This section includes updated information, added since it was first
published in December 2015.
Section Last updated
Introduction 12/08/2019
GypWall classic 08/02/2021
GypWall robust 06/12/2019
GypWall extreme 06/12/2019
GypWall quiet sf 10/06/2019
GypWall staggered 10/06/2019
GypWall quiet 10/06/2019
GypWall quiet iwl 06/12/2019
GypWall audio 08/02/2021
GypWall rapid dB Plus REMOVED 16/03/2020
Non-loadbearing timber stud 08/02/2021
Partitions
CO4
Partitions
C04
Introduction
Partitions
This section contains a full range of lightweight partition and wall
systems for use in new and existing buildings. They cover all applications,
from simple space division to high performance walls
Partitions
C04
Introduction
Partitions
British Gypsum offers a full range of lightweight
partition and wall systems. Our systems are
non-loadbearing and constructed using modern,
drylining techniques. British Gypsum metal
framed partitions and walls can be used in all
types of new and existing buildings, including
private and social housing, apartments,
Partitions
healthcare, educational facilities, recreational
and industrial properties.
C04
They cover all applications, from simple space
division, through to high performance walls
designed to meet the most demanding fire
resistance, sound insulation, impact and height
requirements.
When specifying partitions, a number of performance characteristics are normally used to determine the required solution.
Depending on the project or construction type, these performance parameters could be set by minimum regulatory
standards, or a client or customer requirement for buildings that offer the highest standards of performance and comfort.
Our quick-reference partition system guide, below, allows you to simply select the performance categories of interest and
identify the British Gypsum partitions systems that best satisfy your project requirements.
Duty Maximum
Fire rating height1
Partition
Acoustic performance
performance thickness System Page
Partitions
Medium -
30 - 120 75 - 211 34 - 63 47 - 57 8100 GypWall classic C04.S02.P02
Severe
C04
Heavy -
30 - 90 102 - 208 49 - 63 48 - 55 5700 GypWall staggered C04.S06.P02
Severe
Non-loadbearing timber
30 - 120 88 - 196 34 - 52 - - - C04.S11.P02
stud (internal partitions)
Non-loadbearing timber
60 - 90 141 - 293 56 - 63 48 - 53 - - C04.S11.P05
stud (separating walls)
1
Based on studs at 600mm centres
Additional information
Try out The White Book System Selector, an online tool designed to help find the ideal solutions for your
project needs. Additional information such as BIM data (Revit), NBS clauses, CAD drawings and other
associated items can be downloaded. Visit british-gypsum.com
Introduction
Acoustic performance
Table 1 — Sound insulation performance for residential specification
On-site Laboratory2
Approved Document E (England and Wales) Minimum solution Recommended solution
DnT,w + Ctr dB
(Rw + Ctr ) dB (Rw + Ctr ) dB
On-site Laboratory2
Partitions
Technical Standards Section 5 (Scotland) Minimum solution Recommended solution
DnT,w + Ctr dB
Rw dB Rw dB
C04
or conversion (traditional buildings1)
1
Definition of traditional buildings - A building or part of a building of a type constructed before or around 1919:
a) using construction techniques that were commonly in use before 1919; and
b) with permeable components, in a way that promotes the dissipation of moisture from the building fabric.
2
Minimum solutions provide little or no margin of safety to allow for reduction in performance due to flanking transmission. Recommended solutions have
greater potential to satisfy the requirements of Building regulations.
Table 2 – GypWall classic metal stud partition recommended maximum heights (mm) - based on a limiting deflection of L/240 at
200Pa. Applicable to non fire-rated or BS 476: Part 22 fire-rated constructions only (not applicable to EN 1364-1)
Stud Boarding 600mm 600mm 400mm 400mm 300mm 300mm
each side centres boxed centres boxed centres boxed
48 S 50 1 x 12.5mm 2500 2800 2900 3200 3100 3500
1 x 15mm 2800 3000 3100 3300 3300 3600
2 x 12.5mm 3400 3600 3600 3800 3800 4000
2 x 15mm 3700 3800 3900 4000 4000 4200
48 I 50 1 x 12.5mm 2900 - 3400 - 3700 -
1 x 15mm 3100 - 3500 - 3800 -
Partitions
In all GypWall classic systems, it is recommended that for heights between 4200mm and 8000mm, the Gypframe Deep Flange Floor & Ceiling Channel is
used. Gypframe Extra Deep Flange Floor & Ceiling Channel is used for heights above 8000mm. Additional consideration needs to be given if there is a deflection
head requirement.
Introduction
Table 2 (continued) – GypWall classic metal stud partition recommended maximum heights (mm) - based on a limiting
deflection of L/240 at 200Pa. Applicable to non fire-rated or BS 476: Part 22 fire-rated constructions only (not applicable to
EN 1364-1)
Stud Boarding 600mm 600mm 400mm 400mm 300mm 300mm
each side centres boxed centres boxed centres boxed
92 S 60 1 x 12.5mm 4700 5000 5200 5600 5600 6100
1 x 15mm 4900 5300 5400 5800 5800 6300
2 x 12.5mm 5800 6000 6100 6500 6500 6900
2 x 15mm 6000 6200 6300 6700 6600 7000
92 AS 50 1 x 12.5mm 4700 5100 5200 5700 5700 6200
Partitions
1 x 15mm 4900 5300 5400 5700 5800 6400
2 x 12.5mm 5800 6100 6200 6500 6500 6900
2 x 15mm 6000 6300 6400 6700 6700 7000
92 S 10 1 x 12.5mm 5300 5800 6000 6600 6500 7200
1 x 15mm 5500 6000 6100 6700 6600 7300
C04
2 x 12.5mm 6200 6600 6700 7200 7200 7700
2 x 15mm 6400 6800 6900 7400 7300 7800
92 I 90 1 x 12.5mm 6000 - 6800 - 7400 -
1 x 15mm 6200 - 6900 - 7500 -
2 x 12.5mm 6800 - 7400 - 7900 -
2 x 15mm 6900 - 7500 - 8000 -
146 S 50 1 x 12.5mm 6200 6800 6900 7600 7500 8300
1 x 15mm 6500 7000 7200 7800 7700 8400
2 x 12.5mm 7600 8000 8100 8600 8500 9100
2 x 15mm 7900 8200 8300 8800 8700 9300
146 AS 50 1 x 12.5mm 6600 7100 7300 8000 8000 8800
1 x 15mm 6800 7400 7600 8200 8200 8900
2 x 12.5mm 7800 8200 8400 8900 8900 9500
2 x 15mm 8100 8500 8600 9100 9100 9700
146 I 80 1 x 12.5mm 7900 - 8900 - 9700 -
1 x 15mm 8100 - 9000 - 9800 -
2 x 12.5mm 8800 - 9600 - 10400 -
2 x 15mm 9000 - 9800 - 10500 -
146 TI 90 1 x 12.5mm 8300 - 9400 - 10300 -
1 x 15mm 8400 - 9500 - 10400 -
2 x 12.5mm 9200 - 10100 - 10900 -
2 x 15mm 9400 - 10300 - 11100 -
In all GypWall classic systems, it is recommended that for heights between 4200mm and 8000mm, the Gypframe Deep Flange Floor & Ceiling Channel is
used. Gypframe Extra Deep Flange Floor & Ceiling Channel is used for heights above 8000mm. Additional consideration needs to be given if there is a deflection
head requirement.
To be read in conjunction with system specific details. Refer to relevant system sections
1 1a
1
3
5
5
Partitions
300mm
2
600mm
600mm
600mm
C04
2
300mm
6
7
2 2a
Centres
at 600mm
Centres
at
thereafter
600mm
thereafter
1479mm
1479mm
50mm
50mm
50mm
38mm
30mm
38mm
879mm
879mm
279mm
279mm
Service cut-outs - Gypframe ‘C’ and Gypframe ‘I’ Studs Service cut-outs - Gypframe AcouStuds
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
3 3a
Partitions
11
4
3 6
3
1
C04
2 7
6
4
10
Head and base Junction with masonry and stop end detail
To be read in conjunction with system specific details. Refer to relevant system sections
5 6
2 1
3
Partitions
7a 7b
2 2
1
1
4
3
3
‘T’ junction to optimise acoustic performance and reduce ‘T’ junction to optimise acoustic performance and reduce
flanking transmission flanking transmission
8 9
2 1
1
5
2
3
1 Gyproc plasterboard or Glasroc F specialist board 4 Gypframe GA5 Internal Fixing Angle
2 Gypframe 'C' Stud 5 Gypframe GA6 Splayed Angle
3 Isover insulation
Guidance must be sought from the relevant approval authority e.g. Building Control to establish if a cavity barrier is required (Approved Document B)
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
10 11
1
1
2
2
Partitions
Corner detail - single layer Corner detail - double layer
C04
12 13
16
mm
12 12
mm mm
2
3
1
1
4
14
Installing the screw into the side of the Gypframe Service Support Plate and the web of the Gypframe 'C' Stud will avoid creating excessive distortion to
the lining board.
To be read in conjunction with system specific details. Refer to relevant system sections
15
15mm 7 16 15mm 7
15mm 6 15mm 6
4 4
20mm 15mm 10
3
11
2
1 2
1
Partitions
Deflection head for 15mm downward movement Deflection head for 15mm downward movement and up
and 60 minutes fire resistance to BS 476-22 and BS EN 1364-1 to 120 minutes fire resistance to BS 476-22 and BS EN 1364-1
Not suitable for 60 minutes single layer systems to BS EN 1364-1 Not suitable for 48mm studs to BS EN 1364-1
C04
17 7 18
7
25mm 50mm
8 8
7
25mm 7 50mm
5 5
55mm
30mm
3
3
2
2
1
1
Deflection head for plus or minus 25mm movement Deflection head for 50mm downward movement
and 60 minutes fire resistance to BS 476-22 only and 60 minutes fire resistance to BS 476-22 only
19 20 7
7
25mm 9
50mm
9
7
25mm 7
50mm
5 5
30mm
3 55mm
3
2 2
1 1
Deflection head for plus or minus 25mm movement Deflection head for 50mm downward movement
and 60 minutes fire resistance to BS 476-22 only and 60 minutes fire resistance to BS 476-22 only
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing,
which should be made into Gypframe GFS1 Fixing Strap (or stud nogging in construction detail 16). Continuous Gyproc FireStrip must be installed as shown to
maintain fire performance. Where there is a need for a deflection head in a 90 minute wall, the 120 minute solution can be used (refer to construction detail 16)
or alternatively, please contact the British Gypsum Technical Advice Centre for further guidance.
To minimise loss in acoustic performance refer to C02 S01 P10 Acoustic performance of head details.
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
21 11 22 11
6 6
8 9
5 5
15mm
25mm
15mm
Stud top
25mm
4 4
Stud top
Partitions
15mm
7 7
25mm
10 10
C04
1 12
2 2
3 3
Deflection head 15mm downward movement Deflection head 25mm downward movement
30 minutes fire resistance depending on specification 60 minutes fire resistance depending on specification
BS 476: Part 22: 1987 and BS EN 1364-1 BS 476: Part 22: 1987
23 24
11 11
6 6
8 9
5 5
15mm
25mm
15mm
Stud top
25mm
4
Stud top
4
15mm
Deflection Head
Deflection Head
25mm
Deflection head 15mm downward movement Deflection head 25mm downward movement
90 minutes fire resistance depending on specification 120 minutes fire resistance depending on specification
BS 476: Part 22: 1987 and BS EN 1364-1 BS 476: Part 22: 1987
No fixings should be made through the boards into the flanges of the head channel.
To be read in conjunction with system specific details. Refer to relevant system sections
25
Partitions
150mm
4
C04
1200mm 1200mm
Door frame (maximum 1200mm width) to satisfy BS 5234: Parts 1 & 2: 1992 - Light and Medium Duty (up to 35kg door)
1 Gyproc plasterboard or Glasroc F specialist board 5 Timber door frame and architrave
2 Gypframe 'C' Stud 6 Gypframe 'C' Stud to maintain stud module
3 Gypframe Floor & Ceiling Channel 7 Timber sub-frame
4 Gypframe Floor & Ceiling Channel cut and bent to form door head
Advice should be sought from the door manufacturer prior to the construction of these details.
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
26
150mm
Partitions
4
C04
3
2
300mm
1200mm 1200mm
150mm
Door frame (maximum 1200mm width) to satisfy BS 5234: Parts 1 & 2: 1992 - Heavy and Severe Duty (up to 60kg door)
1 Gyproc plasterboard or Glasroc F specialist board 5 Timber door frame and architrave
2 Gypframe 'C' Stud 6 Gypframe 'C' Stud to maintain stud module
3 Gypframe Floor & Ceiling Channel to sleeve studs 7 Gypframe Floor & Ceiling Channel cut and bent to extend up studs
4 Gypframe Floor & Ceiling Channel cut and bent to form door head
Advice should be sought from the door manufacturer prior to the construction of these details.
At the base, the channel is cut and bent to extend 300mm up the studs and fixed each side with two British Gypsum Wafer Head Drywall Screws. The
studs each side of the opening are sleeved full height of opening with Gypframe Floor & Ceiling Channel.
To be read in conjunction with system specific details. Refer to relevant system sections
27
8
7
Partitions
150mm
4
C04
2
300mm
150mm
Alternative door frame for fixed partition heads only (maximum 1200mm width) to satisfy
BS 5234: Parts 1 & 2: 1992 - Heavy and Severe Duty (up to 60kg door)
1 Gyproc plasterboard or Glasroc F specialist board 6 Gypframe 'C' Stud to maintain stud module
2 Gypframe 'C' Stud 7 Gypframe 'C' Studs fixed back to back with
British Gypsum Drywall Screws at 300mm centres staggered
3 Gypframe Floor & Ceiling Channel to sleeve studs
8 Plasterboard infill (same type as lining) cut to fit between studs
4 Gypframe Floor & Ceiling Channel cut and bent to form door head
9 Gypframe Floor & Ceiling Channel cut and bent to extend up studs
5 Timber door frame and architrave
Advice should be sought from the door manufacturer prior to the construction of these details.
At the base, the channel is cut and bent to extend 300mm up the studs and fixed each side with two British Gypsum Wafer Head Drywall Screws.
The studs each side of the opening are sleeved full height of opening with Gypframe Floor & Ceiling Channel.
The principle of this alternative detail is only suitable for GypWall classic, GypWall robust and GypWall extreme for fixed head situations only.
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
28
3
1
Partitions
150mm
4
C04
5
150mm
Openings 1201 - 3300mm wide, for example double doors or large windows
1 Gypframe 'C' Stud 6 Centre stud required for margin up to 600mm between openings
2 Stud sleeved to full opening height with Gypframe Floor & Ceiling Channel 7 Partition between openings, minimum 600mm for Gypframe 'C' Studs
3 Gypframe studs (appropriate to system) (minimum 300mm for Gypframe 'I' Studs)
4 Gypframe Extra Deep Flange Floor & Ceiling Channel 8 Maximum distance 2400mm (if exceeds 2400mm contact British Gypsum
Technical Advice Centre)
5 Gypframe stud insert
To be read in conjunction with system specific details. Refer to relevant system sections
29 30
Elevation
4
X
Y
Partitions
2
C04
2
Section X - X
1
Fire tested construction in which the damper is supported
3 by the partition (isometric view)
4 31
150mm
6
Section Y - Y
Opening for service penetrations in fire-rated partitions Opening up to 600mm wide for services
1 Gyproc plasterboard or Glasroc F specialist board 5 Damper (by others). Weight of damper should not exceed 57kg.
2 Gypframe 'C' Stud Size of damper should not exceed 1400 x 1200mm
3 Gypframe Floor & Ceiling Channel 6 Gypframe Folded Edge Standard Floor & Ceiling Channel cut and bent
to form opening head and cill
4 Penetration seal if required (refer to damper manufacturer for details)
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
32
Partitions
5
C04
2
33 34
2 6
7 7
Horizontal board joint - double layer Horizontal board joint - single layer
1 Inner layer of Gyproc plasterboard or Glasroc F specialist board 5 British Gypsum Drywall Screws
2 Outer layer of Gyproc plasterboard or Glasroc F specialist board 6 Gyproc plasterboard or Glasroc F specialist board
3 Gypframe GFS1 Fixing Strap 7 Gypframe 'C' Stud
4 Gypframe metal framing 8 Gypframe GFT1 Fixing T (alternatively use Gypframe GSF1 Fixing Strap)
GypWall classic
A highly versatile metal stud partition system
Partitions
through a combination of interchangeable
Gyproc plasterboards, Gypframe metal,
System can be skim
Thistle finish plasters and Saint-Gobain Isover finished with
ThistlePro PureFinish.
insulation
C04
Refer to C02. S01. P49
ShaftWall
Where access is limited to one side only, for example risers, lift shafts, corridors and stair cores,
ShaftWall provides the answer.
Refer to C05. S02. P02.
