You are on page 1of 5

10

A i r Ve n t
V a l v e

183
Air Vent
V a l v e

YAC-3 YAC-3M
YAC-3A YAC-4

10
Air Vent
Valve

Air Vent Valve

Samyang’s air vent valve eliminates air-related problems and prevents pipeline corrosion by
automatically discharging air generated in construction facilitie’s cold/hot water pipelines, water
supply and water heating pipelines, as well as plant’s cold/hot water pipelines and tanks. In
addition, it automatically takes air in when liquid is discharged from pipelines and tanks, thereby
ensuring easy discharge by preventing a creation of a vacuum.

Air Vent Valve


Applicable Applicable Materials
Type Size End connection Page
fluid pressure (MPa) Body Disc, seat

YAC-3 15(1/2“)~25(1”) C3771 NBR, C3604 185


YAC-3A
15(1/2“) Water Maximum 1.0 CAC303 KS PT SCREW 186
YAC-3M EPDM, STS
YAC-4 15(1/2“)~25(1”) GC200 187

184
Air Vent YAC-3 Type Air Vent Valve

V a l v e
YAC-3 Type Air Vent
This is a compact air vent valve that is used for pipelines, hot water boilers, fan coils,
and small- to medium-sized pressure tanks. The adoption of the BBC (Bubble Crush)
method ensures safe operation and prevents water hammers, hunching, etc.

Features
•Bubble Crush(BBC) structure prevent Water Hammers & chattering caused by float in special form
10 distributes rising pressure & bubbles.
•Reliable operation is ensured by spring’s force seat closing.
•Simple & strong structure.
•Compact & outstanding air discharge performance.
•Manual closing device installed on outlet side.
•Manufacture as air vent valve for steam.

Specitications
Type YAC-3
Size 15(½”), 20(¾”), 25(1")
Applicable fluid Cold / hot water
Applicable pressure Maximum 1.0MPa
Fluid temperature 5~100°C
End connection KS PT SCREW
Body C3771
Materials
Disc, seat NBR, C3604
Hydraulic test pressure 1.5MPa
▶ Install a strainer (80 MESH or more) on the leaflet during installation of the valve.

Air discharge volume curve


Maximum consecutive discharge volume (l/h)

Dimensions drawing
Pressure kgf/cm2g

Air discharge volume curve


•When discharging air •When discharge stops
It discharges air that comes in If the water level and float
when the seat is opened by the rises immediately after air
float’s own weight. discharge, the valve closes
by the float’s buoyancy and
spring’s elasticity.
Within 5°
Manual closing cock
Installation example and cautions during handling Plastic tube

•When installing the valve in a pipeline, install it within 5° of a vertical YAC-3


automatic air valve
line.
•When installing the valve indoors, connect the outletside to the
drainage just in case there is leakage.
Gate valve
•Install a manual valve on the inlet side for repair and inspections.
•Close the manual closing cock if there is a leakage.
Pipeline or
pressure tank

185
YAC-3A, 3M Type Air Vent Valve Air Vent

V a l v e
YAC-3A, 3M Type Automatic Air Vent Valve
As an air vent valve for liquid, it automatically discharges remaining air from pipelines and
air from sealed tanks, thereby allowing for smooth flow of fluid.

Features
• Low pressure also operates smoothly.
10
• Disk designs are designed to be free and smooth and sensitive.

• Made for easy repair and inspection.


• Stilleball installation prevents air ingress into the air.

Specitications
Type YAC-3A, 3M
Size 15(½”) YAC-3A Type
Applicable fluid Cold / hot water
Applicable pressure Maximum 1.0MPa
Fluid temperature 5~80°C
End connection e)
KS PTS CREW(Female)
Body CAC303
Materials
Disc, seat EPDM, STS
Hydraulic test pressure 1.5MPa

▶ Install a strainer (40 MESH or more) on the leaflet during installation of the valve.

Air discharge volume curve


Maximum consecutive discharge volume (l/h)

Pressure kgf/cm2g
YAC-3M Type
Dimensions drawing MultI-Function Air Vend
(Air Vend + Strainer + Stone valve)
Installation method and cautionary
measures
1. Install it vertically (within 5˚).
2. When installing indoors, connect the outlet side to
the drainage.
3. Install a manual valve on the inlet side.
4. In case of leakage, close by using the handle.

Measures in case of leakage


1. In case of leakage, close the manual valve on the
lower part of the air vent, open the cap, check
if there are any foreign substances on top of the
disc or seat, wash the foreign substances away, if
any, and then resume normal operation.
2. When reassembling, take caution so that the float
YAC-3A Type YAC-3M Type
is not detached from the press part.
186
Air Vent YAC-4 Type Air Vent Valve

V a l v e
YAC-4 Type Air Vent
As an air vent valve for liquid, it automatically discharges remaining air from pipelines
and air from sealed tanks, thereby allowing for smooth flow of fluid.

Features
• Large discharge capacity covers up to 10~20 kgf/cm2g.
10 • Flexible disc structure for smooth & subtle operation.

• NBR-based seat features outstanding level of air tightness.


• Easy repair & inspections manufactured.

Specitications
Type YAC-4
Size 15(½”), 20(¾”), 25(1")
Applicable fluid Cold / hot water
Applicable pressure Maximum 1.0MPa
Fluid temperature 5~80°C
End connection KS PT SCREW
Body GC200
Materials
Disc, seat STS, EPDM
Hydraulic test pressure 1.5MPa

▶ Install a strainer (40 MESH or more) on the leaflet during installation of the valve.

Dimensions (mm)

Size d A H Weight (kg)


15(½”) ½” 115 153 2.0
20(¾”) ¾” 115 153 2.0
25(1") 1" 115 153 2.2

Dimensions drawing Air discharge volume curve


Maximum consecutive discharge volume (Nm3/h)

1 2 3 4 5 6 7 8 9 10

Pressure (kgf/cm2g)

187

You might also like