Professional Documents
Culture Documents
Air trapped in the system can separator provides air separation while minimizing
produce major problems such space requirements.
as reduced heat transfer, loss
of system efficiency, pipe corro- Taco offers these separators with or without strainers,
sion, pump damage, increased in standard pipe line sizes from 2” to 20” with custom
energy consumption and unit sizes up to 36” pipe size. The wide range of sepa-
irritating noise. The highly rator models have been developed for applications
efficient Taco air separator with flowrates up to 12,500 gpm. This wide range
clears the system of free air and of models allows optimum selections with reduced
reduces un-dissolved sediment pressure drop requirements. The standard product
to save money, energy and is designed for working pressures of 125 psi at 375˚F.
component wear. Unlike many competitive models Optional 150, 250 and 300 psi maximum pressure
each unit is designed, constructed and tested to the units, 375˚F maximum temperature units are also
requirements of Section VIII, Division I of the ASME available. Taco air separators are manufactured from
pressure vessel code as standard. carbon steel listed in ASME Section II. Consult the
factory for higher working pressures, larger sizes or
Designed for use in hydronic heating or cooling non-standard materials of construction.
systems, Taco’s compact, highly efficient air
AIR SEPARATOR
INLET
Baffle forces change in
Water & air flow direction and slows
mixture the velocity, releasing
through the air through the vent.
the inlet.
OUTLET
Return to piping network.
2
Applications
DRAINCOCK
TACO
AIR SEPARATOR
10% Figure 2
8% NAME: FIGURE 8
LOCATION:
6% 90
80
4%
70
60
50
Chiller and Air Separator Location
PSIA
40
2% 30 FAN COIL
20
10
32 50 75 100 125 150 175 200 212
TEMPERATURE (DEGREE F)
Figure 1 TACO
CIRCULATOR
TACO
these points.
UNION
SUCTION
TACO DIFFUSER
MULTI-PURPOSE
VALVE DRAINCOCK
TACO
EXPANSION
CHILLER TANK
Figure 3
4
Applications
In addition, as water is heated from the fill tempera- This fitting directs the air to the top portion of the
ture to the operating temperature, a great deal of tank, and discourages air from migrating back into
air is released. Therefore, the simple act of bringing the system (See Figure 5), when the system cools
the water to operating temperature could lead to on the “off” cycle. Note that since the air is “recycled”
corrosion and air pockets, both of which should be to provide a cushion in the expansion tank,
avoided. this system is called an “Air Control” system.
A method of removing this released air from the pip- Note that the circulator is on the supply side of the
ing system is therefore required. Enter the air separa- boiler. This is the proper location, as it results in the
tor. An air separator is a device that is removes the highest pressure at the top of the system (if the cir-
air from the circulating fluid. culator was on the return side of the boiler, the boiler
pressure drop reduce the pressure at the top.) Having
There are several types of air separators in use today. a higher pressure at the top keeps air in solution, and
Depending upon the type of expansion tank used in helps prevent problems and air binding.
the system, the air separator is part of an Air Control
System or an Air Elimination System.
TANK FITTING
*COLD WATER FILL
TACO TACO
CIRCULATOR FLO-CHEK
18”
TACO
AIR SCOOP
RELIEF
VALVE
BOILER
Figure 4 Figure 5
5
Applications
GATE VALVE
RELIEF
VALVE UNION TACO TACO
AIR SCOOP CIRCULATOR FLO-CHEK
DRAINCOCK WITH VENT
GATE VALVE
UNION
DIAPHRAM TYPE
BOILER EXPANSION TANK DRAINCOCK
Figure 6
TACO DIAPHRAM TYPE
EXPANSION TANK
TACO PRESSURE
REDUCING VALVE
COLD WATER
SUPPLY
6
Applications
DRAINCOCK
are to be installed. These sizes range from 3/4 inch
to 2 inch. TACO DIAPHRAM TYPE
EXPANSION TANK
TACO PRESSURE
VorTech style separators are rated for 150 psi with a REDUCING VALVE
Figure 8
7
Applications
Tangential ASME Air Separators air vents should be installed at the top of each air
Taco Tangential Air Separators are applied in separator. As Air Elimination systems have a per-
commercial, institutional and industrial applications manent separation provided by the bladder or dia-
for the removal of free air in water or water/glycol phragm between the initial tank pre-charge and the
systems. The Tangential design air separators utilize system fluid no loss of pre-charge will occur.
the difference in density to separate free air from
system fluid. (See Taco Catalog# 400-3.1 for additional information.)
drop. Most manufacturers provide a blowdown Air Separator with Captive Air Tank
connection at the bottom of the unit. TACO HY-VENT®
insure that piping between the air vent and the plain TACO
MULTI-PURPOSE
TACO
SUCTION
GATE VALVE
DRAINCOCK
migration of captured air back into the expansion ves- TACO CAPTIVE AIR
sel. Systems with plain steel expansion tanks must not EXPANSION TANK
8
Applications
4900 Series High Efficiency Micro-Bubble These units are designed, built, tested and stamped
Air and Dirt ASME Separator to the requirements ASME Section VIII, Division 1.
