Professional Documents
Culture Documents
NCS
Document 51095
3/08/02 Revision:
ECN 02-074
B1
www.PDF-Zoo.com
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control with remote notifica- mined rate or reaches a predetermined level. Rate-of-rise
tion capability—can provide early warning of a developing fire. heat detectors may be subject to reduced sensitivity over time.
Such a system, however, does not assure protection against For this reason, the rate-of-rise feature of each detector
property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufac- same room as the control panel and in rooms used by the sys-
turer's recommendations, State and local codes, and the rec- tem for the connection of alarm transmission wiring, communi-
ommendations contained in the Guide for Proper Use of cations, signaling, and/or power. If detectors are not so
System Smoke Detectors, which is made available at no located, a developing fire may damage the alarm system, crip-
charge to all installing dealers. A study by the Federal Emer- pling its ability to report a fire.
gency Management Agency (an agency of the United States Audible warning devices such as bells may not alert people
government) indicated that smoke detectors may not go off in if these devices are located on the other side of closed or
as many as 35% of all fires. While fire alarm systems are partly open doors or are located on another floor of a building.
designed to provide early warning against fire, they do not Any warning device may fail to alert people with a disability or
guarantee warning or protection against fire. A fire alarm sys- those who have recently consumed drugs, alcohol or medica-
tem may not provide timely or adequate warning, or simply tion. Please note that:
may not function, for a variety of reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or “smoke” from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: • In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
• Smoke particles may become “cold,” stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control. It is essential to use only equipment
• Smoke particles may be drawn into air returns before listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of Chapter 7 of NFPA
izing-type sensing chambers tend to detect fast-flaming fires 72 shall be followed. Environments with large amounts of
better than smoldering fires. Because fires develop in different dust, dirt or high air velocity require more frequent mainte-
ways and are often unpredictable in their growth, neither type nance. A maintenance agreement should be arranged
of detector is necessarily best and a given type of detector through the local manufacturer's representative. Maintenance
may not provide adequate warning of a fire. should be scheduled monthly or as required by National and/
Smoke detectors cannot be expected to provide adequate or local fire codes and should be performed by authorized pro-
warning of fires caused by arson, children playing with fessional fire alarm installers only. Adequate written records
matches (especially in bedrooms), smoking in bed, and violent of all inspections should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.). Precau-L-3-2002.fm
www.PDF-Zoo.com
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be Like all solid state electronic devices, this system may
connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light-
sources of power before servicing. Control unit and associ- ning-induced transients. Although no system is completely
ated equipment may be damaged by removing and/or insert- immune from lightning transients and interferences, proper
ing cards, modules, or interconnecting cables while the unit is grounding will reduce susceptibility. Overhead or outside
energized. Do not attempt to install, service, or operate this aerial wiring is not recommended, due to an increased sus-
unit until this manual is read and understood. ceptibility to nearby lightning strikes. Consult with the Techni-
CAUTION - System Reacceptance Test after Software cal Services Department if any problems are anticipated or
Changes. To ensure proper system operation, this product encountered.
must be tested in accordance with NFPA 72 Chapter 7 after Disconnect AC power and batteries prior to removing or
any programming operation or change in site-specific soft- inserting circuit boards. Failure to do so can damage circuits.
ware. Reacceptance testing is required after any change, Remove all electronic assemblies prior to any drilling, filing,
addition or deletion of system components, or after any modifi- reaming, or punching of the enclosure. When possible, make
cation, repair or adjustment to system hardware or wiring. all cable entries from the sides or rear. Before making modifi-
All components, circuits, system operations, or software func- cations, verify that they will not interfere with battery, trans-
tions known to be affected by a change must be 100% tested. former, and printed circuit board location.
In addition, to ensure that other operations are not inadvert- Do not tighten screw terminals more than 9 in-lbs.
ently affected, at least 10% of initiating devices that are not Over-tightening may damage threads, resulting in reduced ter-
directly affected by the change, up to a maximum of 50 minal contact pressure and difficulty with screw terminal
devices, must also be tested and proper system operation ver- removal.
ified.
Though designed to last many years, system components
This system meets NFPA requirements for operation at 0-49° can fail at any time. This system contains static-sensitive
C/32-120° F and at a relative humidity of 85% RH - 95% per components. Always ground yourself with a proper wrist strap
ULC - (non-condensing) at 30° C/86° F. However, the useful before handling any circuits so that static charges are
life of the system's standby batteries and the electronic com- removed from the body. Use static-suppressive packaging to
ponents may be adversely affected by extreme temperature protect electronic assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this
system and all peripherals be installed in an environment with Follow the instructions in the installation, operating, and pro-
a nominal room temperature of 15-27° C/60-80° F. gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation
cating device loops. Most devices cannot tolerate more than a by authorized personnel.
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual, may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Canadian
tested and found to comply with the limits for class A Department of Communications.
computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable pro- Le present appareil numerique n'emet pas de bruits radi-
tection against such interference when operated in a oelectriques depassant les limites applicables aux appar-
commercial environment. Operation of this equipment in eils numeriques de la classe A prescrites dans le
a residential area is likely to cause interference, in which Reglement sur le brouillage radioelectrique edicte par le
case the user will be required to correct the interference ministere des Communications du Canada.
at his own expense.
Precau-L-3-2002.fm
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, ONYX™, and VeriFire™ are trademarks, and FlashScan® and VIEW® are registered trademarks of
NOTIFIER. NION™ and UniNet™ are trademarks of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered
trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered
trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark
of GE Plastics, a subsidiary of General Electric Company.
www.PDF-Zoo.com
Table of Contents
www.PDF-Zoo.com
4 Document #51095 Rev.B1 3/7/02
Table of Contents
www.PDF-Zoo.com
6 Document #51095 Rev.B1 3/7/02
NCS Mounting and Connections Installation
Section 1 Installation
1.1 NCS Mounting and Connections
The Network Control Station (NCS) contains a recognized tabletop computer with VGA graphics
for displaying all network events. The NCS is used with the Notifier Noti•Fire•Net system. The
different NCS models all come with the NRT-P3, a high-performance desktop computer.
Analog Fire Panel Operating Manual (AFP-400) 50260 Smoke Control Manual 15712
Canadian Requirements for the AM2020/AFP1010 15631 SLC Manual 51253
Network Interface Board (NIB-96) 15666 MMX-2 Installation Instructions M500-03-00
RM-1 Series Remote Microphones 51138 XP5 Series Transponders 50786
NBG-12LX Pull Station 51093 ACT-2 Audio Coupling Transformer 51118
Not Used
NRT-NETPCB
LEDs
Power
Cord
Socket
UPS
Supervision
Cable
Connection
• The NRT-P3 requires 115 VAC, 50/60Hz primary power or 230 VAC, 50/60 Hz primary power depending upon the
position of the voltage selection switch shown in Figure 1.2 and Figure 1.3.
• Where an NCS is required, the use of a supervised Uninterruptable Power Supply (UPS) is also required (see Figure
1.6)
• The NCS is not suitable for use as a receiving unit.
• The front power switch for the NRT-P3 has been permanently fixed in the ON position.
Power Cord
Voltage selection
Switch
nrtpwcrd.cdr
Mounting Screws
PCLB5Ba.cdr
Mounting Screw
Junction Box
Neutral - White
AC - Black
15 AMPS
MAX
To 115 VAC, 50/60 Black AC HSP-121B AC
L E
Conduit
Hz Primary Power or Q
I
230 VAC, 50/60 Hz White
hsp-121b.cdr
NEUT U
N NEUT
I
Primary Power Green E P
GND GND
Light ON - Normal Power Cord
Light OFF - Requires Service PCLB-6
Ground - Green
Fuse
MON-19BLK
Junction Box
Neutral - White
HSP-121B AC - Black
Black
White
Green
Ground - Green
NCSmoninstonyxnrtnet.cdr
Fuse
Power Cord
Monitor
DB-15 Cable Connection
NCS Computer
Figure 1.5 Installation of MON-19BLK
AC Input
To AC Power of
NCS, Printer, or CRT Use cable P/N 71033 (supplied
with the NCS) from
NRTNETPCB to UPS. Cut and
Note: The Inverter is equipped AC AC Line strip wires as needed. Make all
with automatic transfer. Refer to Load 115 VAC
connections in conduit.
the schematic in the instruction 115 VAC
manual for internal wiring.
DC/AC Inverter
COMM
Inverter
NC
Failure NC
47k ELR
NRT-P3 Computer
Utility Failure
(optional)
Note: Wiring should be in the same
cabinet or use less than 3 feet of conduit.
