approved applicator. The
internal coating shall be applied with a minimum of 3 coats, be free of grooves, and have a
final thickness of 5-9 mils (127-229 µm).
Designs intended to utilize a portable prover or master meter shall make provision for the
following:
• adequate and safe access
• appropriate drain connections,
• spill containment
• wiring meter pulse output and meter run temperature, pressure and density to a
location adjacent to the portable or master meter prover location terminating in a
quick connect plug suitable for the hazardous area classification.
Prover seals and sphere material to be carefully selected according to the process
conditions (temperature, viscosity, etc.). Advice from the sphere/prover Manufacturer shall
be sought accordingly.
Sphere provers shall be provided with the following:
• sphere inflation tools
• sphere measurement tools (tape, not sizing ring)
• sphere retraction tools
• spare sphere
• sphere storage net
Captive displacer provers shall be provided with a leak detection kit.
Prover shall include a legible, permanently affixed tag identifying the following information:
• Manufacturer
• Serial number
• Original base (calibrated) volume(s)
• Pipe outside diameter and wall thickness
• Original calibration date
• Material
With the approval of the Principal, the master meter may be applied in a “Z” configuration
(Appendix F).
11. SAMPLING
11.1 GENERAL
Manual liquid sampling systems (excluding LNG) shall be selected, sized, calibrated and
operated to meet the requirements of:
• API MPMS 8.1, (ANSI/ASTM D4177) - recommended, or,
• ISO 3170.
Automated sampling systems (excluding LNG) shall be selected, sized, calibrated and
operated to meet the requirements of:
• API MPMS 8.2, (ANSI/ASTM D4177) - recommended, or,
• ISO 3171.
For manual sampling systems where water content is the component of interest, the static
mixer requirements of API MPMS 8.2 apply.
Automatic sampling systems for crude oil applications should be designed so that the
sample extractor is inserted into the process line (i.e., sample bypass loops should not be
utilized).
11.2 LNG
LNG sampling shall be as per ISO 8943.
LNG sampling shall meet the requirements as detailed in The GIIGNL LNG Custody
Transfer Handbook. Once the LNG has been re-gasified according to this standard, the
sample transport and sample conditioning facilities shall comply with
DEP 32.31.50.10-Gen.
12.1 GENERAL
All measurement systems installations shall be thoroughly checked and functionally tested
prior to shipment of the packaged unit. Examinations and/or tests may be reviewed
and/or witnessed by the Principal or their authorized agent at the Manufacturer's or the
Supplier’s facility as stated in the purchase order. The appropriate authority may wish to
approve the equipment design and witness calibration tests.
The Manufacturer/Supplier shall contact the Principal at the agreed schedule, i.e., six
weeks before the package delivery date, to schedule a factory acceptance test (FAT) that
will be witnessed by the Principal. The Manufacturer/Supplier shall submit a test procedure
to the Principal for approval six weeks prior to the FAT.
For provers and meters which require in-situ calibration at the Manufacturer’s facility or an
approved independent calibration facility, the Manufacturer/Supplier shall contact the
Principal at the agreed schedule, i.e., six weeks before the meter/prover calibration date, to
provide the opportunity for witnessing of the meter and or prover calibration by the Principal
and where required by the local authority.
The FAT procedure should test all power distribution, grounding, wiring, instrument
installation, calibration and control/measurement system configuration, functionality and
interfaces. The procedure shall include a means of documenting the results of each step of
the test, with space for approval signatures.
The Manufacturer/Supplier shall perform the test in accordance with the procedure, and
then correct any problems that are revealed by the test prior to sending to site.
If off-skid equipment is part of the package, then it shall be temporarily wired to the junction
box on the skid for integrated testing. All connections shall be marked and tagged,
complete with installation instructions and drawings.
The Manufacturer/Supplier shall furnish all drawings, power supplies, computers, HMIs,
wiring harnesses, meters, displays and other equipment required to perform a thorough
test.
FAT wet tests using the process fluid or a suitable substitute and FAT heat soak tests shall
only be required by exception and then only with the approval of the Principal. Skids
destined for off shore applications may require wet tests as part of the FAT.
12.2 SKID
The skid shall be inspected for compliance as follows:
• Layout drawing dimensional agreement,
• General quality of workmanship,
• Equipment access for maintenance and validation.