1 2
One layer of board each side of 48mm One layer of board each side of 48mm
Gypframe ‘C’ Studs at 600mm centres. Gypframe ‘C’ Studs at 600mm centres. 25mm
Linings as in table. Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm kg/m²
Any2 Skim3 Any2 Skim3
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
GypWall classic
For details of when
to specify fire
48mm Gypframe 'C' Studs - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 1b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3
One layer of board each side of 48mm One layer of board each side of 48mm One layer of board each side of 48mm
Gypframe ‘C’ Studs at 600mm centres. Gypframe ‘C’ Studs at 600mm centres. 25mm Gypframe ‘C’ Studs at 600mm centres. 50mm
Linings as in table. Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm Any2 Skim3 kg/m² Any2 Skim3
C04
finish only finish only
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
1 2 3
One layer of board each side of One layer of board each side of 70mm One layer of board each side of 70mm
70mm Gypframe ‘C’ Studs at 600mm Gypframe ‘C’ Studs at 600mm centres. 25mm Gypframe ‘C’ Studs at 600mm centres. 50mm
centres. Linings as in table. Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm kg/m²
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
GypWall classic
For details of when
to specify fire
70mm Gypframe 'C' Studs - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 2b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3
One layer of board each side of 70mm One layer of board each side of 70mm One layer of board each side of 70mm
Gypframe ‘C’ Studs at 600mm centres. Gypframe ‘C’ Studs at 600mm centres. 25mm Gypframe ‘C’ Studs at 600mm centres. 50mm
Linings as in table. Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty rating Approx. System reference
thickness type thickness height1 Rw dB weight
mm mm mm kg/m²
C04
Any2 Skim3 Any32 Skim3
finish only finish only
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
1 2 3 4
One layer of board each side of One layer of board each side of 70mm One layer of board each side of One layer of board each side of
70mm Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at 70mm Gypframe 70 AS 50 AcouStuds 70mm Gypframe 70 AS 50 AcouStuds at
600mm centres. Linings as in table. 600mm centres. 25mm Isover Acoustic at 600mm centres. 50mm 600mm centres. 3 x 25mm
Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table. in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm kg/m²
Any2 Skim3 Any2 Skim3
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
GypWall classic
For details of when
to specify fire
70mm Gypframe AcouStuds - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 3b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3 4
One layer of board each side of One layer of board each side of 70mm One layer of board each side of 70mm One layer of board each side of 70mm
70mm Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at
600mm centres. Linings as in table. 600mm centres. 25mm 600mm centres. 50mm 600mm centres. 3 x 25mm
Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table. in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm kg/m²
C04
Any2 Skim3 Any2 Skim3
finish only finish only
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
1 2 3
One layer of board each side of 92mm One layer of board each side of 92mm One layer of board each side of 92mm
Gypframe ‘C’ Studs at 600mm centres. Gypframe ‘C’ Studs at 600mm centres. 25mm Gypframe ‘C’ Studs at 600mm centres. 50mm
Linings as in table. Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table.
4 5
Partitions
One layer of board each side of 92mm One layer of board each side of 92mm
Gypframe ‘C’ Studs at 600mm centres. 3 x 25mm Gypframe ‘C’ Studs at 600mm centres.
C04
Isover Acoustic Partition Roll (APR 1200) 100mm Isover Modular Roll in the cavity.
in the cavity. Linings as in table. Linings as in table.
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm kg/m²
Any finish2 Skim only3 Any finish2 Skim only3
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Increasing the insulation to 50mm Isover Acoustic Partition Roll (APR 1200) will not improve the system performance.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
GypWall classic
For details of when
to specify fire
92mm Gypframe 'C' Studs - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 4b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3
One layer of board each side of 92mm One layer of board each side of 92mm One layer of board each side of 92mm
Gypframe ‘C’ Studs at 600mm centres. Gypframe ‘C’ Studs at 600mm centres. 25mm Gypframe ‘C’ Studs at 600mm centres. 50mm
Linings as in table. Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table.
4 5
Partitions
One layer of board each side of 92mm One layer of board each side of 92mm
Gypframe ‘C’ Studs at 600mm centres. 3 x 25mm Gypframe ‘C’ Studs at 600mm centres.
C04
Isover Acoustic Partition Roll (APR 1200) 100mm Isover Modular Roll in the cavity.
in the cavity. Linings as in table. Linings as in table.
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm kg/m²
Any finish2 Skim only3 Any finish2 Skim only3
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Increasing insulation to 50mm Isover Acoustic Partition Roll (APR 1200) will not improve this system performance.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection
criteria).
1 2 3 4
One layer of board each side of 92mm One layer of board each side of One layer of board each side of One layer of board each side of 92mm
Gypframe AcouStuds at 600mm centres. 92mm Gypframe AcouStuds at 92mm Gypframe AcouStuds at Gypframe AcouStuds at 600mm centres.
Linings as in table. 600mm centres. 25mm 600mm centres. 50mm 100mm Isover Modular Roll in the
Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200) cavity. Linings as in table.
in the cavity. Linings as in table. in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Increasing insulation to 50mm Isover Acoustic Partition Roll (APR 1200) will not improve this system performance.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
GypWall classic
For details of when
to specify fire
92mm Gypframe AcouStuds - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 5b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3 4
One layer of board each side of 92mm One layer of board each side of One layer of board each side of One layer of board each side of 92mm
Gypframe AcouStuds at 600mm centres. 92mm Gypframe AcouStuds at 92mm Gypframe AcouStuds at Gypframe AcouStuds at 600mm centres.
Linings as in table. 600mm centres. 25mm 600mm centres. 50mm 100mm Isover Modular Roll in the
Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200) cavity. Linings as in table.
in the cavity. Linings as in table. in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
C04
mm mm mm Any2 Skim3 kg/m² Any2 Skim3
finish only finish only
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Increasing insulation to 50mm Isover Acoustic Partition Roll (APR 1200) will not improve this system performance.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
1 2
Two layers of board each side of 48mm Two layers of board each side of 48mm
Gypframe ‘C’ Studs at 600mm centres. Gypframe ‘C’ Studs at 600mm centres. 25mm
Linings as in table. Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating4 weight
mm mm mm kg/m²
Any2 Skim3 Any2 Skim3
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Refer to relevant test reports for observations noted during test.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
GypWall classic
For details of when
to specify fire
48mm Gypframe 'C' Studs - double layer board linings resistance using BS
Refer to C02. S01. P05
Table 6b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2
Two layers of board each side of 48mm Two layers of board each side of 48mm
Gypframe ‘C’ Studs at 600mm centres. Gypframe ‘C’ Studs at 600mm centres. 25mm
Linings as in table. Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating4 weight
mm mm mm Any2 Skim3 kg/m² Any2 Skim3
C04
finish only finish only
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Refer to relevant test reports for observations noted during test.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
1 2 3
Two layers of board each side of 70mm Two layers of board each side of 70mm Two layers of board each side of 70mm
Gypframe ‘C’ Studs at 600mm centres. Gypframe ‘C’ Studs at 600mm centres. 25mm Gypframe ‘C’ Studs at 600mm centres. 50mm
Linings as in table. Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm Any2 Skim3 kg/m² Any2 Skim3
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall classic
For details of when
to specify fire
70mm Gypframe 'C' Studs - double layer board linings resistance using BS
Refer to C02. S01. P05
Table 7b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3
Two layers of board each side of 70mm Two layers of board each side of Two layers of board each side of
Gypframe ‘C’ Studs at 600mm centres. 70mm Gypframe ‘C’ Studs at 600mm centres. 70mm Gypframe ‘C’ Studs at 600mm centres.
Linings as in table. 25mm Isover Acoustic Partition Roll (APR 1200) 50mm Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm kg/m²
Any2 Skim3 Any2 Skim3
C04
finish only finish only
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
1 2
Two layers of board each side of Two layers of board each side of 70mm
70mm Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at 600mm centres.
600mm centres. Linings as in table. 25mm Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm kg/m²
Any2 Skim3 Any2 Skim3
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall classic
For details of when
to specify fire
70mm Gypframe AcouStuds - double layer board linings resistance using BS
Refer to C02. S01. P05
Table 8b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2
Two layers of board each side of Two layers of board each side of 70mm
70mm Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at 600mm centres.
600mm centres. Linings as in table. 25mm Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw dB rating weight
mm mm mm Any2 Skim3 kg/m² Any2 Skim3
C04
finish only finish only
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
1 2 3 4
Two layers of board each side of Two layers of board each side of Two layers of board each side of Two layers of board each side of
92mm Gypframe ‘C’ Studs at 92mm Gypframe ‘C’ Studs at 92mm Gypframe ‘C’ Studs at 92mm Gypframe ‘C’ Studs at 600mm
600mm centres. Linings as in table. 600mm centres. 25mm 600mm centres. 3 x 25mm centres. 100mm Isover Modular Roll in
Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200) the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Increasing the insulation to 50mm Isover Acoustic Partition Roll (APR 1200) will not improve the system performance.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall classic
For details of when
to specify fire
92mm Gypframe 'C' Studs - double layer board linings resistance using BS
Refer to C02. S01. P05
Table 9b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3 4
Two layers of board each side of Two layers of board each side of Two layers of board each side of Two layers of board each side of 92mm
92mm Gypframe ‘C’ Studs at 92mm Gypframe ‘C’ Studs at 92mm Gypframe ‘C’ Studs at Gypframe ‘C’ Studs at 600mm centres.
600mm centres. Linings as in table. 600mm centres. 25mm 600mm centres. 3 x 25mm 100mm Isover Modular Roll in
Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200) the cavity. Linings as in table.
Partitions
in the cavity. Linings as in table. in the cavity. Linings as in table.
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
C04
thickness type thickness height1 Rw (Rw + Ctr) dB rating weight
mm mm mm kg/m²
Any2 Skim3 Any2 Skim3
finish only finish only
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Increasing insulation to 50mm Isover Acoustic Partition Roll (APR 1200) will not improve this system performance.
5
2 x 12.5mm lining thickness is acceptable for 120 minutes BS up to a maximum height of 5700mm but acoustic test data is not available.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
1 2 3 4
Two layers of board each side of Two layers of board each side Two layers of board each side Two layers of board each side of 92mm
92mm Gypframe AcouStuds at of 92mm Gypframe AcouStuds at of 92mm Gypframe AcouStuds at Gypframe AcouStuds at 600mm centres.
600mm centres. Linings as in table. 600mm centres. 25mm 600mm centres. 50mm 100mm Isover Modular Roll in
Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200) the cavity. Linings as in table.
Partitions
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
C04
2 144 Gyproc SoundBloc 2 x 12.5 5000 57 (51) 58 (51) Severe 45 A206A290 A206A290S
3 144 Gyproc SoundBloc 2 x 12.5 5000 58 (53) 59 (53) Severe 45 A206A291 A206A291S
4 144 Gyproc SoundBloc 2 x 12.5 5000 59 (54) 60 (54) Severe 45 A206A292 A206A292S
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall classic
For details of when
to specify fire
92mm Gypframe AcouStuds - double layer board linings resistance using BS
Refer to C02. S01. P05
Table 10b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3 4
Two layers of board each side Two layers of board each side Two layers of board each side Two layers of board each side of 92mm
of 92mm Gypframe AcouStuds at of 92mm Gypframe AcouStuds at of 92mm Gypframe AcouStuds at Gypframe AcouStuds at 600mm centres.
600mm centres. Linings as in table. 600mm centres. 25mm 600mm centres. 50mm 100mm Isover Modular Roll in
Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200) the cavity. Linings as in table.
Partitions
in the cavity. Linings as in table. in the cavity. Linings as in table.
Refer to GypWall robust and GypWall extreme sections for single layer Severe Duty solutions
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
C04
thickness type thickness height1 Rw (Rw + Ctr ) dB rating weight
mm mm mm Any2 Skim3 kg/m² Any2 Skim3
finish only finish only
2 144 Gyproc SoundBloc 2 x 12.5 5800 57 (51) 58 (51) Severe 45 A206A290 A206A290S
3 144 Gyproc SoundBloc 2 x 12.5 5800 58 (53) 59 (53) Severe 45 A206A291 A206A291S
4 144 Gyproc SoundBloc 2 x 12.5 5800 59 (54) 60 (54) Severe 45 A206A292 A206A292S
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
1 2 3
Two layers of board each side of 146mm Two layers of board each side of Two layers of board each side of
Gypframe ‘C’ Studs at 146mm Gypframe ‘C’ Studs at 146mm Gypframe ‘C’ Studs at
600mm centres. Linings as in table. 600mm centres. 25mm 600mm centres. 50mm
Partitions
Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table.
C04
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw (Rw + Ctr ) dB rating weight
mm mm mm Any2 Skim3 kg/m² Any2 Skim3
finish only finish only
2 198 Gyproc SoundBloc 2 x 12.5 4000 55 (49) 56 (49) Severe 43 A206210 A206210S
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall classic
For details of when
to specify fire
146mm Gypframe 'C' Studs - double layer board linings resistance using BS
Refer to C02. S01. P05
Table 11b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3
Two layers of board each side of 146mm Two layers of board each side of 146mm Two layers of board each side of 146mm
Gypframe ‘C’ Studs at Gypframe ‘C’ Studs at Gypframe ‘C’ Studs at
600mm centres. Linings as in table. 600mm centres. 25mm 600mm centres. 50mm
Partitions
Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table.
C04
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
thickness type thickness height1 Rw (Rw + Ctr ) dB rating weight
mm mm mm kg/m²
Any2 Skim3 Any2 Skim3
finish only finish only
2 198 Gyproc SoundBloc 2 x 12.5 7600 55 (49) 56 (49) Severe 43 A206210 A206210S
3 198 Gyproc SoundBloc 2 x 12.5 7600 56 (50) 57 (50) Severe 43 A206244 A206244S
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
1 2 3
Two layers of board each sideof 146mm Two layers of board each side of 146mm Two layers of board each side of 146mm
Gypframe 146 AS 50 AcouStuds at Gypframe 146 AS 50 AcouStuds at 600mm centres. Gypframe 146 AS 50 AcouStuds at 600mm centres.
Partitions
600mm centres. Linings as in table. 50mm Isover Acoustic Partition Roll (APR 1200) 150mm Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. (100mm and 50mm) in the cavity.
Linings as in table.
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
C04
1 198 Gyproc FireLine 2 x 12.5 7800 52 (48) 53 (48) Severe 40 A206A091 A206A091S
1 198 Gyproc FireLine 2 x 12.5 4200 52 (48) 53 (48) Severe 40 A206A091 A206A091S
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
For heights over 8000mm, Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at head and base.
GypWall classic
For details of when
to specify fire
146mm Gypframe AcouStuds - double layer board linings resistance using BS
Refer to C02. S01. P05
Table 12b — Solutions to satisfy the requirements of BS 476: Part 22: 1987
1 2 3
Partitions
of 146mm Gypframe 146 AS 50 AcouStuds 146 AS 50 AcouStuds at 600mm centres. 50mm
150mm Isover Acoustic Partition Roll (APR 1200)
at 600mm centres. Linings as in table. Isover Acoustic Partition Roll (APR 1200)
(100mm and 50mm) in the cavity.
in the cavity. Linings as in table.
Linings as in table.
Detail Partition Board Lining Max Sound insulation Duty Approx. System reference
C04
thickness type thickness partition Rw (Rw + Ctr ) dB rating weight
mm mm height1 Any2 Skim3 kg/m² Any2 Skim3
mm finish only finish only
1 198 Gyproc FireLine 2 x 12.5 7800 52 (48) 53 (48) Severe 40 A206A091 A206A091S
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of Gypframe ‘I’ Studs, or reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
For heights over 8000mm, Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at head and base.
Whilst our GypWall partition systems are non-loadbearing, they Where services such as horizontal ducts, fire dampers and access
are able to provide resistance to levels of horizontal uniformly panels are required to penetrate the wall, their position should be
distributed loads in accordance with BS 6399. pre-determined in order that a framed opening can be provided.
The openings should be constructed using established metal stud
Refer to C02. S01. P26 – Robustness.
procedures.
Planning – key factors Refer to Partitions introduction C04. S01. P16 - construction
details 28-31.
GypWall classic comprises Gypframe 'C' Studs installed at 600mm
centres within Gypframe Floor & Ceiling Channels. The position
Cavity barriers
of services and heavy fixtures should be pre-determined and their
installation planned into the frame erection stage. Minimum 12.5mm Gyproc plasterboard, screw-fixed into the web
Partitions
Gypframe Floor & Ceiling Channels must be securely fixed with a Refer to C06. S07. P02 – Cavity barriers.
row of fixings at 600mm maximum centres. For 94mm and 148mm
channels, two rows of staggered fixings are required, each row at
C04
Control joints
600mm centres and each fixing 25mm in from the flange. If the
Control joints may be required in the partition to relieve stresses
floor is uneven, a 38mm thick timber sole plate equal to the width
induced by expansion and contraction of the structure (refer to
of the channel should be used.
Partitions introduction C04. S01. P10 – construction detail 12). They
should coincide with movement joints within the surrounding
If the concrete or screeded floor is new, consideration should be
structure.
given to the installation of a damp-proof membrane between the
floor surface and the channel or sole plate.
Deflection heads
Partition to structural steelwork junctions Refer to C02. S01. P10 – Building acoustics.
Electrical
The installation of electrical services should be carried out in
accordance with BS 7671. The cut-outs in the studs can be used Handy hint
for routing electrical and other small services (refer to Partitions
introduction C04. S01. P07 – construction detail 2). Switch boxes For alternative stud types and / or reduced
and socket outlets can be supported from Gypframe 99 FC 50 Fixing centres, to increase maximum partition
Channel fixed horizontally between studs, or a high performance height, further options are available.
socket box detail used where higher acoustic performance is Refer to C04. S01. P05, table 2.
required.
Partitions
in Partitions introduction C04. S01. P07 – construction detail 2a
for conventional cut-outs. Cables should be protected by conduit,
SpecSure®
or other suitable precautions taken to prevent abrasion when they
All our systems are covered by SpecSure® when
pass through the metal frame. Service cut-outs should be aligned to
using genuine British Gypsum and Saint-Gobain
allow easy installation of service. If studs require cutting, cut from
Isover products.
C04
the same end of each stud to ensure cut-out alignment.
Independent support
Fixtures
Board finishing
Tiling
Construction details
Gypframe ‘C’ Studs (48 S 50, 70 S 50, 92 S 50, Gypframe Extra Deep Flange Floor & Ceiling
146 S 50) Channels (50 EDC 70, 72 EDC 80, 94 EDC 70,
Vertical stud providing acoustic and structural 148 EDC 80)
performances designed to receive fixing of board Floor and ceiling channels with extra deep flanges
to both sides. for retaining the Gypframe studs at floor and
ceiling junctions for partitions over 8000mm high.
Also used around openings and in deflection heads
(maximum 50mm deflection).
Partitions
Gypframe ‘I’ Studs (70 I 50, 92 I 90, 146 I 80, Gypframe 99 FC 50 Fixing Channel
146 TI 90) A versatile metal fixing channel used to support
Enhanced strength stud that allows for increased medium weight fixtures on walls.
partition height, designed to receive fixing of board.
C04
Gypframe AcouStud (70 AS 50, 92 AS 50, 146 AS 50) Gypframe GFS1 Fixing Strap
Vertical stud providing enhanced acoustic and Used to support horizontal board joints and within
structural performances designed to receive deflection heads.
fixing of board to both sides.