DC DC
Output Output
Charger 1 Charger 2
Sharing
Load
Sense (+)
Remote
Sense (-)
Remote
Equalize
Remote
Sense (+)
Remote
Sharing
Load
Current
Low
Sense (-)
Remote
Equalize
Remote
Failure
Rectifier
Current
Low
Failure
Rectifier
NCSsupsfsonyxnrtnet.cdr
+ 9
8
7
0
1
2
6 3
- 5 4
FMM-1
NRT-NETPCB
UPS Supervision Port
8A AC Maximum
120V AC, 60 Hz
No Connection
No Connection
Input Power
120V AC
120V AC
120V AC
Of UPS
Of UPS
Of UPS
Output
Output
Output
SPARE
GND
GND
GND
Chassis Ground
GND
H
N
H
12
15
10
13
14
11
5
2
9
4
8
1
4
(NO) 47K
Battery ELR
Fail
5(C)
6
(NC)
9 0
+ 8 1
7 2 EMI
_ 6 3 UPS Line
Static
Transformer Charger
5 4 Switch
System Control Filter
Board
FMM-1
Software Type
ID "MTRB"
Inverter Battery
upsprn1fsconyxnrtnet.cdr
Protective Cover
(P/N 08275)
Strain Relief Assembly
(snaps over pluggable terminal block)
strainre.cdr
NRT-
NCSonyx3back.cdr
NETPCB
1.2 Peripherals
1.2.1 Connecting a Line Printer
A printer can be connected to the NCS to print fire alarm and trouble signals (refer to Figure 1.9
and Table 1.3).
DB 9 connector
NCSdbcxonyxnrtnet.cdr
DB 25 connector from PRN Cable
or another listed EDP printer
NCS Printer
DB9 DB25
2 2
3 3
5 7
4 and 6
jumpered
together
8 20
1.3 PC Configurations
To run the NCS program your system must be setup for the following configurations:
1024 x 768 resolution, large fonts, and 65k colors. Refer to Figure 1.10. To set these
configurations, select the Start menu and Settings/Control Panel, double-click Display and select
the Settings tab.
ncspcconfig.jpg
Figure 1.10 PC Configurations
For Windows 2000, the font size is located in a submenu of the Settings screen. Click the
"Advanced" button that appears at the bottom right of the Settings screen. On the next screen,
choose "Large" for font size.
Additionally, for Windows 2000, the Active Desktop setting must be off.
1.4 Software
1.4.1 Installing the NCS Software
Make sure to read the entire set of instructions prior to beginning the NCS software installation.
The NCS software requires Windows 2000 Professional Edition with Service Pack 1or higher, or
Windows NT® with Service Pack 5. The following steps must be completed to install NCS
software in Windows NT® Workstation 4.0 or in Wnidows 2000.
Note: If the NCS is the Master Time Keeper on the network, installing this software will cancel the setting and a Master
Time Keeper will not exist on the network. Enter the date/time in the NCS Local Programming Dialog Box for the NCS to
become the Master Time Keeper again.
Windows NT® is a registered trademark of Microsoft Corporation.
1. Insert the CD-ROM into the appropriate drive. The Setup program will launch automatically if
Autorun is enabled. Otherwise, continue with steps 2 through 10 that follow.
2. Click on the Start button, select Run...
3. At the Command Line prompt, type X:\NCS, where X is your CD drive letter. Steps 2 and 3
will only be necessary for PCs that do not have the Autorun feature enabled.
4. An InstallShield Self-Extracting.exe dialog box will appear, select YES to continue installing
the NCS. InstallShield will start extracting the necessary files for installing the NCS.
5. A Welcome dialog box will appear. Select NEXT to continue installing or CANCEL to return
to the desktop.
6. A User Information dialog box will appear next. Type your name and company at the
designated prompts. Select NEXT to continue or CANCEL to return to the desktop. The
location of the installation directory will be displayed if it exists, and the user will be asked if
he/she would like to make a backup.
7. Next a Select Program Folder dialog box appears. The NCS must be installed in the
directory provided.
8. A Setup Type dialog box will now appear. Choose Typical, Compact or Custom setup by
clicking in the appropriate circle. Select NEXT to continue installing, BACK to view the
previous screen or CANCEL to return to the desktop.
• Typical Install - Installs the most common options, recommended for most users.
• Compact Install - Not available at this time.
• Custom Install - The user chooses the installed options, recommended for advanced users. The
Select Program Folder dialog box displays for this purpose.
9. Next a Start Copying Files dialog box appears showing the type of setup, target folder and
user information that was provided. Select NEXT to begin copying files, BACK to change any
settings or CANCEL to return to the desktop.
10. The NCS will now install the NCS. When setup is complete, a Setup Complete dialog box
appears informing you that the computer will be rebooted. Press OK to perform the reboot.
Caution: The NCS Communications Driver may have to be changed. If the NCS is installed on a
! PC that did not contain the NRT (Network Reporting Terminal), it will use IRQ5 or IRQ7.
The NCS Installation Program sets the IRQ to IRQ5. On Onyx computers, or computers that already
use IRQ5, this must be changed to IRQ7. Please be sure the jumper selection on the NRT-NETPCB
card is set to IRQ7. In addition, please complete the following steps to configure the software:
1. Open a text editor, such as Notepad.
2. Open file ptp20020.ini. This file is located in the \notifier\ncs directory.
3. Look for IRQLevel = REG_DWORD 0x05. Change the 0x05 to 0x07.
4. Save the file, close Notepad.
5. Open the DOS command prompt, and change to the \notifier\ncs directory.
6. Type "regini ptp20020.ini"
7. This completes the software configuration. Reboot the computer for the change to take
effect.
To verify that the NCS Communications Driver is configured correctly, follow these steps in
Windows 2000.
1. From the Start Menu, open Control Panel, then double click on Administrative Tools.
2. Double click on Computer Management.
3. Navigate to System Information, then select Hardware Resources, followed by IRQs.
4. Verify that IRQ7 is displayed, and the Device indicates ptp20020.
4. The Windows NT® Installation Wizard will start to add the new printer.
5. Select the "My Computer" button, click next. The following items should be selected on the
next screens.
4. The Windows NT® Installation Wizard will start to add the new printer.
5. Select the "My Computer" button, click next. The following items should be selected on the
next screens.
Note: If the NCS Line Printer is connected to a serial port, the port settings must match the printer settings.
Section 2 Programming
2.1 Networking the NCS
The Network Control Station (NCS) annunciates system signals on Noti•Fire•Net. Equipment that
connects to Noti•Fire•Net and communicates with other equipment using the network will be
referred to as a network node (for example: AM2020, AFP200 with NAM-232, AFP1010, INA, or
NCS). Noti•Fire•Net is a peer-to-peer network (refer to Figure 2.1), and can be logically grouped
together to form systems. For more information on Noti•Fire•Net, refer to the Noti•Fire•Net
Manual.
The functions of the NCS shall include:
• Display of all events on the network.
• Provide the ability to acknowledge, reset and signal silence all events.
• Provide the ability to graphically set up and annunciate the points to be monitored.
• Allow read status and alter status operation to all fire panels that provide this ability.
• Upload / download programming information for archiving purposes for all fire panels that provide this ability.
• Provide a history viewer with filters that can be run outside the NCS application.
• Setup different levels of operator interaction, based on passwords.
MIB
AM2020
MIB
AFP1010
Fiber Optics
or Single
Twisted-Pair
NCS
AFP-200
NAM-
232
nrtntwka.cdr
MIB
INA
Events are listed from top to bottom (the top being the newest and the bottom being the oldest
event). All events stored in the history buffer are not encrypted, and can be viewed using Microsoft
Access.
The Notifier icon shown below can be found under Notifier on the Start Bar for Windows NT® 4.0
or higher. To launch the NCS software, double-click on the icon.
ncsicon.tif
Figure 2.2 NCS Icon
The Main window is the first window that appears after the NCS application begins communication
on Noti•Fire•Net. The Main window supports changing passwords and accessing other NCS
windows.
! Caution: While running NCS software, DO NOT run other software, including PC Tools,
Screensavers and TSRs, also, DO NOT add disk doubling software at any time.
Caution: If the Parallel Port Key is not connected to the PC, the NCS will power up in Demo
! Mode. In this mode of operation, the program will not communicate on the network.
There are nine menus available from the NCS Start-up window: File, Operator, Action, View,
Screen Navigator, Administration, Graphic, Utilities, and Help.
Below are some examples of auto-vectoring among Groups. For a more detailed explanation of
Groups, refer to "Groups" on page 79.
Screen vectoring uses the same event priority algorithms as the System Interface Window. The
user can still manually change screens using the Select Screen dialog box.
