You are on page 1of 88

Network Control Station

NCS

Document 51095
3/08/02 Revision:
ECN 02-074
B1
www.PDF-Zoo.com
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control with remote notifica- mined rate or reaches a predetermined level. Rate-of-rise
tion capability—can provide early warning of a developing fire. heat detectors may be subject to reduced sensitivity over time.
Such a system, however, does not assure protection against For this reason, the rate-of-rise feature of each detector
property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufac- same room as the control panel and in rooms used by the sys-
turer's recommendations, State and local codes, and the rec- tem for the connection of alarm transmission wiring, communi-
ommendations contained in the Guide for Proper Use of cations, signaling, and/or power. If detectors are not so
System Smoke Detectors, which is made available at no located, a developing fire may damage the alarm system, crip-
charge to all installing dealers. A study by the Federal Emer- pling its ability to report a fire.
gency Management Agency (an agency of the United States Audible warning devices such as bells may not alert people
government) indicated that smoke detectors may not go off in if these devices are located on the other side of closed or
as many as 35% of all fires. While fire alarm systems are partly open doors or are located on another floor of a building.
designed to provide early warning against fire, they do not Any warning device may fail to alert people with a disability or
guarantee warning or protection against fire. A fire alarm sys- those who have recently consumed drugs, alcohol or medica-
tem may not provide timely or adequate warning, or simply tion. Please note that:
may not function, for a variety of reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or “smoke” from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: • In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
• Smoke particles may become “cold,” stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control. It is essential to use only equipment
• Smoke particles may be drawn into air returns before listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of Chapter 7 of NFPA
izing-type sensing chambers tend to detect fast-flaming fires 72 shall be followed. Environments with large amounts of
better than smoldering fires. Because fires develop in different dust, dirt or high air velocity require more frequent mainte-
ways and are often unpredictable in their growth, neither type nance. A maintenance agreement should be arranged
of detector is necessarily best and a given type of detector through the local manufacturer's representative. Maintenance
may not provide adequate warning of a fire. should be scheduled monthly or as required by National and/
Smoke detectors cannot be expected to provide adequate or local fire codes and should be performed by authorized pro-
warning of fires caused by arson, children playing with fessional fire alarm installers only. Adequate written records
matches (especially in bedrooms), smoking in bed, and violent of all inspections should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.). Precau-L-3-2002.fm

www.PDF-Zoo.com
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be Like all solid state electronic devices, this system may
connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light-
sources of power before servicing. Control unit and associ- ning-induced transients. Although no system is completely
ated equipment may be damaged by removing and/or insert- immune from lightning transients and interferences, proper
ing cards, modules, or interconnecting cables while the unit is grounding will reduce susceptibility. Overhead or outside
energized. Do not attempt to install, service, or operate this aerial wiring is not recommended, due to an increased sus-
unit until this manual is read and understood. ceptibility to nearby lightning strikes. Consult with the Techni-
CAUTION - System Reacceptance Test after Software cal Services Department if any problems are anticipated or
Changes. To ensure proper system operation, this product encountered.
must be tested in accordance with NFPA 72 Chapter 7 after Disconnect AC power and batteries prior to removing or
any programming operation or change in site-specific soft- inserting circuit boards. Failure to do so can damage circuits.
ware. Reacceptance testing is required after any change, Remove all electronic assemblies prior to any drilling, filing,
addition or deletion of system components, or after any modifi- reaming, or punching of the enclosure. When possible, make
cation, repair or adjustment to system hardware or wiring. all cable entries from the sides or rear. Before making modifi-
All components, circuits, system operations, or software func- cations, verify that they will not interfere with battery, trans-
tions known to be affected by a change must be 100% tested. former, and printed circuit board location.
In addition, to ensure that other operations are not inadvert- Do not tighten screw terminals more than 9 in-lbs.
ently affected, at least 10% of initiating devices that are not Over-tightening may damage threads, resulting in reduced ter-
directly affected by the change, up to a maximum of 50 minal contact pressure and difficulty with screw terminal
devices, must also be tested and proper system operation ver- removal.
ified.
Though designed to last many years, system components
This system meets NFPA requirements for operation at 0-49° can fail at any time. This system contains static-sensitive
C/32-120° F and at a relative humidity of 85% RH - 95% per components. Always ground yourself with a proper wrist strap
ULC - (non-condensing) at 30° C/86° F. However, the useful before handling any circuits so that static charges are
life of the system's standby batteries and the electronic com- removed from the body. Use static-suppressive packaging to
ponents may be adversely affected by extreme temperature protect electronic assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this
system and all peripherals be installed in an environment with Follow the instructions in the installation, operating, and pro-
a nominal room temperature of 15-27° C/60-80° F. gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation
cating device loops. Most devices cannot tolerate more than a by authorized personnel.
10% I.R. drop from the specified device voltage.

FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual, may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Canadian
tested and found to comply with the limits for class A Department of Communications.
computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable pro- Le present appareil numerique n'emet pas de bruits radi-
tection against such interference when operated in a oelectriques depassant les limites applicables aux appar-
commercial environment. Operation of this equipment in eils numeriques de la classe A prescrites dans le
a residential area is likely to cause interference, in which Reglement sur le brouillage radioelectrique edicte par le
case the user will be required to correct the interference ministere des Communications du Canada.
at his own expense.

Precau-L-3-2002.fm
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, ONYX™, and VeriFire™ are trademarks, and FlashScan® and VIEW® are registered trademarks of
NOTIFIER. NION™ and UniNet™ are trademarks of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered
trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered
trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark
of GE Plastics, a subsidiary of General Electric Company.

www.PDF-Zoo.com
Table of Contents

Section 1 Installation ..............................................................................................................................................7


1.1: NCS Mounting and Connections................................................................................................................7
1.1.1: Related Documentation .....................................................................................................................7
1.1.2: NRT-NET Interface Card ..................................................................................................................8
1.1.3: NCS Equipment.................................................................................................................................8
1.1.4: Primary and Secondary Power ..........................................................................................................8
1.1.5: Connecting the NRT-P3.....................................................................................................................8
1.1.6: Monitor Installation...........................................................................................................................10
1.1.6.1 Installing the MON-19BLK ....................................................................................................10
1.1.7: NCS UPS Supervision.......................................................................................................................12
1.1.7.1 NCS Computer/Monitor/Printer UPS Supervision .................................................................12
1.1.7.2 NCS Printer (only) UPS Supervision ......................................................................................13
1.1.8: Strain Relief.......................................................................................................................................14
1.2: Peripherals ...................................................................................................................................................15
1.2.1: Connecting a Line Printer .................................................................................................................15
1.3: PC Configurations .......................................................................................................................................16
1.4: Software.......................................................................................................................................................16
1.4.1: Installing the NCS Software..............................................................................................................16
1.4.2: Installed Printers................................................................................................................................17
1.4.3: Read/Write CD ROM ........................................................................................................................18
1.4.4: Windows 2000 Secure Desktop Configuration .................................................................................19
Section 2 Programming ..........................................................................................................................................20
2.1: Networking the NCS ...................................................................................................................................20
2.2: NCS Database..............................................................................................................................................20
2.2.1: History Database ...............................................................................................................................21
2.2.2: Graphics Database.............................................................................................................................21
2.3: Power-Up Initialization ...............................................................................................................................21
2.3.1: Data Refresh ......................................................................................................................................21
2.3.1.1 Manual Data Refresh ...............................................................................................................21
2.4: The Start-Up Window..................................................................................................................................21
2.5: NCS Graphical User Interface.....................................................................................................................22
2.5.1: The Graphic Event Window ..............................................................................................................22
2.5.1.1 Automatic Screen Vectoring ...................................................................................................22
2.5.1.2 Title Bar ..................................................................................................................................23
2.5.1.3 Menu Bar .................................................................................................................................23
2.5.1.4 Graphic Floor Plan ..................................................................................................................24
2.5.1.5 Key Map Area .........................................................................................................................24
2.5.1.6 Events Window .......................................................................................................................24
2.5.1.7 Acknowledged Event Box .......................................................................................................25
2.5.1.8 Screen Navigation Tools .........................................................................................................25
2.5.1.9 Date / Time Field ....................................................................................................................25
2.5.1.10 Logo Window ........................................................................................................................26
2.5.1.11 Tool Bar ................................................................................................................................26
2.5.1.12 Alarm / Trouble / Supervisory Alarm / Security Alarm Banners .........................................26
2.5.1.13 Command Area .....................................................................................................................26
2.5.1.14 Current Operator Field ..........................................................................................................27
2.6: Menu Options for Programming .................................................................................................................27
2.6.1: Administration Menu ........................................................................................................................27
2.6.1.1 System Setup ...........................................................................................................................27
2.6.1.2 Network Operations ...............................................................................................................33
2.6.1.3 Archive History Database .......................................................................................................35
2.6.2: Graphic Menu....................................................................................................................................35
2.6.2.1 Graphic Setup ..........................................................................................................................35
2.6.3: Utilities Menu....................................................................................................................................35
2.6.4: The Help Menu..................................................................................................................................36

www.PDF-Zoo.com
4 Document #51095 Rev.B1 3/7/02
Table of Contents

Section 3 Operation ................................................................................................................................................38


3.1: Normal Operation........................................................................................................................................38
3.2: Troubles.......................................................................................................................................................38
3.3: Alarms .........................................................................................................................................................39
3.4: Supervisory, Security, and Pre-Alarm .........................................................................................................41
3.5: Menu Options for Operating the NCS.........................................................................................................41
3.5.1: File Menu ..........................................................................................................................................41
3.5.1.1 Exit ..........................................................................................................................................41
3.5.2: Operator Menu ..................................................................................................................................41
3.5.2.1 Login .......................................................................................................................................41
3.5.2.2 Logout .....................................................................................................................................42
3.5.2.3 Change Password ....................................................................................................................42
3.5.3: The Action Menu ..............................................................................................................................42
3.5.4: The View Menu.................................................................................................................................43
3.5.4.1 Event Counters ........................................................................................................................43
3.5.4.2 The Detailed Events Window .................................................................................................44
3.5.4.3 Current Event Window ...........................................................................................................45
3.5.4.4 Disabled Device Window .......................................................................................................45
3.5.4.5 History Manager .....................................................................................................................45
3.5.5: Screen Navigation .............................................................................................................................46
3.5.6: Trouble with NCS and INA Equipment............................................................................................46
3.6: Read Status/Program ...................................................................................................................................47
Section 4 The History Manager .............................................................................................................................52
4.1: NCS Integrated Operation ...........................................................................................................................52
4.1.1: History Backup..................................................................................................................................56
4.1.1.1 Upload/Download (UPDL) .....................................................................................................57
Section 5 The Graphic Setup Program .................................................................................................................60
5.0.1: NCS Integrated Operation.................................................................................................................60
5.1: Program Layout...........................................................................................................................................60
5.1.1: Floor Plan Tree View ........................................................................................................................61
5.1.2: Group Tree View ...............................................................................................................................61
5.1.3: Floor Plan Device View ....................................................................................................................61
5.1.4: Information Windows .......................................................................................................................61
5.1.5: Tool Bar.............................................................................................................................................62
5.2: Graphic Floor Plans.....................................................................................................................................63
5.2.1: Adding Floor Plans to the NCS.........................................................................................................63
5.2.2: Selecting Floor Plans.........................................................................................................................64
5.2.3: Deleting Floor Plans..........................................................................................................................64
5.2.4: Setting Keymap Links.......................................................................................................................65
5.2.5: Screen Title .......................................................................................................................................65
5.2.6: Guidance Text ...................................................................................................................................65
5.3: Keymap Area...............................................................................................................................................66
5.4: Menu Bar Options .......................................................................................................................................66
5.4.1: File.....................................................................................................................................................66
5.4.2: Screens ..............................................................................................................................................66
5.4.3: Devices..............................................................................................................................................66
5.4.4: View ..................................................................................................................................................68
5.4.5: Setup..................................................................................................................................................68
5.4.6: Help ...................................................................................................................................................69
5.5: Device Icons ................................................................................................................................................69
5.5.1: Devices..............................................................................................................................................69
5.5.2: Detectors ...........................................................................................................................................70
5.5.3: Modules.............................................................................................................................................70
5.5.4: Zones .................................................................................................................................................70

www.PDF-Zoo.com Document 51095 Rev. B1 3/7/02 5


Table of Contents

5.5.5: Linked Files.......................................................................................................................................70


5.5.6: Information Labels ............................................................................................................................70
5.5.7: Navigational Buttons.........................................................................................................................71
5.5.8: Delete Operations..............................................................................................................................72
5.5.9: Searching for Specific Items .............................................................................................................72
5.5.10: Rules for Setting Up Device Graphics ............................................................................................72
5.6: Groups .........................................................................................................................................................73
5.6.1: Level 1 Groups ..................................................................................................................................73
5.6.2: Level 2 Groups .................................................................................................................................73
5.6.3: Group Setup Restrictions ..................................................................................................................73
5.6.4: Group Navigation ..............................................................................................................................73
5.7: Setup Templates...........................................................................................................................................74
5.7.1: Template Groups ...............................................................................................................................74
5.7.2: Hot Templates....................................................................................................................................74
5.8: Custom Bitmap ............................................................................................................................................74
5.9: Template Files .............................................................................................................................................75
5.10: NCS Required Files...................................................................................................................................75
Appendix A: Windows 2000 Security Disable Procedure ..................................................................................76
Appendix B: Miscellaneous Software Installation ..............................................................................................77
Appendix C: Message Tables ................................................................................................................................78

www.PDF-Zoo.com
6 Document #51095 Rev.B1 3/7/02
NCS Mounting and Connections Installation

Section 1 Installation
1.1 NCS Mounting and Connections
The Network Control Station (NCS) contains a recognized tabletop computer with VGA graphics
for displaying all network events. The NCS is used with the Notifier Noti•Fire•Net system. The
different NCS models all come with the NRT-P3, a high-performance desktop computer.

1.1.1 Related Documentation


To obtain a complete understanding of the NCS features and related products or to become familiar
with functions in general, make use of the documentation noted in Table 1.1. The Notifier
document (DOC-NOT) chart provides the current document revision.

Title Number Title Number

AM2020/AFP1010 50119/ CHG-120 50641


Fire Alarm Control Panel 15088
Liquid Crystal Display (LCD-80) 15037 Annunciator Control System 15842
Network Control Station (NCS) 51095 Lamp Driver Modules (LDM) 15885
Intelligent Network Annunciator (INA) 15092 Voice Alarm Multiplex 15889
Universal Zone Coder Installation (UZC-256) 15216 The XP Series Transponder System 15888
Product Installation Document (CCM-1) 15328 Network Adaptor Module (NAM-232) 50038
Product Installation Document 15331 The UDACT Universal Digital Alarm 50050
(MPS-TR) Communicator/Transmitter
AM2020/AFP1010 Operator Instructions 15337 FCPS-24/FCPS-24E Field Charger/Power Supply 50059
Installation, Operation and Application Manual
Notifier Device Compatibility Document 15378 Video Graphics Annunciator System (VGAS) 50251
Installation Manual
Analog Fire Panel (AFP-200) 15511 Media Interface Board (MIB) 50255
Analog Fire Panel Installation Manual (AFP-400) 50253 Repeater (RPT) 50256
Analog Fire Panel Programming Manual (AFP-400) 50259 Noti•Fire•Net Manual 50257

Analog Fire Panel Operating Manual (AFP-400) 50260 Smoke Control Manual 15712
Canadian Requirements for the AM2020/AFP1010 15631 SLC Manual 51253
Network Interface Board (NIB-96) 15666 MMX-2 Installation Instructions M500-03-00
RM-1 Series Remote Microphones 51138 XP5 Series Transponders 50786
NBG-12LX Pull Station 51093 ACT-2 Audio Coupling Transformer 51118

Table 1.1 Related Documentation

NCS Manual PN 51095:B1 3/08/02 7


www.PDF-Zoo.com
Installation NCS Mounting and Connections

1.1.2 NRT-NET Interface Card


The NCS communicates with Noti•Fire•Net through the Network interface card (NRT-NET) and
the Media Interface Board (MIB). The NRT-NET interface card plugs directly into a computer
expansion slot located on the NCS computer. The MIB, which supports the physical connection to
the network, plugs onto the NRT-NET card to complete the network interface. The NRT-NET
interface card provides the following features:
• Allows the NCS computer to communicate on Noti•Fire•Net
• Accepts the following choices of Media Interface Boards:
- twisted-pair (MIB-W)
- Fiber optic (MIB-F)
JP3, IRQ7
The jumper LED illuminates to indicate
provided must that NFN is receiving data.
cover these pins if
the NCS is not an LED illuminates to indicate
NRT upgrade. that NFN is transmitting data.
Note: If the NCS
is an NRT LED illuminates to indicate
upgrade, the pins activity on Channel A.
at JP3, IRQ3 must
be covered. LED illuminates to indicate
activity on Channel B.

JP6 - Present on the NRT-NET card of an Monitors normally closed contacts of


NCS or later model NRT. Do not remove uninterruptible power supply (UPS). If
the jumper at JP6, which is set at 300H. unused, cover pins using supplied jumper.
Figure 1.1 NRT-Net Card
1.1.3 NCS Equipment
The Network Control Station is a kit comprised of:
• a computer
• A MON-19BLK monitor (UL 864 Listed 19 inch monitor)
Refer to Table 1.2 for model numbers and components.
Note: The monitor and mouse, as well as the printer if one is used, must be installed in the same room as the NCS in order
to comply with UL listing requirements.
A PRN-5 printer can be ordered separately.
The NCS computer is referred to in this manual as the NRT-P3. Table 1.2 lists the NCS model numbers
that include computers referenced as NRT-P3.
Model # Components
NCS-M19F NCS computer, mouse, 19" monitor, fiber optic data link
NCS-M19W NCS computer, mouse 19" monitor, wire data link

Table 1.2 NCS Equipment Options


1.1.4 Primary and Secondary Power
The NCS requires connection to a separate dedicated primary AC fire alarm circuit, which must be
labeled "FIRE ALARM." This AC circuit must connect to the line side of the main power feed of
the protected premises. No other equipment can be powered from the fire alarm circuit. The
primary AC circuit wire run must run continuously, without disconnect devices, from the power
source to the NCS. Overcurrent protection for this circuit must comply with Article 760 of the
National Electrical Code as well as local codes. Where an NCS is required, the use of an UL-864
approved supervised UPS is also required. When using a UPS, NCS input voltage must be 115
VAC. The use of 230 VAC is not permitted when employing a UPS.