Gypframe Folded Edge Standard Floor & Ceiling Gypframe GFT1 Fixing T
Channels (50 FEC 50, 72 FEC 50, 94 FEC 50, Used to support horizontal board joints.
148 FEC 50)
Standard floor and ceiling channels for retaining
the Gypframe studs at floor and ceiling junctions Gypframe GA6 Splayed Angle
and around openings to heights not exceeding Steel angle providing framing stability and
4200mm. board support.
Gypframe Deep Flange Floor & Ceiling Channels Gypframe Service Support Plate
(50 DC 60, 72 DC 60, 94 DC 60, 148 DC 60) For installation of 18mm plywood within
Floor and ceiling channels with deep flanges for a partition cavity to support medium to
retaining the Gypframe studs at floor and ceiling heavyweight fixtures.
junctions for partitions 4200mm to 8000mm high.
Also used around openings and in deflection heads
(maximum 30mm deflection).
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
GypWall classic
Board products ( Refer to C10. S03. P02 for details)
Partitions
3
Glasroc H tilebacker is suitable for use in high moisture environments.
C04
Corrosion resistant self-tapping steel screws For fixing boards to Gypframe metal framing
for fixing board to metal framing less than 0.8mm thick or greater (‘I’ studs 0.6mm thick
0.8mm thick ('I' studs less than 0.6mm thick). and greater).
British Gypsum Collated Drywall Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws
for fixing board to metal framing less than for fixing metal to metal framing 0.8mm thick or
0.8mm thick ('I' studs less than 0.6mm thick). greater ('I' studs 0.6mm thick or greater).
GypWall classic
Scan the image with this frame
for more information and
videos related to this system
This is intended to be a basic description of how the system is installed. Or visit gyp.sm/b/l2
For installation guidance refer to the British Gypsum Site Book.
Partitions
Appropriate Gypframe channels are suitably Gypframe 'C' Studs are suitably fixed to Gypframe studs are then friction fitted into
fixed to the floor and soffit. abutments. the Gypframe Floor & Ceiling Channels at
required centres.
C04
Door openings are constructed to suit the The perimeter of the partition is then sealed M&E services can be located within the
partitions' duty rating. on both sides with Gyproc Sealant. partition cavity.
Additional information
For full installation details, refer to the
British Gypsum Site Book, available to
download from british-gypsum.com
GypWall robust
Durable impact resistant partition system
Partitions
one lesson to the next. As a result, the system
provides a lightweight, non-loadbearing System can be skim
finished with
C04
Refer to C02. S01. P49
Key benefits
— Achieves Severe Duty Rating to BS 5234 with
only a single layer of Gyproc DuraLine
plasterboard to each side of the partition
— Reduced maintenance cycles due to impact
resistant nature of Gyproc DuraLine plasterboard
— Fully compatible with other British Gypsum
systems, GypWall robust can be specified
in areas of the building that really need it, whilst
other GypWall partitions can be used in lower
duty performance zones for optimal project value
— Increased levels of acoustic performance are
available when GypWall robust is specified with
Gypframe 92 AS 50 AcouStud – a commonly
chosen solution for school classrooms and
hospital consulting rooms
— Enhanced abrasion resistance can be achieved
through the use of ThistlePro DuraFinish skim
plaster; an ideal finishing solution for
GypWall robust
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 70 S 50 ‘C’ Studs at 600mm Gypframe 70 S 50 ‘C’ Studs at 600mm Gypframe 70 S 50 ‘C’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition
Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity.
Partitions
4 5
C04
One layer of board each side of One layer of board each side of
Gypframe 70 S 50 ‘C’ Studs at 600mm Gypframe 70 S 50 ‘C’ Studs at 600mm
centres. 80mm Isover Modular Roll in centres. 75mm Isover Acoustic Slab in
the cavity. Linings as in table. the cavity. Linings as in table.
Detail Partition Board type Lining Max. Sound insulation Duty Approx. System
thickness thickness partition RwdB rating weight reference
mm mm height1 Any Skim kg/m²
mm Any finish2 Skim only3
finish2 only3
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
GypWall robust
For details of when
to specify fire
70mm Gypframe 'C' Studs - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 1b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 70 S 50 ‘C’ Studs at 600mm Gypframe 70 S 50 ‘C’ Studs at 600mm Gypframe 70 S 50 ‘C’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition
Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity.
Partitions
Linings as in table. Linings as in table.
4 5
C04
One layer of board each side of One layer of board each side of
Gypframe 70 S 50 ‘C’ Studs at 600mm Gypframe 70 S 50 ‘C’ Studs at 600mm
centres. 80mm Isover Modular Roll in centres. 75mm Isover Acoustic Slab in
the cavity. Linings as in table. the cavity. Linings as in table.
Detail Partition Board type Lining Max. Sound insulation Duty Approx. System
thickness thickness partition RwdB rating weight reference
mm mm height1 Any Skim kg/m²
mm Any finish2 Skim only3
finish2 only3
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
1 2 3 4
One layer of board each side of One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 70 I 50 ‘I’ Studs at 600mm Gypframe 70 I 50 ‘I’ Studs at 600mm Gypframe 70 I 50 ‘I’ Studs at 600mm Gypframe 70 I 50 ‘I’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition centres. 80mm Isover Modular Roll in
Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity. the cavity. Linings as in table.
Linings as in table. Linings as in table.
Partitions
Detail Partition Board type Lining Max. Sound Duty rating Approx. System
thickness thickness partition insulation weight reference
mm mm height1 RwdB kg/m²
mm
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
GypWall robust
For details of when
to specify fire
70mm Gypframe 'I' Studs - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 2b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3 4
One layer of board each side of One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 70 I 50 ‘I’ Studs at 600mm Gypframe 70 I 50 ‘I’ Studs at 600mm Gypframe 70 I 50 ‘I’ Studs at 600mm Gypframe 70 I 50 ‘I’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition centres. 80mm Isover Modular Roll in
Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity. the cavity. Linings as in table.
Linings as in table. Linings as in table.
Partitions
Detail Partition Board type Lining Max. Sound Duty rating Approx. System
thickness thickness partition insulation weight reference
mm mm height1 RwdB kg/m²
mm
C04
60 minutes fire resistance
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of reduced stud centres. Maximum partition height can be
increased to 4700mm by using Gypframe 70 I 70 'I' Studs. Refer to C04. S01. P05, Table 2.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
1 2
One layer of board each side of One layer of board each side of
Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at
600mm centres. 25mm Isover Acoustic 600mm centres. 50mm Isover Acoustic
Partition Roll (APR 1200) in the cavity. Partition Roll (APR 1200) in the cavity.
Linings as in table. Linings as in table.
Partitions
Detail Partition Board type Lining Max. Sound insulation Duty Approx. System
thickness thickness partition RwdB rating weight reference
mm mm height1 Any Skim kg/m²
mm Any finish2 Skim only3
finish2 only3
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
GypWall robust
For details of when
to specify fire
70mm Gypframe AcouStuds - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 3b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2
One layer of board each side of One layer of board each side of
Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at
600mm centres. 25mm Isover Acoustic 600mm centres. 50mm Isover Acoustic
Partition Roll (APR 1200) in the cavity. Partition Roll (APR 1200) in the cavity.
Linings as in table. Linings as in table.
Partitions
Detail Partition Board type Lining Max. Sound insulation Duty Approx. System
thickness thickness partition RwdB rating weight reference
mm mm height1 Any Skim kg/m²
mm Any finish2 Skim only3
finish2 only3
C04
60 minutes fire resistance
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 92 S 60 ‘C’ Studs at 600mm Gypframe 92 S 60 ‘C’ Studs at 600mm Gypframe 92 S 60 ‘C’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 3 x 25mm Isover Acoustic
Roll (APR 1200) in the cavity. Partition Roll (APR 1200) in the cavity.
Linings as in table. Linings as in table.
Partitions
Detail Partition Board type Lining Max. Sound insulation Duty Approx. System
thickness thickness partition RwdB rating weight reference
mm mm height1 Any Skim kg/m²
Any finish2 Skim only3
C04
mm finish2 only3
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Increasing insulation to 50mm Isover Acoustic Partition Roll (APR 1200) will not improve this system performance.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
GypWall robust
For details of when
to specify fire
92mm Gypframe 'C' Studs - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 4b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 92 S 60 ‘C’ Studs at 600mm Gypframe 92 S 60 ‘C’ Studs at 600mm Gypframe 92 S 60 ‘C’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 3 x 25mm Isover Acoustic
Roll (APR 1200) in the cavity. Partition Roll (APR 1200) in the cavity.
Linings as in table. Linings as in table.
Partitions
Detail Partition Board type Lining Max. Sound insulation Duty Approx. System
thickness thickness partition RwdB rating weight reference
mm mm height1 Any Skim kg/m²
C04
mm Any finish2 Skim only3
finish2 only3
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of reduced stud centres.
Refer to C04. S01. P05, Table 2. Maximum partition height can be increased to 6200mm by using Gypframe 92 I 90 'I' Studs.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
Increasing insulation to 50mm Isover Acoustic Partition Roll (APR 1200) will not improve this system performance.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
1 2 3
One layer of board each side of 92mm One layer of board each side of 92mm One layer of board each side of 92mm
Gypframe AcouStuds at 600mm centres. Gypframe AcouStuds at 600mm centres. Gypframe AcouStuds at 600mm centres.
Linings as in table. 25mm Isover Acoustic Partition Roll 50mm Isover Acoustic Partition Roll
(APR 1200) in the cavity. Linings as in table. (APR 1200) in the cavity. Linings as in table.
Partitions
Detail Partition Board type Lining Max. Sound insulation Duty Approx. System
thickness thickness partition RwdB rating weight reference
mm mm height1 Any Skim kg/m²
mm Any finish2 Skim only3
finish2 only3
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
GypWall robust
For details of when
to specify fire
92mm Gypframe AcouStuds - single layer board linings resistance using BS
Refer to C02. S01. P05
Table 5b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3
One layer of board each side of 92mm One layer of board each side of 92mm One layer of board each side of 92mm
Gypframe AcouStuds at 600mm centres. Gypframe AcouStuds at 600mm centres. Gypframe AcouStuds at 600mm centres.
Linings as in table. 25mm Isover Acoustic Partition Roll 50mm Isover Acoustic Partition Roll
(APR 1200) in the cavity. Linings as in table. (APR 1200) in the cavity. Linings as in table.
Partitions
Detail Partition Board type Lining Max. Sound insulation Duty Approx. System
thickness thickness partition RwdB rating weight reference
mm mm height1 Any Skim kg/m²
mm Any finish2 Skim only3
finish2 only3
C04
60 minutes fire resistance
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
1 2
One inner layer and one outer layer of One inner layer and one outer layer of
board each side of Gypframe 70 AS 50 board each side of Gypframe 70 AS 50
AcouStuds at 600mm centres. AcouStuds at 600mm centres. 25mm
Linings as in table.
Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table.
Partitions
Detail Partition Inner board type Outer board type Max. Sound insulation Duty Approx. System
thickness mm mm partition RwdB rating weight reference
mm height1 Any Skim kg/m²
Any Skim
mm
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
GypWall robust
For details of when
to specify fire
70mm Gypframe AcouStuds - double layer board linings resistance using BS
Refer to C02. S01. P05
Table 6b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2
One inner layer and one outer layer of One inner layer and one outer layer of
board each side of Gypframe 70 AS 50 board each side of Gypframe 70 AS 50
AcouStuds at 600mm centres. AcouStuds at 600mm centres. 25mm
Linings as in table.
Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table.
Partitions
Detail Partition Inner board type Outer board type Max. Sound insulation Duty Approx. System
thickness mm mm partition RwdB rating weight reference
mm height1 Any Skim kg/m²
Any Skim
mm
C04
finish2 only3 finish2 only3
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved through the use of reduced stud centres.
Refer to C04. S01. P05, Table 2.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to
deflection criteria).
Whilst our GypWall partitions are non-loadbearing, they are able to The designer should consider the thickness tolerances of the
provide resistance to levels of horizontal uniformly distributed loads partition types in relation to the proposed door frame detail. To
in accordance with BS 6399. satisfy BS 5234: Part 2 requirements for Heavy and Severe Duty
Rating partitions, door framing should be specified. The door
Refer to C02. S01. P26 – Robustness.
manufacturer should also be consulted in relation to the door detail.
Fixing floor and ceiling channels Particular care must be taken in selecting
the correct length of British Gypsum
Gypframe Deep Flange Floor & Ceiling Channels must be securely Drywall Screws for fixing Gyproc DuraLine
fixed with a row of fixings at 600mm maximum centres. For 94mm to Gypframe AcouStuds to ensure that
channels and above, two rows of staggered fixings are required, they do not penetrate the web of the
C04
each row at 600mm centres and each fixing 25mm in from the stud. Doing so would create a physical
flange. If the floor is uneven, a 38mm thick timber sole plate equal bridge that would lead to a downgrade in
to the width of the channel should be used. sound insulation performance.
Partition to structural steelwork junctions Partition head deflection designs may be necessary to
accommodate deflections in the supporting floor. Deflection heads
When designing the layout of rooms requiring separation by sound
may also be required to the underside of roof structures subjected
insulating walls abutting structural steelwork, consideration should
to positive and negative pressures.
be given to the potential loss of sound insulation performance
through the steelwork.
To minimise the loss of acoustic performance:
Refer to C02. S01. P10 – Building acoustics.
Refer to C02. S01. P10 – Building acoustics.
GypWall robust
Services Access for maintenance
Penetrations Gyproc Profilex Access Panels are available to provide access for
Penetrations of fire-resistant or sound-insulating constructions maintenance. Access panels must be fully compatible with drywall
for services need careful consideration to ensure that the construction and match the fire rating of the partition.
performance of the element is not downgraded. Consideration also
Refer to profilex.co.uk for further information.
needs to be given to the services themselves so they do not act as
the mechanism of fire spread or sound transmission.
Board finishing
Refer to C02. S01. P32 – Service installations. Refer to C08. S01. P02 – Finishes.
Electrical
The installation of electrical services should be carried out in
accordance with BS 7671. The cut-outs in the studs can be used for
Handy hint
Partitions
routing electrical and other small services.
For increased resistance to accidental surface
Refer to Partitions introduction C04. S01. P07 – construction damage, the use of ThistlePro DuraFinish is
detail 2. recommended.
C04
Switch boxes and socket outlets can be supported from
Gypframe 99 FC 50 Fixing Channel fixed horizontally between studs, Tiling
or a high performance socket box detail where higher acoustic Tiles can be applied to the surface of lightweight partition systems.
performance is required.
Refer to C08. S04. P02 – Tiling.
Where Gypframe AcouStuds are used, services are routed through
50mm x 28mm ‘H’ shaped push-outs, at the same centres as shown Construction details
for conventional cut-outs.
For standard GypWall construction details
Refer to Partitions introduction C04. S01. P07 – construction
Refer to Partitions introduction C04. S01. P07 – construction
detail 2a.
details.
Handy hint
Where access is limited to one side at the
SpecSure®
head, e.g. M+E cages already installed in
All our systems are covered by SpecSure® when
corridors.
using genuine British Gypsum and Saint-Gobain
Refer to C05. S02. P02 – ShaftWall. Isover products.
Independent support
When designing for the installation of services such as fire dampers
and associated ductwork through a GypWall partition, consideration
should be given to the size and weight of the damper - this will
determine whether it can be supported directly from the partition
or needs to be independently supported from the structure.
Fixtures
1 3 2
1
4
6
Partitions
3
C04
Head Base
3 4
1
1
5 6
2
1
1
4
GypWall robust
7
Partitions
150mm
5
C04
7
4
300mm
1200mm 1200mm
1
150mm
Door frame (maximum 1200mm width) to satisfy BS 5234: Parts 1 & 2: 1992 - Heavy and Severe Duty (up to 60kg door)
1 Gyproc DuraLine 5 Gypframe 72 DC 60 Deep Channel cut and bent to form door head
2 Gypframe 70 S 50 'C' Stud 6 Timber door frame and architrave
3 Gypframe 70 S 50 'C' stud at jamb 7 Stud sleeved to full opening height with Gypframe 72 DC 60 Deep
4 Gypframe 72 DC 60 Deep Channel Channel
Advice should be sought from the door manufacturer prior to the construction of these details.
At the base, the channel is cut and bent to extend 300mm up the studs and fixed each side with two British Gypsum Wafer Head Drywall Screws. The
studs each side of the opening are sleeved full height of opening with Gypframe Floor & Ceiling Channel.
Gypframe ‘C’ Studs (70 S 50, 92 S 60) Gypframe GFS1 Fixing Strap
Vertical stud providing acoustic and structural Used to support horizontal board joints and within
performances designed to receive fixing of board deflection heads.
to both sides.
Gypframe ‘I’ Studs (70 I 50, 70 I 70, 92 I 90) Gypframe GFT1 Fixing T
Enhanced strength stud that allows for lining height, Used to support horizontal board joints.
without increasing lining width. Designed to receive
fixing of board to both sides.
Partitions
Gypframe AcouStud (70 AS 50, 92 AS 50) Gypframe GA5 Internal Fixing Angle
Vertical stud providing enhanced acoustic and Steel angle providing framing stability and
structural performances designed to receive board support.
C04
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GA6 Splayed Angle
(72 DC 60, 94 DC 60) Steel angle providing framing stability and
Floor and ceiling channels with deep flanges for board support.
retaining the Gypframe studs at floor and ceiling
junctions for partitions 4200mm to 8000mm high.
Also used around openings and in deflection heads
(maximum 30mm deflection).
Gypframe Extra Deep Flange Floor & Ceiling Gypframe Service Support Plate
Channels (72 EDC 80, 94 EDC 70) For installation of 18mm plywood within
Floor and ceiling channels with extra deep flanges a partition cavity to support medium to
for retaining the Gypframe studs at floor and ceiling heavyweight fixtures.
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum
50mm deflection).
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
British Gypsum Collated Drywall Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws for Corrosion resistant self-tapping steel screws
fixing board to metal framing less than 0.8mm for fixing metal to metal framing 0.8mm thick and
thick ('I' Studs less than 0.6mm thick). greater ('I' Studs 0.8mm thick and greater).