Graphic
Floor Plan
Acknowledged
Events Window
mainscrn.tif
ncsbase.jpg
Figure 2.6 Example of a Graphic Floor Plan
2.5.1.5 Key Map Area
The key Map Area is an overview of the graphics used in the system. It can be set up for navigation
or simply as an accompanying view of the foreground, refer to Figure 2.7.
ncskeymap.tif
Figure 2.7 Key Map Area
2.5.1.6 Events Window
The Events window displays the first of 12 unacknowledged, off-normal events on the network.
The events are grouped by event type (i.e., fire alarm, security alarm, supervisory alarm, and
trouble), and sorted by time within the group, displaying the oldest event first and the newest event
last. The highest event group is displayed on top of the window, the lowest event group on the
bottom of the window, refer to Figure 2.8. All events in this window are color coded. Fire alarms
are designated red, Security Alarms as blue, Supervisory Alarms as orange, Trouble Conditions as
yellow, and Pre-Alarms as cyan.
Address
firevent.tif
A device appearing in this box may be clicked on to display the graphic screen containing the
device. Any device that has been acknowledged is moved from the unacknowledged event window
to the acknowledged event box.
2.5.1.7 Acknowledged Event Box
The acknowledged event window displays the first 12 events on the network. The events are
grouped by event type (i.e., fire alarm, security alarm, supervisory alarm, trouble, etc.), and sorted
by time within the group, displaying the oldest event first and the newest event last. Refer to Figure
2.9.
Time
Event Type
Address
ncsackn.tif
Figure 2.9 Example of the Acknowledged Event Box
The information displayed consists of the event type, the address, and the time that the event was
received (assigned by the NCS). A detail button is provided to expand the event box and display
all events, as well as provide more detailed information for each event. Refer to “The Detailed
Events Window” on page 44 for more information on the Detailed Event Window.
A device appearing in this box may be clicked on to display the screen containing the device. Any
events that have cleared from the device are deleted from the unacknowledged event box, unless
the clear event is an alarm condition that must be acknowledged (i.e., a tracking alarm on an
AM2020/AFP1010 that clears without a reset). In that case the clear alarm will move to the
unacknowledged event box for further action.
2.5.1.8 Screen Navigation Tools
Use the screen navigation tools to advance to different graphic representation screens by using the
< and > arrows, refer to Figure 2.10. Click on the house icon to go directly to the “Home” page,
click the middle icon to open a Text File dialog that is associated with the Graphic Screen box, or
click on the last icon (printer) to print out a screen. In addition, the NCS provides a command to
display all screen names in a dialog box. Double-click one of the screen names to invoke the floor
plan specified.
Forward Arrow
ncsnavig.tif
Print Graphic
Back Arrow
Current Screen Home Screen Text File Associated
(Top Level Screen) with Graphic Screen
ncstoolb.tif
Event Counter
Detailed Events
ncsbanr.tif
Alarm
Pre-Alarm
Figure 2.13 Alarm, Trouble, Supervisory Alarm, Security Alarm and Pre-Alarm Banners
2.5.1.13 Command Area
The command area at the top of the screen allows the user to SAR (signal silence, acknowledge or
reset), the network or a specific node, refer to Figure 2.14. Pressing a button will transmit the
appropriate command over the network. The user has the ability to vector the signal silence and
system reset commands to specific nodes on the network via a pop-up dialog box. The node
address currently on the network and within the users ability to SR (signal silence or reset) will be
displayed in this pop-up dialog box. In addition, another selection will be made available to SR all
off-normal nodes, or all nodes in the system. This will be user configurable in the NCS local
programming dialog box.
ncscomnd.tif
Acknowledge
Initiating a acknowledge command will transmit a point acknowledge or block acknowledge
message to all appropriate nodes. The nodes transmitted to are limited by the nodes programmed
into the system and the user password level.
If the highest priority event in the system is a fire alarm condition, a point acknowledge message
will transmit to the node, acknowledging the point. If the highest priority event in the system is a
security alarm or lower event, a block acknowledge command will be transmitted in the same
manner as in the Command area.
Any point acknowledge or block acknowledge initiation commands will be logged in the history
manager and current event window, if successfully completed. If this message could not be
completed, a error message will be displayed to the user.
System Reset
Initiating a system reset command transmits a system reset message to all appropriate nodes. The
nodes transmitted to are limited by the nodes programmed into the system, the user password level,
and the nodes selected by the user.
The system reset initiated command is logged into the history manager and current event window,
if successfully completed. If this message was not completed, a error message will be displayed to
the user.
Signal Silence
Initiating a signal silence command transmits a signal silence message to all appropriate nodes.
The nodes transmitted to are limited by the nodes programmed into the system, the user password
level, and the nodes selected by the user.
2.5.1.14 Current Operator Field
The current operator field is a window that shows the name of the current operator of the NCS.
Pressing the (...) button to the right will display information about the current operator. Refer to
Figure 2.15.
ncsoper.tif
ncssysad.tif
Figure 2.17 General NCS Tab
ncssetdate.jpg
Add a user to
the NCS
Add or delete
commands from
a user account
Delete a user
from the NCS
NCSfiu5.jpg
Figure 2.20 The User Account Tab
This dialog box also lets the user add, edit and delete users from the NCS. To set up a new user on
the NCS, press the add user button. The new user dialog box appears, prompting for a new user
name (refer to Figure 2.21). Enter a user name up to 19 characters long. Check boxes allow all
system commands or all available nodes to be assigned at once to the new user account. Press OK
to accept the new user name.
To add or delete commands from a user account, press the edit user button. The account edit dialog
box appears with a listing of all commands and all nodes available on the NCS (refer to Figure
2.21). It is necessary to insert data into the screen fields that are marked with an asterisk.
NCSfiu7.jpg
Pressing a check box beside a command selects or deselects it from the user account being edited,
(Figure 2.22). All nodes available on the system are displayed in the accessible nodes section.
Only highlighted nodes are accessible to the user account. Pressing on a node selects or deselects
it. After editing the user account, press OK to accept the changes, (Figure 2.23). Initially only the
Administration Account user can edit accounts; however, any user given access to the Account
command will also have the ability to edit accounts.
Note: All nodes assigned to a given user will have the same set of commands available to them.
To delete a user account from the NCS, highlight the account and press on the delete button from
the account list dialog box.
ncspermission.jp
Figure 2.22 Editing User Information (Permission)
ncsnodes.jpg
Printer Tab
In the System Administration dialog box, under the Printer tab the user can setup the
communications port settings if the printer is connected to a call port, refer to Figure 2.24. The
NCS supports two types of printer:
• An Event (line) printer that can be attached to the COM or LPT port for printing of all events
received by the NCS.
• A Graphics Printer that can be attached to the LPT Port for printing graphics. If attached, it
must be set as the default printer.
Note: If a line and graphic printer are to be used by the NCS, event printer must be connected to a COM port.
ncsprtab.jpg
Figure 2.24 The Printer Tab
Event Printer Setup - The event printer is usually connected to the serial port, but can be
connected to the parallel port. The event printer is used to print all events as they are received by
the NCS. The printer will be activated as soon as the event is received. If the printer is connected
to a serial port, certain options must be selected. These include the communications port the printer
is connected to, the BAUD rate, the parity, the number of data bits, and the number of stop bits.
These settings must match the settings in the printer itself. If the event printer is connected to the
parallel port, these options are not applicable.
The Printer itself must be set with the same options selected here. In addition, the compressed
mode of operation (17 cpi) must be selected. This is required so that an event can be printed on a
single line. If not selected, an event will wrap to the next line.
Graphics Printer Setup - the graphics printer is a laser printer connected to the LPT port. The
setup for this printer must be done in Windows. Any Windows NT 4.0 Workstation compatible
printer that will work connected to the parallel port can be used. This printer is to be used to print
screens, any history file, and any reports generated by the NCS.
Voice Tab
There are two types of voice messages in the NCS. Those that are linked to an event or command,
and those which are linked to a device. Files which are linked to events or commands must be in
the "Waves" directory. Files which will be linked to a device must be in the "Sounds" file directory.
Refer to Figure 2.25.
Events and Command files will be activated automatically when the event happens. Separate event
files can be set up for:
• Alarm and Pre-alarm events.
• Supervisory and Security events.
• Trouble events.
• System Reset, Signal Silence and Acknowledge commands.
• Alter Status Commands (which include enabling or disabling a device and turning a module on and off).
• All Systems Normal (a message that can be invoked when the system returns to an all systems normal state).