Taco 4900 Series High Efficiency Micro-Bubble Air Manufacturers offer micro bubble air and dirt
and Dirt Separators are applied in commercial, insti- separators in working pressures of 125, 150, 250 psi.
tutional and industrial applications for the removal
of free and entrained air. The 4900 Series utilize the When High Efficiency Micro Bubble Air and Dirt
coalescence of micro air bubbles Separators are installed in conventional Air Control
around PALL rings to separate free systems with plain steel expansion tanks (Figure 9)
air from a system fluid. care must be taken to insure that piping between
the air vent and the plain steel tank is pitched at
The 4900 Series incorporates the least 3 degrees to facilitate the migration of captured
highest available coalescence air back in the expansion vessel. Systems with plain
surface area available on the steel expansion tanks must not have automatic vents
market today. This enhanced installed as this will lead to the loss of the expansion
surface area allows the removal tank compression cushion.
of micro-bubbles as small as 15
microns in diameter. The 4900 When High Efficiency Micro Bubble Air and Dirt
Series separators remove up Separators are installed in Air Elimination systems
to 99.6% of the dissolved air (Figure 10) with Captive Air bladder or diaphragm
through the action of coales- style expansion tanks, automatic air vents should
cence. This feature is especially be installed at the top of each air separator. As Air
beneficial in correcting problems Elimination systems have permanent separation
in air entrained systems. provided by the bladder or diaphragm between the
initial tank pre-charge and the system fluid no loss of
Units are designed for low Pressure drops pre-charge air will occur.
typically under 2 PSIG.
(See Taco Catalog# 400-1.4 for additional information.)
An additional feature of the 4900 Series is the
capability to remove dirt sizes as small as 5 microns Applications
from hydronic systems. The 4900 Series separators • Larger systems
remove up to 100% of the free air, 100% of the
entrained air, and up to 99.6% of the dissolved air • Higher efficiencies
in the system fluid. This feature is especially benefi- • Higher velocities
cial in correcting problems in air entrained systems. • Removal of smaller air bubbles,
e.g. removal of air in air entrained
The 4900 Series has been designed in two velocity systems (removes micro air bubbles)
ranges, a standard product series suitable for line • Removal of smaller particles,
velocity to 4.9 ft/sec. and a high velocity series suit- e.g. cleaning of dirty systems
able for line velocities up 11 ft/sec. The performance (removes particles and dirt)
of the 4900 product line has been independently
tested and published. (These test results are available
through your local Taco representative.)
9
Selection Procedure
Problem: Problem:
Select an air separator for a new installation. Select an air separator for an existing installation.
The system will have better than average The system has less than average maintenance and
maintenance and the primary pumps in the there are no strainers in the suction diffusers in the
system have suction diffusers with strainer. orimary pumps.
Conditions: Conditions:
1. Determine the type of air separator required. 1. Determine the type of air separator required.
For removal of air in a system of this larger flow For removal of air in a system of this larger
rate this would require a Taco Air Separator flow rate would require a Taco AC Series Air
with a model number beginning with “AC”. Separator with a model number beginning
with “AC”.
For system with better than average
maintenance and strainers in the pump For a system with less than average
suction diffusers select the standard unit maintenance and no strainers in the
without a strainer. No additional primary pumps select the unit with
letter designation is required. removable strainer for easier cleaning.
This is a model number ending with
2. Determine the velocity range of the AC Series an “F”.
that is suitable for these conditions. The recom-
mended velocity range for the standard unit is 2. Determine the velocity range of the AC Series
10 fps. This would require a unit with a line that is suitable for these conditions. The recom-
size of 6” (7.77 fps) mended velocity range for the AC unit is 10 fps.
This would require a unit with a line size of
3. Determine the size of the AC for the specified 3” (9.98 fps).
maximum pressure drop. For a maximum
pressure drop of 2 ft. the unit size required is 3. Determine the size of the AC for the specified
a 6” (1.8 ft.). This is Model AC06. maximum pressure drop. For a maximum
pressure drop of 2 ft. the unit size required is
a 4” (1.6 ft.). This is Model AC04F.
