Distance protection principles


an

SIPROTEC5 - Application and exercises of system protection


ef
st

21
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
om
Contents

.c
ad
■ Short circuit

ip
■ Distance measurement (principle)
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

@
■ All you need is X

ci
Load- and short circuit impedance

vi

no

om
■ Pickup
fa

.c
Directional measurement

e

ad
st
■ Guideline for zone 1 setting

ip
Redundancy

i@
■ Signal transmission
ic
ov
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 2
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Short Circuit

om
.c
ad
Example

ip
Single phase diagram of 3 phase system, only X considered
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

i@
■ Source VN (L-L) = 20 kV, Ik = 5,77 kA
■ Line 1 4 km zu 0,5 Ω/km

ic
■ Line 2 33% of 3km at 0,5 Ω/km

ov

om
■ What is the short circuit current?

an

.c
■ Which voltages can be measured at the busbars?
ef

ad
st
XSource Xline1 k·Xline2

ip
VSource
ISC ISC
@
ci
vi
no

ISC = VS/(Xsource+Xline1+k·Xline2)
a
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 3
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Short Circuit

om
.c
ad
VLG = 11.54kV 0kV

ip
2Ω 2Ω 0.5Ω 1Ω
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

i@
ic
ov

om
VLG = 2.56kA∙(2Ω +0.5Ω) VLG = 2.56kA∙0.5Ω 2.56kA
an

.c
= 6.4kV = 1.28kV
ef

ad
st

ip
Xmeas = 2.5Ω Xmeas = 0.5Ω

XSet = 2Ω i@ XSet = 1.5Ω


ic
ov

=> No Trip => Trip


an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 4
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance measurement (principle phase- phase)

om
.c
ad
IL1 ZL

ip
ZL = RL + j XL
IL2
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

i@
ZE = RE +j XE
IL3

ic
ov

om
IE ZE

an

.c
UL1 UL2 UL3
ef

ad
st
6 loops: 3 phase- phase loops and

ip
3 phase- ground loops

phase- phase- loop @ UL1-L2 = ZL ( IL1 - IL2)


ci
vi
no

Measured current
measured voltage
a
ef

The same applies to the remaining loops


st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 5
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
om
Distance measurement (principle phase- ground)

.c
ad
IL1 ZL

ip
ZL = RL + j XL

i@
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

IL2
ZE = RE +j XE

ic
IL3

ov
Phase- ground- loop

om
IE ZE

an
ef UL1 = IL1 · ZL - IE · ZE

.c
UL1 UL2 UL3
st

ad
IL1, IE measured current

ip
This equation cannot be solved! Measured voltage

Thus ZE/ZL is used as setting value

XE/XL = 1/3 * (X0/XL – 1)


i @ The same applies to the
ic
remaining loops
ov

RE/RL = 1/3 * (R0/RL – 1)


an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 6
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Zero sequence impedance for cables

om
.c
ad
The zero sequence impedance for a cable is hardly to be calculated

ip
• Z0 depends on enviroment conditions such as:
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

i@
• Other parallel cables, pipelines, rails etc.

ic
• At cables with steel band, Z0 depends on actual current flowing

ov

om
• Magnatizing of steel band

an

.c
ef

ad
st
For correct values:

ip
Z0 should be measured on site at the cables!

i @
ic
ov
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 7
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
om
All you need is X

.c
ad
■ The magnitude of the impedance is

ip
simply calculated from the
magnitudes of current and voltage
X

i@
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

■ Reaktance und resistance were then

ic
calculated by angle measurement,

ov
which can be critical

om
an
■ Errors in this angle measurement will ef

.c
lead to big errors in R but only small

ad
st
errors in X

ip
■ Therefor only X is used for distance
measurement i@
ic
ov

R
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 8
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Typical values for overhead lines and cables

om
.c
ad
R’L1 X’L1 jL1 R’L0 X’L0 jL0 R’LE X’LE R’LE/ X’LE/

ip
R’L1 X’L1
W/km W/km o el. W/km W/km o el. W/km W/km

i@
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

Overheadline 380 kV
earthing wire 0,018 0,25 86 0,17 0,94 80 0,053 0,23 2,94 0,92
4-times bundle

ic
4´Al/St 435/55

ov
Overheadline 220 kV
earthing wire 0,058 0,30 79 0,22 0,99 77 0,053 0,23 0,91 0,77
2-times bundle

an

om
2´Al/St 265/35
Overheadline 110 kV
earthing wire 0,071 ef 0,38 79 0,22 1,10 79 0,050 0,24 0,70 0,63

