Protection Settings: Inverter Manager
Protection Settings: Inverter Manager
Name: Soctrang01
Serial number: 139F0215008201M219
Software version: 1:1.91.001-2
Grid code
Name: Thailand_PEA_large
Version: 180517
Unique ID: 136
Protection settings
Nominal values
Voltage disconnection
Are all values given in Phase/Phase voltage? (1:yes, 0:no) (isPhasePhaseVoltage) 0 (0)
variant selector (0:rest, 1:UL, 2:JP) (VAR_SELECT) 0 (0)
Transient voltage help function (ULLPeakMax) 1000 (1000) [V]
Under voltage stage 8 (UMIN8) disabled (disabled) [V]
Trip time for under voltage stage 8 (T_UMIN8) disabled (disabled) [s]
Under voltage stage 7 (UMIN7) disabled (disabled) [V]
Trip time for under voltage stage 7 (T_UMIN7) disabled (disabled) [s]
Under voltage stage 6 (UMIN6) disabled (disabled) [V]
Trip time for under voltage stage 6 (T_UMIN6) disabled (disabled) [s]
Under voltage stage 5 (UMIN5) disabled (disabled) [V]
Trip time for under voltage stage 5 (T_UMIN5) disabled (disabled) [s]
Under voltage stage 4 (UMIN4) disabled (disabled) [V]
Trip time for under voltage stage 4 (T_UMIN4) disabled (disabled) [s]
Under voltage stage 3 (UMIN3) disabled (disabled) [V]
Trip time for under voltage stage 3 (T_UMIN3) disabled (disabled) [s]
Under voltage stage 2 (far) (UMIN2) 110 (110) [V]
Trip time for under voltage stage 2 (T_UMIN2) 0.3 (0.3) [s]
Under voltage stage 1 (near) (UMIN1) 197 (197) [V]
Trip time for under voltage stage 1 (T_UMIN1) 2 (2) [s]
10 min. mean (EN 50160) (U10M_AVG) disabled (disabled) [V]
Trip time for 10 min. mean (T_U10M_AVG) disabled (disabled) [s]
Over voltage stage 1 (near) (UMAX1) 242 (242) [V]
Trip time for over voltage stage 1 (T_UMAX1) 1 (1) [s]
Over voltage satge 2 (far) (UMAX2) 264 (264) [V]
Trip time for over voltage stage 2 (T_UMAX2) 0.16 (0.16) [s]
Frequency disconnection
(re-) connection
Connection / Re-connection time (more than short interrupt) (T_CON) 30 (30) [s]
Re-connection time (less then short interrupt) (T_RECON) 30 (30) [s]
Maximum time for a short interupt (T_SHT_INT) 0 (0) [s]
Time-to-alarm (T_ALARM) 600 (600) [s]
Minimum connection voltage (UMIN_CON) 198 (198) [V]
Maximum connection voltage (UMAX_CON) 242 (242) [V]
Minimum connection frequency (FMIN_CON) 46.9 (46.9) [Hz]
Maximum connection frequency (FMAX_CON) 52.1 (52.1) [Hz]
Loss of mains
1/ 5
Active frequency shift offset (k0) (LOM_F_SHF_K0) 0.005 (0.005)
Active frequency shift feedback (k1) (LOM_F_SHF_K1) 0.25 (0.25)
Actime LOM - trip time (T_LOM_ACTIVE) 0 (0) [s]
Open Phase detection mode. (1: on, 0: off) (OPEN_PH_DETECT_MOD) 0 (0)
Rate Of Change Of Frequency (ROCOF) (LOM_ROC) disabled (disabled) [Hz/s]
Trip time for ROCOF (T_LOM_ROC) disabled (disabled) [s]
RoCoF threshold (LOM_ROC_THR) disabled (disabled) [Hz]
Disconnection
Protection settings
Manual Restart Mode / Jet Mode (1:Manual Restart 0:Jet Mode / Off ) (RST_MOD) 0 (0)
Enable / disable event trigger for AC over voltage detection (1:On 0:Off) (MAN_RST_OV_VTG) 0 (0)
Enable / disable event trigger for AC under voltage detection (1:On 0:Off) 0 (0)
(MAN_RST_UN_VTG)
Enable / disable event trigger for over fre-quency detection (1:On 0:Off) 0 (0)
(MAN_RST_OV_FREQ)
Enable / disable event trigger for under frequency detection (1:On 0:Off) 0 (0)
(MAN_RST_UN_FREQ)
Enable / disable event trigger for PID de-tection (1:On 0:Off) (MAN_RST_PID) 0 (0)
Enable / disable event trigger for AID de-tection (1:On 0:Off) (MAN_RST_AID) 0 (0)
Support settings
Fault ride through
Basics settings
Mode Select (1: Q(U), 2: Q(P), 3: Q(S), 4: Q(T), 5: Qext, 6: PF(P), 7: PF(U), 8: PF(T), 9: 5 (5)
PFext ) (ModeSelect)
Night mode selection (0:Q@night, 1:?) (NightMode) 0 (0)
Active pow er limitation for reactive pow er support (P_LIM_IF_Q) 100 (100) [%]
Nominal apparent pow er at point of common coupling (Sgrid_nom) disabled (disabled) [kVA]
Voltage drop betw een Point of Common Coupling and generator (UNOMOffset) 0 (0) [V]
Nominal grid voltage (Phase/Phase) (UNOM_LL) 381.051 (381.051) [V]
Immediate controls
Enable the connection w ithin a defined votlage and frequency range (ReleaseToStart) 1 (1)
Shutdow n delay time (T_DELAY_SHUTDOW N) 2 (2) [s]
Ramp in (RmpIncTmm_ONLINE) 1200 (1200) [%/min]
Maximum reactive pow er reduction rate (RmpDecTmm_Q) -1200 (-1200) [%/min]
Maximum reactive pow er increase rate (RmpIncTmm_Q) 1200 (1200) [%/min]
Maximum active pow er reduction rate after external setpoint change (RmpDecTmm_EXT) -1200 (-1200) [%/min]
Maximum active pow er increase rate after external setpoint change (RmpIncTmm_EXT) 1200 (1200) [%/min]
Active pow er (P_ref) 100 (100) [%]
Reactive pow er (Q_ref) 0 (0) [%]
Pow er factor (PF_ref) -1 (-1)
S (S_ref) 0 (0) [%]
SR (SR_ref) 0 (0) [%]
Fallback
2/ 5
FallbackDelay (FallbackDelay) disabled (disabled) [s]
FallbackEnabled (FallbackEnabled) disabled (disabled)
FallbackMaxDuration (FallbackMaxDuration) disabled (disabled) [s]
FallbackPref (FallbackPref) disabled (disabled) [%]
FallbackQref (FallbackQref) disabled (disabled) [%]
FallbackPrefMod (FallbackPrefMod) disabled (disabled)
Maximum active pow er reduction rate if MPP pow er change (RmpDecTmm_SR) -1200 (-1200) [%/min]
Maximum active pow er increase rate if MPP pow er change (RmpIncTmm_SR) 1200 (1200) [%/min]