ACG06-I25R AC04F-125
10
Specifications & Pressure Drops
11
Submittal Data #401-107 Effective: 03/01/13
Submittal Data Information [Refer to all other submittals listed at bottom]
Max. Strainer
Model Number Approx. Approx.
Pipe A B C D E F G H Cv Cv
Free Wt. Wt.
Size Dia. Max. Dia. Inch Flow Area Factor (LBS.) Factor (LBS.)
Less With
Inch Strainer Strainer Inch Inch Inch Inch Inch Inch Base Ring GPM Inch2 Less Strainer With Strainer
2 AC02 AC02F 12 22-1/8 13 7-9/16 7 14 - - 80 31 86 40 72 45
4 AC04 AC04F 16 31-3/8 24 9-5/16 12-3/4 26 12 7 330 80 325 115 272 145
5 AC05 AC05F 16 32-1/2 24 9-3/8 13-3/4 26 12 7 550 112 510 130 422 165
6 AC06 AC06F 20 36-7/8 27 11-1/16 14-3/4 30 16 6-3/4 900 180 750 170 618 215
8 AC08 AC08F 20 45-1/2 27 14-1/16 17-3/8 30 16 6-3/4 1500 246 1260 270 1060 345
10 AC10 AC10F 24 47-3/4 32 14-15/16 17-7/8 36 20 6-3/4 2600 392 2000 350 1670 465
12 AC12 AC12F 30 59-3/4 37 17-5/8 24-1/2 42 24 7-3/4 3400 548 2900 600 2400 775
14 AC14 AC14F 36 68-1/2 44 20-3/4 27 48 30 7-3/4 4700 732 3500 805 2850 1035
16 AC16 AC16F 36 75-1/2 43 22-1/4 31 48 30 7-3/4 6000 845 4600 875 3800 1150
18 AC18 AC18F 48 84-1/4 56 24-5/8 35 64 40 7-3/4 8000 1290 5900 1550 4900 1900
F F
A A
C C
INLET
INLET
TO REMOVE TO REMOVE
STRAINER STRAINER
(FLANGED CONNECTIONS)
Taco Inc., 1160 Cranston Street. Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com
Air Elimination & Control
CA Expansion Tanks
Taco CA Expansion tanks are full acceptance Captive Air expansion tanks that provide
separation of air and water. Tough, durable and long lasting. The Taco CA is available in a
variety of sizes and capacities to fit your application.
-2-
Applications
Air Control Through Not maintaining minimum pres- fixed temperature reducing the
Pressure Control sures will create air problems. pressure reduces the amount of air
All hydronic systems operate Water contains a certain amount that can be dissolved or entrained.
under a variable amount of pres- of entrained air. If this air comes For example at 100˚F and 80 PSIA
sure. For closed systems the pres- out of solution at lower pressures, water can contain 8% air by vol-
sure varies primarily due to the it can increase corrosion rates of ume. At 100˚F and 20 PSIA the
expansion of water as it is heated metals within the system. In addi- percentage decreases to 2%.
or cooled. As the water is heated tion, air can form pockets at the
the pressure increases and as top of pipes and coils of terminal The conclusion is that air is least
the water is cooled the pressure units. These air pockets can actually soluble in water at lowest pres-
decreases. restrict or block flow in a hydronic sure. Air separators should there-
piping system. This is referred to as fore be located at these points.
The pressure in a closed system “air locking”. The lowest pressure in a system
varies between a minimum and a is typically at the expansion tank,
maximum. The minimum is con- Figure 1 shows a solubility curve since this is the point of no pres-
trolled by the fill valve and the for air in water. Note that at a sure change and the location of the
initial fill pressure of the expan- fill valve. Therefore, the general
18%
the tank. 6% 90
80
70
4% 60
50
PSIA
40
30
If the pressure is not maintained
2%
20
10
32 50 75 100 125 150 175 200 212
between these limits then the sys- TEMPERATURE (DEGREE F)
FAN COIL
TACO
CIRCULATOR
TACO
TWIN TEE
TACO
AIR SEPARATOR
TACO PUMP
TACO TACO
MULTI-PURPOSE SUCTION
TACO
VALVE DIFFUSER
EXPANSION
TANK
BOILER
-3-
Applications
FAN COIL
TACO
CIRCULATOR
TACO
TWIN TEE
TACO 4900
AIR SEPARATOR
TACO PUMP
TACO
TACO SUCTION
MULTI-PURPOSE DIFFUSER
VALVE
TACO
EXPANSION
TANK
CHILLER
For multi-story buildings this is The solubility of air in water at this is to install additional air separators
important. If the system pressure pressure and 40˚F is 45%. At the at upper levels of the building. A
is not maintained above atmo- top of the building, assuming, 10 psi hydronic system can have multiple
spheric at the top of the building positive pressure, the solubility is air separators, but should have
then not only will air come out only 4%. only one expansion tank. These air
of solution, but air can actually be separators should be high efficiency
drawn into the system. This will Obviously air will come out of separators similar to Taco’s 4900.