If a higher priority event interrupts a lower priority event, the current voice message will be halted,
and the new voice message will be started.
ncsvoice.tif
Figure 2.25 Voice Tab
Graphic Configuration Tab
Under this tab the user can invoke the main screen on all systems normal, auto display guidance
text, auto display device document, play wave files, display device labels, and also print device and
guidance text and the graphic itself. Click in a box in order to put a check in the category you
would like to display or print. Refer to Figure 2.26 .
graphicstab.tif
The Network Systems Window displays the node number, node type, label, on-line status and
signal silence status in a spread-sheet like view, refer to Figure 2.27. The node type is AM2020/
AFP1010, AFP200, AFP-300/400, INA, etc. The label is a 30 character custom label local to the
NCS that can be entered by the user. The on-line status is either on-line or off-line. The signal
silence status is N/A, Normal, Partial, or Full Silence.
ncsnetop.tif
Figure 2.27 The Network Operations Menu Option
System Setup
The Network System window allows the user to add, delete and edit nodes. The LOCAL NCS
cannot be deleted from the network system window. Upon initial powerup of the software, or if the
software powers up in demo mode, the local NCS will be programmed in as node 0. The operator
must change this node number to initiate network communications. However, if the system is in
demo mode, the address cannot be changed. Nodes can be added or deleted from this list. Editing
a node will allow the user to enter the 30 character custom label, refer to Figure 2.28.
editnode.tif
Node Access
Double-clicking on a particular node in the network system window displays the initial read status
menu, if read status is supported by that node. If it is not, an error message will be displayed, refer
to Figure 2.29.
nodemess.tif
Figure 2.29 Node Access Error Message
From the initial read status menu, the user can now select further read status, alter status and
programming operations. Double-click on the local NCS for a display of the local setting for the
NCS.
In addition, right clicking on a node in the network system window opens the Read Database
Menu, from which the user can choose to view loop, zone, or device information. This information
is displayed in a spread sheet type format, and is read-only. The information is obtained from the
database which is stored on the NCS. Refer to Figure 2.30.
NOTE: THIS INFORMATION IS ONLY UPDATED DURING UPLOAD AND READ STATUS COMMANDS, AND THEREFORE MIGHT NOT
BE UP- TO-DATE.
rdatamen.tif
ncshist.tif
Figure 2.31 The Active History Database
graphmen.tif
ncsstats.jpg
Figure 2.34 Network Statistics
ncshlepmn.jpg
Figure 2.35 The Help Menu
ncssysint.jpg
Figure 2.36 The System Interface Window
Select the System Info button to access information (memory, version, processor, etc.) about the
system you are on.
N OTES...
Section 3 Operation
3.1 Normal Operation
During normal operation, when no fire alarms or troubles exist, the Graphic Interface window will
appear as shown below with an “All Systems Normal” message in top right-side of the window.
"All
Systems
Normal"
ncssysnorm.jpg
message
3.2 Troubles
When a trouble is received from a fire alarm panel it is reported to the NCS. The NCS will report
the trouble in three ways; the trouble icon in the banner will flash, the trouble will be reported in the
Events window, and it will show up in the Event Counters window. Refer to Figure 3.2.
Trouble icon
flashing in the
Banner area.
Trouble reported
in the Events
Trouble reported
Counter Box
in the Events
under New and
window.
Total categories.
Detector
showing the
reported trouble
ncstroub.jpg
Figure 3.2 Troubles Reported to the NCS
Select Acknowledge to acknowledge that a trouble has been reported. The trouble will then be
shown in the Acknowledged Events window, seeFigure 3.3. Select Signal Silence to silence
NAC’s, and select Reset to reset the control panel.
Trouble icon
stops flashing in
Trouble reported the Banner area.
in the Events
Counter Box
under the Total
category.
Trouble moves
to the
Acknowledged
Events window.
ncstrouback.jpg
3.3 Alarms
When an alarm is received from a fire alarm panel it is reported to the NCS. The NCS will report
the alarm in three ways; the alarm icon in the banner will flash, the alarm will be reported in the
Events window, and it will show up in the Event Counters window. Refer to Figure 3.4.
Alarm icon
flashing in the
Banner area.
Alarm reported
in the Events
Counter Box
under New and
Total categories. Alarm reported
in the Events
window.
Detector
showing the
reported alarm
ncsalarm.jpg
Figure 3.4 Alarms Reported to the NCS
Select Acknowledge to acknowledge that an alarm has been reported. The alarm will then be
shown in the Acknowledged Events window, see Figure 3.5. Select Signal Silence to silence
NAC’s, and select Reset to reset the control panel.
Alarm icon
Alarm reported stops flashing in
in the Events the Banner area.
Counter Box
under the Total
category.
Alarm moves to
the Acknowledged
Events window.
ncsalarmack.jpg
ncsfilemen.jpg
Figure 3.6 The File Menu
3.5.1.1 Exit
The Exit command from the file menu exits the NCS program and places the user in the Windows
NT 4.0 Workstation environment. The user is prompted for a password. After entering the correct
password a warning display indicates the user is exiting the NCS application (refer to Figure 3.7).
The user should either press Ok to exit the NCS application or press Cancel to abort.
! Caution: Leaving the NCS application disconnects the NCS from Noti•Fire•Net which leaves the
building unprotected and the NCS not performing Life Safety functions.
ncsexit.tif
Figure 3.7 The Exit Dialog Box
Asterisks are displayed in place of characters when entering a password. After selecting the user
name and entering the password, press Ok to accept the login information. If an error is made
while entering the password during login, a quick warning beep sounds, and the password dialog
box remains on the screen with the user name highlighted.
ncslgout.tif
Figure 3.9 Login Dialog Box
3.5.2.2 Logout
The Logout command is used to exit the NCS. Once logout has been selected, a dialog box appears
asking the user for the password. (refer to Figure 3.10). After entering the password, select Ok to
continue logging out. System commands will not be accessible again until a user logs onto the
NCS.
ncslgout.tif
Figure 3.10 Logout Dialog Box
3.5.2.3 Change Password
The Change Password command allows a user to change their current password. A password can
only be changed by the user who owns the password. Not even the Administration Account user
(the top user account with permanent access to all NCS commands) can change another user's
password.
When the Change Password command is selected, the change password dialog box (refer to Figure
3.11) prompts the user for old and new passwords. Asterisks will appear in place of the entered
characters for both the old and new passwords. Type the old password. Type the new password
and then retype it in the confirm password box to verify the first entry. Press OK to accept the new
password information. ncschpas.tif
offline events, show offline events and perform a data refresh, refer to Figure 3.12.
ncsactin.tif
Figure 3.12 The Action Menu
Data Refresh - Is manually initiated from the NCS to update the off-normal points in the NCS.
This is also automatically done when the NCS is powered up. The NCS has the capability to
initiate a data refresh to five nodes simultaneously to update point information as fast as possible.
These menu options can also be accessed from the NCS Interface Window, Refer to “NCS
Graphical User Interface” on page 22 where they are explained in greater detail.
Figure 3.14.
ncsecoun.tif
Figure 3.14 Event Counters Dialog Box
Event counters are not permanently displayed on the Graphics Screen but invoked when prompted
by the user.
3.5.4.2 The Detailed Events Window
The Detailed Events Window is an advanced Signal Display interface to networked panels. The
Detailed Events Command is displayed from the View Menu in the Start-up Window. The Detailed
Events Window contains all off-normal events, both unacknowledged and acknowledged, that are
currently present in the system, refer to Figure 3.15. It is made up of two parts, “Fire Events and
Non-Fire Events.” Two buttons are provided to toggle between these two parts of the window. The
Fire Events window contains all events that are normally displayed by the fire panel in its display,
which includes all alarm and trouble conditions. Non-Fire Events consist of all events that are only
reported to the history buffer and printer of the fire-panel, such as speaker circuits, and non-
reporting control modules, as well as zone activation.
Select the
blue
button to
view all
non-fire
events.
detailev.tif
Figure 3.15 The Detailed Events Dialog Box (Fire Events Shown)
A scroll bar will be provided if more events are present in the system that can be displayed at one
time. The events are sorted by event type (fire alarm, security alarm, supervisory alarm, trouble,
pre-alarm, acknowledged alarm, acknowledged security alarm, acknowledged supervisory alarm,
acknowledged trouble, and acknowledged pre-alarm) and time. This dialog box will be displayed
in the same position as when previously closed. If left open, it will be refreshed every 6 seconds,
and only if new events of equal or lower priority were received by the NCS. If higher priority
events were received, this window would be updated immediately.
All information received from the node that the event happened on will be displayed in this box.
This includes the event type, the device type, the device label, the first zone referenced in the CBE
equation (for panels that provide this information), the first zone label (for panels that provide this
information), the trouble type (for trouble conditions), the time and date (assigned by the NCS), and
a panel specific type index. This box will be updated during receipt of normal events, as well as
during a data refresh operation. In the latter case most of the information will not be available, and
only the information that is available will be displayed. The NCS provides the ability to print all
events in the Detailed Event box.
ncscurrt.tif
Figure 3.16 Current Events Dialog Box
The user has the option to leave this window on top. This window will also always be displayed in
the same position as when previously closed.