1.1.5 Connecting the NRT-P3


The following steps must be completed when connecting the NRT-P3 (refer to
Figure 1.2 and Figure 1.3).

8 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
NCS Mounting and Connections Installation

1. Cut off the plug end of the computer power cord.


2. Plug the socket end of the power cord into the computer.
3. Remove the screws from around the power supply of the NRT-P3.
4. Attach the PCLB-6 enclosure without the cover to the back of the NRT-P3 using these screws.
5. Install a 3/4-inch (19.05 mm) conduit and fitting in the knock-out hole of the Power Cord
Locking Bracket cover (refer to Figure 1.3).
Caution: Size the 3/4-inch (19.05 mm) conduit so the line cord can reach a junction box at the
!
other end of the conduit.
6. Thread the power cord through the cover and conduit.
7. Attach the PCLB-6 cover to the PCLB-6 using the mounting screws supplied. Ensure that the
PCLB-6 cover holds the power cord socket firmly in place.
8. Connect the power cord to the HSP-121B power line protector as shown in
Figure 1.4.
Note: The HSP-121B power line protector must reside in a junction box.
9. Connect 115 VAC, 50/60 Hz primary power or 230 VAC, 50/60 Hz primary power to the HSP-
121B as shown in Figure 1.4. Primary power connected to the HSP-121B (115 VAC or 230
VAC) depends upon the position of the voltage selection switch shown in Figure 1.2 and
Figure 1.3. All wiring must remain in conduit.
WARNING: Improper voltage selection can damage the NCS and void the warranty on the
! back cover of this manual.
10. Turn power switch on for the circuit.
11. Replace the cover on the PCLB-6 enclosure and secure with two screws.
12. Connect the monitor to the display adapter video connector on the back of the computer (refer
to Figure 1.2). Connect the other end of the video cable to the monitor. The video cable is
provided with screws for secure attachment.
13. Align the keyboard cable plug to mate with the notch in the computer's jack and insert cable.
14. Connect the mouse to the mouse port at the back of the NRT-P3.
15. Refer to Figure 1.5 for monitor power application.
Not Used Noti•Fire•Net
Connections
Microphone Connector
EIA-232
Speaker Connector COM Ports Not Used
1 and 2

Not Used
NRT-NETPCB
LEDs

Power
Cord
Socket

UPS
Supervision
Cable
Connection

Remove these EIA-232 Not used


screws and reuse COM Ports Software Key
for mounting the 3 and 4 connection
Mouse/Keyboard Port
NCSonyx3bk.cdr

PCLB-6 plate Monitor


Power Switch connection NRT-NETPCB Card
Voltage Not Used
(disabled at
Selection factory)
Switch
Figure 1.2 NRT-P3 Connections

NCS Manual PN 51095:B1 3/08/02 9


www.PDF-Zoo.com
Installation NCS Mounting and Connections

• The NRT-P3 requires 115 VAC, 50/60Hz primary power or 230 VAC, 50/60 Hz primary power depending upon the
position of the voltage selection switch shown in Figure 1.2 and Figure 1.3.
• Where an NCS is required, the use of a supervised Uninterruptable Power Supply (UPS) is also required (see Figure
1.6)
• The NCS is not suitable for use as a receiving unit.
• The front power switch for the NRT-P3 has been permanently fixed in the ON position.

Power Cord

Voltage selection
Switch

nrtpwcrd.cdr
Mounting Screws

PCLB5Bb.cdr PCLB-6 Cover


PCLB-6 Knockout
(without cover)

PCLB5Ba.cdr
Mounting Screw

Figure 1.3 Attaching the PCLB-6 to the NRT-P3

Junction Box
Neutral - White

AC - Black
15 AMPS
MAX
To 115 VAC, 50/60 Black AC HSP-121B AC
L E
Conduit
Hz Primary Power or Q
I
230 VAC, 50/60 Hz White
hsp-121b.cdr
NEUT U
N NEUT
I
Primary Power Green E P
GND GND
Light ON - Normal Power Cord
Light OFF - Requires Service PCLB-6
Ground - Green

Fuse

Figure 1.4 Connecting the Power Cord and Primary AC Power


to the Power Line Protector

1.1.6 Monitor Installation


1.1.6.1 Installing the MON-19BLK
The following steps must be completed when connecting the MON-19BLK to the Junction Box and
NRT-P3 (refer to Figure 1.5).
1. Connect the AC Power Cord on the MON-19BLK to the HSP-121B Junction Box.
2. Connect the DB-15 video cable to the video card slot on the NRT-P3.

10 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
NCS Mounting and Connections Installation

MON-19BLK

Junction Box
Neutral - White

HSP-121B AC - Black
Black
White
Green

Ground - Green

NCSmoninstonyxnrtnet.cdr
Fuse

Power Cord
Monitor
DB-15 Cable Connection

NCS Computer
Figure 1.5 Installation of MON-19BLK

NCS Manual PN 51095:B1 3/08/02 11


www.PDF-Zoo.com
Installation NCS Mounting and Connections

1.1.7 NCS UPS Supervision


1.1.7.1 NCS Computer/Monitor/Printer UPS Supervision
Where a Network Reporting Terminal (NCS) is not ancillary, the use of a supervised 115 VAC
Uninterruptable Power Supply (UPS) is required. Refer to Figure 1.6 and Figure 1.7 for wiring
information. A networked AM2020/AFP1010 or INA with an MPS-24A Power Supply must be
located within three feet (.9144 m) of the UPS and wiring must be in conduit.

Negative Bar Positive Bar

AC Input

To AC Power of
NCS, Printer, or CRT Use cable P/N 71033 (supplied
with the NCS) from
NRTNETPCB to UPS. Cut and
Note: The Inverter is equipped AC AC Line strip wires as needed. Make all
with automatic transfer. Refer to Load 115 VAC
connections in conduit.
the schematic in the instruction 115 VAC
manual for internal wiring.
DC/AC Inverter
COMM
Inverter
NC

Failure NC

47k ELR
NRT-P3 Computer
Utility Failure
(optional)
Note: Wiring should be in the same
cabinet or use less than 3 feet of conduit.

DC DC
Output Output

Charger 1 Charger 2
Sharing
Load
Sense (+)
Remote
Sense (-)
Remote

Equalize
Remote
Sense (+)
Remote

Sharing
Load

Current
Low
Sense (-)
Remote
Equalize
Remote

Failure
Rectifier

Current
Low

Failure
Rectifier

NCSsupsfsonyxnrtnet.cdr

+ 9
8
7
0
1
2
6 3
- 5 4

FMM-1

Figure 1.6 NCS Computer UPS Supervision

12 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
NCS Mounting and Connections Installation

1.1.7.2 NCS Printer (only) UPS Supervision

NRT-NETPCB
UPS Supervision Port

Total Output Load


5A AC Maximum
Battery Backed Up

8A AC Maximum
120V AC, 60 Hz

No Connection
No Connection
Input Power

120V AC

120V AC

120V AC
Of UPS

Of UPS

Of UPS
Output

Output

Output

SPARE
GND

GND

GND
Chassis Ground

GND
H

N
H

12

15
10

13

14
11
5
2

9
4

8
1

Relay Contacts Are Rated


500 mA, 28V DC Resistive Load
500 mA, 28V AC }
Note: Cut and Strip
Wires on Cable 1
Assembly P/N 71033 (NO)
(provided with NCS),
and connect as shown.
2(C)
AC
Input
Fail 3
(NC)

4
(NO) 47K
Battery ELR
Fail
5(C)

6
(NC)

9 0
+ 8 1
7 2 EMI
_ 6 3 UPS Line
Static
Transformer Charger
5 4 Switch
System Control Filter
Board
FMM-1
Software Type
ID "MTRB"
Inverter Battery
upsprn1fsconyxnrtnet.cdr

Instrumentation and Control System, Inc.


UPS, Model Number 9300057

Figure 1.7 NCS Printer UPS Supervision

NCS Manual PN 51095:B1 3/08/02 13


www.PDF-Zoo.com
Installation NCS Mounting and Connections

1.1.8 Strain Relief


Strain relief for wiring attached to the NCS wire terminals on the MIB-W is provided by a
protective cover (P/N 08275). The protective cover is supplied with the MIB-W.
The following steps must be completed to connect the protective cover with strain relief:
3. Feed wires to be connected to the terminal block through the back or side access hole of the
protective cover. The hinged covers of the unused access hole can be closed.
4. Attach the wires to the pluggable terminal block.
5. Snap the strain relief assembly over the pluggable terminal block. Use tie wrap to secure the
wires to the protective cover (refer to Figure 1.8).

Tie Wrap Around Wire and


Hinged Cover

Wiring Access Holes and Cable Restraint


Hinged Covers (add after assembly)

Protective Cover
(P/N 08275)
Strain Relief Assembly
(snaps over pluggable terminal block)

strainre.cdr

NRT-

NCSonyx3back.cdr
NETPCB

Figure 1.8 Strain Relief Assembly

14 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Peripherals Installation

1.2 Peripherals
1.2.1 Connecting a Line Printer
A printer can be connected to the NCS to print fire alarm and trouble signals (refer to Figure 1.9
and Table 1.3).

DB 9 connector

NCSdbcxonyxnrtnet.cdr
DB 25 connector from PRN Cable
or another listed EDP printer

Figure 1.9 Serial Port Connections for a Printer Connected to NRT-P3


To connect a PRN-4 or PRN-5 printer to the NCS, a cable with the connections shown in Table 1.3
must be prepared.

NCS Printer
DB9 DB25

2 2
3 3
5 7
4 and 6
jumpered
together
8 20

Table 1.3 Printer Connections


• Only one NCS (including keyboard, mouse, monitor, or any one of these) can be present on the network for other than
National Fire Protection Association (NFPA) 1996-72 Local Service.
• Where an NCS is required, the use of a supervised 115 VAC UPS is also required (see Figure 1.6 or Figure 1.7).
• Locate the printer in the same room as the NCS.
• This printer connection is not for use with VeriFire. Refer to the VeriFire documentation for further information.

NCS Manual PN 51095:B1 3/08/02 15


www.PDF-Zoo.com
Installation PC Configurations

1.3 PC Configurations
To run the NCS program your system must be setup for the following configurations:
1024 x 768 resolution, large fonts, and 65k colors. Refer to Figure 1.10. To set these
configurations, select the Start menu and Settings/Control Panel, double-click Display and select
the Settings tab.

ncspcconfig.jpg
Figure 1.10 PC Configurations
For Windows 2000, the font size is located in a submenu of the Settings screen. Click the
"Advanced" button that appears at the bottom right of the Settings screen. On the next screen,
choose "Large" for font size.
Additionally, for Windows 2000, the Active Desktop setting must be off.

1.4 Software
1.4.1 Installing the NCS Software
Make sure to read the entire set of instructions prior to beginning the NCS software installation.
The NCS software requires Windows 2000 Professional Edition with Service Pack 1or higher, or
Windows NT® with Service Pack 5. The following steps must be completed to install NCS
software in Windows NT® Workstation 4.0 or in Wnidows 2000.
Note: If the NCS is the Master Time Keeper on the network, installing this software will cancel the setting and a Master
Time Keeper will not exist on the network. Enter the date/time in the NCS Local Programming Dialog Box for the NCS to
become the Master Time Keeper again.
Windows NT® is a registered trademark of Microsoft Corporation.

1. Insert the CD-ROM into the appropriate drive. The Setup program will launch automatically if
Autorun is enabled. Otherwise, continue with steps 2 through 10 that follow.
2. Click on the Start button, select Run...
3. At the Command Line prompt, type X:\NCS, where X is your CD drive letter. Steps 2 and 3
will only be necessary for PCs that do not have the Autorun feature enabled.

16 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Software Installation

4. An InstallShield Self-Extracting.exe dialog box will appear, select YES to continue installing
the NCS. InstallShield will start extracting the necessary files for installing the NCS.
5. A Welcome dialog box will appear. Select NEXT to continue installing or CANCEL to return
to the desktop.
6. A User Information dialog box will appear next. Type your name and company at the
designated prompts. Select NEXT to continue or CANCEL to return to the desktop. The
location of the installation directory will be displayed if it exists, and the user will be asked if
he/she would like to make a backup.
7. Next a Select Program Folder dialog box appears. The NCS must be installed in the
directory provided.
8. A Setup Type dialog box will now appear. Choose Typical, Compact or Custom setup by
clicking in the appropriate circle. Select NEXT to continue installing, BACK to view the
previous screen or CANCEL to return to the desktop.
• Typical Install - Installs the most common options, recommended for most users.
• Compact Install - Not available at this time.
• Custom Install - The user chooses the installed options, recommended for advanced users. The
Select Program Folder dialog box displays for this purpose.
9. Next a Start Copying Files dialog box appears showing the type of setup, target folder and
user information that was provided. Select NEXT to begin copying files, BACK to change any
settings or CANCEL to return to the desktop.
10. The NCS will now install the NCS. When setup is complete, a Setup Complete dialog box
appears informing you that the computer will be rebooted. Press OK to perform the reboot.
Caution: The NCS Communications Driver may have to be changed. If the NCS is installed on a
! PC that did not contain the NRT (Network Reporting Terminal), it will use IRQ5 or IRQ7.
The NCS Installation Program sets the IRQ to IRQ5. On Onyx computers, or computers that already
use IRQ5, this must be changed to IRQ7. Please be sure the jumper selection on the NRT-NETPCB
card is set to IRQ7. In addition, please complete the following steps to configure the software:
1. Open a text editor, such as Notepad.
2. Open file ptp20020.ini. This file is located in the \notifier\ncs directory.
3. Look for IRQLevel = REG_DWORD 0x05. Change the 0x05 to 0x07.
4. Save the file, close Notepad.
5. Open the DOS command prompt, and change to the \notifier\ncs directory.
6. Type "regini ptp20020.ini"
7. This completes the software configuration. Reboot the computer for the change to take
effect.
To verify that the NCS Communications Driver is configured correctly, follow these steps in
Windows 2000.
1. From the Start Menu, open Control Panel, then double click on Administrative Tools.
2. Double click on Computer Management.
3. Navigate to System Information, then select Hardware Resources, followed by IRQs.
4. Verify that IRQ7 is displayed, and the Device indicates ptp20020.

1.4.2 Installed Printers


Two printers may be installed to the NCS: an NCS Graphics Printer (optional, any Microsoft Win-
dows compatible printer that is UL ITE listed and installed in the same room as the NCS) which is
used to print out graphics, reports, etc. and an NCS Line Printer (the PRN) which is used only to
print out text.

Note: The NCS Graphic Printer must be a laser printer.

Installing The Graphics Printer


1. Exit the NCS application.

NCS Manual PN 51095:B1 3/08/02 17


www.PDF-Zoo.com
Installation Software

2. From the Start Menu, select Settings, and then Printers.


3. Double-click on the "Add Printer" icon.

4. The Windows NT® Installation Wizard will start to add the new printer.
5. Select the "My Computer" button, click next. The following items should be selected on the
next screens.

• The printer must be connected to LPT1.


• Select the printer that is to be hooked up to the system.
• Select Not Shared.
• Name the printer “NCS Graphic Printer”.
! Caution: This entry is case sensitive: the printer name must be entered exactly as shown.
6. In the printer dialog box, highlight the printer just installed, right click and select properties.
Installing The Line Printer
1. Exit the NCS application.
2. From the Start Menu, select Settings, and then Printers.
3. Double-click on the "Add Printer" icon.

4. The Windows NT® Installation Wizard will start to add the new printer.
5. Select the "My Computer" button, click next. The following items should be selected on the
next screens.

• The printer should be connected to LPT1 or a serial port.


• Select the printer that is to be hooked up to the system.
• Select Not Shared.
• Name the printer “NCS Line Printer”.
6. In the printer dialog box, highlight the printer just installed, right click and select properties.

Note: If the NCS Line Printer is connected to a serial port, the port settings must match the printer settings.

1.4.3 Read/Write CD ROM


File Directories on the NCS contain
Read/
information specific to normal NCS RESET Write CD
operation. User-defined directories for drive
POWER
capturing history files (.HIS) may also exist location
on the NCS. The files in these directories
may be backed up to the Read/Write CD
ROM. The Read/Write CD drive is located Figure 1.11 NCS Computer, Front View, Door Open
as shown in Figure 1.11. Follow the steps
below to copy NCS information onto a CD.
1. Exit NCS
Caution: Exiting the NCS application disconnects the NCS from Noti•Fire•Net which leaves the
!
building unprotected and the NCS not performing Life Safety functions. A firewatch is
recommended in all areas where the NCS is designated as the primary or only reporting station.
2. Load a CD into the CD drive. A CD-R is a one-time writeable CD, a CD-RW can be written
over multiple times.
Caution: Once the CD is in the drive, the door must remain OPEN until the CD is removed. If the
!
drive opens while the door is shut, it will hit the door and may become jammed.
3. Double-click on the "Create CD" icon on the NCS desktop. Easy CD Creator™ will appear.
4. Select "DATA"

18 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Software Installation

5. Select "DATA CD". The program will launch at this point.


6. Select files for backup. The directory C:\NOTIFIER\NCS contains important information and
should be included in the backup. Click the ADD button after each selection.
7. Click "Create CD" button on the toolbar. The CD creation Setup comes up with default
settings.
8. Click OK. The CD writer will copy the selected files onto the CD. When copying is complete,
the message "CD created successfully" will appear.
9. Click OK.