result in loss of system perfor- solution at the top of the building See Taco Catalog #400-1.4 for
mance with areas of low and no with the expansion tank and air additional information.
flow in this portion of the system. separator located at the bottom. By
“over pumping”, to maintain 40 psi Another solution is to locate the
For high rise buildings this is espe- at the top of the building, the solu- expansion tank and air separator at
cially important. Frequently the bility of air goes back up to 10%. the top of the building where the
expansion tank, air separator and pressure is the lowest and the air
fill valve are located at lower levels For pumps located at upper levels
of the building this is even more is least soluble in water. This will
of the building. At upper levels air require the running of a dedicated
will come out of solution as the problematic. Pumps in these loca-
tions can actually be attempting to line from the top of the building to
pressure decreases. This is similar the suction of the system circulat-
to what divers experience as the pump air. For centrifugal pumps the
point at which their head falls off ing pump. This will also reduce the
“bends”. One solution, which size of the expansion tank since the
designers and maintenance per- is in the range of 3% to 5% air vol-
ume in water. difference between the initial fill or
sonnel learned over time, was to minimum pressure and relief valve
“over pump” the system through Maintenance personnel and field or maximum pressure can be larger.
high pump heads. This increased engineers report many instance of
the pressure at upper levels of the poor pump performance due to Not maintaining maximum pres-
building and forced air back into unknown causes. A large portion sure can result in several problems,
the system. of these mysterious problems have including burst diaphragm or blad-
turned out to be secondary pumps ders in partial expansion captive
For example, in a 50 story building, air tanks, weeping relief valves and
the static pressure at the bottom located above expansion tanks.
A better solution to “over pumping” failure of components
of the system could be 250 psi.
-4-
Applications
Causes of over system pressuriza- The tank must now be sized for the This permanent separation allows the
tion can be undersized expansion initial fill volume plus the volume of tank to be precharged on the air side
tanks, water logged air cushion any expanded water. This makes the of the bladder to the minimum oper-
plain steel expansion tanks and tank much larger. ating or fill pressure. This eliminates
burst diaphragms or bladders in the initial water volume needed to
As air is released through air vents,
Captive Air tanks. compress the air from atmospheric
the air cushion in the tank can be
pressure to the system minimum (fill)
absorbed into the system fluid leaving
Pressure Control Through pressure. This allows the bladder
the tank water logged and eliminating
Air Control expansion tank to be charged to the
the system pressure control provided
Many systems designed in the past fill pressure without the introduc-
by the plain steel tank. When this
and some designed today, attempt to tion of system fluid offering a siz-
occurs the expanded water volume
control air by means of an old style able reduction in the required tank
must now seek a new outlet which is
air cushion plain steel tank and air volume (see figure 5 A). The use of
normally the relief valve or thru the
vents in the piping. a Captive Air expansion tank often
rupture of one of the other system
allows the reduction in required tank
componets.
The air cushion plain steel tank uses sizes up to 80% compared to air
a tank filled with water and an air A better solution is to use a Captive cushion or plain steel tanks.
cushion at the top of the tank for Air tank. In a Captive Air tank the air
During system operation any expanded
water to expand into as it is heated. is held captive by the use of a blad-
water, in the diaphragm or bladder,
The initial atmospheric air in the der or diaphragm with the expanded
compresses the precharge air to the
tank must be initially compressed to water being held on one side of the
maximum pressure. This compressed
the fill pressure. This requires an ini- diaphragm or bladder and the air on
air cushion then pushes the fluid back
tial charge or fill of water to accom- the other side.
into the system when it contracts.
plish this as shown in Figure 4.