.c
Al/St 435/35
st

ad
Overheadline 20 kV
Without earthing wire 0,31 0,37 50 0,53 1,58 71 0,073 0,40 0,24 1,08

ip
95 mm2 Al
cable 400 kV
Single phase-oil isol.
Cable 3´1´1200 mm2 Cu
Cable110 kV
0,020 0,22 85 i @
0,049 0,11 66 0,01 -0,036 0,50 -0,16
ic
Gas pressure cablle 0,090 0,14 57 0,39 0,16 22 0,1 0,007 1,11 0,05
ov

40 mm2 Cu
Cable 20 kV
an

3-phase lead isolated 0,16 0,12 37 1,4 0,25 10 0,41 0,043 3,42 0,36
3´120 mm2 Cu
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 9
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Electromechanicle Relay R1Z23a

om
(application for high voltage feeder)

.c
ad
Electromechanicle

ip
relays only provides

i@
circle diagrams
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

I> pickup

ic
L1, L2, L3, M

ov
an

om
Time
measurement
ef Alarm
indications

.c
ZL
st
X

ad
circle

ip
Moving coil relay RLB
i@ D: Distance
N: Direction
R
ic
ov
an

direction
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 10
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
om
Load and short circuit impedance

.c
ad
ip
i@
X
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

Short circuit range


ZL

ic
Distance protection characteristic

ov
ZLF2 RF ZF2

an
ZL
ZLoad ZLF1

om
ZLF1 RF
ef ZLF2
st
ZF1

.c
RF RF ZLoad
jL

ad
j F1 F2
jSC1 SC2
D

ip
R

Short circuit i@
in
reverse
Load
range
ic
direction
ov
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 11
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance protection: Adaptive measuring method

om
.c
ad
n Least Square estimator with

ip
variance control
n Adaptive Zone reach

i@
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

ic
Z1

ov
an

om
ef

.c
st
Estimator 1 (n=5)

ad
Estimator 2 (n=6)
Estimator 3 (n=8)

ip
Estimator 4 (n=10)
Estimator 5 (n=13)

@
Estimator 6 (n=15)
Normal 1 (n = 21)
Normal 2 (n = 26)
i
Normal 3
ic
0 10 20 30 40 50 60 70 80
ov

Jump detected ms
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 12
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Distance protection,

om
Typical operating time characteristic

.c
ad
ip
30

i@
25
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

Operating time (ms)

ic
20

ov
15

an
10

om
5
ef
st

.c
ad
0
10 20 30 40 50 60 70 80 90 100

ip
Short-circuit data: Fault location in % zone reach
SIR = 26
i@
f = 50 Hz
Fault: L1-E
ic
5 shots per fault case Information: Trip times with high speed contacts
ov

Fault inception: 0° ... 90° approx. 5 ms shorter


extension module IO209 required
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 13
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Zone 1 - Setting guidelines

om
.c
ad
X

ip
Line characteristic
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

i@
X1

ic
Recommendation for Zone 1 settings:
X1 » 80...90% of line reactance

ov

om
0,5 * X < R < 2*X important!

an ● R
1, R1E = half load impedance (if possible)

.c
ef
R1

ad
t1 = 0 ms
st
R1E
R

ip
i@
ic
ov

If the measured impedance is within the set characteristic


an

and the set time has expired, a TRIP command is issued


ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 14
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
om
Redundancy

