Professional Documents
Culture Documents
PROTECTION
Stator windings and bearings overheating protection is usually performed by RTD and
thermistor to monitor the temperature.
The overheating is detected by embedded temperature detectors at various points in the stator
winding. The temperature detector coils are normally resistance elements which form one arm
of the Wheatstone bridge circuit. In the case of smaller generator normally below 30 MW, the
generators are not equipped with embedded temperature coil but are usually fitted with
thermal relay and they are arranged to measure the current flowing in the stator winding.
This arrangement only detects overheating caused by overloading and does not provide any
protection against overheating due to failure of cooling systems or short-circuited stator
laminations. Although over current relays, negative phase sequence relays, and devises for
monitoring constant flow are also used to provide a certain degree of thermal overload
protection.
If any unbalancing occurred due to fault in the stator winding itself, that would be cleared
instantaneously by the differential protection provided in the generator. If the unbalancing is
occurred due to any external fault or unbalanced loading in the system, it may remain
undetected or may persist for a significant period of time depending on the protection
coordination of the system. These faults then be cleared by installing a negative phase
sequence relay with the characteristics to match the withstand curve of the machine.
3. OVERVOLTAGE
Mostly Overvoltage occurs because of the increase in the speed of the prime mover due to
sudden loss in the load on the generator.
Overvoltage is due to over speeding of generators and due to faulty operation of voltage
regulators. There are not only the internal but also, the external factors which cause the
overvoltage such as lightning strikes due to which the surge voltage generated by the lighting
may reach to the generator and cause severe damage and so to get protection from this surge
arrestor and surge capacitor is generally used.
At the time of restriking across the contacts of circuit breakers, the transient’s overvoltage gets
generated. This overvoltage is generated due to the switching hence they are called switching
surges and can be limited by the modern circuit breaker, R-C surge suppressors also help in
reducing it.
During the arcing grounds, the transient voltage has amplitude 5times more than the normal
line to neutral peak amplitude and to get protection against such transient use of resistance
earthing is often employed.
CAUSES OF OVERVOLTAGES
a high-speed transient or
PROTECTION
4. LOSS OF EXCITATION
Generator loss of excitation fault means that the excitation current provided by the excitation
system suddenly disappears completely or partially. After the synchronous generator is out of
magnetic, it will be transferred to the asynchronous running state, and the reactive power will
be absorbed from the original reactive power conversion.
CAUSES
The causes of generator loss of magnetism fault are: generator rotor winding fault, excitation
system fault, automatic demagnetization switch trip and circuit fault.
i. Accidental tripping of a field breaker,
ii. Field open circuit,
iii. Field short circuit (flashover of the slip rings),
iv. Voltage regulation system failure, or
v. The loss of supply to the excitation system.
vi. Human error for putting the AVR in manual mode and not controlling efficiently while
generator operation under power factor leading (Under-excited mode)
Two distinct effects of Loss of Excitation Protection are that the machine starts drawing
magnetizing current of large magnitude from the system, and the slip frequency emfs induced
in the rotor circuit; both of them cause overheating of the rotor.
PROTECTION
There are mainly two schemes available for protection against loss of field or excitation of a
generator. In 1st scheme, we use an undercurrent relay connected in shunt with main field
winding circuit. This relay will operate if the excitation current comes below its predetermined
value. If the relay is to operate for complete loss of field along, it must have a setting lies well
below the minimum excitation current value which can be 8% of the rated full load current.
Again, when loss of field occurs due to failure of exciter but not due to problem in the field
circuit (field circuit remains intact) there will be an induced current at slip frequency in the field
circuit. This situation makes the relay to pick up and drop off as per slip frequency of the
induced current in the field. This problem can be overcome in the following manner.
5. OVERSPEEDING FAULT
The simplest explanation for an overspeed is when the generator has been allowed, or has
been forced to operate beyond its designed limits. Depending on the generator’s capabilities,
this will likely result in either a catastrophic failure, as well as a reduced power life going
forward.
Very often overspeed leads to serious damage, not only to the engine itself, but also to
generators and gears.
CAUSES
1. Loses or changes its speed regulations
Most diesel generators, if not all modern generators are designed with appropriate speed
regulations within the system, though this doesn’t mean that they function properly. If the
regulator faults by losing or changing its speed regulations, then it can potentially result in a
wealth of damage.
EFFECTS
As engine overspeed can result in damage to the crankshaft (deformation to push rods), broken
valve seats, defective camshafts, breakdown of turbocharger and breakdown of generator and
gear, the consequences can prove to be costly. Mechanical connection strength can be
overcome by the exceeding stresses due to the increase in operational speed. These can result
in breaking of rotating parts or damage to the machinery itself. Over speed is thus a serious
safety hazard and can lead to a fatal situation.
PREVENTION
It’s the mechanical system that rotates the rotor in alternator or just in simple word runs the
alternator. Typical prime movers are diesel or gas engines, steam turbine, wind – tidal force,
water flow static force in hydroelectric plant with dam etc. It is clearly understandable that any
time a prime mover might fail to keep the alternator running.
CAUSES
The root causes can be traced to simple things like fuel flow shut up in gas /diesel engine,
inadequate water flow in hydroelectric plants etc.
EFFECTS
If the prime mover fails to supply mechanical energy to the generator, the generator will
continue to rotate in motoring mode that means it takes electrical energy from the system
instead of supplying it to the system.
In a steam turbine the steam acts as a coolant maintaining the turbine blades at a constant
temperature. Failure of the supply will therefore result in overheating due to friction, with
subsequent distortion of turbine blades.
PROTECTION
The failure of steam supply can cause severe mechanical damage in addition of imposing a
heavy motoring load on the generator. Reverse power relay is used for this purpose. As soon as
the generator starts rotating in motoring mode, the reverse power relay will trip the generator
set.