1.4.4 Windows 2000 Secure Desktop Configuration


The Onyx computers come pre-installed with Secure Desktop. This application prevents
unauthorized access to non-fire applications. To fully enable the software, and to comply with
UL-864, follow these steps:
1. From the Start Menu, select Secure Desktop, then Secure Setup.
2. The current configuration will indicate "Windows Explorer or Program Manager (Default)".
Change this to "Secure Desktop Icon Settings and General Options".
This will enable operation of certain applications only, such as the NCS and related programs,
VeriFire programs, and CD Burner software. The Windows Explorer Desktop will be replaced with
the Secure Desktop.

NCS Manual PN 51095:B1 3/08/02 19


www.PDF-Zoo.com
Programming Networking the NCS

Section 2 Programming
2.1 Networking the NCS
The Network Control Station (NCS) annunciates system signals on Noti•Fire•Net. Equipment that
connects to Noti•Fire•Net and communicates with other equipment using the network will be
referred to as a network node (for example: AM2020, AFP200 with NAM-232, AFP1010, INA, or
NCS). Noti•Fire•Net is a peer-to-peer network (refer to Figure 2.1), and can be logically grouped
together to form systems. For more information on Noti•Fire•Net, refer to the Noti•Fire•Net
Manual.
The functions of the NCS shall include:
• Display of all events on the network.
• Provide the ability to acknowledge, reset and signal silence all events.
• Provide the ability to graphically set up and annunciate the points to be monitored.
• Allow read status and alter status operation to all fire panels that provide this ability.
• Upload / download programming information for archiving purposes for all fire panels that provide this ability.
• Provide a history viewer with filters that can be run outside the NCS application.
• Setup different levels of operator interaction, based on passwords.

MIB
AM2020

MIB
AFP1010

Fiber Optics
or Single
Twisted-Pair

NCS

AFP-200
NAM-
232
nrtntwka.cdr

MIB
INA

Figure 2.1 Noti•Fire•Net Network

2.2 NCS Database


Upon power-up, the NCS checks for the presence of the databases. If it can not find them, a
warning dialog box will be displayed, and a system error message will be logged to the history
manager and current event window. If the Run Time or Administrator database is missing, the NCS
will not be able to execute, and the program will not start. The only way to correct this situation is
to re-load the NCS software, or restore the databases. If the history database is missing, a new file
will be created. If that database already exists, it will be opened.

20 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Power-Up Initialization Programming

2.2.1 History Database


The History database provides a full history of all changed states that have occurred throughout the
system since the history file was last archived. The type of information stored in the history
database includes:
• All alarm and trouble events received by the system. This includes all activation and clearing of all devices.
• All system messages received from the network. This includes remote acknowledge, reset, signal silence, walk test, etc.
operation.
• Any command operation performed at the NCS. This includes acknowledge, reset, signal silence operation, local
programming, fire panel programming, and alter status action.

Events are listed from top to bottom (the top being the newest and the bottom being the oldest
event). All events stored in the history buffer are not encrypted, and can be viewed using Microsoft
Access.

2.2.2 Graphics Database


The graphics database contains references to all custom device and floor plan bitmaps used in the
NCS. The graphics database is modified through the Graphics Setup Program (GSP). The type of
information that is stored in the graphic database includes: detectors, modules, zone information
including graphics and auto-vectoring capability. Also stored is floor layout information including:
floor plans, keymap graphics, information labels, navigational buttons and group information.
This program can be executed stand-alone, or through the NCS. In stand-alone operation, the user
must copy the database modified into the directory that the NCS resides in. If invoked from the
NCS, the user must update the NCS graphics through the update database command in the NCS.

2.3 Power-Up Initialization


2.3.1 Data Refresh
A data refresh is initiated from the NCS when a node joins the network. This is also done when the
NCS is powered up. The NCS has the capability to initiate a data refresh to five nodes
simultaneously to update point information as fast as possible.
The data refresh is used to update the alarm, trouble, disable, enabled state of all the point
programmed into the graphic screens. It also updates the unacknowledged event box,
acknowledged event box and the expanded event box with any off-normal information found in the
system.
The data refresh option can be selected in the local programming dialog box. It can be turned off
when troubleshooting the network, and also to reduce message traffic upon power-up. However,
for proper operation of the NCS, this option must be enabled. The default setting for this option
will always be on.
2.3.1.1 Manual Data Refresh
Data refresh can be manually invoked under the Action menu; Data Refresh command (available
only to the Administrator Account user). This command is useful when a node is suspected to be
out of synch with the NCS, or automatic data refresh is turned off. The data refresh command can
then be vectored to a specific node and send its off-normal conditions to the NCS. When this
command in invoked, the NCS will first delete all off-normal events stored for that particular node,
then proceed with the data refresh.

2.4 The Start-Up Window


To start the NCS, select the group named Notifier (refer to Figure 2.2). Select the Noti•Fire•Net
icon and press Enter or double-click to start the application.
! Caution: Exit from the NCS software and exit from Windows NT® before turning off the NCS.
Failure to do so could invalidate software settings.

NCS Manual PN 51095:B1 3/08/02 21


www.PDF-Zoo.com
Programming NCS Graphical User Interface

The Notifier icon shown below can be found under Notifier on the Start Bar for Windows NT® 4.0
or higher. To launch the NCS software, double-click on the icon.

ncsicon.tif
Figure 2.2 NCS Icon
The Main window is the first window that appears after the NCS application begins communication
on Noti•Fire•Net. The Main window supports changing passwords and accessing other NCS
windows.

! Caution: While running NCS software, DO NOT run other software, including PC Tools,
Screensavers and TSRs, also, DO NOT add disk doubling software at any time.

Caution: If the Parallel Port Key is not connected to the PC, the NCS will power up in Demo
! Mode. In this mode of operation, the program will not communicate on the network.

There are nine menus available from the NCS Start-up window: File, Operator, Action, View,
Screen Navigator, Administration, Graphic, Utilities, and Help.

2.5 NCS Graphical User Interface


The NCS consists of several different windows, with the main window being the Graphic Event
Window. This window consists of several areas containing pertinent information on the network.
The two main components are the command area (inverted L shaped) and the Graphic Screen.
NCS windows can be invoked by means of a pull-down menu bar or in some cases, command
buttons. The menu bar is located on top of every window, and displays properties pertinent to the
window invoked.

2.5.1 The Graphic Event Window


The basic input/output element of the NCS program is the graphic event window (refer to Figure
2.3). The graphic event window collects and displays alarm and trouble signals from the network.
It allows the operator to see a diagram of any specific area of the monitored network and gives
information about the facility area and the monitored devices. There are main elements to the event
window, which include: Title Bar, Menu Bar, Graphic Floor Plan, Key Map Area, Events Window,
Acknowledged Events Window, Screen Navigation Tools, Date and Time Field, Logo Window,
Tool bar, Alarm, Trouble, Supervisory Alarm, and Security Alarm Banners, Command Area,
Current Operator Field.
2.5.1.1 Automatic Screen Vectoring
The NCS graphics system automatically vectors from any window in the system to the Graphic
Event Window to show the highest priority event. This function is called "Auto-Vectoring”. If an
equal or lower priority event is received while a higher unacknowledged event exists in the
network, no action will be taken. If a different window is invoked while unacknowledged events
are present in the system, auto-vectoring will only initiate when a higher priority event is received.
If the auto-vector option for the device received is enabled, the graphic floor plan will change to
display the floor plan containing the icon, bypassing any group associations. If auto-vectoring is
off, and a group is associated with the device, the floor plan containing the highest level group will
be displayed.

22 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
NCS Graphical User Interface Programming

Below are some examples of auto-vectoring among Groups. For a more detailed explanation of
Groups, refer to "Groups" on page 79.

Auto Vector Group Action


Off No The floor plan containing the device is displayed
Off Yes The floor plan containing the highest level group is displayed
On No The floor plan containing the device is displayed
On Yes The floor plan containing the device is displayed

Screen vectoring uses the same event priority algorithms as the System Interface Window. The
user can still manually change screens using the Select Screen dialog box.

Title Bar Alarm, Trouble,


Logo Window Supervisory Alarm
Security Alarm, and
Menu Bar
Pre-Alarm Banners
Key Map Area
Current
Operator
Command Area Field

Date & Time Field


Screen
Navigation Tool Bar
Tools
Events
Window

Graphic
Floor Plan

Acknowledged
Events Window

mainscrn.tif

Figure 2.3 Elements of the Window (sample screen)


2.5.1.2 Title Bar
The title bar indicates the name of the window and is located on the top left corner, refer to Figure
2.4.
ncsmenu.tif

Figure 2.4 The Title Bar


2.5.1.3 Menu Bar
The menu bar lists the available menus in the NCS. A menu contains a list of commands that
pertain to that particular window, refer to Figure 2.5. To access a menu, select (click once) on the
menu from the menu bar. This opens the menu. From the menu, select a command. An arrow after
a menu option indicates that a dialog box will appear. If the wrong menu is opened, press the menu
bar again or press anywhere outside of the opened menu to close it.
ncsmenu.tif

Figure 2.5 The Menu Bar

NCS Manual PN 51095:B1 3/08/02 23


www.PDF-Zoo.com
Programming NCS Graphical User Interface

2.5.1.4 Graphic Floor Plan


The graphic floor plan is used to view the graphic layout of a building, high-rise or campus type
setting. It comprises the largest screen area in the NCS. It will allow an operator to see a diagram
of any specific area of the monitored network and give the operator information about the facility
area and the monitored devices. The graphic screen is comprised of bitmaps with devices
overlaying them. Refer to Figure 2.6.

ncsbase.jpg
Figure 2.6 Example of a Graphic Floor Plan
2.5.1.5 Key Map Area
The key Map Area is an overview of the graphics used in the system. It can be set up for navigation
or simply as an accompanying view of the foreground, refer to Figure 2.7.

ncskeymap.tif
Figure 2.7 Key Map Area
2.5.1.6 Events Window
The Events window displays the first of 12 unacknowledged, off-normal events on the network.
The events are grouped by event type (i.e., fire alarm, security alarm, supervisory alarm, and
trouble), and sorted by time within the group, displaying the oldest event first and the newest event
last. The highest event group is displayed on top of the window, the lowest event group on the
bottom of the window, refer to Figure 2.8. All events in this window are color coded. Fire alarms
are designated red, Security Alarms as blue, Supervisory Alarms as orange, Trouble Conditions as
yellow, and Pre-Alarms as cyan.

Event Type Time

Address
firevent.tif

Figure 2.8 Events Window


The information displayed consists of the event type, the address, and the time that the event was
received (assigned by the NCS). A detail button is provided to expand the event box to display all
events, as well as provide more detailed information for each event. Refer to “The Detailed Events
Window” on page 44 for more information on the Detailed Event Box.

24 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
NCS Graphical User Interface Programming

A device appearing in this box may be clicked on to display the graphic screen containing the
device. Any device that has been acknowledged is moved from the unacknowledged event window
to the acknowledged event box.
2.5.1.7 Acknowledged Event Box
The acknowledged event window displays the first 12 events on the network. The events are
grouped by event type (i.e., fire alarm, security alarm, supervisory alarm, trouble, etc.), and sorted
by time within the group, displaying the oldest event first and the newest event last. Refer to Figure
2.9.

Time
Event Type

Address

ncsackn.tif
Figure 2.9 Example of the Acknowledged Event Box
The information displayed consists of the event type, the address, and the time that the event was
received (assigned by the NCS). A detail button is provided to expand the event box and display
all events, as well as provide more detailed information for each event. Refer to “The Detailed
Events Window” on page 44 for more information on the Detailed Event Window.
A device appearing in this box may be clicked on to display the screen containing the device. Any
events that have cleared from the device are deleted from the unacknowledged event box, unless
the clear event is an alarm condition that must be acknowledged (i.e., a tracking alarm on an
AM2020/AFP1010 that clears without a reset). In that case the clear alarm will move to the
unacknowledged event box for further action.
2.5.1.8 Screen Navigation Tools
Use the screen navigation tools to advance to different graphic representation screens by using the
< and > arrows, refer to Figure 2.10. Click on the house icon to go directly to the “Home” page,
click the middle icon to open a Text File dialog that is associated with the Graphic Screen box, or
click on the last icon (printer) to print out a screen. In addition, the NCS provides a command to
display all screen names in a dialog box. Double-click one of the screen names to invoke the floor
plan specified.

Forward Arrow
ncsnavig.tif

Print Graphic

Back Arrow
Current Screen Home Screen Text File Associated
(Top Level Screen) with Graphic Screen

Figure 2.10 Screen Navigation Tools


2.5.1.9 Date / Time Field
The Date / Time Field displays the current system time (as set by Windows NT 4.0 Workstation)
within second resolution. This field is updated every second so the current time is always
displayed, refer to Figure 2.11. The NCS is completely Year 2000 compliant.
ncsdatime.tif

Figure 2.11 Date and Time Field

NCS Manual PN 51095:B1 3/08/02 25


www.PDF-Zoo.com
Programming NCS Graphical User Interface

2.5.1.10 Logo Window


This window is used to display a company logo. This logo can be modified using the GSP and
PaintShop Pro to customize it to a particular installation.
2.5.1.11 Tool Bar
A tool bar is available on the right side of the Graphic Interface Screen. Buttons on this tool bar
are used to display the Event Counter and Detailed Event windows, refer to Figure 2.12. These
windows may also be accessed under the View Menu. Refer to “The View Menu” on page 43 for
examples of these windows.

ncstoolb.tif
Event Counter
Detailed Events

Figure 2.12 Tool Bar


2.5.1.12 Alarm / Trouble / Supervisory Alarm / Security Alarm Banners
A set of five symbols are located in the upper right corner of the NCS. These symbols represent
fire-alarms, supervisory alarms, security alarms, trouble, and pre-alarm conditions present in the
system, refer to Figure 2.13. If any of these unacknowledged events are present in the system, the
appropriate symbol will blink. If all events have been acknowledged, the symbol will remain
steady. If the system is at ALL Systems Normal, the four symbols will be replaced by an All
Systems Normal message.
Supervisory Alarm

ncsbanr.tif
Alarm
Pre-Alarm

Security Alarm Trouble

Figure 2.13 Alarm, Trouble, Supervisory Alarm, Security Alarm and Pre-Alarm Banners
2.5.1.13 Command Area
The command area at the top of the screen allows the user to SAR (signal silence, acknowledge or
reset), the network or a specific node, refer to Figure 2.14. Pressing a button will transmit the
appropriate command over the network. The user has the ability to vector the signal silence and
system reset commands to specific nodes on the network via a pop-up dialog box. The node
address currently on the network and within the users ability to SR (signal silence or reset) will be
displayed in this pop-up dialog box. In addition, another selection will be made available to SR all
off-normal nodes, or all nodes in the system. This will be user configurable in the NCS local
programming dialog box.
ncscomnd.tif

Figure 2.14 Command Area


The user has the option to select one, many or all panels to SR. Nodes to SR are limited by the
NCS programming and the individual password ability. The ability to vector the acknowledge
command is not provided.
This dialog box is displayed when the cursor is over the Acknowledge, Signal Silence or Reset
button, and the right mouse button is clicked. Pressing the signal silence and reset button with the
left mouse button bypasses the vector dialog box, and sends the appropriate command to all nodes
programmed into the system (or all off-normal nodes), and accessible with the users password.

26 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Menu Options for Programming Programming

Acknowledge
Initiating a acknowledge command will transmit a point acknowledge or block acknowledge
message to all appropriate nodes. The nodes transmitted to are limited by the nodes programmed
into the system and the user password level.
If the highest priority event in the system is a fire alarm condition, a point acknowledge message
will transmit to the node, acknowledging the point. If the highest priority event in the system is a
security alarm or lower event, a block acknowledge command will be transmitted in the same
manner as in the Command area.
Any point acknowledge or block acknowledge initiation commands will be logged in the history
manager and current event window, if successfully completed. If this message could not be
completed, a error message will be displayed to the user.
System Reset
Initiating a system reset command transmits a system reset message to all appropriate nodes. The
nodes transmitted to are limited by the nodes programmed into the system, the user password level,
and the nodes selected by the user.
The system reset initiated command is logged into the history manager and current event window,
if successfully completed. If this message was not completed, a error message will be displayed to
the user.
Signal Silence
Initiating a signal silence command transmits a signal silence message to all appropriate nodes.
The nodes transmitted to are limited by the nodes programmed into the system, the user password
level, and the nodes selected by the user.
2.5.1.14 Current Operator Field
The current operator field is a window that shows the name of the current operator of the NCS.
Pressing the (...) button to the right will display information about the current operator. Refer to
Figure 2.15.
ncsoper.tif

Figure 2.15 Current Operator Field

2.6 Menu Options for Programming


2.6.1 Administration Menu
The Administration menu (refer toFigure 2.16) gives the user access to three commands: System
Setup, Network Operations, and the Archive History Database.
ncsadmin.tif

Figure 2.16 The Administration Menu


2.6.1.1 System Setup
When clicking on System Setup under the Administration Menu, the user will gain access to the
System Administration dialog box. In this dialog box there are five tabs: General NCS, User
Account, Printer, Voice, and Graphic Configuration, all in which contain NCS programming
options.