Figure 4
Plain steel pressurization process -5-
Applications
This can be seen in the following System fill pressure of 10 psig, This is a difference of greater than
example problem. System volume of 3000 gallons, 81% reduction in required tank size
System: Chilled water at 40˚F with steel piping system, System fill
System volume: 3000 gallons pressure of 65 psig and a 90 psig Another advantage of the perma-
System piping : Steel maxiumum operating pressure. nent separation of air and water in
a Captive Air tank is to eliminate
The ASHRAE formula for plain Sizing a plain steel expansion tank the absorption of air back into the
steel expansion tank sizing is: [(v2/ v1) – 1] – 3aΔt water that is found in air cushion
Vt = Vs or plain steel tanks.
[(v2/ v1) – 1] – 3aΔt
Vt = Vs (Pa/ P1) – (Pa/ P2)
(Pa/ P1) – (Pa/ P2) Location of Expansion Tank
For Location of the expansion tank in
Where the system will also affect system
Vs = 3000 gallons
vt = volume of expansion tank, gal performance.
v1 = .01602 ft3/lb (40˚F)
vs = volume of water in system, gal v2 = .01613 ft3/lb (100˚F)
The expansion tank is the point of
t1 = lower temperature, ˚F Pa = 14.7 psia
no pressure change in the system.
P1 = 65psig +14.7psia = 79.7psia
t2 = higher temperature, ˚F This can be seen from Boyle’s Law:
P2 = 90psig+14.7 psia = 104.7 psia
Pa = atmospheric pressure, psia a = 6.5x 10-6 in/in˚F for steel
P1V1/T1 = P2V2 /T2
P1 = pressure at lower Dt = 60˚F
temperature, psia
If the temperature (T1 and T2) and
P2 = pressure at higher Vt = 388.83 gallons
temperature, psia volume (V1 and V2) are constant
with the pump on or off, then the
v1 = specific volume of water at Sizing of a Captive Air
lower temperature, ft3/lb pressure (P1 and P2) must also
expansion tank
remain constant.
v2 = specific volume of water at
higher temperature, ft3/lb Pa= P1
Therefore the point of connection
a = linear coefficient of thermal
expansion, in./in. -˚F of the expansion tank to the system
[(v2/ v1) – 1] – 3aΔt
Vt = Vs is a point of no pressure change.
= 6.5 x 10 in./in. -˚F for steel
-6
Typically located at the suction side
1 – (Pa/ P2)
= 9.5 x 10-6 in./in. -˚F for copper of the system pumps.
For
DT= (t2 - t1), ˚F Vs = 3000 gallons
V1 = .01602 ft3/lb (40˚F)
Chilled water sizing example: V2 = .01613 ft3/lb (100˚F)
Sizing a plain steel tank for a chilled Pa = 79.7psia (due to tank precharge)
water system with a temperature P1 = 65psig + 14.7psia = 79.7psia
range of 40˚F to 100˚F (ambient P2 = 90psig + 14.7psia = 104.7psia
temperature). a = 6.5x 10-6in/in F for steel
Dt = 60˚F
Vt = 71.55 gallons
-6-
Applications
To prevent air from being drawn Therefore, the general rule of not affect the pressure in the tank.
into the system the pressure in the thumb in hydronic systems is that If there are multiple tanks in the
system must be everywhere above “Expansion tanks should be locat- system then the pump head will
atmospheric pressure. ed on the suction side of pumps.” affect the pressure in the tank.
The pump will be able to transfer
The location of the expansion Multiple expansion tanks will cause water from one tank to the other
tank relative to the pump suction pressure problems in systems. The depending on the pressure dif-
will then determine if the system location of the expansion tank in ference generated by the pump
is everywhere above atmospheric the system is the point of no pres- between the tanks.
pressure. This can be seen in the sure change. The pump head does
following figures.
TACO
atmospheric.
Figure 7 – Expansion tank located on suction side of pump
-7-
Applications
FAN COIL
Figure 8 is a system with two
expansion tanks. The point of no
TACO
EXPANSION
pressure change will be some-
TACO
TANK
where between the two tanks.
CIRCULATOR
TACO
TWIN TEE POINT OF NO PRESSURE CHANGE
IS BETWEEN EXPANSION TANKS
Therefore, the general rule of
TACO
thumb in hydronic systems is that
MULTI-PURPOSE
VALVE
TACO
“Multiple expansion tanks in a
TACO PUMP
AIR SEPARATOR
system is not recommended”
since unstable pressure conditions
TACO
EXPANSION
will result.