Partitions
British Gypsum Wafer Head Drywall Screws
Corrosion resistant self-tapping steel screws for
fixing metal to metal framing less than 0.8mm
C04
thick ('I' Studs less than 0.6mm thick).
GypWall robust
This is intended to be a basic description of how the system is built.
For detailed installation guidance refer to the British Gypsum Site Book.
Partitions
Gypframe Deep Flange or Extra Deep Flange Gypframe Studs are suitably fixed to The perimeter of the partition is then sealed
Floor & Ceiling Channels are suitably fixed abutments. on both sides with Gyproc Sealant.
to the floor and soffit.
C04
Gypframe Studs are then friction fitted into Door openings are constructed to the Heavy M&E services can be located within the
the Gypframe Floor & Ceiling Channels at and Severe door detail. partition cavity.
the required centres.
Isover insulation can also be added to Gyproc DuraLine (and Gyproc SoundBloc
the partition cavity for increased acoustic inner layer if required) plasterboards are
performance. then fixed to the Gypframe framework with
British Gypsum Drywall Screws.
Additional information
For full installation details, refer to the
British Gypsum Site Book, available to
download from british-gypsum.com
GypWall extreme
Ultimate impact and abrasion resistant partition system
Partitions
The GypWall extreme family of partitions have Refer to C02. S01. P49
C04
surpassing all requirements of a full Severe Duty
Rating in accordance with BS 5234: Part 2: 1992. Refer to C01. S01. P07
Key benefits
— Provides performance beyond a Severe Duty
Rating from a lightweight, narrow-footprint
solution
— Heavy fixtures can be secured to a single layer
without the need for additional pattressing
— Reduced maintenance cycles due to a highly
impact and scratch resistant board surface
— Fully compatible with other British Gypsum
systems, meaning GypWall extreme can be
specified in areas of the building that really
need it
Handy hint
For areas of a building where extreme levels of duty are required
to only one side of the construction, for example a partition
between a corridor and a classroom, refer to C04. S04. P08
GypWall extreme / robust hybrid system performance tables.
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition
Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity.
Linings as in table. Linings as in table.
Partitions
4 5
C04
Two layers of board each side of Two layers of board each side of
Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at
600mm centres. Linings as in table. 600mm centres. 25mm Isover Acoustic
Partition Roll (APR 1200) in the cavity.
Linings as in table.
Detail Partition Inner board type ACTIVair Outer board ACTIVair Max. Sound Duty Approx. System
thickness mm technology type technology partition insulation rating weight reference
mm available1 mm available1 height2 Rw dB kg/m²
mm
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall extreme
For details of when
to specify fire
70mm Gypframe ‘C’ Stud and Gypframe AcouStud resistance using BS
Refer to C02. S01. P05
Table 1b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm
centres. Linings as in table. centres. 25mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition
Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity.
Linings as in table. Linings as in table.
Partitions
4 5
C04
Two layers of board each side of Two layers of board each side of
Gypframe 70 AS 50 AcouStuds at Gypframe 70 AS 50 AcouStuds at
600mm centres. Linings as in table. 600mm centres. 25mm Isover Acoustic
Partition Roll (APR 1200) in the cavity.
Linings as in table.
Detail Partition Inner board type ACTIVair Outer board ACTIVair Max. Sound Duty Approx. System
thickness mm technology type technology partition insulation rating weight reference
mm available1 mm available1 height2 Rw dB kg/m²
mm
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
Based on a limiting deflection of L/240 at 200 Pa.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
Detail Partition Inner board type ACTIVair Outer board ACTIVair Max. Sound Duty Approx. System
thickness mm technology type technology partition insulation rating weight reference
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall extreme
For details of when
to specify fire
146mm Gypframe AcouStud resistance using BS
Refer to C02. S01. P05
Table 2b — Solutions to satisfy requirements of BS 476: Part 22: 1987
Partitions
Partition Roll (APR 1200) in the cavity.
Linings as in table.
Detail Partition Inner board type ACTIVair Outer board ACTIVair Max. Sound Duty Approx. System
thickness mm technology type technology partition insulation rating weight reference
C04
mm available mm available1 height2 Rw (Rw + Ctr ) kg/m²
mm dB
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
Based on a limiting deflection of L/240 at 200 Pa.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
1 2 3 4
One layer of board each side of One layer of board each side of One layer of board to side 1 and two One layer of board to side 1 and two
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm layers of board to side 2 of Gypframe layers of board to side 2 of Gypframe
centres. Linings as in table. centres. 50mm Isover Acoustic Partition 70 AS 50 AcouStuds at 600mm centres. 70 AS 50 AcouStuds at 600mm centres.
Roll (APR 1200) in the cavity. Linings as in table. 50mm Isover Acoustic Partition Roll
Linings as in table. (APR 1200) in the cavity.
Linings as in table.
Partitions
Detail Partition Board type and ACTIVair Board type and ACTIVair Max. Sound Duty Approx. System
thickness thickness (side 1) technology thickness (side 2) technology partition insulation rating weight reference
mm mm available mm available1 height2 Rw dB kg/m²
C04
mm
Gyproc WallBoard 15 -
3 115 Gyproc DuraLine 15 -
+ Rigidur h 12.5 4200 47 Severe3 40 X606A019
Gyproc SoundBloc 15 -
3 -
115 Gyproc DuraLine 15
+ Rigidur h 12.5 4200 49 Severe3 44 X606A021
Gyproc WallBoard 15 -
4 115 Gyproc DuraLine 15 -
+ Rigidur h 12.5 4200 52 Severe3 40 X606A020
Gyproc SoundBloc 15 -
4 -
115 Gyproc DuraLine 15
+ Rigidur h 12.5 4200 55 Severe3 44 X606A022
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall extreme
For details of when
to specify fire
70mm Gypframe 'C' Stud and Gypframe AcouStud resistance using BS
Refer to C02. S01. P05
Table 3b - Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3 4
One layer of board each side of One layer of board each side of One layer of board to side 1 and two One layer of board to side 1 and two
Gypframe 70 S 60 ‘C’ Studs at 600mm Gypframe 70 S 60 ‘C’ Studs at 600mm layers of board to side 2 of Gypframe layers of board to side 2 of Gypframe
centres. Linings as in table. centres. 50mm Isover Acoustic Partition 70 AS 50 AcouStuds at 600mm centres. 70 AS 50 AcouStuds at 600mm centres.
Roll (APR 1200) in the cavity. Linings as in table. 50mm Isover Acoustic Partition Roll
Linings as in table. (APR 1200) in the cavity.
Linings as in table.
Partitions
Detail Partition Board type and ACTIVair Board type and ACTIVair Max. Sound Duty Approx. System
thickness thickness (side 1) technology thickness (side 2) technology partition insulation rating weight reference
mm mm available mm available1 height2 Rw dB kg/m²
C04
mm
Gyproc WallBoard 15 -
3 115 Gyproc DuraLine 15 -
+ Rigidur h 12.5 4200 47 Severe3 40 X606A019
Gyproc SoundBloc 15 -
3 -
115 Gyproc DuraLine 15
+ Rigidur h 12.5 4200 49 Severe3 44 X606A021
Gyproc WallBoard 15 -
4 115 Gyproc DuraLine 15 -
+ Rigidur h 12.5 4200 52 Severe3 40 X606A020
Gyproc SoundBloc 15 -
4 -
115 Gyproc DuraLine 15
+ Rigidur h 12.5 4200 55 Severe3 44 X606A022
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
These systems have an ACTIVair board option available, which improves indoor air quality. Alternatively, all systems can be skim finished
with ThistlePro PureFinish, which contains ACTIVair technology. Refer to C08. S02. P05 and C02. S01. P49 for further details.
2
Based on a limiting deflection of L/240 at 200 Pa.
3
The resistance to impact of Rigidur h is higher than the most severe criteria set out in BS 5234. British Gypsum has conducted a number of additional
structural performance and durability tests beyond Severe Duty to better reflect actual use in high traffic areas. Search for substantiation report on
british-gypsum.com and type in the reference number.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Gypframe Deep Flange Floor & Ceiling Channel or Gypframe Extra Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
Whilst our GypWall partition systems are non-loadbearing, they Control joints may be required in the partition to relieve stresses
are able to provide resistance to levels of horizontal uniformly induced by expansion and contraction of the structure. They should
distributed loads. coincide with movement joints within the surrounding structure.
Refer to C02. S01. P26 – Robustness. Refer to Partitions introduction C04. S01. P10 – construction
detail 12.
Planning – key factors
Deflection heads
GypWall extreme comprises Gypframe 'C' Studs installed at 600mm
centres within Gypframe Deep Flange Floor & Ceiling Channels. Partition head deflection designs may be necessary to
The position of services and heavy fixtures should be accommodate deflections in the supporting floor. Deflection heads
pre-determined and their installation planned into the frame may also be required to the underside of roof structures subjected
Partitions
Fixing floor and ceiling channels To minimise the loss of acoustic performance:
Gypframe Deep Flange Floor & Ceiling Channels must be securely Refer to C02. S01. P10 – Building acoustics.
fixed with a row of fixings at 600mm maximum centres. For 94mm
C04
channels and above, two rows of staggered fixings are required, For deflection head design:
each row at 600mm centres and each fixing 25mm in from the
Refer to Partitions introduction C04. S01. P11 – construction
flange. If the floor is uneven, a 38mm thick timber sole plate equal
details 15-22.
to the width of the channel should be used.
Services
If the concrete or screeded floor is new, consideration should be
given to the installation of a damp-proof membrane between the Penetrations
floor surface and the channel or sole plate. Penetrations of fire-resistant or sound-insulating constructions
for services need careful consideration to ensure that the
Splicing performance of the element is not downgraded. Consideration also
needs to be given to the services themselves so they do not act as
To extend studs, overlap by 600mm (minimum). Fix together using
the mechanism of fire spread or sound transmission.
British Gypsum Wafer Head Drywall Screws or steel pop rivets (two
to each flange), or by using the Gyproc Stud Interlocking Tool twice Refer to C02. S01. P32 – Service installations.
to each flange.
Electrical
Refer to Partitions introduction C04. S01. P07 – construction
The installation of electrical services should be carried out in
detail 1.
accordance with BS 7671. The cut-outs in the studs can be used for
routing electrical and other small services (Partitions introduction
Partition to structural steelwork junctions
C04. S01. P07 – construction detail 2). Switch boxes and socket
When designing the layout of rooms requiring separation by sound outlets can be supported from Gypframe 99 FC 50 Fixing Channel
insulating walls abutting structural steelwork, consideration should fixed horizontally between studs, or a high performance socket box
be given to the potential loss of sound insulation performance detail used where higher acoustic performance is required.
through the steelwork.
Refer to C02. S01. P10 – Building acoustics. Where Gypframe AcouStuds are used, services are routed through
50mm x 28mm ‘H’ shaped push-outs, at the same centres as shown
Door openings in Partitions introduction C04. S01. P07 – construction detail 2a
for conventional cut-outs. Cables should be protected by conduit,
The designer should consider the thickness tolerances of the or other suitable precautions taken to prevent abrasion when they
partition types in relation to the proposed door frame detail. pass through the metal frame. Service cut-outs should be aligned to
To satisfy BS 5234 requirements for Heavy and Severe Duty allow easy installation of service. If studs require cutting, cut from
partitions, door framing should be specified as shown in Partitions the same end of each stud to ensure cut-out alignment.
introduction C04. S01. P14 – construction details 26. The door
manufacturer should also be consulted in relation to the door detail. Independent support
If a plastered finish is specified, the thickness of the door or glazing When designing for the installation of services such as fire
frame must allow for the thickness of the plaster finish. dampers and associated ductwork through a GypWall partition,
consideration should be given to the size and weight of the
Cavity barriers damper - this will determine whether it can be supported directly
from the partition or needs to be independently supported from
Minimum 12.5mm Gyproc plasterboard screw-fixed into the web the structure.
of perimeter channels or vertical studs will provide a satisfactory
closure to flame or smoke. Refer to Partitions introduction C04. S01. P17 – construction
details 28-31.
Refer to C06. S07. P02 – Cavity barriers.
GypWall extreme
Fixtures Board finishing
Due to the inherent strength of Rigidur h, some fixtures can be For increased resistance to accidental damage, a skim coat of
made directly to the board – please see the Rigidur h for commercial ThistlePro DuraFinish plaster may be applied.
applications Product Data Sheet and the British Gypsum Site Book
Refer to the Rigidur h for commercial applications Product Data
for more information, available to download from
Sheet, available to download from british-gypsum.com
british-gypsum.com. Heavyweight fixtures (to BS 5234), such
as wash basins and wall cupboards, can be fixed using plywood
Tiling
secured with Gypframe Service Support Plates.
Tiles can be applied to the surface of lightweight partition systems.
Refer to C02. S01. P33 – Service installations.
Refer to C08. S04. P02 – Tiling
Access for maintenance
Construction details
Partitions
Gyproc Profilex Access Panels are available to provide access for
maintenance. Access panels must be fully compatible with drywall For standard GypWall construction details
construction and match the fire rating of the partition. Refer to Partitions introduction C04. S01. P07 – construction
details
Refer to profilex.co.uk for further information.
C04
Handy hint SpecSure®
— Rigidur h is available as a special order in All our systems are covered by SpecSure® when
sizes up to 2.5m x 6.0m, reducing the using genuine British Gypsum and Saint-Gobain
amount of tape and jointing required Isover products.
— The use of insulation within the partition
cavity to provide a higher acoustic
performance than may initially be
required, will help to future proof for
subsequent changes of room use
— Cut-outs in the Gypframe Studs can be
used to accommodate horizontal service
runs. Installers should be made aware of
this to avoid vertical misalignment of
cut-outs between adjacent studs
1 2
4 1
2
Partitions
2
C04
Head Base
3 4
1
1
1 Rigidur h 5 Bulk fill with Gyproc jointing materials (where gap exceeds 5mm)
2 Gypframe ‘C’ Stud 6 Skirting
3 Gypframe Deep Flange Floor & Ceiling Channel 7 Internal blockwork
4 Gyproc Sealant 8 DriLyner basic wall lining system
GypWall extreme
Gypframe metal components ( Refer to C10. S02. P02 for details)
Partitions
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GA5 Internal Fixing Angle
(72 DC 60, 148 DC 60) Steel angle providing framing stability and
Floor and ceiling channels with deep flanges for board support.
C04
retaining the Gypframe studs at floor and ceiling
junctions for partitions 4200mm to 8000mm high.
Also used around openings and in deflection heads
(maximum 30mm deflection).
Gypframe Extra Deep Flange Floor & Ceiling Gypframe GA6 Splayed Angle
Channels (72 EDC 80, 148 EDC 80) Steel angle providing framing stability and
Floor and ceiling channels with extra deep flanges board support.
for retaining the Gypframe studs at floor and ceiling
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum
50mm deflection).
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
than 0.8mm thick. greater (‘I’ stud 0.6mm thick and greater).
British Gypsum Wafer Head Drywall Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws for
C04
for fixing metal to metal framing less than fixing metal to metal framing 0.8mm thick
0.8mm thick (‘I’ studs less than 0.6mm thick). (‘I’ studs 0.6mm thick and greater).
Gyproc AquaBead
An easy to apply, water, activated adhesive corner
bead, for reinforcing external 90°C angles in taped
and jointed plasterboard constructions.
GypWall extreme
Finishing products ( Refer to C10. S06. P02 for details)
Partitions
common backgrounds including undercoat plasters
and plasterboard. For more information refer to
C02. S01. P49.
C04
Thistle SprayFinish ThistlePro Magnetic
To provide a plaster skim finish by spray or hand To provide a plaster skim finish that provides an
application, ideal for medium to large projects. attraction to magnets used to finish a wide range
of backgrounds, including undercoat plasters and
plasterboard.
Gypframe Deep Flange or Extra Deep Flange Gypframe Studs are suitably fixed to The perimeter of the partition is then sealed
Floor & Ceiling Channels are suitably fixed abutments. on both sides with Gyproc Sealant.
to the floor and soffit.
C04
Gypframe studs are then friction fitted into Door openings are constructed to the Heavy M&E services can be located within the
the Gypframe Deep Flange Floor & Ceiling and Severe Duty detail. partition cavity.
Channels at required centres.
Isover insulation can also be added to Gyproc DuraLine, Gyproc SoundBloc or Rigidur h boards are then fixed as the outer
the partition cavity for increased acoustic Gyproc WallBoard plasterboards may be layer to all Gypframe framing members
performance. installed as either an inner layer, or as part with Rigidur Screws.
of the GypWall extreme / robust hybrid system
with British Gypsum Drywall Screws. It is recommended that Rigidur H
boards are pre-drilled and countersunk
screw locations for improved ease of
installation. For further information, refer to
the British Gypsum Good Practice Guide.
Additional information
For full installation details, refer to the
British Gypsum Site Book, available to
download from british-gypsum.com
GypWall quiet sf
Single frame acoustic separating wall system
Partitions
This makes it the ideal solution for a wide
range of buildings where it is important System can be skim
finished with
ThistlePro PureFinish.
to provide occupants with a comfortable
C04
Refer to C02. S01. P49
Key benefits
— Very efficient use of floor space due to a high
level of acoustic performance being achieved
with a minimal partition width
— Reduced sound transmission is achieved
through the use of Gypframe RB1 Resilient Bar
to provide a high degree of isolation between
the Gypframe 'C' Studs and the high
performance Gyproc plasterboard lining
— Additional acoustic performance can be
achieved with the application of
Thistle MultiFinish plaster skim on selected
specifications
1 2 3
Two layers of board each side of Gypframe ‘C’ Two layers of board each side of Gypframe ‘C’ Two layers of board each side of Gypframe ‘C’
Studs at 600mm centres with Gypframe RB1 Studs at 600mm centres with Gypframe RB1 Studs at 600mm centres with Gypframe RB1
Partitions
Resilient Bar at 600mm centres to one side. 50mm Resilient Bar at 600mm centres to both sides. Resilient Bar at 600mm centres to one side. 50mm
Isover Acoustic Partition Roll (APR 1200) 50mm Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table. in the cavity. Linings as in table.