12.3 INSTRUMENTATION
12.3.1 General
All Instruments shall be inspected, tested and calibrated as per the Manufacturer’s quality
assurance process.
Although not specifically defined as part of the Process Automation Systems (PAS),
custody transfer measurement systems shall be inspected and tested in accordance with
DEP 62.10.08.11-Gen. and the requirements of this Section.
12.3.2 Meters
In addition to the Manufacturer’s standard calibrations, custody transfer meters shall be
factory or flow loop calibrated as required as per DEP 32.32.00.94-Gen. Meter calibrations
for applications without provision for in-situ proving shall be witnessed by the Principal or a
representative.
As part of the inspection procedure, the upstream and downstream straight run piping
lengths and quality shall be confirmed.
12.3.3 Provers
Provers, excluding captive displacer provers, shall be inspected prior to assembly. All
provers shall be water drawn at the Manufacturer’s facility prior to shipment. The
inspection and water draw shall be witnessed as detailed in DEP 32.32.00.94-Gen.
12.3.4 Samplers
For crude oil applications, the sampler system performance test shall be performed after
commissioning under the direction of the sampler Manufacturer, suitable consultant or
Principal’s measurement specialist. This test shall be witnessed as detailed in
DEP 32.32.00.94-Gen.
12.3.5 QMIs
QMIs shall be factory tested at the QMI Manufacturer’s facility. As part of the skid FAT,
testing shall be limited to a dry test without process fluids to confirm correct power and
signal wiring, outputs, fault indicators, etc. The QMI system performance test shall be
performed after commissioning.
12.3.6 Computational devices
Tests of computation devices shall include, but not be limited to the following:
a) Verification of proper configuration of computational devices,
12.5 ELECTRICAL
Custody transfer measurement systems/skids intended for use outside of North America
shall be tested and inspected as per DEP 63.10.08.11-Gen. and for those systems/skids
intended for use inside North America as per DEP 63.10.08.14-Gen.
Individual pieces of equipment (e.g., provers, meters, valves) and skid packages shall
be prepared for shipment by the Manufacturer/Supplier as follows:
a) Package shall be de-pressurized, drained or blown dry of any hazardous material
and/or water prior to shipment.
b) All connection points shall be appropriately tagged.
c) Any vent lines that are capped and/or sealed for shipping shall be flagged for
removal prior to service.
d) Threaded and tube openings shall be sealed and plugged with suitable protectors to
prevent damage to threads or tubing and prevent the ingress of dirt or packing
material.
e) Flange faces, where applicable, shall be coated with a suitable rust preventative and
shall be protected with wood or plastic flange covers, securely bolted to the flange.
f) Panel and shelter exhaust vents and air intakes shall be covered with appropriately
secured plastic.
g) Fragile or sensitive pieces of equipment shall be removed and packaged separately.
h) Ancillary devices shall be crated or boxed, at the Supplier’s discretion unless
specified on the data sheets, in such a fashion to preclude, within reason, damage in
transit.
i) Documents, tags or instructions necessary for proper unpacking and protection after
unpacking shall be enclosed and their location marked on the outer covering.
14. DOCUMENTATION
14.1 GENERAL
All drawings, manuals, datasheets shall be provided, as a minimum, in native electronic
format as specified by the Principal. Other formats and the quantity of electronic and
hardcopy copies shall be defined by the Principal for each project.
Approval of drawings by the Principal does not release the Contractor, Manufacturer or
Supplier from the responsibility for proper design, fabrication and functioning of the
equipment and systems provided.
All preliminary drawings and data sheets shall be as built (i.e., updated to reflect as
supplied condition).
Instrument data sheets shall utilize the Principal’s format or a format approval by the
Principal.
15. REFERENCES
In this DEP, reference is made to the following publications:
NOTES: 1. Unless specifically designated by date, the latest edition of each publication shall be used,
together with any amendments/supplements/revisions thereto.
2. The DEPs and most referenced external standards are available to Shell staff on the SWW (Shell
Wide Web) at http://sww.shell.com/standards/.
3. The latest edition of Standard Drawings can be found in DEP 00.00.06.06-Gen.
Amendment A01
SHELL STANDARDS
DEP feedback form DEP 00.00.05.80-Gen.
Standard drawings index DEP 00.00.06.06-Gen.