3.5.4.4 Disabled Device Window
The disabled device window contains all disabled devices in the system. A disabled device can be
directly selected (double-clicked) from the list of events, and re-enabled. A confirmation dialog
box will be displayed, confirming the enable command. If the point enabled is a AM2020 or
AFP1010 zone, right clicking on the point will bring up another menu. This menu will give the
user an option of using the Zone Enable or Group Zone Enable command for the zone. All zones
will be colored to make them stand out within the window.
ncsdisdv.tif
ncsarrow.tif
Figure 3.18 The Screen Navigation Menu
ncsarrow.tif
Figure 3.19 Next and Previously Viewed Arrow Keys
ncsdetread.jpg
Figure 3.20 Detector Read Status
Control and Monitor Modules
To perform Read Status on a module in the system, select the node the module is connected to from
the Select System dialog box. Select OK. A node dialog box will appear. Select the Module tab.
Enter the address of the module desired to perform Read Status. Select Program. The Module
dialog box will appear. This dialog box displays the current programming for the module and
whether the module is in alarm, trouble, or disabled (refer to Figure 3.21).
ncsmodread.jpg
Figure 3.21 Monitor Module read Status
Zones
To perform Read Status on an AM2020/AFP1010 zone in the system, select the node the zone is
connected to from the Select System dialog box. Select OK. A node dialog box appears. Select
the Zone tab. Enter the zone number desired to perform Read Status. Select Program. The Zone
dialog box will appear. This dialog box displays the current programming for the zone and whether
the zone is in alarm, trouble, or is disabled (refer to Figure 3.22).
ncszonerd.jpg
To perform Read Status on an annunciator point, select the Annunciator tab from the Node dialog
box. Enter the address of the point desired to perform Read Status. Select Program. The
Annunciator Point dialog box displays. This dialog box shows the type of annunciator point and
whether it is in Alarm, Trouble, or Off (refer to Figure 3.23).
ncsannunrd.jpg
Figure 3.23 Annunciator Point Read Status
System Data I
ncssysdat1.jpg
ncssysdat2.jpg
Figure 3.25 System Data II Point Read Status
System Data III
Notes...
history.tif
Figure 4.1 Current History Database
To maximize operations while the History Manager is running, new events of equal or lower
priority, will not automatically be shown. Instead, a “Refresh Grid” button will indicate if new
events have been received. If this button is grayed out, the History Manager is showing all events
that have been received. If this button is not grayed out, then new events have been received by the
NCS, but are not currently being displayed by the History Manager. Once this button is pressed,
the History Manager will query the database to show the new events received, and vector to the top
of the page and display them, refer to Figure 4.2
refresh.tif
archivhs.tif
Figure 4.3 Opening a Archived History File
archive.tif
operlis.tif
Figure 4.5 Example of an Operator List Dialog Box
Number of Events
The number of entries in the history database is shown at all times. If a custom filter view is
selected, the number of entries will be equal to the number of events shown, refer to Figure 4.6.
numevnt.tif
Note: The events marked * may be combined with any other search criteria.
Searching and displaying events in the history manager won’t adversely affect the NCS operation.
Any operation of this type is conducted as a low priority event. Refer to Figure 4.7 for an example
of search dialog box and Figure 4.8 for a search showing only Administration logins.
custfilt.tif
Figure 4.7 Example of a Search Dialog Box
custadmn.tif
viscolm.tif
Figure 4.9 Select Visible Columns Dialog Box
Printing
The current history database, or any stored database, can be printed to the NCS Graphics printer
connected to the NCS. The Print command located under the File menu invokes the common
printer dialog box, (refer to Figure 4.10) enabling the selection of a printer. The printout consists of
the information shown in the history manager. Columns that are not visible, will not print out. If a
custom filter has been selected, only the events that are a part of the filter will be printed.
hisprint.tif
hisback.tif
Figure 4.11 Archive History Dialog Box
Automatic History Backup
The NCS can be automatically setup to back up a history file when the NCS reaches a user
selectable number of entries, with ranges from 10,000 to 100,000 events. In addition, the history
database can be backed up any day of the month, ranging from 1 to 28.
The current history file will be saved to a file name made up of the current date with a “a” prefix,
denoting an automatic backup. If more the one backup has occurred in any given day, a “01” will
be added to the file. For example, “a061298-1-.his” indicates the first file backed up automatically
on June 12th, 1998. A “a061298-2.his” file indicates that a second file was backed up that day.
The path and filename of the old history file will be saved in the new history file. All history files
are backed up in the \{install}\HistoryArchives directory.
4.1.1.1 Upload/Download (UPDL)
The upload / download window is used to upload or download the database from a node. Options
are available to initiate uploads, downloads, schedule uploads, and abort any current actions.
Information about the node number, status indication and progress indication will be displayed by
the upload / download. Select UPDL under the View menu option and a Main Screen will appear
showing nodes and their completion percentage, refer toFigure 4.12.
ncsudmain.jpg
All upload / download messages that affect the operation are stored in the history window and
current event window. This includes initiating the upload / download process, aborting the process,
or any errors that will prohibit the process from completing successfully. A message will also be
stored in these windows if the upload / download has successfully completed.
Upload - Before an upload is initiated, the NCS will query the user for a database file to store the
received information in. All uploaded information, including the database version, will first be
stored in the NCS run-time database. After the upload is complete, the NCS will copy the
information for the node upload from the run-time database to the database specified by the user.
Refer to Figure 4.13 for an example screen of uploading nodes.
ncsupload.jpg
Figure 4.13 Uploading Nodes Screen
If the database specified is an older version, an error dialog box will be displayed, indicating the
problem. The upload is not allowed to proceed at this time. The Verifire utility has the ability to
convert an older database format to the current database format.
Download - The NCS will query the user for a database to download. It will open the database
specified, and check the version. If the database version is old, the NCS will display an error dialog
box indicating the problem. The user is not given the option to continue the download. Refer to
Figure 4.14 for an example of a download screen.
ncsudown.jpg
Note: The Verifire utility has the ability to convert an older database format to the current database format.
Scheduled Uploads - The NCS has the ability to schedule uploads on a monthly or “one shot”
basis. The one shot will provide the ability to schedule a set of panels to upload only once. Options
will be made available for the starting time and which nodes to upload. If a monthly upload is
selected, the day and time must be specified. If a one shot upload is specified, the exact data and
time must be specified. All scheduling options, including dates, times, and nodes selected, will be
NCS database.
ncssched.jpg
Figure 4.15 Scheduled Uploads Screen
• Once Only Upload - This option will allow the user to upload a set of panels on a “one-shot” basis. A date and time for
the upload is entered and the NCS initiates the upload at that time.
• Monthly - The NCS has the ability to schedule uploads on a monthly basis. The user can select the day of the month
and time to upload. The NCS can then upload the specified set of nodes every month at the specified time. To alleviate
the problem of how many days are in a month, the plug-in only allows a range of 1 - 28 for the day specified.
• Multiple Panel Upload - The NCS has the capability of uploading or downloading up to five nodes at a time.
Menu Bar
Key-Map Area
Toolbar
Graphics Area
Tree View Window
(Screen Device View)
ncsgspint.jpg
ncstree.jpg
Figure 5.2 Floor Plan Screen Tree View Example
ncsgrview.jpg
infowin.jpg
Figure 5.5 The Information Window
Double-clicking on any of these fields displays a file dialog box. This allows the user to change the
keymap or floor plan, select a new guidance text file, or change the name of the screen that is
currently edited, refer to Figure 5.6 for an example. If a floor plan is changed, a “Save Screen”
option appears, refer to Figure 5.7, allowing the user to save all current changes. This option only
appears if changes have been made to the current screen. In addition, double clicking on the floor
screen name in the Tree View Window also saves any current changes that have been made.
selectfl.jpg
Figure 5.6 File Dialog Box savescrn.jpg
Create Group
If a template group is defined, then pressing the short cut button will display a dialog box from
which a template can be chosen. If a template is not defined, then the first 40 items in the directory
will be displayed in a picture box. For example, if the Create Zones Button is pressed, and no
templates are defined, the first 40 icons found in the device directory will be displayed in a picture
box. However, if templates are defined, a selection of all zone templates will be shown. After a
template is chosen, only the icons associated with that template will be displayed. Select a toolbar
icon and a library of icons associated with that button will appear. Choose an icon by clicking on it
and dragging it to a location on the floor plan screen.
floorpl.jpg
If a new floor plan or keymap is to be added, a blank floor plan and key map will appear with the
floor plan title. This floor plan can be altered entirely in PaintShop Pro, or in other graphic
programs such as Paint and then pasted into the screen. Double-clicking on a floor plan or keymap
will invoke PaintShop Pro where any changes or edits can be made to the drawing. When
PaintShop Pro is exited, the file date and time are checked on the hard drive. If the date or time of
the file has changed, the bitmap is copied over the existing floorplan and displayed in the GUI.