C04
Detail Partition Board type1 Lining Stud Max. Sound insulation Duty Approx. System reference
thickness thickness size partition Rw (Rw + Ctr) dB5 rating weight
mm mm mm height2 kg/m²
mm Any3 Skim4 Any3 Skim4
finish only finish only
1 223 Gyproc SoundBloc 2 x 15 146 5000 62 (57) 63 (57) Severe 51 A316017 A316017S
Gyproc FireLine + 1 x 15 +
1 147 70 4000 61 (53) 62 (53) Severe 53 Q606040 Q606040S
Gyproc DuraLine 1 x 15
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
For improved durability and impact resistance, the outer layer can be replaced with a layer of 15mm Gyproc DuraLine.
3
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
Sound insulation performance for partitions finished using jointing or plaster skim.
4
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
5
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1)
For heights above 4200mm Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection criteria).
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
GypWall quiet sf
For details of when
to specify fire
70mm, 92mm and 146mm Gypframe ‘C’ Stud resistance using BS
Refer to C02. S01. P05
Table 1b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3
Two layers of board each side of Gypframe ‘C’ Two layers of board each side of Gypframe ‘C’ Two layers of board each side of Gypframe ‘C’
Studs at 600mm centres with Gypframe RB1 Studsat 600mm centres with Gypframe RB1 Studs at 600mm centres with Gypframe RB1
Partitions
Resilient Bar at 600mm centres to one side. 50mm Resilient Bar at 600mm centres to both sides. Resilient Bar at 600mm centres to one side. 50mm
Isover Acoustic Partition Roll (APR 1200) 50mm Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table. in the cavity. Linings as in table.
C04
Detail Partition Board type1 Lining Stud Max. Sound insulation Duty Approx. System reference
thickness thickness size partition Rw (Rw + Ctr) dB5 rating weight
mm mm mm height2 kg/m²
mm Any3 Skim4 Any3 Skim4
finish only finish only
1 223 Gyproc SoundBloc 2 x 15 146 6900 62 (57) 63 (57) Severe 51 A316017 A316017S
Gyproc FireLine + 1 x 15 +
1 147 70 4200 61 (53) 62 (53) Severe 53 Q606040 Q606040S
Gyproc DuraLine 1 x 15
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
For improved durability and impact resistance, the outer layer can be replaced with a layer of 15mm Gyproc DuraLine.
2
Based on a limiting deflection of L/240 at 200 Pa. For increased heights Gypframe 'I' Studs could be used (Refer to table 2 within this section)
3
Sound insulation performance for partitions finished using jointing or plaster skim.
4
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
5
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1)
For heights above 4200mm Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection criteria).
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Studs at 600mm 2 x 12.5mm board, 2 x 15mm board, 19mm + 12.5mm board, Gypframe RB1 Resilient Bar
centres Gypframe RB1 Resilient Bar Gypframe RB1 Resilient Bar Gypframe RB1 Resilient Bar both sides
to one side to one side to one side
1
The above have not been subjected to acoustic tests and therefore any sound insulation performances are opinion only.
For heights between 4200mm and 8000mm Gypframe Deep Flange Floor & Ceiling Channel should be used.
Partitions
C04
GypWall quiet sf
Building design Door openings
GypWall quiet sf comprises Gypframe 'C' Studs installed at Any openings will require very careful detailing to minimise the
600mm centres within Gypframe Floor & Ceiling Channels and loss of acoustic performance of the partition. Consult with an
Gypframe RB1 Resilient Bars horizontally fixed to one or both sides. Acoustic Consultant. Specialist heavy acoustic doorsets may require
additional support.
Planning – key factors
Refer to construction detail 8 within this section.
The position of services and heavy fixtures should be
pre-determined and their installation planned into the frame Framing surround for openings
erection stage. Timber sole plates should be considered where
Where services such as horizontal ducts, fire dampers and access
the floor is uneven. All penetrations will need to be adequately
panels are required to penetrate the wall, their position should be
fire-stopped.
pre-determined in order that a framed opening can be provided.
Partitions
The openings should be constructed using established metal stud
procedures.
Handy hint
Refer to Partitions introduction C04. S01. P16 – construction
details 28-31.
Be aware that if working to centre lines on a
C04
plan, GypWall quiet sf systems incorporating
Cavity barriers
Gypframe RB1 Resilient Bar to one side only
are not symmetrical. Stone mineral wool (by others) cut neatly to fit across the cavity
forms a suitable closure.
If the concrete or screeded floor is new, consideration should be For optimum performance all air paths should be sealed.
given to the installation of a damp-proof membrane between the Gyproc Sealant should be applied to the perimeter of the inner layer
floor surface and the channel or sole plate. immediately prior to fitting the face layer board on the side(s) of the
partition where resilient bars are located.
Penetrations
Partition to structural steelwork junctions
Penetrations of fire-resistant or sound-insulating constructions
When designing the layout of rooms requiring separation by sound
for services need careful consideration to ensure that the
insulating walls abutting structural steelwork, consideration should
performance of the element is not downgraded. Consideration also
be given to the potential loss of sound insulation performance
needs to be given to the services themselves so they do not act as
through the steelwork.
the mechanism of fire spread or sound transmission.
If you require a wider partition to fully encompass structural steel, Refer to C02. S01. P32 – Service installations.
refer to GypWall quiet or GypWall quiet iwl.
Electrical Fixtures
The installation of electrical services should be carried out in
Lightweight fixtures can be made directly to the partitions.
accordance with BS 7671. The cut-outs in the studs can be used
Medium weight fixtures can be made to Gypframe 99 FC 50 Fixing
for routing electrical and other small services (refer to Partitions
Channel. Heavyweight fixtures (to BS 5234), such as wash basins
introduction C04. S01. P07 – construction detail 2). Switch boxes
and wall cupboards, can be fixed using plywood secured with a
and socket outlets can be supported from Gypframe 99 FC 50 Fixing
Gypframe Service Support Plates. In all instances the
Channel fixed horizontally between studs, or a high performance
Gypframe Service Support Plates are fixed to the side without a
socket box detail used where higher acoustic performance is
Gypframe RB1 Resilient Bar.
required.
Medium and heavy weight fixtures can only be made when the
Where Gypframe AcouStuds are used, services are routed through
lining boards are fixed directly to the stud framing. The installation
50mm x 28mm ‘H’ shaped push-outs, at the same centres as shown
of fixings may downgrade the acoustic performance of the wall,
Partitions
the same end of each stud to ensure cut-out alignment. of a partition, consider using GypWall quiet or GypWall quiet iwl.
SpecSure®
All our systems are covered by SpecSure® when
using genuine British Gypsum and Saint-Gobain
Isover products.
GypWall quiet sf
1 2
5
6
6
2
Partitions
3
10
11
C04
15
1
3
Junction with masonry
4 3
17
2
14
12
6
15mm
13
15mm
9 20mm
8 16
4
7 1
6 2
3
5
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board
fixing, which should be made into Gypframe GFS1 Fixing Strap. Continuous Gyproc FireStrip must be installed as shown to maintain fire performance.
4 5
3
3
2 2
1
1
Partitions
5
4
C04
5 4
Corner - resilient bar to external corner Corner - resilient bar to internal corner
6 7
3 3
2 2
1 1
6 6
4 4
5 5
‘T’ junction (resilient bar on opposite side) ‘T’ junction (resilient bar on abutment side)
Guidance must be sought from the relevant approval authority e.g. Building Control to establish if a cavity barrier is required (Approved Document B)
150mm
Partitions
4
C04
8
7
2
300mm
10
1200mm 1200mm
11
150mm
Door frame to satisfy BS 5234: Parts 1 and 2: 1992 - Heavy and Severe Duty (up to 60kg door)
Advice should be sought from the door manufacturer prior to the construction of these details.
Gypframe ‘C’ Studs (70 S 50, 92 S 50, 146 S 50) Gypframe 99 FC 50 Fixing Channel
Vertical stud providing acoustic and structural A versatile metal fixing channel used to support
performances designed to receive fixing of board medium weight fixtures on walls.
after installation of Gypframe RB1 Resilient Bars.
Gypframe Folded Edge Standard Floor & Ceiling Gypframe GFS1 Fixing Strap
Channels (72 FEC 50, 94 FEC 50, 148 FEC 50) Used to support horizontal board joints and within
Standard floor and ceiling channels for retaining the deflection head.
Gypframe studs at floor and ceiling junctions and
Partitions
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GFT1 Fixing T
(72 DC 60, 94 DC 60, 148 DC 60) Used to support horizontal board joints.
C04
Gypframe Extra Deep Flange Floor & Ceiling Gypframe RB1 Resilient Bar
Channels (72 EDC 80, 94 EDC 70, 148 EDC 80) Acoustically engineered channel to separate board
Floor and ceiling channels with extra deep flanges fixing from the primary frame. Fixed horizontally to
for retaining the Gypframe studs at floor and ceiling face of studs.
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum
50mm deflection).
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
Glasroc F firecase
Non-combustible glass-reinforced gypsum board.
Used to form deflection head.
Partitions
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
C04
British Gypsum Drywall Screws British Gypsum Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws
for fixing board to metal framing less than for fixing board to metal framing 0.8mm thick and
0.8mm thick ('I' studs less than 0.6mm thick). greater (‘I’ studs 0.6mm thick and greater).
British Gypsum Collated Drywall Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws for
for fixing board to metal framing less than fixing metal to metal framing 0.8mm thick and
0.8mm thick ('I' studs less than 0.6mm thick). greater ('I' studs 0.6mm thick and greater).
GypWall quiet sf
This is intended to be a basic description of how the system is built.
For detailed installation guidance refer to the British Gypsum Site Book.
Partitions
Gypframe Floor & Ceiling channels are Gypframe 'C' Studs are suitably fixed to The perimeter of the partition is then
suitably fixed to the floor and soffit. abutments and door openings. sealed with Gyproc Sealant except where
Gypframe RB1 Resilent Bars are to be
If you are using Gypframe RB1 Resilient Bars Ensure Gyproc CoreBoard to the deflection installed on that side. Where Gypframe RB1
C04
on one side of the partition only, the dimensions head takes into account the width of the
Resilient Bars are to be installed, the
will be offset by 16mm. This needs to be Gypframe RB1 Resilent Bars.
Gyproc Sealant is applied to the perimeter
considered when detailing to show locations of
partition layouts. of the first layer of board.
Gypframe 'C' Studs are fitted vertically to a Gypframe RB1 Resilient Bars are fixed Gypframe RB1 Resilient Bars are installed
friction-fit within the channel sections, to transverse to the stud framing. vertically to abutment and door studs to
form the framework. Studs are fitted to all Gypframe RB1 Resilient Bars are joined by accept perimeter fixings for the Gyproc
face the same way. nesting them together over a Gypframe plasterboard linings.
‘C’ Stud using British Gypsum Wafer Head
Drywall Screws. Gypframe RB1 Resilient
Bars are normally fixed with the base flange
on the top side, with the exception of the
uppermost bar, which is fixed base flange
down to provide board fixing at the head.
Isover Acoustic Partition Roll (APR 1200) Gyproc plasterboards are fixed with To maintain acoustic performance care
insulation is added to the partition cavity British Gypsum Drywall Screws to the must be taken to select the correct length
for optimal acoustic performance. Gypframe RB1 Resilient Bars with all joints screws to avoid them contacting or penetrating
the Gypframe 'C' Studs when fixing Gyproc
staggered. Where Gyproc Plank is required plasterboards to Gypframe RB1 Resilient Bar.
as an inner layer, it is fixed horizontally to
the Gypframe RB1 Resilient Bars at each
bar position.
GypWall staggered
Staggered stud acoustic partition system
Partitions
performance and partition width are required.
System can be skim
finished with
ThistlePro PureFinish.
Key benefits
C04
Refer to C02. S01. P49
Refer to C04. S07. P02 – GypWall quiet and C04. S08. P02 – GypWall quiet iwl
1 2 3 4
Gypframe SC1 Spacer Clips and Gypframe SC2 Spacer Clips and Gypframe SC1 Spacer Clips and Gypframe SC2 Spacer Clips and
alternate studs staggered in the alternate studs staggered in the alternate studs staggered in the alternate studs staggered in the
channel at 300mm centres. Linings and channel at 300mm centres. Linings and channel at 300mm centres. Linings and channel at 300mm centres. Linings and
insulation as in table. insulation as in table. insulation as in table. insulation as in table.
C04
Detail Partition Board Lining Max. partition Sound insulation Duty Approx. System
thickness type thickness height2 Rw (Rw + Ctr ) dB rating weight reference
mm mm1 mm mm kg/m²
25mm3 50mm3 25mm3 Any Skim
any any skim finish4 only5
finish4 finish4 only5
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
For improved durability and impact resistance, the outer layer of Gyproc SoundBloc can be replaced with a layer of 15mm Gyproc DuraLine. On single layer
linings this will improve duty rating to Severe Duty.
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
Isover Acoustic Partition Roll (APR 1200) insulation.
4
Sound insulation performance for partitions finished using jointing or plaster skim.
5
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
6
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1)
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked
with British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
GypWall staggered
For details of when
to specify fire
60 / 72 and 92 / 148 combinations resistance using BS
Refer to C02. S01. P05
Table 1b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3 4
Partitions
Gypframe SC1 Spacer Clips and Gypframe SC2 Spacer Clips and Gypframe SC1 Spacer Clips and Gypframe SC2 Spacer Clips and
alternate studs staggered in the alternate studs staggered in the alternate studs staggered in the alternate studs staggered in the
channel at 300mm centres. Linings and channel at 300mm centres. Linings and channel at 300mm centres. Linings and channel at 300mm centres. Linings and
insulation as in table. insulation as in table. insulation as in table. insulation as in table.
C04
Detail Partition Board Lining Max. Sound insulation Duty Approx. System
thickness type thickness partition Rw (Rw + Ctr ) dB rating weight reference
mm mm1 mm height2 kg/m²
25mm3 50mm3 25mm3 Any Skim
mm
any any skim finish4 only5
finish4 finish4 only5
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
For improved durability and impact resistance, the outer layer of Gyproc SoundBloc can be replaced with a layer of 15mm Gyproc DuraLine. On single layer
linings this will improve duty rating to Severe Duty.
2
Based on a limiting deflection of L/240 at 200 Pa.
3
Isover Acoustic Partition Roll (APR 1200) insulation.
4
Sound insulation performance for partitions finished using jointing or plaster skim.
5
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
6
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1)
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked
with British Gypsum.
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head
(subject to deflection criteria).
Building design
details 28-31.
two rows of staggered fixings are required, each row at 600mm
centres and each fixing 25mm in from the flange. If the floor is
Cavity barriers
uneven, a 38mm thick timber sole plate equal to the width of the
channel should be used. Stone mineral wool (by others) cut neatly to fit across the cavity
forms a suitable closure.
If the concrete or screeded floor is new, consideration should be
given to the installation of a damp-proof membrane between the Acoustic performance
floor surface and the channel or sole plate.
The partition achieves high levels of sound insulation by virtue of
the separation between the two rows of studs. It is important that
Splicing
this isolation is maintained, and that services, fixtures, etc, do not
To extend studs, overlap by 600mm (minimum). Fix together using form a bridge between the two linings.
British Gypsum Wafer Head Jack-Point Screws or steel pop rivets
Refer to C02. S01. P10 – Building acoustics.
(two to each flange), or by using the Gyproc Stud Interlocking Tool
twice to each flange.
Deflection heads
Refer to Partitions introduction C04. S01. P07 – construction
Performance details apply to fixed head constructions. Partition
detail 1.
head deflection designs may be necessary to accommodate
deflections in the supporting floor. Deflection heads may also be
Partition to structural steelwork junctions
required to the underside of roof structures subjected to positive
When designing the layout of rooms requiring separation by sound and negative pressures.
insulating walls abutting structural steelwork, consideration should
be given to the potential loss of sound insulation performance The partitions can incorporate head deflection designs to optimise
through the steelwork. sound insulation performance.
Refer to C02. S01. P10 – Building acoustics. Refer construction details 2 and 3.
GypWall staggered
Switch boxes and socket outlets can be supported from Gypframe
99 FC 50 Fixing Channel fixed horizontally between studs, or a
high performance socket box detail used where higher acoustic
performance is required.
Partitions
Independent support
C04
damper - this will determine whether it can be supported directly
from the partition or needs to be independently supported from
the structure.
Fixtures
Board finishing
Refer to C08. S01. P02 – Finishes.
Tiling
SpecSure®
All our systems are covered by SpecSure® when
using genuine British Gypsum and Saint-Gobain
Isover products.
1 2
6 9
3 10
6
5
15mm
15mm 12
1
13
4
20mm 3
11
Partitions
2
2
C04
5 3
3
9
7
6 15
25mm
4
13
25mm 14
30mm 11
2
4
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the uppermost board fixing, which should
be made into Gypframe GFS1 Fixing Strap. Continuous Gyproc FireStrip must be installed as shown in order to maintain fire performance. Gypframe Steel Angle
or approved decorative trim (by others) should be fixed to the soffit either side of the partition as shown to maintain the acoustic performance. Where ±
deflection is a requirement, Gypframe SC1 or SC2 Spacer Clips must be pre-fixed to the ‘I‘ studs to avoid the risk of disengagement once deflection is taken up.
GypWall staggered
5 6
3
7
2
1
9
5
5
4
4
Partitions
1
C04
Junction with masonry Corner
7 8
2
2
1
5
1
6
3
2
3
Guidance must be sought from the relevant approval authority e.g. Building Control to establish if a cavity barrier is required (Approved Document B)
Gypframe ‘I’ Studs (60 I 70, 92 I 90) Gypframe SC1 Spacer Clip
Enhanced strength stud that allows for partition Clip to aid positioning and securing of
height, without increasing partition width designed Gypframe 60 I 70 ‘I’ Studs.
to receive fixing of board to one side only.
Gypframe ‘C’ Studs (70 S 50, 146 S 50) Gypframe SC2 Spacer Clip
Vertical stud providing acoustic and structural Clip to aid positioning and securing of
performances designed to receive fixing of board. Gypframe 92 I 90 ‘I’ Studs.
Partitions
Gypframe Folded Edge Standard Floor & Ceiling Gypframe 99 FC 50 Fixing Channel
Channels (72 FEC 50, 148 FEC 50) A versatile metal fixing channel used to support
C04
Standard floor and ceiling channels for retaining the medium weight fixtures on walls.