The use of SI quantities and units (endorsement of ISO/IEC 80000) DEP 00.00.20.10-Gen.
Equipment in LPG Installations DEP 30.06.10.11-Gen.
Protective coatings for onshore facilities DEP 30.48.00.31-Gen.
Loading facilities for bulk road vehicles DEP 31.06.11.11-Gen.
Piping classes - Basis of design DEP 31.38.01.10-Gen.
Piping - General requirements DEP 31.38.01.11-Gen.
Piping classes – Refining and chemicals DEP 31.38.01.12-Gen.
Piping classes – Exploration and production DEP 31.38.01.15-Gen.
Shop and field fabrication of piping DEP 31.38.01.31-Gen.
Fiscal and sales allocation models for Upstream production systems DEP 32.00.00.12-Gen.
Process control domain – Enterprise industrial automation DEP 32.01.20.12-Gen.
information technology and security
Process control domain - Security requirements for suppliers DEP 32.01.23.17-Gen.
Instruments for measurement and control DEP 32.31.00.32-Gen.
Instrumentation for equipment packages DEP 32.31.09.31-Gen.
On-line process analysers DEP 32.31.50.10-Gen.
Analyser housing DEP 32.31.50.13-Gen.
Liquid custody transfer metering system (requisition sheet) DEP 32.32.00.94-Gen.
Control valves - Selection, sizing, and specification DEP 32.36.01.17-Gen.
Static DC uninterruptible power supply (DC UPS) units DEP 33.65.50.31-Gen.
Static A.C. uninterruptible power supply unit (static A.C. UPS unit) DEP 33.65.50.32-Gen.
Vertical storage tanks – Selection design and construction DEP 34.51.01.31-Gen.
(amendments/supplements to EN14015)
Selection of materials for life cycle performance (Upstream facilities) - DEP 39.01.10.11-Gen.
Materials selection process
Inspection and functional testing of instruments DEP 62.10.08.11-Gen.
Field commissioning of electrical installations and equipment DEP 63.10.08.11-Gen.
Field commissioning and testing of electrical installations and DEP 63.10.08.14-Gen.
equipment for North American application
Spare parts DEP 70.10.90.11-Gen.
Design of pressure relief, flare and vent systems DEP 80.45.10.10-Gen.
STANDARD DRAWINGS
Flanged thermowell DN 40 (NPS 1-1/2), ASME classes up to 1500 S 38.113
incl.
AMERICAN STANDARDS
Orifice metering of natural gas and other related hydrocarbon fluids, AGA Report No. 3, Part 2
Part 2 - Specification and installation requirements
Natural gas energy measurement AGA Report No. 5
Standard Guide for Petroleum Measurement Tables Petroleum ANSI/ASTM D1250, Vol. I
Measurement Tables Volume Correction Factors, Volume I
Table 5A and Table 6A
Standard Guide for Petroleum Measurement Tables Petroleum ANSI/ASTM D1250, Vol. II
Measurement Tables Volume Correction Factors, Volume II
Table 5B and Table 6B
Standard Guide for Petroleum Measurement Tables Petroleum ANSI/ASTM D1250, Vol. III
Measurement Tables Volume Correction Factors
Volume III - Table 6C
Addendum to Volume III - Table 6C/IX - Table 54C Volume
Correction-MTBE)
Standard Guide for Petroleum Measurement Tables, Petroleum ANSI/ASTM D1250, Vol. IV
Measurement Tables Volume Correction Factors, Volume IV
Table 23A and Table 24A
Standard Guide for Petroleum Measurement Tables, Petroleum ANSI/ASTM D1250, Vol. V
Measurement Tables Volume Correction Factors, Volume V
Table 23B and Table 24B
Standard Guide for Petroleum Measurement Tables, Petroleum ANSI/ASTM D1250, Vol. VI
Measurement Tables Volume Correction Factors, Volume VI
Table 24C
Standard Guide for Petroleum Measurement Tables, Petroleum ANSI/ASTM D1250,
Measurement Tables Volume Correction Factors, Volume VII Vol. VII
Table 53A and Table 54A
Standard Guide for Petroleum Measurement Tables, Petroleum ANSI/ASTM D1250,
Measurement Tables Volume Correction Factors, Volume VIII Vol. VIII
Table 53B and Table 54B
Standard Guide for Petroleum Measurement Tables, Petroleum ANSI/ASTM D1250, Vol. IX
Measurement Tables Volume Correction Factors, Volume IX
Table 54C
Standard Guide for Petroleum Measurement Tables, Petroleum ANSI/ASTM D1250,
Measurement Tables Volume Correction Factors, Volume XI/XII Vol. XI/XIII
Tables 1-4, 8-14, 21,22,26-31, 33, 34, 51, 56-58