NCS Manual PN 51095:B1 3/08/02 27


www.PDF-Zoo.com
Programming Menu Options for Programming

General NCS Tab


This tab contains all NCS programming options which include Port A and Port B Thresholds, the
speaker frequencies for Alarm and Trouble, the Time Sync options, a Data Refresh option, a UPS
Supervision option, a single port or dual port supervision indication, a Reset/Signal Silence Option,
a History Backup option, a Master Time Keeper option (refer to Figure 2.17).

Click here to set the


NCS as the current
time keeper, see
Figure 2.18.

Click here to set the


current system time,
see Figure 2.19..

ncssysad.tif
Figure 2.17 General NCS Tab

ncssetdate.jpg

Figure 2.18 Setting the NCS as the Current Time Keeper


ncssettime.jpg

Figure 2.19 Setting System Time

28 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Menu Options for Programming Programming

User Account Tab


In the System Administration dialog box, the User Account Tab displays a Current Users list (refer
to Figure 2.20) where all user accounts currently setup on the NCS are displayed.

Add a user to
the NCS

Add or delete
commands from
a user account

Delete a user
from the NCS

NCSfiu5.jpg
Figure 2.20 The User Account Tab
This dialog box also lets the user add, edit and delete users from the NCS. To set up a new user on
the NCS, press the add user button. The new user dialog box appears, prompting for a new user
name (refer to Figure 2.21). Enter a user name up to 19 characters long. Check boxes allow all
system commands or all available nodes to be assigned at once to the new user account. Press OK
to accept the new user name.
To add or delete commands from a user account, press the edit user button. The account edit dialog
box appears with a listing of all commands and all nodes available on the NCS (refer to Figure
2.21). It is necessary to insert data into the screen fields that are marked with an asterisk.

NCSfiu7.jpg

Figure 2.21 Editing User Information (General)

NCS Manual PN 51095:B1 3/08/02 29


www.PDF-Zoo.com
Programming Menu Options for Programming

Pressing a check box beside a command selects or deselects it from the user account being edited,
(Figure 2.22). All nodes available on the system are displayed in the accessible nodes section.
Only highlighted nodes are accessible to the user account. Pressing on a node selects or deselects
it. After editing the user account, press OK to accept the changes, (Figure 2.23). Initially only the
Administration Account user can edit accounts; however, any user given access to the Account
command will also have the ability to edit accounts.
Note: All nodes assigned to a given user will have the same set of commands available to them.

To delete a user account from the NCS, highlight the account and press on the delete button from
the account list dialog box.

ncspermission.jp
Figure 2.22 Editing User Information (Permission)

ncsnodes.jpg

Figure 2.23 Editing User Information (Nodes)

30 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Menu Options for Programming Programming

Printer Tab
In the System Administration dialog box, under the Printer tab the user can setup the
communications port settings if the printer is connected to a call port, refer to Figure 2.24. The
NCS supports two types of printer:
• An Event (line) printer that can be attached to the COM or LPT port for printing of all events
received by the NCS.
• A Graphics Printer that can be attached to the LPT Port for printing graphics. If attached, it
must be set as the default printer.

Note: If a line and graphic printer are to be used by the NCS, event printer must be connected to a COM port.

ncsprtab.jpg
Figure 2.24 The Printer Tab
Event Printer Setup - The event printer is usually connected to the serial port, but can be
connected to the parallel port. The event printer is used to print all events as they are received by
the NCS. The printer will be activated as soon as the event is received. If the printer is connected
to a serial port, certain options must be selected. These include the communications port the printer
is connected to, the BAUD rate, the parity, the number of data bits, and the number of stop bits.
These settings must match the settings in the printer itself. If the event printer is connected to the
parallel port, these options are not applicable.
The Printer itself must be set with the same options selected here. In addition, the compressed
mode of operation (17 cpi) must be selected. This is required so that an event can be printed on a
single line. If not selected, an event will wrap to the next line.
Graphics Printer Setup - the graphics printer is a laser printer connected to the LPT port. The
setup for this printer must be done in Windows. Any Windows NT 4.0 Workstation compatible
printer that will work connected to the parallel port can be used. This printer is to be used to print
screens, any history file, and any reports generated by the NCS.
Voice Tab
There are two types of voice messages in the NCS. Those that are linked to an event or command,
and those which are linked to a device. Files which are linked to events or commands must be in
the "Waves" directory. Files which will be linked to a device must be in the "Sounds" file directory.
Refer to Figure 2.25.

NCS Manual PN 51095:B1 3/08/02 31


www.PDF-Zoo.com
Programming Menu Options for Programming

Events and Command files will be activated automatically when the event happens. Separate event
files can be set up for:
• Alarm and Pre-alarm events.
• Supervisory and Security events.
• Trouble events.
• System Reset, Signal Silence and Acknowledge commands.
• Alter Status Commands (which include enabling or disabling a device and turning a module on and off).
• All Systems Normal (a message that can be invoked when the system returns to an all systems normal state).

If a higher priority event interrupts a lower priority event, the current voice message will be halted,
and the new voice message will be started.

To select a wave file


for an event, select
under the Wave File
directory. A drop-
down menu will
supply the user with
available wave files.

ncsvoice.tif
Figure 2.25 Voice Tab
Graphic Configuration Tab
Under this tab the user can invoke the main screen on all systems normal, auto display guidance
text, auto display device document, play wave files, display device labels, and also print device and
guidance text and the graphic itself. Click in a box in order to put a check in the category you
would like to display or print. Refer to Figure 2.26 .
graphicstab.tif

Figure 2.26 Graphic Configuration Tab

32 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Menu Options for Programming Programming

2.6.1.2 Network Operations


The Network Operations command located under the Administration menu opens a Network
Systems Window that allows the user to set up the nodes that the NCS will monitor, check the
current state of all nodes programmed in, and access the read status and alter status menus for a
particular node.

The Network Systems Window displays the node number, node type, label, on-line status and
signal silence status in a spread-sheet like view, refer to Figure 2.27. The node type is AM2020/
AFP1010, AFP200, AFP-300/400, INA, etc. The label is a 30 character custom label local to the
NCS that can be entered by the user. The on-line status is either on-line or off-line. The signal
silence status is N/A, Normal, Partial, or Full Silence.

ncsnetop.tif
Figure 2.27 The Network Operations Menu Option
System Setup
The Network System window allows the user to add, delete and edit nodes. The LOCAL NCS
cannot be deleted from the network system window. Upon initial powerup of the software, or if the
software powers up in demo mode, the local NCS will be programmed in as node 0. The operator
must change this node number to initiate network communications. However, if the system is in
demo mode, the address cannot be changed. Nodes can be added or deleted from this list. Editing
a node will allow the user to enter the 30 character custom label, refer to Figure 2.28.
editnode.tif

Figure 2.28 Editing a Node Dialog Box


There is a second window available to the user which indicates the nodes that are present on the
network, but not programmed into the NCS. The information displayed includes the node number
and node type. Double-click on any nodes in the dialog box to program it into the NCS. The NCS
will only display events, act on, and communicate, with nodes that are programmed into the NCS.
Another option available is to auto-program all nodes on the network once network
communications has been established. This option will automatically add the node number, type
and status in this list.

NCS Manual PN 51095:B1 3/08/02 33


www.PDF-Zoo.com
Programming Menu Options for Programming

Node Access
Double-clicking on a particular node in the network system window displays the initial read status
menu, if read status is supported by that node. If it is not, an error message will be displayed, refer
to Figure 2.29.

nodemess.tif
Figure 2.29 Node Access Error Message
From the initial read status menu, the user can now select further read status, alter status and
programming operations. Double-click on the local NCS for a display of the local setting for the
NCS.
In addition, right clicking on a node in the network system window opens the Read Database
Menu, from which the user can choose to view loop, zone, or device information. This information
is displayed in a spread sheet type format, and is read-only. The information is obtained from the
database which is stored on the NCS. Refer to Figure 2.30.
NOTE: THIS INFORMATION IS ONLY UPDATED DURING UPLOAD AND READ STATUS COMMANDS, AND THEREFORE MIGHT NOT
BE UP- TO-DATE.

rdatamen.tif

Figure 2.30 Read Database Menu

34 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Menu Options for Programming Programming

2.6.1.3 Archive History Database


The Archive History Database menu option allows the user to archive the current history database,
and open a new one, refer to Figure 2.31.

ncshist.tif
Figure 2.31 The Active History Database

2.6.2 Graphic Menu


The Graphic Menu option is used to bring your graphics created in the GSP into the NCS, or invoke
the Graphics Setup Program.

graphmen.tif

Figure 2.32 The Graphic Menu


2.6.2.1 Graphic Setup
The graphics in the NCS are programmed using the Graphic Setup Program (GSP). This program
can be run from the NCS or executed as a stand-alone program. It is used to set up all floor plans,
device icons, links, etc. in the program. All graphics information is stored in graphics.mdb. Refer
to the Graphic Setup Program in the Operations section in this manual on how to use the program.
Refer to “The Graphic Setup Program” on page 60 for an in-depth explanation of the GSP.

2.6.3 Utilities Menu


The Utilities Menu allows the user to edit speech files, compact databases, and view network
communication statistics. The Edit Speech File opens up the Voice tab which also can be opened
through the System Administration menu. The Compact Database compacts and saves a database
for transferring information onto a floppy disk. *Network Statistics allows the user to troubleshoot
network statistics as well as view them, refer to Figure 2.34. The user can choose to view local or
remote devices or reset all nodes.
*The Network Statistics selection is only useful when consulting with a Technical Services representative.
utilitmen.tif

Figure 2.33 The Utilities Menu

NCS Manual PN 51095:B1 3/08/02 35


www.PDF-Zoo.com
Programming Menu Options for Programming

ncsstats.jpg
Figure 2.34 Network Statistics

2.6.4 The Help Menu


The Help menu allows the user to access a help file without exiting an application. The About
command displays a splash screen which shows the copyright and part number of the software
(refer to Figure 2.36).

ncshlepmn.jpg
Figure 2.35 The Help Menu

ncssysint.jpg
Figure 2.36 The System Interface Window
Select the System Info button to access information (memory, version, processor, etc.) about the
system you are on.

36 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Menu Options for Programming Programming

N OTES...

NCS Manual PN 51095:B1 3/08/02 37


www.PDF-Zoo.com
Operation Normal Operation

Section 3 Operation
3.1 Normal Operation
During normal operation, when no fire alarms or troubles exist, the Graphic Interface window will
appear as shown below with an “All Systems Normal” message in top right-side of the window.

"All
Systems
Normal"
ncssysnorm.jpg

message

Figure 3.1 System Interface Window


The user can perform functions associated with the following buttons without having to enter a
password, these functions can be performed under the Action Menu or directly from the Interface
Window.
ACKNOWLEDGE - The Acknowledge button acknowledges events currently in the system.
Alarms are acknowledged individually, and troubles are acknowledged as a group (block
acknowledge). Receiving unit mode is not supported on the NCS and all nodes on the network
should be configured for block acknowledge.
SIGNAL SILENCE - The Signal Silence button silences all control modules in the system that are
programmed as silenceable. The System Interface Window will reflect that a signal silence is
requested.
RESET - The Reset button resets all fire panels for the particular system in which it was requested.

3.2 Troubles
When a trouble is received from a fire alarm panel it is reported to the NCS. The NCS will report
the trouble in three ways; the trouble icon in the banner will flash, the trouble will be reported in the
Events window, and it will show up in the Event Counters window. Refer to Figure 3.2.

38 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Alarms Operation

Trouble icon
flashing in the
Banner area.

Trouble reported
in the Events
Trouble reported
Counter Box
in the Events
under New and
window.
Total categories.

Detector
showing the
reported trouble

ncstroub.jpg
Figure 3.2 Troubles Reported to the NCS
Select Acknowledge to acknowledge that a trouble has been reported. The trouble will then be
shown in the Acknowledged Events window, seeFigure 3.3. Select Signal Silence to silence
NAC’s, and select Reset to reset the control panel.

Trouble icon
stops flashing in
Trouble reported the Banner area.
in the Events
Counter Box
under the Total
category.

Trouble moves
to the
Acknowledged
Events window.
ncstrouback.jpg

Figure 3.3 Acknowledging Troubles on the NCS

3.3 Alarms
When an alarm is received from a fire alarm panel it is reported to the NCS. The NCS will report
the alarm in three ways; the alarm icon in the banner will flash, the alarm will be reported in the
Events window, and it will show up in the Event Counters window. Refer to Figure 3.4.

NCS Manual PN 51095:B1 3/08/02 39


www.PDF-Zoo.com
Operation Alarms

Alarm icon
flashing in the
Banner area.
Alarm reported
in the Events
Counter Box
under New and
Total categories. Alarm reported
in the Events
window.

Detector
showing the
reported alarm

ncsalarm.jpg
Figure 3.4 Alarms Reported to the NCS
Select Acknowledge to acknowledge that an alarm has been reported. The alarm will then be
shown in the Acknowledged Events window, see Figure 3.5. Select Signal Silence to silence
NAC’s, and select Reset to reset the control panel.

Alarm icon
Alarm reported stops flashing in
in the Events the Banner area.
Counter Box
under the Total
category.

Alarm moves to
the Acknowledged
Events window.
ncsalarmack.jpg

Figure 3.5 Acknowledging Alarms on the NCS

40 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Supervisory, Security, and Pre-Alarm Operation

3.4 Supervisory, Security, and Pre-Alarm


When a supervisory, security, or pre-alarm signal is received from the control panel it is reported to
the NCS. The NCS will report the supervisory, security, and pre-alarm in three ways; the
appropriate icon in the banner will flash, the supervisory, security, or pre-alarm will be reported in
the Events window, and it will show up in the Event Counters window.
Select Acknowledge to acknowledge that a supervisory, security, or pre-alarm has been reported: it
will then be shown in the Acknowledged Events window under its appropriate category. Select
Signal Silence to silence NAC’s, and select Reset in order to reset the control panel.

3.5 Menu Options for Operating the NCS


3.5.1 File Menu
The File Menu (refer to Figure 3.6) allows for printer setup, or exiting the NCS application.

ncsfilemen.jpg
Figure 3.6 The File Menu
3.5.1.1 Exit
The Exit command from the file menu exits the NCS program and places the user in the Windows
NT 4.0 Workstation environment. The user is prompted for a password. After entering the correct
password a warning display indicates the user is exiting the NCS application (refer to Figure 3.7).
The user should either press Ok to exit the NCS application or press Cancel to abort.

! Caution: Leaving the NCS application disconnects the NCS from Noti•Fire•Net which leaves the
building unprotected and the NCS not performing Life Safety functions.

ncsexit.tif
Figure 3.7 The Exit Dialog Box

3.5.2 Operator Menu


The Operator Menu allows the user to Login, Logout, and Change Password of the NCS, refer to
Figure 3.8.
ncsopmen.tif

Figure 3.8 The Operator Menu


3.5.2.1 Login
The Login command allows the user to gain access to the NCS by selecting his or her name in the
dialog box. Both a user name and a password are required to log on (refer to Figure 3.9). When
the NCS is first powered up, the initial user name is Admin. After initial login, the Administration
Account password must be changed to something other than Admin to ensure system security. The
administration account user should then set up accounts with temporary passwords for all operators
that will be accessing the NCS. Passwords can be up to 19 characters long.

NCS Manual PN 51095:B1 3/08/02 41


www.PDF-Zoo.com
Operation Menu Options for Operating the NCS

Asterisks are displayed in place of characters when entering a password. After selecting the user
name and entering the password, press Ok to accept the login information. If an error is made
while entering the password during login, a quick warning beep sounds, and the password dialog
box remains on the screen with the user name highlighted.

ncslgout.tif
Figure 3.9 Login Dialog Box
3.5.2.2 Logout
The Logout command is used to exit the NCS. Once logout has been selected, a dialog box appears
asking the user for the password. (refer to Figure 3.10). After entering the password, select Ok to
continue logging out. System commands will not be accessible again until a user logs onto the
NCS.

ncslgout.tif
Figure 3.10 Logout Dialog Box
3.5.2.3 Change Password
The Change Password command allows a user to change their current password. A password can
only be changed by the user who owns the password. Not even the Administration Account user
(the top user account with permanent access to all NCS commands) can change another user's
password.
When the Change Password command is selected, the change password dialog box (refer to Figure
3.11) prompts the user for old and new passwords. Asterisks will appear in place of the entered
characters for both the old and new passwords. Type the old password. Type the new password
and then retype it in the confirm password box to verify the first entry. Press OK to accept the new
password information. ncschpas.tif

Figure 3.11 Change Password Dialog Box

3.5.3 The Action Menu


From this menu, the user can acknowledge events, reset the system, perform a signal silence, hide

42 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Menu Options for Operating the NCS Operation

offline events, show offline events and perform a data refresh, refer to Figure 3.12.

ncsactin.tif
Figure 3.12 The Action Menu

• Acknowledge - Allows the function of acknowledge to be performed across the allowable


network nodes.
• Reset - Allows the function of system reset to be performed across the allowable network
nodes. The user can reset all nodes at one time, all off-normal nodes at one time, or select
individual nodes of choice.
• Signal Silence - Allows the function of signal silence to be performed across the allowable
network nodes. The user can signal silence all nodes at one time, all off-normal nodes at one
time, or select individual nodes of choice.
• Hide Offline Events - Hides all offline events. For example, if a node is disconnected from a
network with active events, then this selection will mask them from the graphic workstation.
• Show Offline Events - Displays all offline events. For example, if a node is disconnected
from a network with active events, this option will unmask offline nodes that have active
events.

Data Refresh - Is manually initiated from the NCS to update the off-normal points in the NCS.
This is also automatically done when the NCS is powered up. The NCS has the capability to
initiate a data refresh to five nodes simultaneously to update point information as fast as possible.
These menu options can also be accessed from the NCS Interface Window, Refer to “NCS
Graphical User Interface” on page 22 where they are explained in greater detail.

