Professional Documents
Culture Documents
Version: 2.4.00
Licenced to: MUHAMMAD HASSAN Serial no: [dongle]
File: ZONE 8 SPARE STORE ROOMprj.prj - Results 4/1/2021
Error messages:
No error detected
22
23
81002 19
18
17 20
21
16 81001
15
1314
12
11
10
9
4
3 8
7
6
2 5
1
VdS SCHADENVERHÜTUNG CEODEUX B08405000 Page: 2
Version: 2.4.00
Licenced to: MUHAMMAD HASSAN Serial no: [dongle]
File: ZONE 8 SPARE STORE ROOMprj.prj - Results 4/1/2021
Section- Starting- Endnode Length Height Pipetype Diameter Fitting Component Nb of containers
No: node Nozzle [m] [m] [mm] ** * code coefficient IG55 quantity
Legend of pipetypes
Type Pipeclass Pipe roughness
10 Hoses and Ball Valves smooth
20 Welded Manifold smooth
43 Sch40 pipe ANSI B36.10 ASTM A53/A106 grade B black pipe
30 Nozzles smooth
Legend of components
Code Type Resistance coefficient
134 B0480 IG DN16 2.520
100 Directional Valve 1.000
VdS SCHADENVERHÜTUNG CEODEUX B08405000 Page: 3
Version: 2.4.00
Licenced to: MUHAMMAD HASSAN Serial no: [dongle]
File: ZONE 8 SPARE STORE ROOMprj.prj - Results 4/1/2021
Nozzle data:
Legend of nozzles:
Type Number C1 C2 C3 C4 C5 C6
of orifices
8 1 0.00000 0.00000 0.00000 0.00000 0.00000 0.00000
VdS SCHADENVERHÜTUNG CEODEUX B08405000 Page: 4
Version: 2.4.00
Licenced to: MUHAMMAD HASSAN Serial no: [dongle]
File: ZONE 8 SPARE STORE ROOMprj.prj - Results 4/1/2021
Zone Total Volume of Calculated Total Max. Over- Design Extinguish- Design Design Design
volume building volume surface pressure temp. conc. factor conc. quantity
[m³] parts [m³] [m³] [m²] [mbar] [°C] [% Vol] [% Vol] [kg]
1 ZONE 8 196.1 0.0 196.1 205.4 5.000 20.0 35.0 1.25 43.6 158.65
Calculation results:
Discharge time:
Discharge time : 113.2 s
System information:
Pipe system working pressure: 36.7 bar abs
Container working pressure: 216.9 bar abs
Total network volume: 234.7 l
VdS SCHADENVERHÜTUNG CEODEUX B08405000 Page: 6
Version: 2.4.00
Licenced to: MUHAMMAD HASSAN Serial no: [dongle]
File: ZONE 8 SPARE STORE ROOMprj.prj - Results 4/1/2021
Pipe system pressures during the controlled phase of the discharge 38.1 seconds after start
Nozzle data:
Max. transport time difference between nozzles 81002 and 81001 is 0.00 s
VdS SCHADENVERHÜTUNG CEODEUX B08405000 Page: 8
Version: 2.4.00
Licenced to: MUHAMMAD HASSAN Serial no: [dongle]
File: ZONE 8 SPARE STORE ROOMprj.prj - Results 4/1/2021
Concentrations:
Component list:
Nozzle-type Number C1 C2 C3 C4 C5 C6
150 87.5
75
125
62.5
100
50
75
37.5
50
25
25 12.5
0 0
0 25 50 75 100 125 150 0 25 50 75 100 125 150
Time [s] Time [s]
1.3 300
250
1.0
200
0.8
150
0.5
100
0.3 50
0.0 0
0 25 50 75 100 125 150 0 25 50 75 100 125 150
Time [s] Time [s]
12.5
40
10
30
7.5
20
5
10
2.5
0 0
0 25 50 75 100 125 150 0 25 50 75 100 125 150
Time [s] Time [s]