Gypframe studs at floor and ceiling junctions and
around openings to heights not exceeding 4200mm,
whilst also containing Gypframe Spacer Clips.
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GFS1 Fixing Strap
(72 DC 60, 148 DC 60) Used to support horizontal board joints, and within
Floor and ceiling channels with deep flanges for deflection heads.
retaining the Gypframe studs at floor and ceiling
junctions for partitions 4200mm to 8000mm high.
Also used around openings and in deflection heads Gypframe GFT1 Fixing T
(maximum 30mm deflection), whilst also containing Used to support horizontal board joints.
Gypframe Spacer Clips.
Gypframe Extra Deep Flange Floor & Ceiling Gypframe GA5 Internal Fixing Angle
Channels (72 EDC 80, 148 EDC 80) Steel angle providing framing stability and
Floor and ceiling channels with extra deep flanges board support.
for retaining the Gypframe studs at floor and ceiling
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum Gypframe GA6 Splayed Angle
50mm deflection), whilst also containing Gypframe Steel angle providing framing stability and
Spacer Clips. board support.
GypWall staggered
Board products ( Refer to C10. S03. P02 for details)
Partitions
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
C04
Fixing products ( Refer to C10. S04. P02 for details)
British Gypsum Jack-Point Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws for
for fixing board to metal framing 0.8mm thick and fixing metal to metal framing 0.8mm thick and
greater (‘I’ studs 0.6mm thick and greater). greater (‘I’ studs 0.6mm thick and greater).
Gyproc FireStrip
A soft extruded linear intumescent gap sealer
to maintain fire resistance located directly to
the underside of the soffit when forming a
deflection head.
GypWall staggered
This is intended to be a basic description of how the system is built.
For detailed installation guidance refer to the British Gypsum Site Book.
Partitions
Gypframe Floor & Ceiling channels are Gypframe 'C' Studs are suitably fixed at The perimeter of the partition is then sealed
suitably fixed to the floor and soffit. abutments and door openings. on both sides with Gyproc Sealant.
C04
Gypframe SC1 or SC2 Spacer Clips are The studs are then friction fitted into Door openings are constructed to the Heavy
inserted to the top and bottom of the the Gypframe Channels, alternating the and Severe Duty rating door detail.
Gypframe 60 I 70 or 92 I 90 'I' Studs direction of the clip to create a staggered
respectively. stud framework.
M&E services can be located within the Isover Acoustic Partition Roll (APR 1200) is Gyproc SoundBloc plasterboards are then
partition cavity. Care should be taken to added to the partition cavity. screw fixed to alternate Gypframe ‘I’ Studs
prevent bridging, for example socket boxes and other framing members with
making contact with the opposing studs. British Gypsum Jack-Point Screws.
Additional information
For full installation details, refer to the
British Gypsum Site Book, available to
download from british-gypsum.com
GypWall quiet
Twin frame high performance acoustic wall system
Partitions
Key benefits
— GypWall quiet can provide up to an estimated System can be skim
finished with
90 minutes fire protection to structural steel ThistlePro PureFinish.
C04
Refer to C02. S01. P49
enclosed within its cavity, whilst maintaining
the room-to-room acoustic performance
— Twin-frame design allows services and
structural steel to easily be accommodated Refer to C01. S01. P07
GypWall quiet iwl provides greater levels of acoustic insulation, through the use of a totally isolated
twin stud frameworks.
Refer to C04. S08. P02 – GypWall quiet iwl
1 2 3
Two Gypframe 48 S 50 ‘C’ Stud frameworks braced at Two Gypframe 48 S 50 ‘C’ Stud frameworks braced Two Gypframe 48 S 50 ‘C’ Stud frameworks braced at max.
Partitions
max. 1200mm centres. Studs at 600mm centres. at max. 1200mm centres. Studs at 600mm centres. 1200mm centres. Studs at 600mm centres.
Isover Acoustic Partition Roll (APR 1200) in the cavity Isover Acoustic Slab in the cavity (cavity width 190mm). Isover Acoustic Partition Roll (APR 1200) in the cavity
(cavity width 137mm). Linings and insulation as in table. Linings and insulation as in table. (cavity width 237mm). Linings and insulation as in table.
C04
Detail Partition Board type Lining Max. Insulation Sound insulation Duty Approx. System reference
thickness mm thickness partition thickness Rw (Rw + Ctr ) dB rating weight
mm mm height1 mm kg/m²
mm Any2 Skim3 Any2 Skim3
finish only finish only
Gyproc Plank + 1 x 19 +
1 200 6200 25 61 (47) - Severe 55 A216001 -
Gyproc SoundBloc 1 x 12.5
Gyproc Plank + 1 x 19 +
1 200 5000 25 61 (47) - Severe 55 A216001 -
Gyproc SoundBloc 1 x 12.5
Gyproc Plank + 1 x 19 +
3 300 5000 25 62 (52)4 - Severe 55 A216002 -
Gyproc SoundBloc 1 x 12.5
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
2
Sound insulation performance for partitions finished using jointing or plaster skim.
3
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
4
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1).
For heights above 4200mm Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection criteria).
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
GypWall quiet
For details of when
to specify fire
48mm Gypframe 'C' Studs with cross braces resistance using BS
Refer to C02. S01. P05
Table 1b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3
Two Gypframe 48 S 50 ‘C’ Stud frameworks braced at Two Gypframe 48 S 50 ‘C’ Stud frameworks braced Two Gypframe 48 S 50 ‘C’ Stud frameworks braced at
Partitions
max. 1200mm centres. Studs at 600mm centres. at max. 1200mm centres. Studs at 600mm centres. max. 1200mm centres. Studs at 600mm centres.
Isover Acoustic Partition Roll (APR 1200) in the cavity Isover Acoustic Slab in the cavity (cavity width 190mm). Isover Acoustic Partition Roll (APR 1200) in the cavity
(cavity width 137mm). Linings and insulation as in table. Linings and insulation as in table. (cavity width 237mm). Linings and insulation as in table.
Detail Partition Board type Lining Max. Insulation Sound insulation Duty Approx. System reference
C04
thickness mm thickness partition thickness Rw (Rw + Ctr ) dB rating weight
mm mm height2 mm kg/m²
mm Any3 Skim4 Any3 Skim4
finish only finish only
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
To achieve an estimated 120 minutes fire resistance, substitute 2 x 15mm Gyproc SoundBloc for 2 x 15mm Gyproc DuraLine.
2
Based on limiting deflection of L/240 at 200 Pa.
3
Sound insulation performance for partitions finished using jointing or plaster skim.
4
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
5
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1).
For heights above 4200mm Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection criteria).
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
1
Estimated fire protection to structural steelwork within this partition cavity. Based on metal stud thermocouple data.
2
For improved durability and impact resistance, the outer layer of Gyproc FireLine or Gyproc SoundBloc can be replaced with a layer of 15mm Gyproc DuraLine.
3
Based on four-sided exposure, with no vertical joints aligning with the column, and boards not fixed to the column to maintain air space (10mm for BS or
C04
GypWall quiet
Building design Services
GypWall quiet comprises twin row Gypframe 'C' Studs at 600mm Penetrations
centres within twin row Gypframe Floor & Ceiling Channels. For Penetrations of fire-resistant or sound-insulating constructions
heights up to 2400mm each pair of studs must be cross braced at for services need careful consideration to ensure that the
mid-height. Where multiple braces are required the braces must be performance of the element is not downgraded. Consideration also
located at 1200mm vertical centres staggered by 600mm. needs to be given to the services themselves so they do not act as
the mechanism of fire spread or sound transmission.
Planning — key factors
Refer to C02. S01. P32 – Service installations.
The position of services and heavy fixtures should be
pre-determined and their installation planned into the frame Electrical
erection stage. All penetrations will need to be adequately stopped The installation of electrical services should be carried out in
for fire and acoustics. accordance with BS 7671. The cut-outs in the studs can be used for
Partitions
routing electrical and other small services (Partitions introduction
Fixing floor and ceiling channels C04. S01. P07 – construction detail 2). Switch boxes and socket
Gypframe Floor & Ceiling Channels must be securely fixed with a outlets can be supported from Gypframe 99 FC 50 Fixing Channel
row of fixings at 600mm maximum centres. If the floor is uneven, fixed horizontally between studs, or a high performance socket box
detail used where higher acoustic performance is required.
C04
a 38mm thick timber sole plate equal to the width of the channel
should be used.
Independent support
If the concrete or screeded floor is new, consideration should be When designing for the installation of services such as fire
given to the installation of a damp-proof membrane between the dampers and associated ductwork through a GypWall partition,
floor surface and the channel or sole plate. consideration should be given to the size and weight of the
damper - this will determine whether it can be supported directly
Splicing from the partition or needs to be independently supported from
the structure.
To extend studs, overlap by 600mm (minimum). Fix together using
British Gypsum Wafer Head Drywall Screws or steel pop rivets (two Refer to Partitions introduction C04. S01. P17 – construction
to each flange), or by using the Gyproc Stud Interlocking Tool twice details 29-31.
to each flange.
Fixtures
Refer to Partitions introduction C04. S01. P07 – construction
detail 1. Lightweight fixtures can be made directly to the partitions. Medium
weight fixtures can be made to Gypframe 99 FC 50 Fixing Channel.
Partition to structural steelwork junctions Heavyweight fixtures (to BS 5234), such as wash basins and wall
cupboards, can be fixed using plywood secured with Gypframe
When designing the layout of rooms requiring separation by sound
Service Support Plates.
insulating walls abutting structural steelwork, consideration should
be given to the potential loss of sound insulation performance Refer to C02. S01. P33 – Service installations.
through the steelwork.
Board finishing
Refer to C02. S01. P10 – Building acoustics.
Refer to C08. S01. P02 – Finishes.
Door openings
Tiling
Any openings will require careful detailing if the acoustic
performance is to be maintained. Specialist heavy acoustic door sets Tiles can be applied to the surface of lightweight partition systems.
may require additional support. Refer to C08. S04. P02 – Tiling
Cavity barriers
Stone mineral wool cut neatly to fit across the cavity forms a
suitable closure. SpecSure®
Deflection heads All our systems are covered by SpecSure® when
Partition head deflection designs may be necessary to using genuine British Gypsum and Saint-Gobain
accommodate deflections in the supporting floor. Isover products.
Deflection heads may also be required to the underside of roof
structures subjected to positive and negative pressures.
Special detailing to minimise the loss of acoustic performance:
1 2
6
10
11
4 6
15mm
15mm
1 13
20mm
12
Partitions
5 9
2 5
C04
6
4
1 Gyproc plasterboard 7 Bulk fill with Gyproc jointing materials (where gap exceeds 5mm)
2 Gypframe ‘C’ Stud 8 Skirting
3 Gypframe 99 FC 50 Fixing Channel (at 1200mm vertical centres staggered 9 Gypframe Deep Flange Floor & Ceiling Channel suitable fixed through
fire-stop to structure
by 600mm centres of multiple braces)
10 Gyproc FireStrip
4 Gypframe Folded Edge Standard Floor & Ceiling Channel
11 Gyproc CoreBoard or Glasroc F firecase
5 Isover insulation suitably supported at head
12 Gypframe GFS1 Fixing Strap
6 Gyproc Sealant
13 Gypframe Steel Angle
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing,
which should be made into Gypframe GFS1 Fixing Strap (or stud nogging in C04. S01. P11 – construction detail 16). Continuous Gyproc FireStrip must be
installed as shown to maintain fire performance. Where there is a need for a deflection head in a 90 minute wall, the 120 minute solution can be used (refer to
Partitions introduction C04. S01. P11 – construction detail 16) or alternatively, please contact the British Gypsum Technical Advice Centre for further guidance.
3 4
2 2
3 3
1 1
Partitions
4 4
C04
5
'T' Junction Alternative ‘T’ junction with Gypframe GA5 Internal Fixing Angle
5 6
2 2
3 3
1 1
4 4
Guidance must be sought from the relevant approval authority e.g. Building Control to establish if a cavity barrier is required (Approved Document B)
Gypframe Folded Edge Standard Floor & Ceiling Gypframe GA5 Internal Fixing Angle
Channels (50 FEC 50) Steel angle providing framing stability and
Standard floor and ceiling channels for retaining the board support.
Partitions
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GA6 Splayed Angle
C04
Gypframe Extra Deep Flange Floor & Ceiling Gypframe Service Support Plate
Channels (50 EDC 70) For installation of 18mm plywood within
Floor and ceiling channels with extra deep flanges a partition cavity to support medium to
for retaining the Gypframe studs at floor and ceiling heavyweight fixtures.
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum
50mm deflection).
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
British Gypsum Drywall Screws British Gypsum Wafer Head Drywall Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws
for fixing board to metal framing less than for fixing metal to metal framing less than
0.8mm thick. 0.8mm thick.
Partitions
Plasterboard accessories ( Refer to C10. S05. P02 for details)
C04
Jointing compounds, ready mixes and adhesives A soft extruded linear intumescent gap sealer
for reinforcement and finishing of board joints. to maintain fire resistance located directly to
Primers and sealers for treatment of boards for the underside of the soffit when forming a
pre-decoration. deflection head.
Plaster accessories
Designed for the reinforcement and finishing of
board joints before plaster skimming.
Partitions
GypWall quiet
This is intended to be a basic description of how the system is built.
For detailed installation guidance refer to the British Gypsum Site Book.
Partitions
Gypframe Floor & Ceiling Channels are Gypframe ‘C’ Studs are suitably fixed to The perimeter of each frame is then sealed
suitably fixed to the floor and soffit in abutments in two rows. with Gyproc Sealant.
two rows.
C04
Gypframe 'C' Studs are then friction fitted The two frameworks are braced with Mechanical and electrical services can be
into the Gypframe Floor & Ceiling Channels Gypframe 99 FC 50 Fixing Channel located within the partition cavity.
at the required centres. Door openings are attached to the Gypframe 'C' Studs with
constructed to the Heavy and Severe Duty British Gypsum Wafer Head Drywall Screws,
Rating door detail. two screws per junction.
Isover insulation is added to the partition Gyproc plasterboards are then fixed to the
cavity for increased acoustic performance. Gypframe framework with British Gypsum
Drywall Screws.
Additional information
For full installation details, refer to the
British Gypsum Site Book, available to
download from british-gypsum.com
Partitions
or premium developments.
System can be skim
finished with
ThistlePro PureFinish.
Key benefits
C04
Refer to C02. S01. P49
1 2 3
Partitions
Two layers of board fixed to the outside Two layers of board fixed to the outside Two layers of board fixed to the outside
faces of two Gypframe 48 I 50 ‘I’ Stud faces of two Gypframe 60 I 70 ‘I’ Stud faces of two Gypframe 60 I 50 ‘I’ Stud
frameworks with studs at 600mm frameworks with studs at 600mm frameworks with studs at 600mm
C04
centres. 50mm Isover Acoustic Partition centres. 100mm Isover Acoustic centres. 100mm Isover Acoustic
Roll (APR 1200) in the cavity (cavity Partition Roll (APR 1200) in the cavity Partition Roll (APR 1200) in the cavity
width 140mm). Linings as in table. (cavity width 190mm). (cavity width 190mm).
Linings as in table. Linings as in table.
Detail Partition Board type Lining Max. partition Sound insulation Duty rating Approx. System
thickness thickness height2 Rw (Rw + Ctr )2 weight reference
mm mm mm dB kg/m²
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is more onerous.
2
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1)
3
RD = Robust Detail E-WS-2 - approved Robust Detail solution designed to achieve minimum DnT,w + Ctr 45dB. Minimum 60mm Gypframe ‘I’ Studs required.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the company’s fixing recommendations are strictly observed. Any variation in the specification should be checked with
British Gypsum.
1 2 3
Partitions
Two layers of board fixed to the outside Two layers of board fixed to the outside Two layers of board fixed to the outside
faces of two Gypframe 48 I 50 ‘I’ Stud faces of two Gypframe 60 I 70 ‘I’ Stud faces of two Gypframe 60 I 50 ‘I’ Stud
frameworks with studs at 600mm frameworks with studs at 600mm frameworks with studs at 600mm
C04
centres. 50mm Isover Acoustic Partition centres. 100mm Isover Acoustic centres. 100mm Isover Acoustic
Roll (APR 1200) in the cavity (cavity Partition Roll (APR 1200) in the cavity Partition Roll (APR 1200) in the cavity
width 140mm). Linings as in table. (cavity width 190mm). (cavity width 190mm).
Linings as in table. Linings as in table.
Detail Partition Board type Lining Max. partition Sound insulation Duty rating Approx. System
thickness thickness height1 Rw (Rw + Ctr )2 weight reference
mm mm mm dB kg/m²
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on limiting deflection of L/240 at 200 Pa.
2
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1)
3
RD = Robust Detail E-WS-2 - approved Robust Detail solution designed to achieve minimum DnT,w + Ctr 45dB. Minimum 60mm Gypframe ‘I’ Studs required.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the company’s fixing recommendations are strictly observed. Any variation in the specification should be checked with
British Gypsum.
1
Estimated fire protection to structural steelwork within the partition cavity. Based on metal stud thermocouple data.
2
For improved and durability impact resistance, the outer layer of Gyproc FireLine or Gyproc SoundBloc can be replaced with a layer of 15mm Gyproc DuraLine.
3
Based on four-sided exposure, with no vertical joints aligning with the column, and boards not fixed to the column to maintain air space
Partitions
Stud type1 2 x 12.5mm boards maximum heights 2 x 15mm boards maximum heights
48 I 50 2700 2800
60 I 50 3000 3300
60 I 70 3600 3900
70 I 70 42002 43002
92 I 90 57002 /50002, 3 58002 /50002, 3
146 I 80 7200 /5000
2 2, 3
75002 /50002, 3
1
Based on a limiting deflection of L/240 at 200 Pa. Greater heights can be achieved by reducing stud centres for BS 476: Part 22: 1987. Contact the
Technical Advice Centre for further advice.
2
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection criteria).
3
For BS EN 1364-1, the heights are limited to 5000mm maximum fire state field of application.