3.5.4 The View Menu


From the View Menu, the user can see the number of events that have occurred from the Event
Counter window option, see a detailed list of all events, fire and non-fire from the Detailed Events
option, view the last 1,000 events that have happened in the system from the Current Events option,
and disable devices (once the device is disabled, the user can enable it again by double-clicking on
the device, from the window itself) from the Disable Devices option, view the History Manager and
UPDL (refer to Figure 3.13).
ncsview.tif

Figure 3.13 The View Window Menu


3.5.4.1 Event Counters
The Event Counter window contains the new and total events on the network. The information
displayed in the window consists of fire alarms, pre-alarms, security alarms, supervisory alarms
and troubles. The new and total field areas are capable of displaying a five digit number. Refer to

NCS Manual PN 51095:B1 3/08/02 43


www.PDF-Zoo.com
Operation Menu Options for Operating the NCS

Figure 3.14.

ncsecoun.tif
Figure 3.14 Event Counters Dialog Box
Event counters are not permanently displayed on the Graphics Screen but invoked when prompted
by the user.
3.5.4.2 The Detailed Events Window
The Detailed Events Window is an advanced Signal Display interface to networked panels. The
Detailed Events Command is displayed from the View Menu in the Start-up Window. The Detailed
Events Window contains all off-normal events, both unacknowledged and acknowledged, that are
currently present in the system, refer to Figure 3.15. It is made up of two parts, “Fire Events and
Non-Fire Events.” Two buttons are provided to toggle between these two parts of the window. The
Fire Events window contains all events that are normally displayed by the fire panel in its display,
which includes all alarm and trouble conditions. Non-Fire Events consist of all events that are only
reported to the history buffer and printer of the fire-panel, such as speaker circuits, and non-
reporting control modules, as well as zone activation.

Select the
blue
button to
view all
non-fire
events.

detailev.tif
Figure 3.15 The Detailed Events Dialog Box (Fire Events Shown)
A scroll bar will be provided if more events are present in the system that can be displayed at one
time. The events are sorted by event type (fire alarm, security alarm, supervisory alarm, trouble,
pre-alarm, acknowledged alarm, acknowledged security alarm, acknowledged supervisory alarm,
acknowledged trouble, and acknowledged pre-alarm) and time. This dialog box will be displayed
in the same position as when previously closed. If left open, it will be refreshed every 6 seconds,
and only if new events of equal or lower priority were received by the NCS. If higher priority
events were received, this window would be updated immediately.
All information received from the node that the event happened on will be displayed in this box.
This includes the event type, the device type, the device label, the first zone referenced in the CBE
equation (for panels that provide this information), the first zone label (for panels that provide this
information), the trouble type (for trouble conditions), the time and date (assigned by the NCS), and
a panel specific type index. This box will be updated during receipt of normal events, as well as
during a data refresh operation. In the latter case most of the information will not be available, and
only the information that is available will be displayed. The NCS provides the ability to print all
events in the Detailed Event box.

44 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Menu Options for Operating the NCS Operation

3.5.4.3 Current Event Window


The current event window contains all network and local events, as well as system messages
received by the NCS. This can be manually invoked by clicking on the message button to review
the current events in the system. A maximum of 1000 events can be displayed in the system
message box (refer to Figure 3.16), with the newest event displayed on the bottom of the window.
If more than 1000 events are reached, the oldest event will be deleted. The events displayed in this
window are sorted by time and date, with the time column being displayed first. Events in this
window will be color coded, using the same color scheme as in the Unacknowledged Event Box.

ncscurrt.tif
Figure 3.16 Current Events Dialog Box
The user has the option to leave this window on top. This window will also always be displayed in
the same position as when previously closed.
3.5.4.4 Disabled Device Window
The disabled device window contains all disabled devices in the system. A disabled device can be
directly selected (double-clicked) from the list of events, and re-enabled. A confirmation dialog
box will be displayed, confirming the enable command. If the point enabled is a AM2020 or
AFP1010 zone, right clicking on the point will bring up another menu. This menu will give the
user an option of using the Zone Enable or Group Zone Enable command for the zone. All zones
will be colored to make them stand out within the window.

ncsdisdv.tif

Figure 3.17 Disabled Devices Dialog Box


The Disabled Device window will only be refreshed when the device is disabled or enabled, but at
a rate no greater than 6 seconds. This window will also be displayed in the same position as when
previously closed. The NCS provides the ability to print all events in the disabled device window.
3.5.4.5 History Manager
The user may select the History Manager Window from under the View Menu. The History
Manager is a program that records all operator actions and all events (alarms and troubles) that
have occurred in the system. Refer to Section 4 on page 52 for a detailed description of the History
Manager.

NCS Manual PN 51095:B1 3/08/02 45


www.PDF-Zoo.com
Operation Menu Options for Operating the NCS

3.5.5 Screen Navigation


Under this menu option the user can view different graphic building representations which have
been setup by the Graphic Setup Program. Select Next or Previously Viewed screens to view the
floor representations, see Figure 3.18. The user may perform this same function by pressing the <
and > arrows above the graphic, see Figure 3.19.

ncsarrow.tif
Figure 3.18 The Screen Navigation Menu

ncsarrow.tif
Figure 3.19 Next and Previously Viewed Arrow Keys

3.5.6 Trouble with NCS and INA Equipment


Signals originating at the NCS and INA are transmitted to other reporting nodes (i.e., NCS or
another INA) on the network. All local troubles are reported with the exception of node off-line
conditions which depend on the local settings of the NCS or INA and are reported individually by
all reporting nodes.
Below is a list of trouble messages which are exclusive to the NOTI•FIRE•NET ™ network
environment.
Node XXX Communications Failure
The node is programmed into the system but does not exist physically on the network, or the
node is physically attached to the network but is not programmed into the Command Center.

Communication Link Failure in Port A


Data is not being received on network (MIB) Port A. This trouble is only reported if the node
is configured for dual port supervision.

Communication Link Failure in Port B


Data is not being received on network (MIB) Port B. This trouble is only reported if the node is
configured for dual port supervision.

Lan Communications Failure


The specific network node can no longer communicate with the rest of the network, indicating
a problem with the network connections (refer to Appendix A of this manual for more
information).

46 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Read Status/Program Operation

3.6 Read Status/Program


The Read Status feature of the NCS allows the operator to display the status of nodes or devices

communicating on and programmed into the NOTI•FIRE•NET . Only AM2020/AFP1010 and
AFP-400 devices are supported for read status operations in this software release.
Detectors
To perform Read Status on a detector in the system, select the node the detector is connected to
from the Select System dialog box. Select OK. A node dialog box appears. Select the Detector tab.
Enter the address of the detector that is desired to perform Read Status. Select Program. The
Detector dialog box appears. This dialog box displays the current programming for the detector,
the verification counter, percentage of alarm, and whether the detector is in alarm, trouble, or
disabled (refer to Figure 3.20).

ncsdetread.jpg
Figure 3.20 Detector Read Status
Control and Monitor Modules
To perform Read Status on a module in the system, select the node the module is connected to from
the Select System dialog box. Select OK. A node dialog box will appear. Select the Module tab.
Enter the address of the module desired to perform Read Status. Select Program. The Module
dialog box will appear. This dialog box displays the current programming for the module and
whether the module is in alarm, trouble, or disabled (refer to Figure 3.21).

NCS Manual PN 51095:B1 3/08/02 47


www.PDF-Zoo.com
Operation Read Status/Program

ncsmodread.jpg
Figure 3.21 Monitor Module read Status
Zones
To perform Read Status on an AM2020/AFP1010 zone in the system, select the node the zone is
connected to from the Select System dialog box. Select OK. A node dialog box appears. Select
the Zone tab. Enter the zone number desired to perform Read Status. Select Program. The Zone
dialog box will appear. This dialog box displays the current programming for the zone and whether
the zone is in alarm, trouble, or is disabled (refer to Figure 3.22).

ncszonerd.jpg

Figure 3.22 Zone Read Status


Annunciator Points

48 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Read Status/Program Operation

To perform Read Status on an annunciator point, select the Annunciator tab from the Node dialog
box. Enter the address of the point desired to perform Read Status. Select Program. The
Annunciator Point dialog box displays. This dialog box shows the type of annunciator point and
whether it is in Alarm, Trouble, or Off (refer to Figure 3.23).

ncsannunrd.jpg
Figure 3.23 Annunciator Point Read Status
System Data I

ncssysdat1.jpg

Figure 3.24 System Data I Point Read Status


System Data II

NCS Manual PN 51095:B1 3/08/02 49


www.PDF-Zoo.com
Operation Read Status/Program

ncssysdat2.jpg
Figure 3.25 System Data II Point Read Status
System Data III

Figure 3.26 System Data III Point Read Status

50 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Read Status/Program Operation

Notes...

NCS Manual PN 51095:B1 3/08/02 51


www.PDF-Zoo.com
The History Manager NCS Integrated Operation

Section 4 The History Manager


The History Manager program is designed to directly integrate with the NCS, or operate as a stand-
alone program that can be used to view the history file at any given time. On PCs that have the
NCS installed, the History Manager can only be invoked through the NCS.

4.1 NCS Integrated Operation


When the History Manager is invoked, the History database is opened and all events are shown,
refer to Figure 4.1. While the History Manager is running, and a new, higher priority event is
received as the current one, the History Manager automatically shuts down to display the new
event. If equal or lower priority events are received, the History Manager will not shut down.

history.tif
Figure 4.1 Current History Database
To maximize operations while the History Manager is running, new events of equal or lower
priority, will not automatically be shown. Instead, a “Refresh Grid” button will indicate if new
events have been received. If this button is grayed out, the History Manager is showing all events
that have been received. If this button is not grayed out, then new events have been received by the
NCS, but are not currently being displayed by the History Manager. Once this button is pressed,
the History Manager will query the database to show the new events received, and vector to the top
of the page and display them, refer to Figure 4.2
refresh.tif

Figure 4.2 Refresh Grid Button

52 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
NCS Integrated Operation The History Manager

Stored History Files


The History Manager, by default, displays the currently active history database. This is indicated
by the program in the title bar. The user can open older history databases under the File menu,
Open Archived History File command, refer to Figure 4.3. This operation will close the current
database and open the selected one. The History Manager will indicate that the current history file
is no longer displayed by showing the path and file name of the current history database in the title
bar. See Figure 4.4 for an example of an archived history database.

archivhs.tif
Figure 4.3 Opening a Archived History File

archive.tif

Figure 4.4 Example of an Archived History Database


The current history database can be re-opened by selecting the Current History File command
under the File menu. If the history manager is shut down and later re-opened, and an old history
database was previously selected, the dialog box will be shown indicating this. The dialog box will
then ask if the user wants to open the current history database, or continue with the one selected.
Operator List
The History Manager provides an Operator List via a control tab on the main screen. This tab,
when invoked, will display all operators who have logged on to the system and the last login time
and date. This list is part of the history database, and therefore will be cleared whenever a new
history database is opened. Refer to Figure 4.5.

NCS Manual PN 51095:B1 3/08/02 53


www.PDF-Zoo.com
The History Manager NCS Integrated Operation

operlis.tif
Figure 4.5 Example of an Operator List Dialog Box
Number of Events
The number of entries in the history database is shown at all times. If a custom filter view is
selected, the number of entries will be equal to the number of events shown, refer to Figure 4.6.
numevnt.tif

Figure 4.6 Number of Events Shown on the History Database


Stand Alone Operation
In stand alone operation, the History Manager works similar to the NCS Integrated operation.
When the History Manager is powered up, a blank history file is initially displayed. The user has to
manually open any history file.
Custom Filters
The history manager will allow the operator to view the events using the following search criteria:
• All events
• All events while a specific operator was logged in*.
• All events by node number, loop number or device number*. They can be independently set.
• Events with a particular device status (fire alarm, security alarm, supervisory alarm, point or system trouble, module
activation, disabled device, operator login in/out, system programming and other events)*.
• Events which happened between in a given time frame*.
• Events received by device types, including detectors, modules, zones, bell circuits, panel circuits and other devices.

Note: The events marked * may be combined with any other search criteria.

Searching and displaying events in the history manager won’t adversely affect the NCS operation.
Any operation of this type is conducted as a low priority event. Refer to Figure 4.7 for an example
of search dialog box and Figure 4.8 for a search showing only Administration logins.

54 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
NCS Integrated Operation The History Manager

custfilt.tif
Figure 4.7 Example of a Search Dialog Box

custadmn.tif

Figure 4.8 Example of a Search of Administration Logins Only


If the user selects a custom filter view, the History Manager will indicate this by highlighting the
“Custom Filter” button. Refer to Figure 4.8. If the user doesn’t have any custom filters applied, the
“All Events” view will be displayed, and the "All Events" button will be highlighted. Pushing
either button will bring up the associated screen.
Visible columns
This command displays a window with all column types that can be shown in the History Manager.
A column can be selected or deselected, thereby hiding it from view. Each column can be resized
enabling the user to decide which columns they want to be shown, and the size of each column,
refer to Figure 4.9. These options are stored in the registry and invoked every time the History
Manager is powered up.

NCS Manual PN 51095:B1 3/08/02 55


www.PDF-Zoo.com
The History Manager NCS Integrated Operation

viscolm.tif
Figure 4.9 Select Visible Columns Dialog Box
Printing
The current history database, or any stored database, can be printed to the NCS Graphics printer
connected to the NCS. The Print command located under the File menu invokes the common
printer dialog box, (refer to Figure 4.10) enabling the selection of a printer. The printout consists of
the information shown in the history manager. Columns that are not visible, will not print out. If a
custom filter has been selected, only the events that are a part of the filter will be printed.

hisprint.tif

Figure 4.10 Print Dialog Box

4.1.1 History Backup


The history buffer may contain an unlimited number of entries. However, once the number reaches
100,000 events, a dialog box will be displayed. The dialog box will instruct the user to open a new
database and archive the current database.
The operator has the ability to archive the current database for backup, and thereby create a new,
blank history buffer. This is done directly through the NCS, by using the Archive History
command under the Administration menu. This command opens a dialog box to save the current
history database, with a .his extension (see Figure 4.11)

56 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
NCS Integrated Operation The History Manager

hisback.tif
Figure 4.11 Archive History Dialog Box
Automatic History Backup
The NCS can be automatically setup to back up a history file when the NCS reaches a user
selectable number of entries, with ranges from 10,000 to 100,000 events. In addition, the history
database can be backed up any day of the month, ranging from 1 to 28.
The current history file will be saved to a file name made up of the current date with a “a” prefix,
denoting an automatic backup. If more the one backup has occurred in any given day, a “01” will
be added to the file. For example, “a061298-1-.his” indicates the first file backed up automatically
on June 12th, 1998. A “a061298-2.his” file indicates that a second file was backed up that day.
The path and filename of the old history file will be saved in the new history file. All history files
are backed up in the \{install}\HistoryArchives directory.
4.1.1.1 Upload/Download (UPDL)
The upload / download window is used to upload or download the database from a node. Options
are available to initiate uploads, downloads, schedule uploads, and abort any current actions.
Information about the node number, status indication and progress indication will be displayed by
the upload / download. Select UPDL under the View menu option and a Main Screen will appear
showing nodes and their completion percentage, refer toFigure 4.12.
ncsudmain.jpg

Figure 4.12 Upload/Download Main Window

NCS Manual PN 51095:B1 3/08/02 57


www.PDF-Zoo.com
The History Manager NCS Integrated Operation

All upload / download messages that affect the operation are stored in the history window and
current event window. This includes initiating the upload / download process, aborting the process,
or any errors that will prohibit the process from completing successfully. A message will also be
stored in these windows if the upload / download has successfully completed.
Upload - Before an upload is initiated, the NCS will query the user for a database file to store the
received information in. All uploaded information, including the database version, will first be
stored in the NCS run-time database. After the upload is complete, the NCS will copy the
information for the node upload from the run-time database to the database specified by the user.
Refer to Figure 4.13 for an example screen of uploading nodes.

Select the [...] button to


choose a database.

ncsupload.jpg
Figure 4.13 Uploading Nodes Screen
If the database specified is an older version, an error dialog box will be displayed, indicating the
problem. The upload is not allowed to proceed at this time. The Verifire utility has the ability to
convert an older database format to the current database format.
Download - The NCS will query the user for a database to download. It will open the database
specified, and check the version. If the database version is old, the NCS will display an error dialog
box indicating the problem. The user is not given the option to continue the download. Refer to
Figure 4.14 for an example of a download screen.
ncsudown.jpg

Figure 4.14 Downloading Nodes Screen

58 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
NCS Integrated Operation The History Manager

Note: The Verifire utility has the ability to convert an older database format to the current database format.

Scheduled Uploads - The NCS has the ability to schedule uploads on a monthly or “one shot”
basis. The one shot will provide the ability to schedule a set of panels to upload only once. Options
will be made available for the starting time and which nodes to upload. If a monthly upload is
selected, the day and time must be specified. If a one shot upload is specified, the exact data and
time must be specified. All scheduling options, including dates, times, and nodes selected, will be
NCS database.

ncssched.jpg
Figure 4.15 Scheduled Uploads Screen
• Once Only Upload - This option will allow the user to upload a set of panels on a “one-shot” basis. A date and time for
the upload is entered and the NCS initiates the upload at that time.
• Monthly - The NCS has the ability to schedule uploads on a monthly basis. The user can select the day of the month
and time to upload. The NCS can then upload the specified set of nodes every month at the specified time. To alleviate
the problem of how many days are in a month, the plug-in only allows a range of 1 - 28 for the day specified.
• Multiple Panel Upload - The NCS has the capability of uploading or downloading up to five nodes at a time.

NCS Manual PN 51095:B1 3/08/02 59


www.PDF-Zoo.com
The Graphic Setup Program Program Layout

Section 5 The Graphic Setup Program


The Graphic Setup Program allows the creation of floorplans and devices as well as associating
information about each device.