.c
ad
■ Locale redundancy

ip
■ Z2 for faults of 80% … 100% of the line
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

i@
Remote redundancy

ic

ov
■ Z2 … ZX für

om
breaker fail or protection fail

an

.c
ef
Zones can be added

ad
st
in 7SA8

ip
(function points needed!)
i@
ic
ov
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 15
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Fault detection techniques

om
.c
ad
Over- current fault detection

ip
X
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

Voltage dependant

i@
over- current fault detection

ic
U Voltage and

ov

om
angle dependant
over- current
an

.c
ef fault detection

ad
R
st
Impedance

ip
fault

i@ detection
ic
I> Ij> I >>
ov

I
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 16
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Reach of overcurrent starter
ph-ph fault as an example

om
.c
ad
ISC(2) [kA]
110 kV

ip
2,5 net SCC(3)" = 1500 MVA
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

i@
40 MVA
uT = 15 %
2,0 20 kV

ic

om
ov
400/1 A D I >start = 1,5 · IN = 600 A

an
1,5

.c
UN · 1,1
ISC(2) = ISC

ad
OH-line
ef
2 · (ZS + ZS + ZL' · l) 95/15 Al/St
st
N T
1,0
Z'L = 0,483 W/km

ip
I >start = 600 A
0,5 i@
ic
ov
an

10 20 30 40 50 60 l [km]
reach of OC starter
ef

ca. 35 km
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 17
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Determination of fault direction

om
.c
ad
ip
i@
Current area for
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

Impedance area for


forward faults X forward faults
USC
ISC

ic
ZSC
jSC

ov
jSC

om
an
ef R

.c
st

ad
ISC Z'SC

ip
Current area for Impedance area for
reverse faults
i@ reverse faults
ic
current / voltage diagram
ov

impedance diagram
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 18
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
om
Alternatives for the Directional Measurement

.c
ad
ip
~ ~ ~

i@
~ ~ ~
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

fault L1-E

ic
~ ~ ~

ov
Zgrid Relay Zline

an
VL1
Vf

om
VN
ef If
st

.c
VL3

ad
VL3 VL2 VL2
fault-free VL1

ip
faulty phase voltage
Vf
i@ VN
If If
ic
ov

VL3 VL2 VL3 VL2


Vdir
an

healthy-phase voltage voltage memory


ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 19
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
om
Teleprotection schemes

.c
ad
Why use tele- protection?

ip
i@
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

1 2

ic
ov
an
Faults in this area Faults in this area Faults in this area

om
ef
are cleared after t2
at line end 2
are cleared without additional
time delay at both line ends
are cleared after t2
at line end 1
st

.c
Faults on approximately 70% of the line length are cleared

ad
without delay at both line ends

ip
Faults in the remaining 30% of the line length
are cleared with a time delay.
i@
Remedy: Exchange of information between the two line ends
ic
Required: Communication channel (PLC, microwave radio, fibre optic, etc.)
ov

Tele- protection logic (dedicated device or internal


function in numerical protection devices)
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 20
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
Teleprotection scheme - Permissive Overreach

om
.c
Z1 Z1B or Z2

ad
ip
A B
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

i@
Z1B or Z2
Z1

ic
ov
Trip

om
Trip

an

.c
ef

ad
Trip Z1 and ³1 ³1 Trip Z1 and
st
further zones further zones

ip
@
& &
TS TS
& ³1
i ³1 &
ic
S S
R R
ov

Z1B Z1B
T1B T1B
(A) (B)
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 21
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
om
Teleprotection scheme

.c
ad
What is different in setting of teleprotection system compared to SIPROTEC 4?

ip
SIPROTEC 4 SIPROTEC 5

i@
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

ic
Zone Z1B must be used for Every zone (even more than one) can be

ov
teleprotection schemes used for teleprotection schemes

an
Zone Z1B will trip only, in combination Each zone will trip with the set trip delay

om
with teleprotection schemes ef time
st

.c
Therefore, typical trip time setting is Therefore, typical trip time setting for used

ad
0ms for Z1B teleprotection zone should not be 0ms

ip
i @
ic
ov
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 22
21 SIPROTEC 4 - Application and exercises of system protection
Folienmaster 20130305
File: D:\Schulungen\SIPROTEC5\7SA8\englisch\21_Distance_protection_principles_7SA8_V01.odp
om
Teleprotection scheme

.c
ad
How to set setting of teleprotection system in SIPROTEC 5 similar to SIPROTEC 4?

ip
i@
Kursunterlagen für Igor Stefanovic, stefanovici@ipad.com

•Add new stage


•Rename new stage to Z1B

ic
•Use this zone Z1B for teleprotection scheme

ov
•Set delay time for Z1B stage to oo (infinite)

an

om
ef

.c
st

ad
ip
i@
ic
ov
an
ef
st

Restricted © Siemens AG 2015 All rights reserved. Siemens Power Academy TD Seite 23