Each screen contains a floorplan, keymap, screen description and guidance text. Although each
floor plan has a corresponding numeric identifier assigned to it, only the screen name is displayed
on the NCS main form. The Graphic Setup Program displays the name of the current screen, as
well as the floor plan filename, the keymap filename, and the guidance text file name that is
associated with the screen.
delsrdi.jpg
Figure 5.13 Deleting a Floor Plan Confirmation Dialog Box
gspkeymplk.jpg
gspfile.jpg
Figure 5.16 The File Menu
5.4.2 Screens
Under the Screens menu option, the user can create a new graphic screen, select a previous graphic
screen, delete a graphic screen or set a keymap link to a graphic screen, see Figure 5.17.
gspscreen.jpg
5.4.3 Devices
gspdevice.jpg
gspgrpsetup.jpg
Figure 5.20 Setting Up Groups
gspdevdet.jpg
Figure 5.21 Detectors
gspdevmod.jpg
gspdevinfol.jpg
Figure 5.24 Information Labels
gspdevnb.jpg
Figure 5.25 Navigation Buttons
5.4.4 View
The View menu option allows the user to customize the toolbar to the users preference and view
screen statistics. Screen statistics include: device (detectors, modules, zones) count, graphic
(labels, navigation buttons) count and a Total count (combination of both).
gspview.jpg
5.4.5 Setup
The Setup menu allows the user to edit the site logo in Paint Shop Pro.
setupmenu.jpg
5.4.6 Help
gsphelp.jpg
Figure 5.28 The Help Menu
5.5.1 Devices
A symbol can be used to graphically represent a device (detector, module or zone) in the fire alarm
system. In addition to a graphical representation of the device, the user can assign device
descriptions and link pictures, documents and sound to the device. The NCS does not permit one
device to be displayed on multiple screens; a device can only appear on one screen.
A new device can be added to the system by using the Devices Menu command or through the
toolbar. When using the toolbar, select the appropriate detector, module or zone you would like to
add. After this command is executed, a library of icons will be displayed to select a symbol
representing the device, refer to Figure 5.29.
detbox.jpg
newdetbx.jpg
Figure 5.30 New Detector Dialog Box
The active icon will blink during an active condition, and steady when acknowledged. Once the
point returns to normal, the normal bitmap is displayed. The trouble, disabled device and pre-alarm
icons also operate the same way.
5.5.2 Detectors
Detectors have other symbols associated with them; an active icon, a trouble icon, a disabled
device icon and a pre-alarm icon. The appropriate icon will be displayed for an event, the device
label blinks if an event is unacknowledged, and is steady if the event is acknowledged.
5.5.3 Modules
Modules show an active, trouble and disabled device symbol. If the module can be disabled from
the NCS, the Disable Device option must be chosen. If the module is an output module, and can be
activated from the NCS, then the Control On/Off option must be chosen.
5.5.4 Zones
A zone shows an active and disabled device symbol.
infolbl.jpg
Figure 5.31 Information Labels Dialog Box
To add an information label under the Devices menu option, select the Information Label option to
the New Information Label command, or select the information label icon on the toolbar. After this
command is executed, a library of icons will be displayed to select a symbol representing the
information label. If template groups are defined for that label, then a group must be chosen before
a label is selected. Once a label is selected, a new label dialog box will be displayed where the user
can enter text information about the information label.
Double-click on a device label icon and drag it to the corresponding area on the graphic floor plan,
it will then appear on the screen. Double-click on the information label in the NCS to display the
text file associated with the information label. Information labels can be moved around the screen
without being deleted and recreated.
navbut2.jpg
Figure 5.33 Setup Links Dialog Box
5.6 Groups
Groups allow the creation of screen hierarchies for displaying the pathway to an off normal device,
starting at a top level site view. Two levels of grouping, Level 1 and Level 2, are used to associate
devices with a single bitmap. A Level 1 group can have either Level 2 groups or actual devices
associated to it. A Level 2 group must be associated upwards to a Level 1 group (in the floor plan
hierarchy), and will have devices associated below it. The two levels of grouping plus the floor
plan where the actual off-normal device is located offer three main view levels for floor plan
navigation. These levels coupled with Navigation Buttons offer a variety of setup possibilities for
graphics.
The graphics are no longer limited to one top screen, therefore the “Home Screen” is the first screen
created. This screen is shown on NCS / GSP Startup. This ability to have many top screens means
that Level 1 Groups can exist on different screens, each representing the Top Screen of a different
graphic path.
A hot template is defined for a specific device, (the hot template and the device are actually one item).
This allows the user to easily copy information from one device to another. Once the information for
a device hot template is changed, all new devices created from it will have the new information.
Devices created with the hot template before it was changed will not contain the new information.
editncsg.jpg
4. Keymap Directories
{install}\Keymaps\Genkey.bmp
\Olefloor.bmp
\NotProgK.bmp
5. Device Directories
{install}\Device...Detector, Module, Zone BMP’s
\Group...Group BMPs
\Inflabel...Device Information label BMPs
\Navigate...Device navigation button BMPs
\Pictures...Device associated bitmaps
\Sounds...Device wave files
\Docs...all text files
Note: Groups and Group screens should be created first if grouping is to be used.
AutoAdminLogon:REG_SZ:1
DefaultPassword:REG_SZ:<password> (Password is the password entered by the
administrator in Step 6.)
9. Exit the Windows 2000 Registry, and reboot Windows 2000. When it starts, the log-on screen
should be bypassed.
AFP-200 Type
AFP-200 Message NCS Message
I.D.
Supervisory activated: ACTIVE SUPERVISORY custom point label activated: Supervisory Sprvsry Mntr custom point label
zone label 01:40P 3/06/00 M04 zone label N12L1M4 13:40:00 3/06/00
trouble: TROUBL SUPERVISORY custom point label zone trouble: Trouble Supervisory Sprvsry Mntr custom point
label OPEN CIRCUIT 02:07P 3/06/00 M04 label zone label Open Circuit N12L1M4 14:07:00 3/06/00
Tamper activated: ACTIVE TAMPER custom point label zone label activated: Supervisory Sprvsry Mntr custom point label
02:20P 3/06/00 M05 zone label N12L1M5 14:20:00 3/06/00
trouble: TROUBL TAMPER custom point label zone label trouble: Trouble Supervisory Sprvsry Mntr custom point
OPEN CIRCUIT 02:43P 3/06/00 M05 label Open Circuit zone label N12L1M5 14:43:00 3/06/00
Non-Fire activated: ACTIVE NONFIRE custom point label zone label activated: *Active Non Alarm custom point label zone
02:07P 3/06/00 M06 label N12L1M6 13:10:00 15/06/00
trouble: TROUBL NONFIRE custom point label zone label trouble: Trouble Non Alarm custom point label zone label
OPEN CIRCUIT 02:21P 3/06/00 M06 Open Circuit N12L1M6 14:21:00 3/06/00
Hazard Alert activated: ACTIVE HAZARD ALERT custom point label activated: Supervisory Hazard Alert custom point label
zone label 02:33P 3/06/00 M07 zone label N12L1M7 14:33:00 3/06/00
trouble: TROUBL HAZARD ALERT custom point label trouble: Trouble Supervisory Hazard Alert custom point
zone label OPEN CIRCUIT 02:47P 3/06/00 M07 label zone label Open Circuit N12L1M7 14:47:00 3/06/00
Fire Control activated: ACTIVE FIRE CONTROL custom point label activated: *Active Non Alm Mon custom point label zone
zone label 03:21P 3/06/00 M08 label N12L1M8 15:21:00 3/06/00
trouble: TROUBL FIRE CONTROL custom point label trouble: Trouble Non Alm Mon custom point label zone
zone label OPEN CIRCUIT 03:35P 3/06/00 M08 label Open Circuit N12L1M8 15:35:00 3/06/00
Abort Switch activated: ACTIVE ABORT SWITCH custom point label activated: *Active Abort Switch custom point label zone
zone label 03:07P 3/06/00 M09 label N12L1M9 15:07:00 3/06/00
trouble: TROUBL ABORT SWITCH custom point label trouble: Trouble Supervisory Hazard Alert custom point
zone label OPEN CIRCUIT 04:17P 3/06/00 M09 label zone label Open Circuit N12L1M9 16:17:00 3/06/00
Man. Release activated: ALARM: MAN. RELEASE custom point label activated: Alarm: Man Release custom point label zone
zone label 04:34P 3/06/00 M10 label N12L1M10 16:34:00 3/06/00
trouble: TROUBL MAN. RELEASE custom point label trouble: Trouble Man Release custom point label zone
zone label OPEN CIRCUIT 04:58P 3/06/00 M10 label Open Circuit N12L1M10 16:58:00 3/06/00
Trouble Mon activated: TROUBL TROUBLE MON custom point label activated: Trouble Trbl Monitor custom point label zone
zone label SHORT CIRCUIT 08:24A 3/06/00 M12 label N12L1M12 08:24:00 3/06/00
trouble: TROUBL TROUBLE MON custom point label trouble: Trouble Trbl Monitor custom point label zone
zone label OPEN CIRCUIT 08:36A 3/06/00 M12 label Open Circuit N12L1M12 08:36:00 3/06/00
Burglar Ala activated: ACTIVE BURGLAR ALA custom point label activated: Security Area Monitor custom point label zone
zone label 08:52A 3/06/00 M13 label N12L1M13 08:52:00 3/06/00
trouble: ACTIVE BURGLAR ALA custom point label zone trouble: Trouble Security Area Monitor custom point label
label 09:33A 3/06/00 M13 zone label Security Tamper N12L1M13 09:33:00 3/06/00
Silence activated: ACTIVE SILENCE custom point label zone label activated: *Active Silence custom point label zone label
11:34A 3/06/00 M14 N12L1M14 11:34:00 3/06/00
trouble: TROUBL SILENCE custom point label zone label trouble: Trouble Silence custom point label zone label
OPEN CIRCUIT 11:45A 3/06/00 M14 Open Circuit N12L1M14 11:45:00 3/06/00
Pas Inhibit activated: ACTIVE PAS INHIBIT custom point label zone activated: *Active Pas Inhibit custom point label zone label
label 12:04P 3/06/00 M15 N12L1M15 12:04:00 3/06/00
trouble: TROUBL PAS INHIBIT custom point label zone trouble: Trouble Pas Inhibit custom point label zone label
label OPEN CIRCUIT 12:10P 3/06/00 M15 Open Circuit N12L1M7 12:10:00 3/06/00
*Will be displayed only in History Manager, Current Event window and NonFire Event window in the NCS
AFP-200 Type
AFP-200 Message NCS Message
I.D.