5.0.1 NCS Integrated Operation


If the GSP is called up from the NCS, all operations are identical. However, when the GSP is
exited, graphics.mdb is not automatically updated. Instead, the database can be updated in the NCS
using the Update Graphic Database command under the Graphics menu. If the NCS is not running
at the time the database is updated, the database can be updated once the NCS is powered up, and
the update command is executed.
In both the Standalone and NCS integrated operations, on power-up the existence of the backup
database will be checked. If it exists, then a dialog box will be displayed indicating that it was
found. The user then has the option to use this database, or the graphics database. If the graphics
database is chosen, recent edits might be lost.

5.1 Program Layout


The Graphic Setup Program (GSP) consists of several different windows. The main graphics area
and key-map area have the same size and location as in the NCS. This allows the user to place
screen floorplans and devices, and see them exactly as they would appear in the NCS. Refer to
Figure 5.1.

Title Bar Information Window

Menu Bar

Key-Map Area

Toolbar

Graphics Area
Tree View Window
(Screen Device View)
ncsgspint.jpg

Figure 5.1 Graphic Setup Program Interface Window


In addition, the top area has room for displaying the current screen information and command
buttons. The area to the right of the main graphics screen contains the Tree View Window which is
similar to a Windows Explorer type structure, refer to Figure 5.2. The Tree View Window offers
three different views of the system:

60 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Program Layout The Graphic Setup Program

5.1.1 Floor Plan Tree View


This view shows how the different screens are linked through groups. A path from the left to the
right identifies screens containing lower groups, down to the floor plan containing only devices.
This view can also be used to navigate through the screens. Double-click on a floor plan name to
display the appropriate floor plan. Refer to Figure 5.2.

ncstree.jpg
Figure 5.2 Floor Plan Screen Tree View Example

5.1.2 Group Tree View


This view shows which devices are linked to a group. The groups and devices associated with the
group are shown. Double-clicking on an item in this view will bring up the appropriate dialog box
to change any settings. Refer to Figure 5.3.

ncsgrview.jpg

Figure 5.3 Group Tree View Example

5.1.3 Floor Plan Device View


This view shows all screens in the system, and the devices associated with a screen, which includes
information labels and navigational buttons. Double-clicking on a floor plan displays the screen,
double-clicking on a device displays the edit dialog box for the device. Refer to Figure 5.4.
ncsscview.jpg

Figure 5.4 Floor Plan Device View Example

5.1.4 Information Windows


The Information Window contains the information about the current screen that is edited. This
includes the screen Description, keymap file name, guidance text file name, and floor plan file
name. Refer to Figure 5.5.

NCS Manual PN 51095:B1 3/08/02 61


www.PDF-Zoo.com
The Graphic Setup Program Program Layout

infowin.jpg
Figure 5.5 The Information Window
Double-clicking on any of these fields displays a file dialog box. This allows the user to change the
keymap or floor plan, select a new guidance text file, or change the name of the screen that is
currently edited, refer to Figure 5.6 for an example. If a floor plan is changed, a “Save Screen”
option appears, refer to Figure 5.7, allowing the user to save all current changes. This option only
appears if changes have been made to the current screen. In addition, double clicking on the floor
screen name in the Tree View Window also saves any current changes that have been made.

selectfl.jpg
Figure 5.6 File Dialog Box savescrn.jpg

Figure 5.7 Save Screen Option Dialog Box

5.1.5 Tool Bar


A toolbar is available through the Information Window. This toolbar is not restricted to the
Information Window and can float to other areas of the screen. The toolbar contains shortcut
buttons for various graphic operations, including: creating groups, detectors, modules, zones,
information labels and navigation buttons, creating hot keys (hot templates) and editing a floor plan
or key map. Refer to Figure 5.8.
Create Navigation Button
Create Detector Create Zone
Edit File Plan
toolbar.jpg

Create Group

Create Module Display Hot Keys


Edit Keymap
Create Information Label

Figure 5.8 Tool Bar

62 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Graphic Floor Plans The Graphic Setup Program

If a template group is defined, then pressing the short cut button will display a dialog box from
which a template can be chosen. If a template is not defined, then the first 40 items in the directory
will be displayed in a picture box. For example, if the Create Zones Button is pressed, and no
templates are defined, the first 40 icons found in the device directory will be displayed in a picture
box. However, if templates are defined, a selection of all zone templates will be shown. After a
template is chosen, only the icons associated with that template will be displayed. Select a toolbar
icon and a library of icons associated with that button will appear. Choose an icon by clicking on it
and dragging it to a location on the floor plan screen.

5.2 Graphic Floor Plans


Floor plans are bitmaps that are displayed on the main screen of the NCS. The bitmaps measure
780 x 538 pixels and are customized through Paint Shop Pro, a third party program that is packaged
with the NCS. All floor plan bitmaps must be stored in the directory \{install}\Floors. All images
saved with Paint Shop Pro must be saved in bitmap formats, not as the default .psp extension.

5.2.1 Adding Floor Plans to the NCS


A floor plan can be added to the NCS by selecting the Screens menu option, New Screens
command from the menu bar. A confirmation dialog box is then displayed. This dialog box allows
the user to select an existing floor plan and keymap, or create a new floor plan and key-map. In
both cases, a floor plan title must be selected. Refer to Figure 5.9.

floorpl.jpg

Figure 5.9 “New Screen” Dialog Box


If an existing floor plan or keymap is to be added, a dialog box appears allowing the user to select a
floor plan, refer to Figure 5.10 for an example. Once the floor plan and keymap are selected, they
will be displayed in the Graphic Setup Program.
floorpic.jpg

Figure 5.10 Existing Floor Plan Dialog Box (Example)

NCS Manual PN 51095:B1 3/08/02 63


www.PDF-Zoo.com
The Graphic Setup Program Graphic Floor Plans

If a new floor plan or keymap is to be added, a blank floor plan and key map will appear with the
floor plan title. This floor plan can be altered entirely in PaintShop Pro, or in other graphic
programs such as Paint and then pasted into the screen. Double-clicking on a floor plan or keymap
will invoke PaintShop Pro where any changes or edits can be made to the drawing. When
PaintShop Pro is exited, the file date and time are checked on the hard drive. If the date or time of
the file has changed, the bitmap is copied over the existing floorplan and displayed in the GUI.
Each screen contains a floorplan, keymap, screen description and guidance text. Although each
floor plan has a corresponding numeric identifier assigned to it, only the screen name is displayed
on the NCS main form. The Graphic Setup Program displays the name of the current screen, as
well as the floor plan filename, the keymap filename, and the guidance text file name that is
associated with the screen.

5.2.2 Selecting Floor Plans


The screen selecting command displays a dialog box which contains all screens with their
corresponding floor plan number, and a preview window. It allows the user to select a floor plan
for editing purposes. Once a screen floor plan has been selected, click the OK button and the new
floor plan with all its associations will be displayed, refer to Figure 5.11.

Figure 5.11 Selecting Floor Plans Dialog Box selflpln.jpg

5.2.3 Deleting Floor Plans


The Graphic Setup Program allows the operator to delete screens. When this operation is selected,
a dialog box containing all screens in the GSP, with the corresponding floor plan number, will be
displayed. In addition, this dialog box will contain a preview of the floor plan belonging to the
screen that is to be deleted, refer to Figure 5.12.
delscrn.jpg

Figure 5.12 Deleting Floor Plans Dialog Box


A confirmation dialog box will be displayed before the floor plan is actually deleted from the
system, refer to Figure 5.13. Deleting a floor plan causes all devices, information labels, navigation
buttons, etc. that are on the screen, to also be deleted. The physical bitmap files for keymaps and
floorplans are not deleted.

64 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Graphic Floor Plans The Graphic Setup Program

delsrdi.jpg
Figure 5.13 Deleting a Floor Plan Confirmation Dialog Box

5.2.4 Setting Keymap Links


A key map can be linked to a floor plan diagram if desired. In the NCS, when an area in the key
map is double-clicked, the screen linked to the key map will appear. This allows easy navigation of
the graphics.
Keymap links can be set under the Screens menu, Set Keymap Link command. When this
command is activated, a dialog box appears, displaying all screens in the system, refer to Figure
5.14. Once the keymap and screen are linked, the floor plan will be displayed when the
corresponding keymap area is selected.

gspkeymplk.jpg

Figure 5.14 Selecting Keymap Links Dialog Box

5.2.5 Screen Title


The screen title describes the present screen. A 40-character floor plan title can be entered. All
screen titles are available for viewing and navigating from the Tree View Window.

5.2.6 Guidance Text


Guidance Text can be added to any screen. Guidance text may contain instruction or warnings
applicable to the displayed area. The text is entered using the guidance text viewer/editor, refer to
Figure 5.15. The guidance text can be printed automatically or by device activation from within the
NCS or manually by user selection. To manually print guidance text by user selection, press the
button to display, choose auto display, and select auto print.
textfl.jpg

Figure 5.15 Guidance Text Dialog Box Example

NCS Manual PN 51095:B1 3/08/02 65


www.PDF-Zoo.com
The Graphic Setup Program Keymap Area

5.3 Keymap Area


Keymaps are bitmaps which are created and assigned during the new screen process. The bitmaps
measure 327 X 167 pixels. Keymaps are displayed above the floor plan on the Main NCS screen.
The Keymap acts as an overview for the floor plan it belongs to. Every floor plan must have a
keymap assigned to it, although the same Keymap may be assigned to different screens. Keymaps
can be customized through Paint Shop Pro. If a keymap link has been created, double-click the
keymap while in the NCS to bring up the associated screen.

5.4 Menu Bar Options


5.4.1 File
Select Exit Setup to close the Graphic Setup Program and return to the NCS, see Figure 5.16.

gspfile.jpg
Figure 5.16 The File Menu

5.4.2 Screens
Under the Screens menu option, the user can create a new graphic screen, select a previous graphic
screen, delete a graphic screen or set a keymap link to a graphic screen, see Figure 5.17.

gspscreen.jpg

Figure 5.17 The Screens Menu

5.4.3 Devices
gspdevice.jpg

Figure 5.18 The Devices Menu


gspdevgr.jpg

Figure 5.19 Groups

66 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Menu Bar Options The Graphic Setup Program

gspgrpsetup.jpg
Figure 5.20 Setting Up Groups

gspdevdet.jpg
Figure 5.21 Detectors

gspdevmod.jpg

Figure 5.22 Modules


gspdevzon.jpg

Figure 5.23 Zones

NCS Manual PN 51095:B1 3/08/02 67


www.PDF-Zoo.com
The Graphic Setup Program Menu Bar Options

gspdevinfol.jpg
Figure 5.24 Information Labels

gspdevnb.jpg
Figure 5.25 Navigation Buttons

5.4.4 View
The View menu option allows the user to customize the toolbar to the users preference and view
screen statistics. Screen statistics include: device (detectors, modules, zones) count, graphic
(labels, navigation buttons) count and a Total count (combination of both).
gspview.jpg

Figure 5.26 The View Menu

5.4.5 Setup
The Setup menu allows the user to edit the site logo in Paint Shop Pro.
setupmenu.jpg

Figure 5.27 The Setup Menu

68 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Device Icons The Graphic Setup Program

5.4.6 Help

gsphelp.jpg
Figure 5.28 The Help Menu

5.5 Device Icons


After a floor plan and keymap screen have been created, Device Graphics can be added. Device
Graphics include Level1 Groups, Level2 Groups, Devices (detectors, modules and zones),
Navigation Buttons, and Information Labels. All device bitmaps must be stored in the
{install}\device directory, Groups must be stored in the {install}\group directory.

5.5.1 Devices
A symbol can be used to graphically represent a device (detector, module or zone) in the fire alarm
system. In addition to a graphical representation of the device, the user can assign device
descriptions and link pictures, documents and sound to the device. The NCS does not permit one
device to be displayed on multiple screens; a device can only appear on one screen.
A new device can be added to the system by using the Devices Menu command or through the
toolbar. When using the toolbar, select the appropriate detector, module or zone you would like to
add. After this command is executed, a library of icons will be displayed to select a symbol
representing the device, refer to Figure 5.29.
detbox.jpg

Figure 5.29 Detector Library of Icons


Once a device is selected, a new device dialog box is displayed where the user can enter address
information about the device, Figure 5.30. For detectors, modules and zones, options are available
to link a sound file, document and/or picture to the symbol. In addition, each of these devices can
be linked to a group. If grouping is to be used, the groups and group screens should be created
before actual devices. Devices can also be set to auto-vector, in this case the Auto-Navigate option
must be selected.

NCS Manual PN 51095:B1 3/08/02 69


www.PDF-Zoo.com
The Graphic Setup Program Device Icons

newdetbx.jpg
Figure 5.30 New Detector Dialog Box
The active icon will blink during an active condition, and steady when acknowledged. Once the
point returns to normal, the normal bitmap is displayed. The trouble, disabled device and pre-alarm
icons also operate the same way.

5.5.2 Detectors
Detectors have other symbols associated with them; an active icon, a trouble icon, a disabled
device icon and a pre-alarm icon. The appropriate icon will be displayed for an event, the device
label blinks if an event is unacknowledged, and is steady if the event is acknowledged.

5.5.3 Modules
Modules show an active, trouble and disabled device symbol. If the module can be disabled from
the NCS, the Disable Device option must be chosen. If the module is an output module, and can be
activated from the NCS, then the Control On/Off option must be chosen.

5.5.4 Zones
A zone shows an active and disabled device symbol.

5.5.5 Linked Files


Sound, document and picture files can be linked with a device. To access these files through the
NCS software, the files must be in specific directories on the PC.
• Pictures (scanned photos) must be in the {install}\Pictures directory.
• Text files (instructions etc.) must be in the {install}\docs directory.
• Sound files (verbal instructions or warnings) must be in {install}\Sounds directory.
These files can also be manually activated by the operator.

5.5.6 Information Labels


Information labels are bitmaps that can be added to a floor plan for additional information. These
labels are generally symbols representing biohazard, flammable or other important information,
refer to Figure 5.31. Information labels do not receive information regarding alarms and troubles
from the system from the system.

70 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Device Icons The Graphic Setup Program

infolbl.jpg
Figure 5.31 Information Labels Dialog Box
To add an information label under the Devices menu option, select the Information Label option to
the New Information Label command, or select the information label icon on the toolbar. After this
command is executed, a library of icons will be displayed to select a symbol representing the
information label. If template groups are defined for that label, then a group must be chosen before
a label is selected. Once a label is selected, a new label dialog box will be displayed where the user
can enter text information about the information label.
Double-click on a device label icon and drag it to the corresponding area on the graphic floor plan,
it will then appear on the screen. Double-click on the information label in the NCS to display the
text file associated with the information label. Information labels can be moved around the screen
without being deleted and recreated.

5.5.7 Navigational Buttons


Navigational Buttons can be placed anywhere on a graphic screen. These buttons are then linked to
other screens in the NCS. Place the cursor over a navigational button to see the label of the floor
plan associated with that button.
To create a navigational button link, select the Navigational Button icon on the toolbar or select the
Devices Menu option, New Navigation Button. A dialog box will appear that contain a navigation
button, refer to Figure 5.32. Double-click on the button and drag it to the appropriate area on the
graphic floor plan. After the navigation button is dragged on the screen another dialog box will
appear allowing you to set up a link, refer to Figure 5.33.
navbut5.jpg

Figure 5.32 Navigation Button Dialog Box

NCS Manual PN 51095:B1 3/08/02 71


www.PDF-Zoo.com
The Graphic Setup Program Device Icons

navbut2.jpg
Figure 5.33 Setup Links Dialog Box

5.5.8 Delete Operations


To delete a particular button, device or information label from a screen, place the mouse over the
symbol and right-click on the mouse (or use the Devices menu option, delete module, detector,
zone, etc.). A dialog box will appear allowing the user to delete a symbol.

5.5.9 Searching for Specific Items


Once many screens are entered, finding a particular device without displaying each floor plan is
difficult. The NCS has a Find command located under the Devices menu option, under each device
category, which allows the user to find a device by entering in its device label or address Refer to
Figure 5.34. Once the label or address is entered, the appropriate floor will be invoked. For easier
viewing, select the Flash Label checkbox to make the device blink for two seconds. For
information labels and navigation buttons, the option to blink the graphic is given (no labels for
these).
findcom.jpg

Figure 5.34 Example of a Find Dialog Box for Detectors

5.5.10 Rules for Setting Up Device Graphics


The following rules must be followed when setting up device graphics.
• A Level 1 Group must be created before any Level 2 Groups.
• Groups must be created before their associated devices.
• A floor Plan containing Level 1 Groups can contain any Graphic Device.
• A Level 2 Group should not be placed on a screen where a Level 1 Group resides.
• Any Floor Plan can contain a Navigational Button, which functions as a link to another Floor Plan.
• Any floor Plan can contain Information Labels, which display text when double-clicked.
• If any Groups are created (or exist already when beginning an edit session), the default auto-
vectoring setting is set to false.

72 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Groups The Graphic Setup Program

5.6 Groups
Groups allow the creation of screen hierarchies for displaying the pathway to an off normal device,
starting at a top level site view. Two levels of grouping, Level 1 and Level 2, are used to associate
devices with a single bitmap. A Level 1 group can have either Level 2 groups or actual devices
associated to it. A Level 2 group must be associated upwards to a Level 1 group (in the floor plan
hierarchy), and will have devices associated below it. The two levels of grouping plus the floor
plan where the actual off-normal device is located offer three main view levels for floor plan
navigation. These levels coupled with Navigation Buttons offer a variety of setup possibilities for
graphics.
The graphics are no longer limited to one top screen, therefore the “Home Screen” is the first screen
created. This screen is shown on NCS / GSP Startup. This ability to have many top screens means
that Level 1 Groups can exist on different screens, each representing the Top Screen of a different
graphic path.