GypWall quiet iwl comprises a twin frame of Gypframe 'I' Studs at Any openings will require careful detailing if the acoustic
600mm centres within a twin row of Gypframe Floor & Ceiling performance is to be maintained. Specialist heavy acoustic door sets
Channels. may require additional support.
Partitions
Refer to Partitions introduction C04. S01. P16 – construction
Partition to structural steelwork junctions detail 28-31
C04
be given to the potential loss of sound insulation performance Stone mineral wool (by others) cut neatly to fit across the cavity
through the steelwork. forms a suitable closure.
Deflection heads
Refer to C02. S01. P10 – Building acoustics. — Ensure that the quilt covers the whole
wall area without gaps
For deflection head design: — Make sure the quilt is compressed by
Partitions
twin frames
Refer to construction detail 7 within this section.
— Make sure there is no connection
Fixtures between the two leaves
Lightweight fixtures can be made directly to the partition linings. — Stagger joints in wall linings to avoid
C04
Board finishing
Refer to C08. S01. P02 – Finishes.
Tiling
SpecSure®
Tiles can be applied to the surface of lightweight partition systems.
Refer to C08. S04. P02 – Tiling All our systems are covered by SpecSure® when
using genuine British Gypsum and Saint-Gobain
Robust detail E-WS-2 Isover products.
2 16
13
9
1
14
15
Partitions
5
2
6
7 13
C04
8
Base on concrete floor with screed 15mm deflection head - up to 60 minutes fire resistance
3 4
10
1
11
2
12
3
13 13
3 1
9
9
Guidance must be sought from the relevant approval authority e.g. Building Control to establish if a cavity barrier is required (Approved Document B)
5 6
1
1
4
4
2
Partitions
11
2
11
C04
12
10
11
25mm
7
25mm
25mm 8
5
9
6
2
1
4
Gypframe ‘I’ Studs (48 I 50, 60 I 50, 60 I 70, 70 I 50, Gypframe 99 FC 50 Fixing Channel
70 I 70, 92 I 90, 146 I 80) A versatile metal fixing channel used to support
Enhanced strength stud that allows for increased medium weight fixtures on walls.
partition height, without increasing partition width.
Designed to receive fixing of board to one side only.
Gypframe ‘C’ Studs (48 S 50, 60 S 50, 70 S 50, Gypframe GFS1 Fixing Strap
70 S 60, 92 S 50, 92 S 60, 92 S 10, 146 S 50) Used to support horizontal board joints and within
Vertical stud. Used at abutments and openings. deflection heads.
Partitions
Gypframe Folded Edge Standard Floor & Ceiling Gypframe GA5 Internal Fixing Angle
Channels (50 FEC 50, 62 FEC 50, 72 FEC 50, 94 FEC 50, Steel angle providing framing stability and
C04
148 FEC 50) board support.
Standard floor and ceiling channels for retaining the
Gypframe studs at floor and ceiling junctions and
around openings to heights not exceeding 4200mm.
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GA6 Splayed Angle
(50 DC 60, 62 DC 60, 72 DC 60, 94 DC 60, 148 DC 60) Steel angle providing framing stability and
Floor and ceiling channels with deep flanges for board support.
retaining the Gypframe studs at floor and ceiling
junctions for partitions 4200mm to 8000mm high.
Also used around openings and in deflection heads
(maximum 30mm deflection).
Gypframe Extra Deep Flange Floor & Ceiling Gypframe Service Support Plate
Channels (50 EDC 70, 72 EDC 80, 94 EDC 70, For installation of 18mm plywood within
148 EDC 80) a partition cavity to support medium to
Floor and ceiling channels with extra deep flanges heavyweight fixtures.
for retaining the Gypframe studs at floor and ceiling
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum
50mm deflection).
Gyproc DuraLine1
Gypsum plasterboard with fire resistant additives
and a high density core for enhanced sound
insulation and impact resistance performance.
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
British Gypsum Collated Drywall Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws for
for fixing board to metal framing less than fixing metal to metal framing 0.8mm thick and
0.8mm thick ('I' studs less than 0.6mm thick). greater ('I' studs 0.6mm thick and greater).
Partitions
Gyproc AquaBead
An easy to apply, water, activated adhesive corner
bead, for reinforcing external 90°C angles in taped
and jointed plasterboard constructions.
Partitions
common backgrounds including undercoat plasters
and plasterboard. For more information refer to
C02. S01. P49.
C04
Thistle SprayFinish ThistlePro Magnetic
To provide a plaster skim finish by spray or hand To provide a plaster skim finish that provides an
application, ideal for medium to large projects. attraction to magnets used to finish a wide range
of backgrounds, including undercoat plasters and
plasterboard.
Gypframe Floor & Ceiling Channels are Gypframe ‘C’ Studs are suitably fixed to The perimeter of each frame is then sealed
suitably fixed to the floor and soffit in abutments in two rows. with Gyproc Sealant.
two rows.
C04
Gypframe 'I' Studs are then friction fitted Door openings are constructed to the Heavy M&E services can be located within the
into the Gypframe Channels at the required and Severe Door Duty Rating detail. partition cavity.
centres.
Isover Acoustic Partition Roll (APR 1200) is Gyproc plasterboards are then fixed to the
added to the partition cavity. Gypframe framework with British Gypsum
Drywall Screws and British Gypsum
Jack-Point Screws.
Additional information
For full installation details, refer to the
British Gypsum Site Book, available to
download from british-gypsum.com
GypWall audio
The ultimate sound insulating wall system
Partitions
Key benefits System can be skim
finished with
ThistlePro PureFinish.
— Optimal sound insulation performance is
C04
Refer to C02. S01. P49
4 5 6 7
Partitions
C04
Detail Partition Board type1 Lining Max. partition height2 mmIsover Sound Duty Approx. System
thickness thickness Fixing Channels GAB3 Acoustic Cladding insulation rating weight reference
mm mm braces at braces at Roll 40 Rw kg/m²
3600mm centres 3300mm centres mm (Rw + Ctr )
dB
1 300 Gyproc SoundBloc 2 x 12.5 8000 8000 100 67 (56) Severe 47 A326001
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
For improved durability and impact resistance, the outer layer of Gyproc FireLine or Gyproc SoundBloc can be replaced with a layer of 15mm Gyproc DuraLine.
2
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection
criteria). For heights over 8000mm, Gypframe Extra Deep Flange Floor and Ceiling Channel should be used at base and head. The maximum heights quoted are
limited by the fire state field of application or by limiting deflection L/240 at 200 Pa, whichever is more onerous.
3
Minimum density 62kg/m³.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Each pair of studs must be braced at least once, staggered to the adjacent pairs, irrespective of the partition height or specified bracing centres.
4 5 6 7
Partitions
C04
Detail Partition Board type1 Lining Max. partition height2 mm Isover Sound Duty Approx. System
thickness thickness Fixing Channels GAB3 Acoustic Cladding insulation rating weight reference
mm mm braces at braces at Roll 40 Rw kg/m²
3600mm centres 3300mm centres mm (Rw + Ctr )
dB
L/2403 L/1253 L/2403 L/1253
mm mm mm mm
1 300 Gyproc SoundBloc 2 x 12.5 8000 9500 8000 10000 100 67 (56) Severe 47 A326001
1 300 Gyproc SoundBloc 2 x 15 8000 9500 8000 10000 100 69 (60) Severe 55 A326002
Gyproc Plank + 1 x 19 +
2 300 8000 9500 8000 10000 100 70 (60) Severe 58 A326003
Gyproc SoundBloc 1 x 12.5
3 550 Gyproc SoundBloc 3 x 15 9000 11500 9500 11500 100 75 (69) Severe 80 A326016
4 550 Gyproc SoundBloc 3 x 15 9000 11500 9500 11500 2 x 100 76 (68) Severe 80 A326013
4 x 100 +
5 600 Gyproc SoundBloc 3 x 15 9000 11500 9500 11500 2x 100 stone 77 (69) Severe 80 A326017
mineral wool4
3 x 100 +
6 600 Gyproc SoundBloc 3 x 15 9000 11500 9500 11500 2 x 100 stone 77 (69) Severe 80 A326018
mineral wool4
3 x 100 +
7 800 Gyproc SoundBloc 3 x 15 9500 11500 9000 11500 2 x 100 stone 80 (71) Severe 80 A326019
mineral wool4
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
For improved durability and impact resistance, the outer layer of Gyproc FireLine or Gyproc SoundBloc can be replaced with a layer of 15mm Gyproc DuraLine.
2
For heights between 4200mm and 8000mm, Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection
criteria). For heights over 8000mm, Gypframe Extra Deep Flange Floor and Ceiling Channel should be used at base and head.
3
Refer to deflection criteria, in design section.
4
Minimum density 62kg/m3.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and filled,
or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover components
are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with British Gypsum.
Each pair of studs must be braced at least once, staggered to the adjacent pairs, irrespective of the partition height or specified bracing centres.
1
Estimated fire protection to structural steelwork within the partition cavity. Based on metal stud thermocouple data.
2
For improved durability and impact resistance, the outer layer of Gyproc FireLine or Gyproc SoundBloc can be replaced with a layer of 15mm Gyproc DuraLine.
3
Based on four-sided exposure, with no vertical joints aligning with the column, and boards not fixed to the column to maintain air space
(10mm for BS or 50mm for EN).
C04
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
For improved durability and impact resistance, the outer layer of Gyproc FireLine or Gyproc SoundBloc can be replaced with a layer of 15mm Gyproc DuraLine.
2
Minimum density 62kg/m3.
GypWall audio
Building design Control joints
GypWall audio comprises braced twin rows of Gypframe 92 S 10 'C' Control joints may be required in the partition to relieve stresses
Studs installed at 600mm centres within Gypframe Floor & Ceiling induced by expansion and contraction of the structure (refer to
Channels. Partitions introduction C04. S01. P10 – construction detail 12). They
should coincide with movement joints within the surrounding structure.
Planning – key factors
Deflection heads
The position of services and heavy fixtures should be
pre-determined and their installation planned into the frame Partition head deflection designs may be necessary to
erection stage. accommodate deflections in the supporting floor. Deflection heads
may also be required to the underside of roof structures subjected
to positive and negative pressures.
Designers and site management should give full consideration to
Partitions
the potential exposure of GypWall audio to differential pressures, Refer to construction details 4 and 5 within this section.
such as wind loadings during installation.
Deflection criteria
Fixing floor and ceiling channels
Our normal recommendation is to build to a deflection criteria
Gypframe Floor & Ceiling Channels must be securely fixed with two L/240 at 200 Pa, however it is common for this system to be built
C04
rows of staggered fixings, each row at 600mm centres and each to L/125 at 200 Pa (BS 476: Part 22: 1987 fire resistance only).
fixing 25mm in from the flange. If the floor is uneven, a 38mm thick
timber sole plate equal to the width of the channel should be used. Partitions built to a maximum height based on L/125 at 200 Pa
If the concrete or screeded floor is new, consideration should be will exhibit greater deflection compared to partitions built to
given to the installation of a damp-proof membrane between the a maximum height based on L/240 at 200 Pa. Partitions with
floor surface and the channel or sole plate. deflection characteristics outside the standard L/240 criteria
will exhibit more flex during installation and in general use,
Splicing and therefore we recommend you verify the acceptibility of the
deflections with the relevant interested parties before
To extend studs, overlap by 600mm (minimum). Fix together using
specifying / installing partitions based on L/125 criteria.
British Gypsum Wafer Head Drywall Screws or steel pop rivets (two
to each flange), or by using the Gyproc Stud Interlocking Tool twice
Cross bracing
to each flange.
Laboratory tests were carried out on walls without bracing. The
Refer to Partitions introduction C04. S01. P07 – construction
results, however, are a realistic representation of site conditions in
detail 1.
which Gypframe 99 FC 50 Fixing Channel cross-braces are fitted
at the recommended 3600mm maximum centres, provided that
Partition to structural steelwork junctions
appropriate measures are taken on site to eliminate flanking sound
When designing the layout of rooms requiring separation by sound transmission. All braces must be staggered by half distance of the
insulating walls abutting structural steelwork, consideration should brace centres. Test evidence is provided by British Gypsum Report
be given to the potential loss of sound insulation performance ATR 1299, where a site test on a large multi-screen cinema wall
through the steelwork. achieved comparable performance to the equivalent specification
Refer to C02. S01. P10 – Building acoustics. tested in the laboratory without bracing.
Door openings Acoustic designers may prefer the option of a resilient acoustic
brace. The Gypframe GAB3 Acoustic Brace has been shown in tests
Any openings will require careful detailing if the acoustic
not to downgrade acoustic performance in laboratory conditions.
performance is to be maintained. Specialist heavy acoustic doorsets
However, as a result of the mechanics of this brace fixing centres
may require additional support.
should be reduced from 3600mm to 3300mm, staggered by half
distance of brace centres. Maximum recommended wall heights
Framing surround for openings
will vary.
Where services such as horizontal ducts, fire dampers and access
Refer to tables 1a and 1b within this section.
panels are required to penetrate the wall, their position should be
pre-determined in order that a framed opening can be provided.
The minimum and maximum wall widths for which
Refer to C04. S01. P16 – Service installations. Gypframe GAB3 Acoustic Brace can be used without modification
are 300mm and 600mm respectively. Likewise, the minimum and
Cavity barriers maximum cavity width between the two stud frames for which
Stone mineral wool cut neatly to fit across the cavity forms Gypframe GAB3 Acoustic Brace can be used without modification
a suitable closure. are 100mm and 400mm respectively.
The Gypframe GAB3 Acoustic Brace may be cut using a hacksaw Fixtures
or powertool. If required, the Gypframe GAB Acoustic Brace can be
Lightweight fixtures can be made directly to the partition linings.
extended by fixing a short length of Gypframe 92 S 10 ‘C’ Stud to
Medium weight fixtures can be made to Gypframe 99 FC 50
one brace with four British Gypsum Wafer Head Jack-Point Screws
Fixing Channel. Heavyweight fixtures (to BS 5234) such as wash
(ensure a 75mm minimum overlap to each stud with no contact
basins and wall cupboards, can be fixed using plywood secured by
to board lining). The short length of stud should also be fixed to
Gypframe Service Support Plates.
the vertical studs with four British Gypsum Wafer Head Jack-Point
Screws. Refer to C02. S01. P33 – Service installations.
Care should be taken to ensure Gypframe GAB3 Acoustic Braces Access for maintenance
are correctly and fully engaged and not mis-aligned. Where
Gyproc Profilex Access Panels are available to provide access for
partition heights are specified based on lateral restraint from a
maintenance. Access panels must be fully compatible with drywall
Partitions
bracing centres.
Refer to C08. S01. P02 – Finishes
Board fixing
Tiling
In common with building practice, the twin frame wall should be
Tiles can be applied to the surface of lightweight partition systems.
boarded progressively from each side of the partition. This will help
prevent differential loadings on the framework. Refer to C08. S04. P02 – Tiling
Services
Penetrations
Penetrations of fire-resistant or sound-insulating constructions SpecSure®
for services need careful consideration to ensure that the
performance of the element is not downgraded. Consideration also All our systems are covered by SpecSure® when
needs to be given to the services themselves so they do not act as using genuine British Gypsum and Saint-Gobain
the mechanism of fire spread or sound transmission. Isover products.
Electrical
The installation of electrical services should be carried out in
accordance with BS 7671. The cut-outs in the studs can be used
for routing electrical and other small services (refer to Partitions
introduction C04. S01. P07 – construction detail 2). Switch boxes
and socket outlets can be supported from Gypframe 99 FC 50 Fixing
Channel fixed horizontally between studs, or a high performance
socket box detail used where higher acoustic performance is
required.
Independent support
When designing for the installation of services such as fire
dampers and associated ductwork through a GypWall partition,
consideration should be given to the size and weight of the
damper - this will determine whether it can be supported directly
from the partition or needs to be independently supported from
the structure.
GypWall audio
1
3
600mm
2
Partitions
5
C04
Splicing and acoustic bracing
3
600mm
3 4 11
9
4 10
6 6
15mm
15mm 13
20mm
1
12
Partitions
5
1
2
C04
5
14
10
6
25mm
13
25mm
15
12
30mm
7 2
4
6
1 Gyproc plasterboard 9 Gypframe Deep Flange Floor & Ceiling Channel suitably fixed through
fire-stop to structure
2 Gypframe 92 S 10 ‘C’ Stud
10 Gyproc FireStrip
3 Gypframe 99 FC 50 Fixing Channel
11 Gyproc CoreBoard or Glasroc F firecase
4 Gypframe Floor & Ceiling Channel
12 Gypframe GFS1 Fixing Strap
5 Isover Cladding Roll 40
13 Gypframe GA4 Steel Angle
6 Gyproc Sealant
14 Timber head plate suitably fixed to structure
7 Bulk fill with Gyproc jointing materials (where gap exceeds 5mm)
15 Gypframe Extra Deep Flange Floor & Ceiling Channel suitably fixed to
8 Skirting
timber head plate
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing,
which should be made into Gypframe GFS1 Fixing Strap. Continuous Gyproc FireStrip must be installed as shown to maintain fire performance.
GypWall audio
6 7
2 2
3 3
1 1
Partitions
6
C04
4 4
‘T’ junction Alternative ‘T’ junction using GA5 Internal Fixing Angle
8 9
2 2
3 3
1 1
Guidance must be sought from the relevant approval authority e.g. Building Control to establish if a cavity barrier is required (Approved Document B)
Gypframe Folded Edge Standard Floor & Ceiling Gypframe GFS1 Fixing Strap
Channels 94 FEC 50 Used to support horizontal board joints and within
Standard floor and ceiling channels for retaining the deflection heads.
Partitions
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GA5 Internal Fixing Angle
94 DC 60 Steel angle providing framing stability and
C04
Floor and ceiling channels with deep flanges for board support.
retaining the Gypframe studs at floor and ceiling
junctions for partitions 4200mm to 8000mm high.
Also used around openings and in deflection heads
(maximum 30mm deflection).
Gypframe Extra Deep Flange Floor & Ceiling Gypframe GA6 Splayed Angle
Channels 94 EDC 70 Steel angle providing framing stability and
Floor and ceiling channels with extra deep flanges board support.
for retaining the Gypframe studs at floor and ceiling
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum
50mm deflection).