Standard Guide for Petroleum Measurement Tables, Petroleum ANSI/ASTM D1250,
Measurement Tables Volume Correction Factors, Volume XIII Vol. XIII
Table 5D and Table 6D
GERMAN STANDARDS
Standardization of the signal level for the failure information of digital NAMUR NE-43
transmitters
Issued by: NAMUR Geschäftsstelle
INTERNATIONAL STANDARDS
GIIGNL LNG Custody Transfer Handbook GIIGNL
Issued by: International Group of Liquefied Natural Gas Importers – Paris, France
Automatic level gauges for measuring the level of liquid in fixed OIML R85
storage tanks Part 1: Metrological and technical requirements – Tests
Dynamic measuring systems for liquids other than water OIML R117
Issued by: International Organization of Legal Metrology or Organisation
Internationale de Métrologie Légale
A.1.8 The system of all measurements, the type of instruments used, the use of derived
measurement values instead of direct measurements, the procedures for maintenance and
calibration, the methods and criteria by which measurement corrections will be made and
other items relevant to the measurement of the (insert fluid name(s)) at the Delivery Point
shall be mutually agreed upon between Sellers and Buyer and shall be specified in a
Measurement Manual.
A.1.9 A draft of the Measurement Manual shall be prepared prior to start-up. Within a period of 3
months after start-up of the measuring station at the Delivery Point, the Measurement
Manual shall be finalized, reviewed and approved by appropriate parties. This Manual shall
specify the detailed methods and instruments for measuring and/or calculating the quantity,
composition and physical properties of the (fluid) delivered, the calibration and maintenance
procedures and the inaccuracies of the instruments.
Matters not fully provided for in this DEP shall be dealt with in accordance with the relevant
local regulations, as provided for in this Sales Agreement or as mutually agreed upon by
the Parties.
A.2.2 The volume delivered at the Delivery Point shall be calculated on a continuous basis from
the delivered flow measured on-line determined according to (A.1.5). The calculation
method shall be specified in the Measurement Manual.
A.2.3 The delivered quantity of the [fluid] shall be measured and calculated in accordance with
DEP 32.32.00.11-Gen.
A.2.4 Buyer's visits to the measuring station at the Delivery Point, the calibrations and checks of
the measuring instruments and the procedures for dealing with improper measurements or
incorrect operation of the instrumentation shall all be in accordance with the Measurement
Manual.
A.2.5 Buyer is entitled at its sole risk and expense to connect a telemetering system to Seller’s
measurement system at the Delivery Point. Signals to be transferred shall be mutually
agreed.
A.2.6 At the request of Buyer, Sellers shall make available to Buyer at the Delivery Point the flow,
pressure and temperature signals measured at the Delivery Point and, at Buyer's request
the fluid density measurement signals for on-line transfer via Buyer's telemetering system.
The inclusion of any other quality factor(s) of the [fluid] than those specified in the contract
is subject to mutual agreement between Sellers and Buyer. Buyer is allowed to witness the
calibration of any part of the measurement system that affects the measurement signals
that have been made available.
A.2.7 Sellers shall give at least forty-eight (48) hours' notice to Buyer of regular sampling
(referred to in (A.1.7)) of [fluid] at the Delivery Point for determination by laboratory analysis
of the composition and physical properties of the [fluid]. Buyer and Sellers shall mutually
agree upon the frequency or change of frequency of regular sampling. Buyer may request,
with reasons given, spot samples of the [fluid] at the Delivery Point, and Sellers shall inform
Buyer of the time of sampling. The regular and spot samples will be collected by the
appropriate technique according to ISO 3170 or ISO 3171. Parties may agree on other
methods if more appropriate in view of all prevailing circumstances.