TANK
CHILLER
Types of Expansion Tanks
Figure 8 – Multiple expansion tanks in system Air Cushion Plain Steel
Expansion Tank
FAN COIL
TACO
CIRCULATOR
TACO
tional and industrial applications
MULTI-PURPOSE
VALVE
TACO
for the control of pressure in
TACO PUMP AIR SEPARATOR
hydronic systems. The air cushion
plain steel tank uses a tank filled
with water and an air cushion at
CHILLER
-8-
Applications
the air is “recycled” to provide a Partial Acceptance Captive Air Partial Acceptance
cushion in the expansion tank, this Diaphragm Expansion Tank Captive Air Bladder
system is called an “Air Control” Taco CX partial acceptance Expansion Tank
system. As noted previously the air Captive Air diaphragm expansion Taco CBX partial accep-
cushion in the tank can be deplet- tanks are applied in commercial, tance bladder Captive
ed due to absorption of air into institutional and Air expansion tanks are
the water. It can also be depleted industrial applica- applied in commercial,
by loosing air through air vents in tions for the con- institutional and indus-
the piping. Care must also be taken trol of pressure in trial applications for the
to insure that piping between the hydronic systems. control of pressure in
air separator and the plain steel Diaphragm tanks use hydronic systems. CBX
expansion tank is pitched at least a diaphragm to per- bladder tanks use a field replace-
3 degrees (Figure 9) to facilitate manently separate able bladder to permanently sepa-
the migration of captured air back the air and water. rate the air and water.
into the expansion vessel. Systems In a diaphragm tank the air is held This permanent separation allows
with plain steel expansion tanks captive by the use of a diaphragm the tank to be precharged on the
must not have automatic air vents with the expanded water being air side to the minimum operat-
installed as this will lead to the loss held on one side of the diaphragm ing or fill pressure. This eliminates
of the expansion tank air cushion. and air on the other. many gallons of water to compress
if air is lost in the tank then the This permanent separation allows atmospheric pressure air in an air
tank will become water logged. the tank to be precharged on the cushion or plain steel tank to the
With a water-logged expansion air side to the minimum operat- fill pressure. This allows the reduc-
tank, the expanded water must ing or fill pressure. This eliminates tion in Captive Air expansion tank
now seek a new outlet which can many gallons of water to compress sizes of up to 80% compared to air
be the relief valve on one of the atmospheric pressure air in an air cushion or plain steel tanks.
major components. cushion or plain steel tank to the
As note previously the tank must fill pressure. This allows the reduc- In a bladder tank the bladder is not
be sized for the expansion of the tion in Captive Air expansion tank attached to the tank wall like a dia-
water in the system plus the ini- sizes of up to 80% compared to air phragm tank. Rather it is suspend-
tial charge of water to compress cushion or plain steel tanks. ed inside the tank very much like a
atmospheric air in the tank to In a diaphragm tank the diaphragm balloon. Expanded water flows into
the fill pressure. This makes the is attached to the tank wall and the inside of the bladder. Air is on
tank much larger. The tank is also cannot move inside the tank. As a the outside of the bladder between
subject to corrosion with the pres- result the tank has a limited accep- the bladder and the tank. As a
ence of air and oxygen in the tank. tance volume. In addition, there is result no water is in contact with
some water in contact with the the tank wall minimizing corrosion
Applications tank wall providing an opportunity In a partial acceptance bladder tank
• Smaller systems
for corrosions. the bladder is of limited accep-
• Lower cost tance volume and does not stretch.
• Ceiling mounted to Applications As a result, if there is an overpres-
save floor space • Smaller systems
sure condition in the system the
• Lower cost bladder will burst, again, very much
like a balloon.
Applications
-9- • Larger systems
• Lower cost
Applications
Full Acceptance Captive Air This permanent separation allows the tank. As a result no water is in
Bladder Expansion Tank the tank to be precharged on the contact with the tank wall minimiz-
Taco CA full acceptance blad- air side to the minimum operat- ing corrosion.
der Captive Air expansion tanks ing or fill pressure. This eliminates
are applied in many gallons of water to compress In a full acceptance bladder tank
commercial, atmospheric pressure air in an air the bladder is of full acceptance
institutional cushion or plain steel tank to the volume and can expand to the full
and industrial fill pressure. This allows the reduc- volume of the tank. As a result, the
applications tion in Captive Air expansion tank bladder will not burst if the system
for the control sizes of up to 80% compared to air experiences an overpressure con-
of pressure cushion or plain steel tanks. dition.
in hydronic In a bladder tank the bladder is
systems. CA not attached to the tank wall like Applications
• Larger systems
tanks use a a diaphragm tank. Rather it is sus-
field replace- pended inside the tank very much • Systems where reliability
able bladder to like a balloon. Expanded water and lower maintenance
costs are important
permanently flows into the inside of the blad-
separate the der. Air is on the outside of the
air and water. bladder between the bladder and
-10-
Selection Procedure
-11-
Selection Procedure
EXAMPLE 2
Problem:
Select an expansion tank for a
Calculation of Net system expansion –
heating water installation. The
mechanical room and expansion Net System Expansion
tank are located on the roof. First = Vs {[(v2/ v1)-1] – 3 α Δt}
cost is a major consideration.