5.6.1 Level 1 Groups


A Level 1 group requires a normal state bitmap and a description. A label is created from the
Group description and displayed bottom center of the group bitmap. This label flashes when an
off-normal event is received for an associated device. The flashing occurs by alternating the
normal group description with the color and text of an off-normal event. Optional active and
trouble bitmaps can be assigned to a group for these conditions.

5.6.2 Level 2 Groups


A Level 2 group requires an associated Level 1 group name, normal state bitmap, and a description.
An optional active and trouble bitmap can be assigned and displayed when any off-normal
conditions occur for the group. The Level 1 groups are selected from an available list box. If no
Level 1 groups exist, an error message is displayed and the Level 2 setup is cancelled.
A label is created from the group description and displayed bottom center of the group bitmap.
This label will flash when an off-normal event is received for an associated device. The flashing
occurs by alternating the normal group description with color and text of an off-normal event.

5.6.3 Group Setup Restrictions


The following are restrictions for groups:
• If a device on a floor plan is associated with a group, then all other devices on that floor plan
are automatically restricted to the groups contained on the screen where the associated group
resides. In other words, if L1D1 is associated with a specific group 2, then L1D2 on that floor
plan must also be associated with group 2, or another group on the screen where group 2
resides.
• Screens can contain group 1 icons or group 2 icons, but they can not be intermixed. If a floor
plan has a group defined, all other groups on that floor plan must be of the same level, either
Level 1 or Level 2.

5.6.4 Group Navigation


If a device goes into alarm or trouble, while auto-vectoring is off and a floor plan is displayed that
contains the device linked, then the screen with the group containing the device where the event has
occurred will appear and the group label will flash. This can indicate that an off-normal condition
has occurred within the area that the group monitors. Double clicking on the group will either
invoke the floor plan containing a Level 2 group (assuming that the first group was a level 1 group),
or the device that is off-normal. If a Level 2 group is defined, then the floor plan containing this
group will be invoked, and change to its off-normal bitmap. Double clicking now will invoke the
off-normal device.
If the device is directly linked to the top level group, then double-clicking on the device will invoke
the floor plan that contains that group.

NCS Manual PN 51095:B1 3/08/02 73


www.PDF-Zoo.com
The Graphic Setup Program Setup Templates

5.7 Setup Templates


Templates can be defined to make device setups easier. Templates can be defined to group a
number of device graphic file options together, or to define a Hot Template which contains the
same bitmap and options for the device.

5.7.1 Template Groups


A template contains specific bitmap file groupings for modules, detectors, zones, information
labels, groups, and navigation buttons. These templates can be shown on the main screen, and used
to drag items on the screen. They are designed to logically group specific devices on a dialog box,
with each icon shown. A maximum of 40 icons can be shown per template.
When creating a template, a dialog box listing all items in the directory is displayed. Select the
checkbox next to the items to add them to the template.

5.7.2 Hot Templates


A hot template is a setup of specific modules, detectors or zones. Once a device has been added to
a screen, an option within the device setup saves it as a hot template. These hot templates can then
be used to set up other devices with the same options. The hot templates saved can be invoked
from the toolbar.
Note: If a device that defines a hot template is deleted, the hot template will also be deleted.

A hot template is defined for a specific device, (the hot template and the device are actually one item).
This allows the user to easily copy information from one device to another. Once the information for
a device hot template is changed, all new devices created from it will have the new information.
Devices created with the hot template before it was changed will not contain the new information.

5.8 Custom Bitmap


The bitmap that appears on the NCS main window next to the keymap area can be customized.
Changes to this bitmap can be done through PaintShop Pro. To call up this file under the Setup
menu select the Edit NCS Graphic command. When the graphics are updated, changes to the
Custom bitmap are also updated. Refer to Figure 5.35.

editncsg.jpg

Figure 5.35 Example of Editing a Bitmap in PaintShop Pro

74 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Template Files The Graphic Setup Program

5.9 Template Files


For the creation of blank floor plans, and invoking PaintShop Pro, several files are required for the
program to operate correctly. These files can not be deleted. If they are missing, the program will
not operate correctly.

5.10 NCS Required Files


3. Floor Directories
{install}\Floors\Genfloor.bmp
\Olefloor.bmp
\NotProgF.bmp

4. Keymap Directories
{install}\Keymaps\Genkey.bmp
\Olefloor.bmp
\NotProgK.bmp

5. Device Directories
{install}\Device...Detector, Module, Zone BMP’s
\Group...Group BMPs
\Inflabel...Device Information label BMPs
\Navigate...Device navigation button BMPs
\Pictures...Device associated bitmaps
\Sounds...Device wave files
\Docs...all text files

Note: Groups and Group screens should be created first if grouping is to be used.

NCS Manual PN 51095:B1 3/08/02 75


www.PDF-Zoo.com
Windows 2000 Security Disable Procedure Disable Procedure

Appendix A: Windows 2000 Security Disable Procedure


A.1 Disable Procedure
In the Windows 2000 environment, a log-on box is displayed requesting a user name and password
each time Windows 2000 starts up. The Windows 2000 log-on box may be disabled if the NCS
software login function is sufficient for security or if the NCS software is to start automatically
once Windows 2000 is running. Once the NCS software starts, the user must still choose Login
under the File menu and enter a user name and password to gain access to the NCS. Note: The
Login function in the NCS software can not be eliminated. To eliminate the Windows 2000 log-on
box, execute the following steps:
1. From Program Manager, go to the File menu (for Windows 2000 users, select Start, then Run).
Select Run and type regedt32. This brings up the Windows 2000 Registry.
2. Go to the HKEY_LOCAL_MACHINE dialog box.
3. Double-click on Software, then on Microsoft.
4. Double-click on Windows 2000, followed by Current Version, and then Winlogon. At this
point the screen will be split into two sections. The section on the left side contains the tree
structure of the registry and the right side contains values stored in the registry.
5. From the Edit menu, select Add Value. A dialog box will pop up. Under Value Name, type
DefaultPassword (do not change the displayed data type).
6. Press OK. Another dialog box will pop up. Under String, enter the current password of the
NT administrator. The password is case sensitive, so be sure it is entered correctly. Press OK
for the change to take effect.
7. From the Edit menu, select Add Value again. Under Value Name, type AutoAdminLogon.
Press OK. Under String, enter 1 (do not change the displayed data type).
8. Verify that the two new variables entered in the previous steps appear on the right side of the
screen. The variables should appear as follows:

AutoAdminLogon:REG_SZ:1
DefaultPassword:REG_SZ:<password> (Password is the password entered by the
administrator in Step 6.)
9. Exit the Windows 2000 Registry, and reboot Windows 2000. When it starts, the log-on screen
should be bypassed.

A.2 Re-Enable Procedure


To re-enable Windows 2000 security, follow steps 1-3 above. Tab over to the right section of the
screen and select the AutoAdminLogon variable. From the Edit menu, select Delete. Press OK.
Do the same for the DefaultPassword variable. Exit the Registry, and reboot Windows 2000.

76 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Installing PaintShop Pro 7.0 Miscellaneous Software Installation

Appendix B: Miscellaneous Software Installation


B.1 Installing PaintShop Pro 7.0
• Run Setup.exe from the PSP 7.0 CD (all default options are recommended).

B.2 Installing the Secure Desktop Software


This software must be installed and configured to comply with UL-864. Follow these steps to
install and configure the software.
1. Run setup.exe from the Installation CD.
2. After setup has completed, configure the software by running the Secure Setup program from
the Secure Desktop Program Group.
3. Select "Secure Desktop Icon Settings and General Options" instead of "Windows Explorer or
Program Manager (Default)".
4. Under "Non-Specific User", select Setup, then select F1. Browse to the NCS directory, select
NCS.exe. Make sure to select "App Start Enabled". Also select this option for all other
programs that will be selected.
5. Select F2. Browse to the VeriFire Tools directory (if installed), and select nts.exe.
6. Select F3. Browse to the VeriFire-1020 directory and select veri1020.exe.
7. Select F4. Browse to \program files\Adaptec\Easy CD Creator 4\Create CD\createcd.exe.
This will enable the CD burner software.
8. Select F5. Browse to \program files\Jasic Software Inc\Paint Shop Pro 7\psp.exe. This
completes setting up the programs to run on the PC.
9. Under Options, select Alt-Tab, Sft-Alt-Tab, Ctrl-ESC, Alt-ESC, Sft-Alt-ESC, Ctrl-Alt-ESC
and Sft-Ctrl-Alt-ESC. These keystrokes will not be permitted.
10. Go to the Password Tab, select Exit Password. Enter a password that is easily remembered.
The default password is "admin".
11. Click on the "Registry" button. Select "Secure Desktop Gina", and select "Disable Ctrl-Alt-
Del". Select "Automatic Login Enabled", if that feature is desired.
12. Click on "OS Policy", and sleect "Windows 2000 / ME". Under Task Manager, select
"Disabled".
The PC must now be rebooted for the settings to take effect. After the PC powers back up, the
Windows Desktop will be replaced with the Secure Desktop. Click on the setup button to change
any other options.

NCS Manual PN 51095:B1 3/08/02 77


www.PDF-Zoo.com
Message Tables Messages

Appendix C: Message Tables


C.1 Messages
Some messages differ between the AFP-200, AFP-400 and the NCS. Table C.1 and Table C.2
depict AFP-200 messages as they appear on the NCS. Table C.3 through Table C.5 depict AFP-
300/400 messages as they appear on the NCS. If the system displays a message that is not self-
explanatory and is not listed in this section, contact a Notifier Representative. For more
information on INAs and their troubles, refer to the INA manual.

78 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Messages Message Tables

AFP-200 Type
AFP-200 Message NCS Message
I.D.

Supervisory activated: ACTIVE SUPERVISORY custom point label activated: Supervisory Sprvsry Mntr custom point label
zone label 01:40P 3/06/00 M04 zone label N12L1M4 13:40:00 3/06/00

trouble: TROUBL SUPERVISORY custom point label zone trouble: Trouble Supervisory Sprvsry Mntr custom point
label OPEN CIRCUIT 02:07P 3/06/00 M04 label zone label Open Circuit N12L1M4 14:07:00 3/06/00

Tamper activated: ACTIVE TAMPER custom point label zone label activated: Supervisory Sprvsry Mntr custom point label
02:20P 3/06/00 M05 zone label N12L1M5 14:20:00 3/06/00

trouble: TROUBL TAMPER custom point label zone label trouble: Trouble Supervisory Sprvsry Mntr custom point
OPEN CIRCUIT 02:43P 3/06/00 M05 label Open Circuit zone label N12L1M5 14:43:00 3/06/00

Non-Fire activated: ACTIVE NONFIRE custom point label zone label activated: *Active Non Alarm custom point label zone
02:07P 3/06/00 M06 label N12L1M6 13:10:00 15/06/00

trouble: TROUBL NONFIRE custom point label zone label trouble: Trouble Non Alarm custom point label zone label
OPEN CIRCUIT 02:21P 3/06/00 M06 Open Circuit N12L1M6 14:21:00 3/06/00

Hazard Alert activated: ACTIVE HAZARD ALERT custom point label activated: Supervisory Hazard Alert custom point label
zone label 02:33P 3/06/00 M07 zone label N12L1M7 14:33:00 3/06/00

trouble: TROUBL HAZARD ALERT custom point label trouble: Trouble Supervisory Hazard Alert custom point
zone label OPEN CIRCUIT 02:47P 3/06/00 M07 label zone label Open Circuit N12L1M7 14:47:00 3/06/00

Fire Control activated: ACTIVE FIRE CONTROL custom point label activated: *Active Non Alm Mon custom point label zone
zone label 03:21P 3/06/00 M08 label N12L1M8 15:21:00 3/06/00

trouble: TROUBL FIRE CONTROL custom point label trouble: Trouble Non Alm Mon custom point label zone
zone label OPEN CIRCUIT 03:35P 3/06/00 M08 label Open Circuit N12L1M8 15:35:00 3/06/00

Abort Switch activated: ACTIVE ABORT SWITCH custom point label activated: *Active Abort Switch custom point label zone
zone label 03:07P 3/06/00 M09 label N12L1M9 15:07:00 3/06/00

trouble: TROUBL ABORT SWITCH custom point label trouble: Trouble Supervisory Hazard Alert custom point
zone label OPEN CIRCUIT 04:17P 3/06/00 M09 label zone label Open Circuit N12L1M9 16:17:00 3/06/00
Man. Release activated: ALARM: MAN. RELEASE custom point label activated: Alarm: Man Release custom point label zone
zone label 04:34P 3/06/00 M10 label N12L1M10 16:34:00 3/06/00

trouble: TROUBL MAN. RELEASE custom point label trouble: Trouble Man Release custom point label zone
zone label OPEN CIRCUIT 04:58P 3/06/00 M10 label Open Circuit N12L1M10 16:58:00 3/06/00

Trouble Mon activated: TROUBL TROUBLE MON custom point label activated: Trouble Trbl Monitor custom point label zone
zone label SHORT CIRCUIT 08:24A 3/06/00 M12 label N12L1M12 08:24:00 3/06/00

trouble: TROUBL TROUBLE MON custom point label trouble: Trouble Trbl Monitor custom point label zone
zone label OPEN CIRCUIT 08:36A 3/06/00 M12 label Open Circuit N12L1M12 08:36:00 3/06/00

Burglar Ala activated: ACTIVE BURGLAR ALA custom point label activated: Security Area Monitor custom point label zone
zone label 08:52A 3/06/00 M13 label N12L1M13 08:52:00 3/06/00

trouble: ACTIVE BURGLAR ALA custom point label zone trouble: Trouble Security Area Monitor custom point label
label 09:33A 3/06/00 M13 zone label Security Tamper N12L1M13 09:33:00 3/06/00
Silence activated: ACTIVE SILENCE custom point label zone label activated: *Active Silence custom point label zone label
11:34A 3/06/00 M14 N12L1M14 11:34:00 3/06/00

trouble: TROUBL SILENCE custom point label zone label trouble: Trouble Silence custom point label zone label
OPEN CIRCUIT 11:45A 3/06/00 M14 Open Circuit N12L1M14 11:45:00 3/06/00

Pas Inhibit activated: ACTIVE PAS INHIBIT custom point label zone activated: *Active Pas Inhibit custom point label zone label
label 12:04P 3/06/00 M15 N12L1M15 12:04:00 3/06/00

trouble: TROUBL PAS INHIBIT custom point label zone trouble: Trouble Pas Inhibit custom point label zone label
label OPEN CIRCUIT 12:10P 3/06/00 M15 Open Circuit N12L1M7 12:10:00 3/06/00

*Will be displayed only in History Manager, Current Event window and NonFire Event window in the NCS

Table C.1 AFP-200 Messages as They Appear on the NCS (page 1 of 2)

NCS Manual PN 51095:B1 3/08/02 79


www.PDF-Zoo.com
Message Tables Messages

AFP-200 Type
AFP-200 Message NCS Message
I.D.
System Reset activated: ACTIVE SYSTEM RESET custom point activated: *Active System Reset custom point label zone
label zone label 12:21P 3/06/00 M16 label N12L1M16 12:21:00 3/06/00

trouble: TROUBL SYSTEM RESET custom point label trouble: Trouble System Reset custom point label zone
zone label OPEN CIRCUIT 12:39P 3/06/00 M16 label Open Circuit N12L1M16 12:39:00 3/06/00
Smoke Detect activated: ALARM: SMOKE DETECT custom point activated: Alarm: Smoke Detect custom point label zone
label zone label 12:46P 3/06/00 M17 label N12L1M17 12:46:00 3/06/00

trouble: TROUBL SMOKE DETECT custom point trouble: Trouble Smoke Detect custom point label zone
label zone label OPEN CIRCUIT 02:06P 3/06/00 M17 label Open Circuit N12L1M17 14:06:00 3/06/00
Heat Detect activated: ALARM: HEAT DETECT custom point activated: Alarm: Heat Detect custom point label zone label
label zone label 02:16P 3/06/00 M18 N12L1M18 14:16:00 3/06/00

trouble: TROUBL HEAT DETECT custom point label trouble: Trouble Heat Detect custom point label zone label
zone label OPEN CIRCUIT 02:26P 3/06/00 M18 Open Circuit N12L1M18 14:26:00 3/06/00
Water Flow activated: ALARM:WATERFLOW custom point label activated: Alarm: Water Flow custom point label zone label
zone label 03:18P 3/06/00 M19 N12L1M19 15:18:00 3/06/00

trouble: TROUBL WATERFLOW custom point label trouble: Trouble Water Flow custom point label zone label
zone label OPEN CIRCUIT 03:28P 3/06/00 M19 Open Circuit N12L1M19 15:28:00 3/06/00
Pre-Alarm activated: PREALM SMOKE (PHOTO) custom point activated: Pre Alarm Smoke (Photo) AFP200 PREALM
label ALERT: 1.31/1.50% 05:21P 3/06/00 D01 ALERT Pre-Alarm Alert N12L1D1 17:21:00 3/06/00

trouble: (not applicable) Trouble: (not applicable)


*Will be displayed only in History Manager, Current Event window and NonFire Event window in the NCS

Table C.2 AFP-200 Messages As They Appear on the NCS (page 2 of 2)