The analysis shall include the composition and physical properties of the [fluid] as specified
in the contract, unless Buyer and Sellers agree otherwise. Sellers shall inform Buyer of all
results of all determinations by Sellers of the composition and physical properties of the
regular samples. Buyer shall have the right to be represented to witness the sampling and
to verify that the composition and physical properties are determined in accordance with the
standards specified in (A.1.5). Should Buyer, although notified, not be represented, the
sampling and determination by Sellers shall be considered valid until the following sampling
and determination.
Buyer's facilities and for Buyer to fulfil its obligations under the [fluid] Sales
Agreement;
3. Under no circumstances shall Sellers agree with Buyer that agreed measurement
signals from Sellers' production location(s) will be used for monitoring of contract
limits.
Signals of measurements at the outlet of Sellers' production location(s):
a) At the request of Buyer, Sellers shall make available to Buyers at the Delivery Point
the flow, temperature and pressure measurement signals at the outlet of Sellers'
production location(s) for on-line transfer via Buyer's telemetering system.
b) At the request of Buyer, Sellers shall make available to Buyer at the Delivery Point
the requested signals of installed quality measurements at the production location(s)
for on-line transfer via Buyer's telemetering system.
c) If, in Buyer's opinion, not yet installed quality measurements at Sellers' production
location(s) are necessary for the proper operation of Buyer's facilities and for Buyer
to fulfil its obligations under the Agreement, then Buyer and Sellers shall jointly
decide on the installation of any such measuring equipment. Before implementing
such additional measurements, Parties shall agree to what extent each Party shall
bear the cost of such additional measurement(s) in view of their respective
obligations under the Agreement. Sellers shall not unreasonably withhold their
concurrence with Buyer's request unreasonably.
d) Buyer shall be allowed to witness the calibration of any part of the measurement
system at the production location that affects agreed measurement signals to Buyer.
FLOW COMPUTER
TT
FT TE TW PT 9 AT SP
DP
AE FC FE SM
1 2 3 4 5 6 7 8 10 11 12 13 14 15
Components: Notes:
1) Air Eliminator (AE) 1) Schematic is generic in nature and therefore all elements may not be required for a specific application.
2) Strainer with pressure loss monitor (DP) For example, for a mass measurement application using a coriolis meter, the strainer, flow conditioner,
3) Upstream straight length or flow conditioner (FC) pressure, temperature and density transmitters are not required.
4) Meter (FT) 2) Air eliminator is mandatory for truck and marine unloading applications but typically not required for pipeline
5) Downstream straight lengths applications.
6) Temperature element/transmitter (TE,TT) 3) Strainer required for most but not all meter types.
7) Valida ion thermowell (TW) 4) Upstream and downstream meter straight length requirement varies with meter type and upstream piping
8) Pressure transmitter (if required) (PT) disturbances.
9) Prover valves 5) Flow transmitter (FT) may be close coupled to flow sensor (FE) or remote mounted.
10) Double block and bleed prover divert valve 6) Analyzers are typically water cut monitors or densitometers.
11) Static mixer (if required) (SM) 7) No components such as analyzer fast loops or pressure relief valves should be between meter and prover
12) Analyzer (e.g., water cut, densitometer) (AT) taps.
13) Sample point (manual or on-line) (SP) 9) Pressure relief valves should be located to preclude unmeasured fluids via a leaky relief valve.
14) Flow control valve 10) Static mixer may be required upstream of sample point and/or analyzer.
15) Check valve 11) Spacer plate installed downstream of meter downstream straight length requirement to be utilized to
Rev. 9 facilitate disassembly of meter run.