System piping copper.
= 1000 {[(.01692/.01602) -1] – 3 (9.5x10-6) 200}
Conditions:
System volume 1,000 gallons. = 1000 {.05047}
Minimum temperature = 40 F
Maximum temperature = 240 F = 50.48 gallons
Building height = 50 ft
Relief Valve at boiler = 50 psig Calculate required tank volume –
Sizing of a Captive Air
expansion tank [(v2/ v1) – 1] – 3aΔt
Vt = Vs
Pa= P1 1 – (Pa/ P2)
[(v2/ v1) – 1] – 3aΔt
Vt = Vs Vt = 1000 {[(.01692/.01602) -1] – 3 (9.5x10-6) 200}/ (1 – 24.04/64.7)
1 – (Pa/ P2)
= 80.32 gallons
v1= .01602 ft3/lb (40˚F)
Because first cost is a major consideration select a partial acceptance
v2= .01692 ft3/lb (240˚F)
Captive Air bladder tank model CBX425. This tank is lower first cost
α=9.5x 10-6in/in F for copper piping than a full acceptance Captive Air tank. However, it is subject to a
Δt=200 F burst bladder under over pressure conditions. Acceptance volume of
Determine minimum pressure – the tank is 61 gallons. The volume of the tank is 112 gallons.
Minimum pressure equals static
pressure plus 5 psi positive pressure
at top of the building (assume 10 ft
of static pressure).
P1
= 10ft x .434 psi/ft + 5 psi
(positive pressure) + 14.7 psia
= 24.04 psi
Maximum pressure equal the
relief valve setting
P2 = 50 psig +14.7 psia
= 64.7 psia
-12-
Product Data
TANK H B D R SHIPPING
VOLUME HEIGHT DIAMETER DIAMETER RADIUS WEIGHT SYSTEM
Model CONNECTION
Number
GAL. LIT. INCH MM INCH MM INCH MM INCH MM LBS. Kg SIZE
CA90-125 23 90 29-1/8 740 16 406 20 508 4-1/4 108 120 55 1" NPT (25.4mm)
CA140-125 37 140 40-1/8 1019 16 406 20 508 4-1/2 114 195 88 1" NPT (25.4mm)
CA215-125 57 215 58-7/8 1495 16 406 20 508 4-1/2 114 290 132 1" NPT (25.4mm)
CA300-125 79 300 57-3/4 1467 20 508 24 610 5 127 320 145 1-1/2" NPT (38.1mm)
CA450-125 119 450 77-3/8 1965 20 508 24 610 5 127 400 181 1-1/2" NPT (38.1mm)
CA500-125 132 500 85-3/4 2178 20 508 24 610 5 127 420 191 1-1/2" NPT (38.1mm)
CA600-125 158 600 71-7/8 1826 24 610 30 762 6-1/4 159 460 209 1-1/2" NPT (38.1mm)
CA700-125 185 700 80-5/8 2048 24 610 30 762 6-1/4 159 525 238 1-1/2" NPT (38.1mm)
CA800-125 211 800 89-7/8 2283 24 610 30 762 6-1/4 159 590 268 1-1/2" NPT (38.1mm)
CA900-125 238 900 73-1/8 1857 30 762 36 914 7-7/16 189 690 313 1-1/2" NPT (38.1mm)
CA1000-125 264 1000 79 2007 30 762 36 914 7-7/16 189 790 358 1-1/2" NPT (38.1mm)
CA1100-125 291 1100 85-1/4 2165 30 762 36 914 7-7/16 189 865 392 1-1/2" NPT (38.1mm)
CA1200-125 317 1200 91 2311 30 762 36 914 7-7/16 189 940 426 1-1/2" NPT (38.1mm)
CA1300-125 344 1300 97 2464 30 762 36 914 7-7/16 189 980 445 1-1/2" NPT (38.1mm)
CA1400-125 370 1400 103 2616 30 762 36 914 7-7/16 189 1020 463 1-1/2" NPT (38.1mm)
CA1500-125 396 1500 73-3/8 1864 40 1016 48 1219 10-15/16 278 1200 544 1-1/2" NPT (38.1mm)
CA1600-125 422 1600 76-5/8 1946 40 1016 48 1219 10-15/16 278 1380 626 1-1/2" NPT (38.1mm)
CA1800-125 475 1800 83-1/2 2121 40 1016 48 1219 10-15/16 278 1515 687 1-1/2" NPT (38.1mm)
CA2000-125 528 2000 90-3/8 2296 40 1016 48 1219 10-15/16 278 1650 748 1-1/2" NPT (38.1mm)
CA2500-125 660 2500 107-1/8 2721 40 1016 48 1219 10-15/16 278 1838 834 1-1/2" NPT (38.1mm)
CA3000-125 792 3000 94-1/8 2391 44 1118 54 1372 11-7/16 291 2025 919 2" NPT (50.8mm)
CA4000-125 1056 4000 120-3/4 3067 44 1118 54 1372 11-7/16 291 2400 1089 2" NPT (50.8mm)
CA5000-125 1320 5000 150-1/4 3816 44 1118 54 1372 11-7/16 291 3100 1406 2" NPT (50.8mm)
CA7500-125 1980 7500 128-3/4 3270 62 1575 72 1829 11-1/2 292 3850 1746 3" NPT (76.2mm)