80 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Messages Message Tables

AFP-300/400
AFP-300/400 Message NCS Message
Type I.D.
Smoke Detect alarm (short): ALARM: Smoke Detect device label zone alarm (short): Alarm: Smoke Detect device label zone
label 01:27:00p 03/07/00 M121 label N232L1M21 13:27:00 03/07/00

trouble: TROUBLE SMOKE DETECT device label trouble: Trouble Smoke Detect device label Invalid Reply
Z05 INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Heat Detect alarm (short): ALARM: HEAT DETECT device label alarm (short): Alarm: Heat Detect device label zone label
zone label 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00

trouble: TROUBL HEAT DETECT device label Z05 trouble: Trouble Heat Detect device label Invalid Reply
INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Pull Station alarm (short): ALARM: PULL STATION device label alarm (short): Alarm: Pull Station device label zone label
zone label 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00

trouble: TROUBL PULL STATION device label Z05 trouble: Touble Pull Station device label Invalid Reply
INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Monitor alarm (short): ALARM: MONITOR device label zone alarm (short): Alarm: Monitor device label zone label
label 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00

trouble: TROUBL MONITOR device label Z05 trouble: Trouble Monitor device label Invalid Reply
INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
(blank) alarm (short): ALARM: device label zone label alarm (short): Alarm device label zone label N232L1M21
01:27:00p 03/07/00 M121 13:27:00 03/07/00

trouble: TROUBL device label Z05 INVALID REPLY trouble: Trouble device label Invalid Reply N232L1M21
01:27:00p 03/07/00 M121 13:27:00 03/07/00
Abort Switch alarm (short): ACTIVE ABORT SWITCH device label alarm short: Active Abort Switch device label zone label
zone label 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00

trouble: TROUBL ABORT SWITCH device label Z05 trouble: Trouble Abort Switch device label Invalid Reply
INVALID REPLAY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Man. Release alarm (short): ALARM: MAN. RELEASE device label alarm (short): Alarm: Man. Release device label zone label
zone label 01:27p 03/07/00 M121 N232L1M21 01:27:00 03/07/00

trouble: TROUBL MAN. RELEASE device label Z05 trouble: Trouble Man. Release device label Inalid Reply
INVALID REPLY 01:27:00p 03/07/00 M121 N232L1M21 13:27:00 03/07/00
Silence alarm (short): ACTIVE SILENCE device label zone alarm (short): Active Silence device label zone label
label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00

trouble: TROUBL SILENCE device label Z05 trouble: Trouble Silence device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
System Reset alarm (short): ACTIVE SYSTEM RESET device label alarm (short): Active System Reset device label zone label
zone label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00

trouble: TROUBL SYSTEM RESET device label Z05 trouble: Trouble System Reset device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
Security alarm (short and open): ACTIVE SECURITY device alarm (short and open): Security Burglar Ala device label
label zone label 12:40:00p 03/07/00 M121 zone label N232L1M21 12:40:00 03/07/00

trouble: TROUBL SECURITY device label Z05 trouble: Trouble Burglar Ala device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
Trouble MON alarm (short): TROUBL TROUBLE MON device label alarm (short): Troubl Trouble Mon device label Short
Z05 SHORT CIRCUIT 12:40:00p 03/07/00 M121 Circuit N232L1M21 12:40:00 03/07/00

trouble: TROUBL TROUBLE MON device label Z05 trouble: Trouble Trouble Mon device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00:00 03/07/00
PAS Inhibit alarm (short): ACTIVE PAS INHIBIT device label zone alarm (short): Active Pas Inhibit device label zone label
label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00

trouble: TROUBL PAS INHIBIT device label Z05 trouble: Trouble Pas Inhibit device label Invalid Reply
INVALID REPLY 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
AllCall Page alarm (short): ACTIVE ALLCALL PAGE device label alarm (short): Active Allcall Page device label zone label
zone label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00

trouble: TROUBL ALLCALL PAGE device label Z05 trouble: Trouble Allcall Page device label INVALID
INVALID REPLY 12:40:00p 03/07/00 M121 REPLY N232L1M21 12:40:00 03/07/00

Table C.3 AFP-300/400 Messages As They Appear on the NCS (page 1 of 3)

NCS Manual PN 51095:B1 3/08/02 81


www.PDF-Zoo.com
Message Tables Messages

AFP-300/400
AFP-300/400 Message NCS Message
Type I.D.
Tamper alarm (short): ACTIVE TAMPER device label zone label alarm (short): Supervisory Tamper device label zone label
12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00

trouble: TROUBL TAMPER device label Z05 INVALID trouble: Trouble Tamper device label Invalid Reply N232L1M21
REPLY 12:40:00p 03/07/00 M121 12:40:00 03/07/00
Fire Control alarm (short): ACTIVE FIRE CONTROL device label alarm (short): Active Fire Control device label zone label
zone label 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00

trouble: TROUBL FIRE CONTROL device label Z05 trouble: Trouble Fire Control device label Invalid Reply
INVALID 12:40:00p 03/07/00 M121 N232L1M21 12:40:00 03/07/00
Tele. Page alarm (short): ACTIVE TELE. PAGE device label zone alarm (short): Active Tele. Page device label zone label
label 03:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00

trouble: TROUBL TELE. PAGE device label Z05 trouble: Trouble Tele Page device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Comb. Monitor alarm (short): ALARM: COMB. MONITOR device label alarm (short): Alarm: Comb Monitor device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00

trouble: TROUBL COMB. MONITOR device label Z05 trouble: Trouble Comb. Monitor device labelInvalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Sprinkler Sys alarm (short): ALARM: SPRINKLER SYS device label alarm (short): Alarm: Sprinkler Sys device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00

trouble: TROUBL SPRINKLR SYS device label Z05 trouble: Trouble Sprinklr Sys device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Second Shot alarm (short): ACTIVE SECOND SHOT device zone alarm (short): Active Second Shot device label zone label
label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00

trouble: TROUBL SECOND SHOT device label Z05 trouble: Trouble Second Shot device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Man Rel Dlay alarm (short): ALARM : MAN REL DLAY device label alarm (short): Alarm: Man Rel Dlay device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00

trouble: TROUBL MAN REL DLAY device label Z05 trouble: Trouble Man Rel Dlay device label Invalild Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Hazard Alert alarm (short): ACTIVE HAZAD ALERT device label alarm (short): Supervisory Hazard Alert device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00

trouble: TROUBL HAZARD ALERT device label Z05 trouble: Trouble Hazard Alert device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Supervisory alarm (short): ACTIVE SUPERVISORY device label alarm (short): Supervisory Supervisory device label zone label
zone label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00

trouble: TROUBL SUPERVISORY device label Z05 trouble: Trouble Supervisory device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Waterflow alarm short: ALARM: WATERFLOW device label zone alarm (short): ALARM: WATER FLOW device label zone label
label 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00

trouble: TROUBL WATERFLOW device label Z05 trouble: Trouble Water Flow device label Invalid Reply
INVALID REPLY 3:15:00P 03/07/00 M121 N232L1M21 15:15:00 03/07/00
Control on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00

trouble: TROUBL CONTROL device label Z05 trouble: Trouble Control device label Invalid Reply N232L1M1
INVALID REPLY 12:07:00P 3/16/00 M101 12:07:00 3/16/00
Relay on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00

trouble: TROUBL RELAY device label Z05 INVALID trouble: Trouble Relay device label Invalid Reply N232L1M1
12:07:00 3/16/00
Bell Circuit on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00

trouble: TROUBL BELL CIRCUIT device label Z05 trouble: Trouble Bell Circuit device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00
*All AFP300/AFP400 messages that say 'No Annunciation' will be displayed in the History Buffer, only.

Table C.4 AFP-300/400 Messages As They Appear on the NCS (page 2 of 3)

82 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
Messages Message Tables

AFP-300/400
AFP-300/400 Message NCS Message
Type I.D.

Strobe Ckt on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00

trouble: TROUBL STROBE CKT device label Z05 trouble: Trouble Strobe Ckt device label Invalid Reply N232L1M1
INVALID REPLY 12:07:00P 3/16/00 M101 12:07:00 3/16/00

Horn Circuit on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00

trouble: TROUBL HORN CIRCUIT device label Z05 trouble: Trouble Horn Circuit device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00

Audible Ckt on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00

trouble: TROUBL AUDIBLE CKT device label Z05 trouble: Trouble Audible Ckt device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00

Rel End Bell on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00

trouble: TROUBL REL END BELL device label ZR1 trouble: Trouble Rel End Bell device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00

Release Ckt on: No Annunciation* on: Active AFP400 Output Device N232L1M1 12:07:00 3/16/00

trouble: TROUBL RELEASE CKT device label ZR1 trouble: Trouble Release Ckt device label Invalid Reply
INVALID REPLY 12:07:00P 3/16/00 M101 N232L1M1 12:07:00 3/16/00

Rel Ckt Ulc on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00

trouble: TROUBL REL CKT ULC device label ZR1 trouble: Trouble Rel Ckt ULC device label Invalid Reply
INVALID REPLY 04:55:00P 3/16/00 M101 N232L1M1 16:55:00 3/16/00

Rel Audible on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00

trouble: TROUBL REL AUDIBLE device label ZR1 trouble: Trouble Rel Audible device label Invalid Reply
INVALID REPLY 04:55:00P 3/16/00 M101 N232L1M1 16:55:00 3/16/00

Nonreset Stl on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00

trouble: TROUBL NONRESET CTL device label Z05 trouble: Trouble Nonreset Ctl device label Invalid Reply
INVALID REPLY 04:55:00P 3/16/00 M101 N232L1M1 16:55:00 3/16/00

Telephone on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00

trouble: TROUBL TELEPHONE device label Z05 trouble: Trouble Telephone device label Invalid Reply N232L1M1
INVALID REPLY 04:55:00P 3/16/00 M101 16:55:00 3/16/00

Rel Code Bell on: No Annunciation* on: Active AFP400 Output Device N232B1 16:55:00 3/16/00

trouble: TROUBL REL CODE BELL device label ZR1 trouble: Trouble Rel Code Bell device label Invalid Reply
N232B1 16:55:00 3/16/00

Instant Rele on: No Annunciation* on:Active AFP400 Output Device N232L1M21 04:55:00P 3/16/00

trouble: TROUBL INSTANT RELE device label Z05 trouble: Instant Rele device label Invalid Reply N232L1M1
INVALID REPLY 04:55:00P 3/16/00 M101 16:55:00 3/16/00

Relea Form C on: No Annunciation* on: Active AFP400 Output Device N232L1M21 16:55:00 3/16/00

trouble: TROUBL RELEA FORM C device label Z R1 trouble: Trouble Relea Form C device label Invalid Reply
INVALID REPLY 04:55:00P 3/16/00 M101 N232L1M21 16:55:00 3/16/00

Speaker on: No Annunciation* on: Active AFP400 Output Device N232L1M1 16:55:00 3/16/00

trouble: TROUBL SPEAKER device label Z05 trouble: Trouble Speaker device label Invalid Reply N232L1M1
INVALID REPLY 04:55:00P 3/16/00 M101 16:55:00 3/16/00

*Any AFP-300/AFP400 messages that say 'No Annunciation' will be displayed in the History Buffer, only.

Table C.5 AFP-400 Messages as They Appear on the NCS (page 3 of 3)

NCS Manual PN 51095:B1 3/08/02 83


www.PDF-Zoo.com
Message Tables Messages

Notes

84 NCS Manual PN 51095:B1 3/08/02


www.PDF-Zoo.com
INDEX

Numerics disabled device window 45

71033 cable, supplied with NCS 13 E


A Event Counter window 43
Events window 24
acknowledge 27, 38, 42
acknowledged event window 25
Administration menu 27
F
Files, required, NCS 75
AFP200 20, 33 FMM-1 12, 13
AFP-300/400 33 fonts, PC 16
alarm 39
acknowledge 40
reporting 39
G
graphic event window 22
AM2020/AFP1010 12, 20, 33
graphic floor plan 24
Aministration menu
Adding 63
General NCS Tab 28
customizing 63
Graphic Configuration Tab 32
Deleting 64
Printer Tab 31
device icons 69
User Account Tab 29
editing 64
Voice Tab 31

B
key map, setting links 65
Graphic Setup Program (GSP) 35, 60–75
Information Window 60, 61
Banners 23, 26, 38, 39, 41

C
key map area 60
Menu Bar 60, 66–69
Toolbar 60, 62
Caution Tree View Window 60
case sensitivity, printer installation 18 Graphical User Interface 22
conduit size 9 graphics events window 23
door over CD drive 18 Groups 73
exiting the NCS 18, 21, 41 Level 1 73
NCS Demo mode 22 Level 2 73
Run NCS software alone 22 Navigation 73
The NCS Communications Driver may have to be changed... setup restrictions 73
17 Guidance Text 65
colors, PC 16
column types, visibility 55
command area 26
H
Help menu 36
communications port settings 31 hierarchies, screen 73
Compact Database 35 History Backup option 28
current event window 45 History Manager 52–59
current operator field 27 database 52
Current Users list 29 display priority 52
to edit 29

D
Open Archived History File 53
Operator List 53
Refresh Grid 52
data refresh 21, 28, 43 search criteria 54
database 20 stand alone operation 54
graphics 21 History Manager window 45
history 21 Home Screen 73
history, archiving 35, 56 HSP-121B power line protector 9, 10
printing 56
see also History Manager
Upload/Download (UPDL) fron node 57
I
INA 12, 20, 33, 46, 78
Date / Time Field 25 Information Labels 70
DB-15 video cable 10 adding 71
demo mode 33 deleting 72
Detailed Events window 44
Non-Fire Events 44
Device Icons 69
J
Junction Box 9, 10

K
adding 69
deleting 72
Find command 72
linked files 70 key map area 24, 66
setup rules 72 see also Graphic Setup Program

NCS Manual P/N 51095:B1 3/8/02 85


www.PDF-Zoo.com
INDEX

L zone 48
Read/Write CD ROM 18
Logo Window 26 Related Documentation 7

M Reset 28, 38, 42


resolution, PC 16
Master Time Keeper 16, 28
Media Interface Board (MIB) 8 S
MIB-F 8 SAR (signal silence, acknowledge or reset) 26
MIB-W 8 screen navigation tools 25
monitor 8, 10 Secure Desktop
mouse 9 Software installation 77
MPS-24A Power Supply 12 UL-864 compliance 19

N Windows 2000 Configuration 19


security signal 41
NAM-232 20 acknowledging 41
Navigational Buttons 71 reporting 41
adding 71 signal silence 27, 28, 38, 42
deleting 72 speaker frequencies, alarm & trouble 28
NCS functions 20 SR (signal silence or reset) 26
Network interface card (NRT-NET) Start-Up Window 21
IRQ5 8 Strain relief, for MIB wires 14
jumper selection 8 supervisory signal 41
LED identification 8 acknowledging 41
UPS Monitor 8 reporting 41
Network interface card (NRT-NETPCB) 8 system reset 27
network node 20, 21, 30
edit and display 33–34 T
network statistics 35 Templates, setup 74
Noti-Fire-Net 8, 20 Time Sync options 28
NRT-P3 7, 10 tool bar 26
connecting 8 Tree View Window 61
model numbers 8 trouble 38
primary power 10 acknowledge 39

O Communications Link Failure 46


Lan Communications Failure 46
offline events, show or hide 43 Node Communications Failure 46

P Trouble Messages 79–83

U
Paint Shop Pro 63, 66
Installation 77 UPS 8, 10
PaintShop Pro 75 UPS Supervision 12, 13, 28
password 41, 42
changing 42 V
PCLB-6 enclosure 9 voice messages 31
Port thresholds 28 "Sounds" directory 31
Power-Up Initialization 21 "Waves" directory 31
pre-alarm signal 41 edit speech files 35
acknowledging 41
reporting 41
printer 8
W
Warning
graphic 17, 31 Improper voltage selection 9
line 17, 31 Windows 2000 16
line, cable connections 15 Windows 2000 Workstation
PRN-5 8 Disable Procedure 76
setup 31 Windows NT Workstation 22
UPS Supervision 13
Programming 20
Menu Options 27

R
Read Status 47
annunciator point 49
module 47
System Data 49

86 NCS Manual P/N 51095:B1 3/8/02


www.PDF-Zoo.com
Limited Warranty

NOTIFIER® warrants its products to be free from defects in materials


and workmanship for eighteen (18) months from the date of manufac-
ture, under normal use and service. Products are date stamped at
time of manufacture. The sole and exclusive obligation of NOTIFIER®
is to repair or replace, at its option, free of charge for parts and labor,
any part which is defective in materials or workmanship under normal
use and service. For products not under NOTIFIER® manufacturing
date-stamp control, the warranty is eighteen (18) months from date of
original purchase by NOTIFIER®’s distributor unless the installation
instructions or catalog sets forth a shorter period, in which case the
shorter period shall apply. This warranty is void if the product is
altered, repaired or serviced by anyone other than NOTIFIER® or its
authorized distributors or if there is a failure to maintain the products
and systems in which they operate in a proper and workable manner.
In case of defect, secure a Return Material Authorization form from our
customer service department. Return product, transportation prepaid,
to NOTIFIER®, 12 Clintonville Road, Northford, Connecticut 06472-
1653.
This writing constitutes the only warranty made by NOTIFIER® with
respect to its products. NOTIFIER® does not represent that its prod-
ucts will prevent any loss by fire or otherwise, or that its products will in
all cases provide the protection for which they are installed or
intended. Buyer acknowledges that NOTIFIER® is not an insurer and
assumes no risk for loss or damages or the cost of any inconvenience,
transportation, damage, misuse, abuse, accident or similar incident.
NOTIFIER® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE,
OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION
ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL
NOTIFIER® BE LIABLE FOR ANY LOSS OF OR DAMAGE TO
PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING
OUT OF THE USE OF, OR INABILITY TO USE NOTIFIER® PROD-
UCTS. FURTHERMORE, NOTIFIER® SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE
COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR
INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty
made by NOTIFIER®. No increase or alteration, written or verbal, of
the obligation of this warranty is authorized.
"NOTIFIER" is a registered trademark.

WarNL-2001-9.fm 8/31/2001
www.PDF-Zoo.com
World Headquarters NOTIFIER is an operation of
12 Clintonville Road
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118

www.notifier.com

www.PDF-Zoo.com

You might also like