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
GypWall audio
Board products ( Refer to C10. S03. P02 for details)
Gyproc CoreBoard
Gypsum plasterboard with fire and moisture
resistant additives used to form deflection head.
British Gypsum Jack-Point Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws
Partitions
for fixing board to metal framing 0.8mm thick and for fixing metal to metal framing 0.8mm thick
greater (‘I’ studs 0.6mm thick and greater). and greater.
C04
Gyproc Jointing Materials Gyproc Control Joint
Jointing compounds, ready mixes and adhesives To accommodate structural movement of up
for reinforcement and finishing of board joints. to 7mm.
Primers and sealers for treatment of boards for
pre-decoration.
low frequency.
C04
GypWall audio
This is intended to be a basic description of how the system is built.
For detailed installation guidance refer to the British Gypsum Site Book.
Partitions
Gypframe Floor & Ceiling Channels are suitably Gypframe 92 S 10 'C' Studs are fixed at Gyproc Sealant is applied to the frame
fixed to the floor and soffit in two rows. abutments and door openings in two rows. perimeters to seal airpaths.
C04
Gypframe 92 S 10 'C' Studs are then friction The Gypframe 92 S 10 'C' Studs are then or staggered Gypframe 99 FC 50 Fixing
fitted into the Gypframe Channels at the braced together in pairs with either Channels.
required centres, and door openings are staggered Gypframe GAB3 Acoustic Braces,
constructed to the Heavy and Severe Duty
Rating door detail.
M&E services can be located within the Insulation is added to the partition cavity. Gyproc plasterboards are then fixed to
partition cavity. the Gypframe framework with
British Gypsum Jack-Point Screws.
Additional information
For full installation details, refer to the
British Gypsum Site Book, available to
download from british-gypsum.com
Partitions
(England and Wales) and Technical Handbook
Section 5 (Scotland). There are two build System can be skim
finished with
ThistlePro PureFinish.
solutions: 450mm stud framing without
C04
Refer to C02. S01. P49
Key benefits
— GypWall rapid dB Plus combines high levels of
performance and a narrow footprint, compared
with timber and masonry alternatives
— Speed and efficiency of installation are achieved
through the use of lightweight Gypframe stud
framing and single layer Gyproc SoundBloc rapid
linings, with a special width and thickness
configuration
— Services are easily accommodated within the
partition; through the pre-finished service
cut-outs within Gypframe AcouStuds
It can be decorated with standard emulsion paint or combined with specialist paint finishes,
including blackboard and whiteboard.
Refer to Products C10. S06. P06 – Plasters and plaster accessories
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 43 AS 50 AcouStuds at 900mm centres. Gypframe 43 AS 50 AcouStuds at 450mm centres. Gypframe 70 AS 50 AcouStuds at 450mm centres.
43mm Gypframe GWR2 mid-height nogging. Linings as in table. Linings as in table.
Linings as in table.
Partitions
4 5 6
C04
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 43 AS 50 AcouStuds at 900mm centres. Gypframe 43 AS 50 AcouStuds at 450mm centres. Gypframe 70 AS 50 AcouStuds at 450mm centres.
43mm Gypframe GWR2 mid-height nogging. 25mm Isover Acoustic Partition Roll (APR 1200). 25mm Isover Acoustic Partition Roll (APR 1200).
25mm Isover Acoustic Partition Roll (APR 1200). Linings as in table. Linings as in table.
Linings as in table.
Detail Partition Board type1 Lining Maximum partition Sound insulation Duty rating Approx. System
thickness thickness height RwdB weight reference
mm mm mm kg/m²
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
1 2 3
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 43 AS 50 AcouStuds at 900mm centres. Gypframe 43 AS 50 AcouStuds at 450mm centres. Gypframe 70 AS 50 AcouStuds at 450mm centres.
43mm Gypframe GWR2 mid-height nogging. Linings as in table. Linings as in table.
Linings as in table.
Partitions
4 5 6
C04
One layer of board each side of One layer of board each side of One layer of board each side of
Gypframe 43 AS 50 AcouStuds at 900mm centres. Gypframe 43 AS 50 AcouStuds at 450mm centres. Gypframe 70 AS 50 AcouStuds at 450mm centres.
43mm Gypframe GWR2 mid-height nogging. 25mm Isover Acoustic Partition Roll (APR 1200). 25mm Isover Acoustic Partition Roll (APR 1200).
25mm Isover Acoustic Partition Roll (APR 1200). Linings as in table. Linings as in table.
Linings as in table.
Detail Partition Board type1 Lining Maximum partition Sound insulation Duty rating Approx. System
thickness thickness height RwdB weight reference
mm mm mm kg/m²
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Based on a limiting deflection of L/240 at 200 Pa.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
There are two build solutions; 450mm stud framing without Lightweight fixtures can be made directly to the partition linings.
noggings, and 900mm stud framing with horizontal noggings. Medium weight fixtures can be made to Gypframe 99 FC 50 Fixing
Channel. Heavyweight fixtures (to BS 5234), such as wash basins
Planning – key factors and wall cupboards, can be fixed using plywood secured with
Gypframe Service Support Plate.
The position of services should be pre-determined and their
installation planned into the frame erection stage. Refer to C02. S01. P33 – Service installations.
Refer to C02. S01. P10 – Building acoustics. Refer to C08. S04. P02 – Tiling.
Services
Electrical
The installation of electrical services should be carried out in SpecSure®
accordance with BS 7671. The cut-outs in the studs can be used
for routing electrical and other small services (Refer to Partitions All our systems are covered by SpecSure® when
introduction C04. S01. P07 – construction detail 2a). Switch boxes using genuine British Gypsum and Saint-Gobain
and socket outlets can be supported from Gypframe 99 FC 50 Fixing Isover products.
Channel fixed horizontally between studs, or a high performance
socket box detail used where higher acoustic performance is
required.
Heating pipes
Where heating pipes, particularly micro-bore systems, are to be
located within the partition, it is recommended that only one pipe
is passed through each aperture in the metal framework. If this
cannot be accommodated for whatever reason, it may then be
necessary to incorporate proprietary pipe restraining clips or other
means of keeping the pipes apart to prevent vibration noise.
Ducts
Where a large number of electrical cables or pipes have to be
accommodated, a service duct can be created by closing up the stud
centres to 450mm and omitting the intermediate nogging.
Electrical cables should be attached using an appropriate cable
retaining device in order to satisfy the requirements of BS 7671.
3 4
1 3
Partitions
9
C04
4
Junction with masonry
(900mm stud centres with horizontal noggings)
4
2
1
5
7
3
9
6
5 8
4 5
1
4
2 3
1 15mm Gyproc SoundBloc rapid 6 Bulk fill with Gyproc jointing materials (where gap exceeds 5mm)
2 Gypframe 43 AS 50 AcouStud 7 Skirting
3 Gypframe GWR3 Floor and Ceiling Channel 8 Blockwork
4 Gypframe GWR2 Nogging Channel (only required when studs are 9 DriLyner basic wall lining system
installed at 900mm centres)
5 Gyproc Sealant
6 7
5
8
1
4
4
2
3
5
Partitions
8 9
1
3
2
4
4
10
Section A–A
Partitions
1
C04
300mm
B
Section B–B
A
A
4
150mm
Door frame detailing to BS 5234 - Medium Duty Rating, studs either side of door opening fully sleeved
12
A
Snip legs
A
Bend up 2
90°
A Bend
Bend up 5
down
90°
A 180°
Bend
down A = depth from door head to legs of head channel
180° B = width of formed door head
Forming door head where studs either side of door opening have a timber ground fitted
1 Gypframe AcouStud fully sleeved with Gypframe channel 5 Finished assembly fixed to Gypframe AcouStuds with
(both sides of opening) British Gypsum Wafer Head Drywall Screws
2 Gypframe Floor & Ceiling channel 6 Mitre cuts
3 Gypframe Floor & Ceiling channel cut and bent to form door head
4 Door set
provide stability.
Gypframe GWR3 floor & Ceiling Channel Gypframe Service Support Plate
Floor and ceiling channels for retaining the vertical For installation of 18mm plywood within
C04
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
British Gypsum Drywall Screws British Gypsum Wafer Head Drywall Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws
for fixing board to metal framing less than for fixing metal to metal framing less than
0.8mm thick. 0.8mm thick.
Partitions
common backgrounds including undercoat plasters
and plasterboard. For more information refer to
C02. S01. P49.
C04
Thistle SprayFinish ThistlePro Magnetic
To provide a plaster skim finish by spray or hand To provide a plaster skim finish that provides an
application, ideal for medium to large projects. attraction to magnets used to finish a wide range
of backgrounds, including undercoat plasters and
plasterboard.
Gypframe Floor & Ceiling Channels are Gypframe Floor & Ceiling Channels are The perimeter of the partition is sealed on
suitably fixed to the floor and soffit. suitably fixed to abutments to form the both sides with Gyproc Sealant.
perimeter framework.
C04
Gypframe AcouStuds can be friction-fitted or Gypframe AcouStuds can be friction- Where Gypframe stud framing is installed at
vertically at 450mm centres to form the fitted vertically at 900mm centres to form 900mm centres, Gypframe GWR2 Nogging
framework, the framework. Channels are located horizontally between
each pair of studs at mid-height. Additional
framing is installed as required to support
heavy fixtures.
Isover Acoustic Partition Roll (APR 1200) Gyproc SoundBloc rapid boards are
can also be added to the partition cavity for screw-fixed to all framing members with
increased acoustic performance. British Gypsum Drywall Screws to form
the lining.
Additional information
For full installation details, refer to the
British Gypsum Site Book, available to
download from british-gypsum.com
Partitions
Key benefits System can be skim
finished with
ThistlePro PureFinish.
— High levels of acoustic performance are
C04
Refer to C02. S01. P49
If you’re looking for a Duty Rating in accordance with BS 5234: Part 2: 1992
Refer to C04. S01. P03 – Partitions performance matrix.
1 2 3
One layer of board each side of timber Two layers of board each side of timber Remedial treatment on one side
studs at 600mm centres. Insulation and studs at 600mm centres. Insulation and of existing plasterboard partition
linings as in table. linings as in table. (minimum 1 x 12.5mm plasterboard
Partitions
Detail Partition Board type Lining Stud Sound insulation RwdB System
thickness thickness size No insulation With insulation reference
mm mm mm1
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Stud sizes quoted are minimum.
2
25mm Isover Acoustic Partition Roll (APR 1200) insulation.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked
with British Gypsum.
To establish the maximum cold state height for the partition refer to the relevant structural timber standards or a suitably qualified Structural Engineer.
In addition, for EN fire resistance the maximum height must not exceed the tested height (usually 3000mm).
1 2 3 4
One layer of board each side of timber Two layers of board each side of timber Remedial treatment on one side One layer of board each side of timber
studs at 600mm centres. Insulation and studs at 600mm centres. Insulation and of existing plasterboard partition studs at 600mm centres and 65mm
Partitions
linings as in table. linings as in table. (minimum 1 x 12.5mm plasterboard Isover Acoustic Partition Roll (APR 1200)
each side of 75mm x 38mm studs at in the cavity. Linings as in table.
600mm centres) using 50mm x 50mm
timber battens at 600mm centres,
50mm Isover Acoustic Partition Roll
(APR 1200) between the studs with
Gypframe RB1 Resilient Bar at 600mm
C04
centres (fixed horizontally).
Linings as in table.
Detail Partition Board type Lining Stud Sound insulation RwdB System
thickness thickness size No insulation With insulation reference
mm mm mm1
1 93 Gyproc WallBoard 1 x 15 63 x 38 - 40 2
A026010
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Stud sizes quoted are minimum.
2
25mm Isover Acoustic Partition Roll (APR 1200) insulation.
3
Specification based on BR 128 only for use in Scotland, please refer to Building standards technical handbook 2019 Section 2.
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked
with British Gypsum.
To establish the maximum cold state height for the partition refer to the relevant structural timber standards or a suitably qualified Structural Engineer.
In addition, for EN fire resistance the maximum height must not exceed the tested height (usually 3000mm).
1 2 3
Two separate timber frames spaced Two layers of board each side of 75mm Two layers of board each side of 75mm
50mm apart, consisting of 89mm x x 38mm timber studs at 600mm centres x 38mm timber studs at 600mm centres
38mm timber studs at 600mm centres with Gypframe RB1 Resilient Bars fixed with Gypframe RB1 Resilient Bars fixed
Partitions
with noggings. Two layers of board each horizontally to one side at 600mm horizontally to both sides at 600mm
side. 100mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition
Roll (APR 1200) between the studs on Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity.
one side. Linings as in table. Linings as in table. Linings as in table.
C04
Detail Partition Board type Lining Stud Sound insulation System reference
thickness thickness size Rw (Rw+ Ctr)
mm mm mm dB
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked
with British Gypsum.
To establish the maximum cold state height for the partition refer to the relevant structural timber standards or a suitably qualified Structural Engineer.
In addition, for EN fire resistance the maximum height must not exceed the tested height (usually 3000mm).
1 2 3 4
Two separate timber frames spaced Two separate timber frames spaced Two layers of board each side of 75mm Two layers of board each side of 75mm
50mm apart, consisting of 89mm x 50mm apart, consisting of 89mm x x 38mm timber studs at 600mm centres x 38mm timber studs at 600mm centres
38mm timber studs at 600mm centres 38mm timber studs at 600mm centres with Gypframe RB1 Resilient Bars fixed with Gypframe RB1 Resilient Bars fixed
with noggings. Two layers of board each with noggings. Two layers of board each horizontally to one side at 600mm horizontally to both sides at 600mm
Partitions
side. 25mm Isover Acoustic Partition Roll side. 100mm Isover Spacesaver centres. 50mm Isover Acoustic Partition centres. 50mm Isover Acoustic Partition
(APR 1200) between the studs on one Ready-Cut between the studs on one Roll (APR 1200) in the cavity. Roll (APR 1200) in the cavity.
side. Linings as in table. side. Linings as in table. Linings as in table. Linings as in table.
Detail Partition Board type Lining Stud Sound insulation System reference
C04
thickness thickness size Rw (Rw+ Ctr)
mm mm mm dB
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
Test conducted to BS 476:Part 21: 1987 (loadbearing)
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked
with British Gypsum.
To establish the maximum cold state height for the partition refer to the relevant structural timber standards or a suitably qualified Structural Engineer.
In addition, for EN fire resistance the maximum height must not exceed the tested height (usually 3000mm).
The position of services and heavy fixtures should be Timber should be aligned and level, and should meet the
pre-determined and their installation planned into the frame requirements of BS 5268. The dimensions and assembly of timber
erection stage. If a plastered finish is specified, the thickness of the supports should be sufficient to allow positive fixing of plasterboard
door or glazing frame must allow for the thickness of the plaster finish. without bounce or undue deflection. When the above fixing
conditions cannot be met, a timber batten should be securely fixed
To minimise the risk of cracking at the plasterboard joints, to the side of the timber support to increase the bearing surface.
seasoned timber with a moisture content not exceeding that
recommended in BS 5268 should be used. The contractor should Where boards are fixed at maximum centres in adverse conditions,
ensure that timber supports are accurately spaced, aligned, the standard of lining can be affected. Adverse conditions can
and levelled. generally be described as conditions where high humidity occurs,
principally in the cold, damp, autumn / winter period. They also refer
Partitions
Cavity barriers to buildings under construction over this period, where both the
structure and wet applications, such as plastering and screeding,
Cavity barriers may be required to satisfy the requirements of
are subject to slow drying conditions (refer to table 3).
Building Regulations.
Electrical and other small service runs can be routed within the 1200 600
timber stud cavity. The installation of electrical services should be 15 900 450
carried out in accordance with BS 7671. Switch boxes and socket 1200 600
outlets can be supported from timber stud noggings. Gyproc Plank 19 600 600
Partition junctions
Nail popping
Board finishing
Refer to C08. S01. P02 – Finishes.
Tiling
Partitions
Tiles up to 32kg/m2 can be applied to the surface of lightweight
partition systems.
C04
Important information
Ensure British Gypsum Drywall Screws
have a minimum of 25mm penetration
into the timber frame.
1 2
2
4
4
3
2
4
1
7
Partitions
3
C04
6
3
4
2
4 5
8
3
1
1 3
1 Gyproc plasterboard 5 Bulk fill with Gyproc jointing materials (where gap exceeds 5mm)
2 Timber framing 6 Skirting
3 Isover insulation 7 Timber noggings at 600mm centres
4 Gyproc Sealant 8 Timber door frames and architrave
Partitions
inner layer.
C04
Gypsum plasterboard with a controlled 10 kg/m² Gypsum plasterboard with fire resistant additives
weight for specific sound insulation performance and a high density core for enhanced sound
in accordance with Robust Details used within the insulation and impact resistance performance.
residential sector.
Gyproc SoundBloc1
Gypsum plasterboard with a high density core for
enhanced sound insulation performance.
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
Gyproc AquaBead
An easy to apply, water, activated adhesive corner
bead, for reinforcing external 90° angles in taped
and jointed plasterboard constructions.
Gyproc Styletrims
Primed, pre-formed aluminium trims for design
effects with plasterboard.
Partitions
Timber framing is fixed to the perimeter, Door openings are formed by fixing full M&E services can be located within the
abutments, and to frame any openings, height timber studs to each side, together partition cavity before the partition has
using suitable fixings. Timber studs are with a timber head piece. Door casings are been boarded. Timber noggings are fixed
fixed at specified centres. then fixed to the timber ground. Additional to support recessed switch boxes / socket
C04
framing is installed as required to support outlets.
heavy fixtures.
Where Gypframe RB1 Resilient Bars are Isover insulation can also be added to the The perimeter of the partition is sealed on
required, these are fixed horizontally to partition cavity for increased acoustic both sides with Gyproc Sealant.
the timber studs to one or both sides as performance.
specified.
Gyproc plasterboards are screw-fixed to all Horizontal board joints are backed with
timber supports, or to the Gypframe RB1 timber noggings or Gypframe RB1 Resilient
Resilient Bars with British Gypsum Drywall Bars as required.
Screws.