System Reset activated: ACTIVE SYSTEM RESET custom point activated: *Active System Reset custom point label zone
label zone label 12:21P 3/06/00 M16 label N12L1M16 12:21:00 3/06/00
trouble: TROUBL SYSTEM RESET custom point label trouble: Trouble System Reset custom point label zone
zone label OPEN CIRCUIT 12:39P 3/06/00 M16 label Open Circuit N12L1M16 12:39:00 3/06/00
Smoke Detect activated: ALARM: SMOKE DETECT custom point activated: Alarm: Smoke Detect custom point label zone
label zone label 12:46P 3/06/00 M17 label N12L1M17 12:46:00 3/06/00
trouble: TROUBL SMOKE DETECT custom point trouble: Trouble Smoke Detect custom point label zone
label zone label OPEN CIRCUIT 02:06P 3/06/00 M17 label Open Circuit N12L1M17 14:06:00 3/06/00
Heat Detect activated: ALARM: HEAT DETECT custom point activated: Alarm: Heat Detect custom point label zone label
label zone label 02:16P 3/06/00 M18 N12L1M18 14:16:00 3/06/00
trouble: TROUBL HEAT DETECT custom point label trouble: Trouble Heat Detect custom point label zone label
zone label OPEN CIRCUIT 02:26P 3/06/00 M18 Open Circuit N12L1M18 14:26:00 3/06/00
Water Flow activated: ALARM:WATERFLOW custom point label activated: Alarm: Water Flow custom point label zone label
zone label 03:18P 3/06/00 M19 N12L1M19 15:18:00 3/06/00
trouble: TROUBL WATERFLOW custom point label trouble: Trouble Water Flow custom point label zone label
zone label OPEN CIRCUIT 03:28P 3/06/00 M19 Open Circuit N12L1M19 15:28:00 3/06/00
Pre-Alarm activated: PREALM SMOKE (PHOTO) custom point activated: Pre Alarm Smoke (Photo) AFP200 PREALM
label ALERT: 1.31/1.50% 05:21P 3/06/00 D01 ALERT Pre-Alarm Alert N12L1D1 17:21:00 3/06/00
AFP-300/400
AFP-300/400 Message NCS Message
Type I.D.
Smoke Detect alarm (short): ALARM: Smoke Detect device label zone alarm (short): Alarm: Smoke Detect device label zone
label 01:27:00p 03/07/00 M121 label N232L1M21 13:27:00 03/07/00
trouble: TROUBLE SMOKE DETECT device label trouble: Trouble Smoke Detect device label Invalid Reply
Z05 INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Heat Detect alarm (short): ALARM: HEAT DETECT device label alarm (short): Alarm: Heat Detect device label zone label
zone label 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
trouble: TROUBL HEAT DETECT device label Z05 trouble: Trouble Heat Detect device label Invalid Reply
INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Pull Station alarm (short): ALARM: PULL STATION device label alarm (short): Alarm: Pull Station device label zone label
zone label 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
trouble: TROUBL PULL STATION device label Z05 trouble: Touble Pull Station device label Invalid Reply
INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Monitor alarm (short): ALARM: MONITOR device label zone alarm (short): Alarm: Monitor device label zone label
label 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
trouble: TROUBL MONITOR device label Z05 trouble: Trouble Monitor device label Invalid Reply
INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
(blank) alarm (short): ALARM: device label zone label alarm (short): Alarm device label zone label N232L1M21
01:27:00p 03/07/00 M121 13:27:00 03/07/00
trouble: TROUBL device label Z05 INVALID REPLY trouble: Trouble device label Invalid Reply N232L1M21
01:27:00p 03/07/00 M121 13:27:00 03/07/00
Abort Switch alarm (short): ACTIVE ABORT SWITCH device label alarm short: Active Abort Switch device label zone label
zone label 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
trouble: TROUBL ABORT SWITCH device label Z05 trouble: Trouble Abort Switch device label Invalid Reply
INVALID REPLAY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Man. Release alarm (short): ALARM: MAN. RELEASE device label alarm (short): Alarm: Man. Release device label zone label
zone label 01:27p 03/07/00 M121 N232L1M21 01:27:00 03/07/00
trouble: TROUBL MAN. RELEASE device label Z05 trouble: Trouble Man. Release device label Inalid Reply
INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Silence alarm (short): ACTIVE SILENCE device label zone alarm (short): Active Silence device label zone label
label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
trouble: TROUBL SILENCE device label Z05 trouble: Trouble Silence device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
System Reset alarm (short): ACTIVE SYSTEM RESET device label alarm (short): Active System Reset device label zone label
zone label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
trouble: TROUBL SYSTEM RESET device label Z05 trouble: Trouble System Reset device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
Security alarm (short and open): ACTIVE SECURITY device alarm (short and open): Security Burglar Ala device label
label zone label 12:40:00p 03/07/00 M121 zone label N232L1M21 12:40:00 03/07/00
trouble: TROUBL SECURITY device label Z05 trouble: Trouble Burglar Ala device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
Trouble MON alarm (short): TROUBL TROUBLE MON device label alarm (short): Troubl Trouble Mon device label Short
Z05 SHORT CIRCUIT 12:40:00p 03/07/00 M121 Circuit N232L1M21 12:40:00 03/07/00
trouble: TROUBL TROUBLE MON device label Z05 trouble: Trouble Trouble Mon device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00:00 03/07/00
PAS Inhibit alarm (short): ACTIVE PAS INHIBIT device label zone alarm (short): Active Pas Inhibit device label zone label
label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
trouble: TROUBL PAS INHIBIT device label Z05 trouble: Trouble Pas Inhibit device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
AllCall Page alarm (short): ACTIVE ALLCALL PAGE device label alarm (short): Active Allcall Page device label zone label
zone label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
trouble: TROUBL ALLCALL PAGE device label Z05 trouble: Trouble Allcall Page device label INVALID
INVALID REPLY 12:40:00p 03/07/00 M121 REPLY N232L1M21 12:40:00 03/07/00
AFP-300/400
AFP-300/400 Message NCS Message
Type I.D.