CA10000-125 2640 10000 158-1/4 4020 62 1575 72 1829 11-1/2 292 4500 2041 3" NPT (76.2mm)
System
Charging Valve Enclosure R Connection
(SEE TABLE)
Lifting Ring
H
Lifting Ring
B
D
-13-
Mechanical Specifications
-14-
Mechanical Specifications
Part 2 PRODUCTS
2.1 ASME Full Bladder D. Automatic Cold Water Fill Part 3 EXECUTION
TYPE EXPANSION Assembly (field installed 3.1 INSTALLATION
TANKS by others): Pressure
reducing valve, reduced A. Install specialties in
A. Manufactures: pressure double check back accordance with
1. Taco, Inc; Model CA ______: flow preventer, test cocks, manufacturer’s instructions.
www.taco-hvac.com strainer, vacuum breaker, and
valved by-pass. B. Where large air quantities can
2. ITT Bell & Gossett accumulate, provide enlarged
E. Size: air collection standpipes.
3. Amtrol Inc 1. HW Tank Capacity:
___________., C. Provide manual air vents at
4. Substitutions: _____________ system high points and as
See Section 01600 - acceptance volume. indicated.
Product Requirements.
2. CW Tank Capacity: D. For automatic air vents in
B. Construction: Welded steel, ___________., ceiling spaces or other
designed, tested and stamped _____________ concealed locations, provide
in accordance with ASME acceptance volume. vent tubing to nearest drain.
(BPV code sec VIII, div 1);
supplied with National Board F. Hot Water Heating System: E. Air separator and expansion
Form U-1, rated for working tank to be installed on the
pressure of 150 psi , with 1. Select expansion tank suction side of the system
flexible heavy duty butyl pressure relief valve at pumps. Expansion tank to
rubber bladder. Bladder shall _____ psi maximum. be tied into system piping
be able to accept the full in close proximity to air
volume of the expansion tank 2. Set pressure reducing separator and system fill line.
and shall be removable and valve at ____ psi.
replaceable. F. Provide valved drain and hose
G. Chilled Water System: connection on strainer blow
C. Accessories: Pressure gage down connection.
(field installed in adjacent 1. Select expansion tank
piping by others) and pressure relief valve at G. Provide relief valves on
air-charging fitting ; precharge _____ psi maximum. pressure tanks, low
to ____ psi. pressure side of reducing
2. Set pressure reducing valves, heat exchangers, and
valve at _____ psi. expansion tanks.
-15-
Mechanical Specifications
H. Select system relief valve K. Clean and flush glycol system N. Feed glycol solution to system
capacity so that it is greater before adding glycol solution. through make-up line with
than make-up pressure Refer to Section 15189. pressure regulator, venting
reducing valve capacity. system high points.
Select equipment relief L. Feed glycol solution to system
valve capacity to exceed through make-up line with O. Perform tests determin-
rating of connected pressure regulator, venting ing strength of glycol and
equipment. system high points. water solution and submit
written test results.
I. Pipe relief valve outlet to M. Feed glycol solution to system
nearest floor drain. through make-up line with
pressure regulator,
J. Where one line vents several venting system high points.
relief valves, make cross Set to fill at ___ psi.
sectional area equal to sum
of individual vent areas.
-16-
Notes
-17-
Notes
-18-
Notes
-19-
Taco quality
through & through
Taco Inc., 1160 Cranston Street. Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com