FC FC FC
FE FT FE FT FE FT
TT TT TT
TW TW TW
PT PT PT
Pipe
Prover
or
Master
Meter
SP AT
FT TT TW PT
FE
FC
FT TT TW PT
FE
FC
LEGEND
L3 TCP/IP Ethernet
4 - 20 mA signal
& HART capability
Process Control Network RS-232
RS-485 Modbus
Differential pressure
L2 TCP/IP Ethernet
FIT
Lxx transmitter low range
PIT
Pressure transmitter
Moxa A Moxa B
Fiscal Measurement Network x
QT
Density transmitter
x
FC FC FC FC
Run 1A Run 1B Run 2A Run 2B
RS485/RS232
Printer Printer
Convertor
Switch Switch
FIT FIT
H1 H3
Chromatograph
Chromatograph
FIT Ticket FIT Ticket
H2 Printer H4 Printer
Gas
Gas
1
2
FIT FIT
PIT TIT PIT TIT
L1 L3
2 2 4 4
FIT PIT TIT QT FIT PIT TIT QT
L2 1 1 1 L4 3 3 2
Run 1 Run 2
Common header
Figure G.1 Dual run liquid orifice mass metering station with full redundancy
EXTERNAL
VENDORS BUSINESS
INTERNET USERS
Domain
Office
INTERNAL BUSINESS
TPA
HISTORIAN USERS &
SERVER
APPLICATIONS
L4 Office Network
TCP/IP Ethernet
Mirror image
Process Control
Access Domain
PCDP Note:
HISTORIAN PCAD
Process Control Domain
Portal
CCR
DCS
Process Control
Domain
The resolution of values presented on the visual display shall be sufficient to verify the
calculation accuracy.
It shall be possible to read the digital signal from the A/D converter as an
unscaled/uncompensated value, presented in a binary, hexadecimal or decimal form.
It shall be possible to read the pulses received from a meter directly (pulse transmission
check).
Flow computers shall accept the fault status of input devices but need not duplicate the
diagnostic functions of fit-for-purpose software associated with these devices.
Full documentation of the flow computer software shall be available providing the functional
design and the implementation of the package (e.g., for audit purposes).
The total error of the analogue to digital converter of the flow computer, including
resolution, linearity, repeatability and other random errors, shall not exceed ± 0.02 %.
Algorithm and unintentional rounding-off errors for computations of custody transfer
quantities in the flow computer shall be less than ± 0.001 %.
The flow computer shall be housed in accordance with the Manufacturer's
recommendations with respect to environmental conditions (temperature, vibration, etc.).
The flow computer firmware shall be subject to a regime of version control and be
identifiable by a unique version number.
The serial data transmission links shall be continuously monitored and an alarm generated
if faults are detected. The supervisory computer should be equipped with watchdog
functionality to monitor the performance of data transfer between flow computer and
supervisory computer.
The custody transfer computing system shall have sufficient communication capability for
recording devices and alarm printers where required by legislation.
The flow computer shall provide ample recording and logging functions through a secure
communication facility to other systems (e.g., transmission of hourly or daily reports). The
following functions shall be provided by the flow computer system (if applicable):
a) storage of accumulated custody transfer quantities for each metering run and the
total metering system and an option to print these quantities;
b) alarm reports;
c) change logs,
d) monthly storage of measured parameters and accumulated quantities for each
metering run. An option to print-out such data;
e) communication facilities via VDU, printer and terminal.
The custody transfer supervisory computer shall, for each meter run, automatically log and
store at intervals of 1 h and 24 h: cumulative applicable quantities of mass, volume and
energy, and average values of pressure, temperature and density.
The retention time for storing these data shall comply with local regulations or the contract,
whichever is the longer.
The metering system shall be powered by an uninterruptible power supply (UPS); refer to
DEP 33.65.50.31-Gen. and DEP 33.65.50.32-Gen. Failure of the normal power supply and
UPS fault status shall be monitored and alarmed by the flow computer.
Additional back-up facilities in each computer shall ensure that custody transfer data are
not lost under any circumstances.
The flow computer response to changes of the metering system's secondary input signals
shall not be greater than 1 s.
The custody transfer measurement system shall be connected to the Process Control
Network (PCN) via the supervisory computer. There shall be no other connections between
the Custody Transfer Measurement Network and the Process Control Network.
The Supervisory computer shall include the capability (e.g., an OPC (OLE for Process
Control) server) to send the data to and from the data historian. The data historian shall be
the only location where users can get access to the custody transfer data.
Internal business users and applications shall not be able to directly access the supervisory
or custody transfer flow computers.
External business users, e.g., contract partners, shall only be able to access metering data
as remote users under a Third Party Access (TPA) agreement.
Manufacturers/Suppliers shall be able to access the Custody Transfer Measurement
Network for diagnostics and repairs only via a thin client in the Process Control Domain.
No modems shall be connected to the metering hardware and instrumentation.
Control and automation (C&A) maintainers shall be allowed access to the Custody Transfer
Measurement Network and hardware. The use of laptops and portable media shall be in
strict compliance with general PCD security requirements as per DEP 32.01.20.12-Gen.