Tamper alarm (short): ACTIVE TAMPER device label zone label alarm (short): Supervisory Tamper device label zone label
12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
trouble: TROUBL TAMPER device label Z05 INVALID trouble: Trouble Tamper device label Invalid Reply N232L1M21
REPLY 12:40:00p 03/07/00 M121 12:40:00 03/07/00
Fire Control alarm (short): ACTIVE FIRE CONTROL device label alarm (short): Active Fire Control device label zone label
zone label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
trouble: TROUBL FIRE CONTROL device label Z05 trouble: Trouble Fire Control device label Invalid Reply
INVALID 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
Tele. Page alarm (short): ACTIVE TELE. PAGE device label zone alarm (short): Active Tele. Page device label zone label
label 03:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
trouble: TROUBL TELE. PAGE device label Z05 trouble: Trouble Tele Page device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Comb. Monitor alarm (short): ALARM: COMB. MONITOR device label alarm (short): Alarm: Comb Monitor device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
trouble: TROUBL COMB. MONITOR device label Z05 trouble: Trouble Comb. Monitor device labelInvalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Sprinkler Sys alarm (short): ALARM: SPRINKLER SYS device label alarm (short): Alarm: Sprinkler Sys device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
trouble: TROUBL SPRINKLR SYS device label Z05 trouble: Trouble Sprinklr Sys device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Second Shot alarm (short): ACTIVE SECOND SHOT device zone alarm (short): Active Second Shot device label zone label
label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
trouble: TROUBL SECOND SHOT device label Z05 trouble: Trouble Second Shot device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Man Rel Dlay alarm (short): ALARM : MAN REL DLAY device label alarm (short): Alarm: Man Rel Dlay device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
trouble: TROUBL MAN REL DLAY device label Z05 trouble: Trouble Man Rel Dlay device label Invalild Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Hazard Alert alarm (short): ACTIVE HAZAD ALERT device label alarm (short): Supervisory Hazard Alert device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
trouble: TROUBL HAZARD ALERT device label Z05 trouble: Trouble Hazard Alert device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Supervisory alarm (short): ACTIVE SUPERVISORY device label alarm (short): Supervisory Supervisory device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
trouble: TROUBL SUPERVISORY device label Z05 trouble: Trouble Supervisory device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Waterflow alarm short: ALARM: WATERFLOW device label zone alarm (short): ALARM: WATER FLOW device label zone label
label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
trouble: TROUBL WATERFLOW device label Z05 trouble: Trouble Water Flow device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Control on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00
trouble: TROUBL CONTROL device label Z05 trouble: Trouble Control device label Invalid Reply N232L1M1
INVALID REPLY 12:07:00P 3/16/00 M101 12:07:00 3/16/00
Relay on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00
trouble: TROUBL RELAY device label Z05 INVALID trouble: Trouble Relay device label Invalid Reply N232L1M1
12:07:00 3/16/00
Bell Circuit on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00
trouble: TROUBL BELL CIRCUIT device label Z05 trouble: Trouble Bell Circuit device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00
*All AFP300/AFP400 messages that say 'No Annunciation' will be displayed in the History Buffer, only.
AFP-300/400
AFP-300/400 Message NCS Message
Type I.D.
Strobe Ckt on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00
trouble: TROUBL STROBE CKT device label Z05 trouble: Trouble Strobe Ckt device label Invalid Reply N232L1M1
INVALID REPLY 12:07:00P 3/16/00 M101 12:07:00 3/16/00
Horn Circuit on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00
trouble: TROUBL HORN CIRCUIT device label Z05 trouble: Trouble Horn Circuit device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00
Audible Ckt on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00
trouble: TROUBL AUDIBLE CKT device label Z05 trouble: Trouble Audible Ckt device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00
Rel End Bell on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00
trouble: TROUBL REL END BELL device label ZR1 trouble: Trouble Rel End Bell device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00
Release Ckt on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00
trouble: TROUBL RELEASE CKT device label ZR1 trouble: Trouble Release Ckt device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00
Rel Ckt Ulc on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00
trouble: TROUBL REL CKT ULC device label ZR1 trouble: Trouble Rel Ckt ULC device label Invalid Reply
INVALID REPLY 04:55:00P 3/16/00 M101 N232L1M1 16:55:00 3/16/00
Rel Audible on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00
trouble: TROUBL REL AUDIBLE device label ZR1 trouble: Trouble Rel Audible device label Invalid Reply
INVALID REPLY 04:55:00P 3/16/00 M101 N232L1M1 16:55:00 3/16/00
Nonreset Stl on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00
trouble: TROUBL NONRESET CTL device label Z05 trouble: Trouble Nonreset Ctl device label Invalid Reply
INVALID REPLY 04:55:00P 3/16/00 M101 N232L1M1 16:55:00 3/16/00
Telephone on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00
trouble: TROUBL TELEPHONE device label Z05 trouble: Trouble Telephone device label Invalid Reply N232L1M1
INVALID REPLY 04:55:00P 3/16/00 M101 16:55:00 3/16/00
Rel Code Bell on: No Annunciation* on: Active AFP400 Output Device N232B1 16:55:00 3/16/00
trouble: TROUBL REL CODE BELL device label ZR1 trouble: Trouble Rel Code Bell device label Invalid Reply
N232B1 16:55:00 3/16/00
Instant Rele on: No Annunciation* on:Active AFP400 Output Device N232L1M21 04:55:00P 3/16/00
trouble: TROUBL INSTANT RELE device label Z05 trouble: Instant Rele device label Invalid Reply N232L1M1
INVALID REPLY 04:55:00P 3/16/00 M101 16:55:00 3/16/00
Relea Form C on: No Annunciation* on: Active AFP400 Output Device N232L1M21 16:55:00 3/16/00
trouble: TROUBL RELEA FORM C device label Z R1 trouble: Trouble Relea Form C device label Invalid Reply
INVALID REPLY 04:55:00P 3/16/00 M101 N232L1M21 16:55:00 3/16/00
Speaker on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00
trouble: TROUBL SPEAKER device label Z05 trouble: Trouble Speaker device label Invalid Reply N232L1M1
INVALID REPLY 04:55:00P 3/16/00 M101 16:55:00 3/16/00
*Any AFP-300/AFP400 messages that say 'No Annunciation' will be displayed in the History Buffer, only.
Notes
B
key map, setting links 65
Graphic Setup Program (GSP) 35, 60–75
Information Window 60, 61
Banners 23, 26, 38, 39, 41
C
key map area 60
Menu Bar 60, 66–69
Toolbar 60, 62
Caution Tree View Window 60
case sensitivity, printer installation 18 Graphical User Interface 22
conduit size 9 graphics events window 23
door over CD drive 18 Groups 73
exiting the NCS 18, 21, 41 Level 1 73
NCS Demo mode 22 Level 2 73
Run NCS software alone 22 Navigation 73
The NCS Communications Driver may have to be changed... setup restrictions 73
17 Guidance Text 65
colors, PC 16
column types, visibility 55
command area 26
H
Help menu 36
communications port settings 31 hierarchies, screen 73
Compact Database 35 History Backup option 28
current event window 45 History Manager 52–59
current operator field 27 database 52
Current Users list 29 display priority 52
to edit 29
D
Open Archived History File 53
Operator List 53
Refresh Grid 52
data refresh 21, 28, 43 search criteria 54
database 20 stand alone operation 54
graphics 21 History Manager window 45
history 21 Home Screen 73
history, archiving 35, 56 HSP-121B power line protector 9, 10
printing 56
see also History Manager
Upload/Download (UPDL) fron node 57
I
INA 12, 20, 33, 46, 78
Date / Time Field 25 Information Labels 70
DB-15 video cable 10 adding 71
demo mode 33 deleting 72
Detailed Events window 44
Non-Fire Events 44
Device Icons 69
J
Junction Box 9, 10
K
adding 69
deleting 72
Find command 72
linked files 70 key map area 24, 66
setup rules 72 see also Graphic Setup Program
L zone 48
Read/Write CD ROM 18
Logo Window 26 Related Documentation 7
U
Paint Shop Pro 63, 66
Installation 77 UPS 8, 10
PaintShop Pro 75 UPS Supervision 12, 13, 28
password 41, 42
changing 42 V
PCLB-6 enclosure 9 voice messages 31
Port thresholds 28 "Sounds" directory 31
Power-Up Initialization 21 "Waves" directory 31
pre-alarm signal 41 edit speech files 35
acknowledging 41
reporting 41
printer 8
W
Warning
graphic 17, 31 Improper voltage selection 9
line 17, 31 Windows 2000 16
line, cable connections 15 Windows 2000 Workstation
PRN-5 8 Disable Procedure 76
setup 31 Windows NT Workstation 22
UPS Supervision 13
Programming 20
Menu Options 27
R
Read Status 47
annunciator point 49
module 47
System Data 49
WarNL-2001-9.fm 8/31/2001
www.PDF-Zoo.com
World Headquarters NOTIFIER is an operation of
12 Clintonville Road
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.notifier.com
www.PDF-Zoo.com