PAM COMPLEX WATER OUTLETS TO PUB DRAIN/OPEN SEA

Sea Water Outlets 23-Aug-17

DISCHARGING WS FLOW (m3/s)


PAM OUTLET SIZE INVERT LEVEL
No. WS OUTLET location WS SUPPLY Plant/Equipment
DIRECTION Original design + Max WS Flow (maximum (mm) (m ACD)
Original Design Current (max) + 10%, A
10%, B of A or B)

E-121A/B/C 0.63 - 0.63


EGS 2.24 - 2.24
12.50
1 North of PAM III North 1WS SE 10.81 - 10.81 5300 x 2000 -2.00
SA/SB/SC 1.17 - 1.17
Subtotal 14.85 13.75 14.85

2 North of PAM V North 1WS Rohm & Haas 1.82 0.19 2.00 2.00 1400 x 1000 0.00

2SE 12.36 - 12.36


2SA/2SC 3.55 - 3.55
13.70
3 2SU-2Z-139 VI North 2WS 2SP 0.30 - 0.30 4000 x 1800 -2.20
2E-121A/B/C 0.44 - 0.44
Subtotal 16.65 15.07 16.65

4 2SU-2Z-140 VII North 2WS TPC-2 2.78 3.26 3.06 3.26 1500 x 1500 -1.90

5 2SU-2Z-141 VIII East 2WS CPSC-2 3.61 1.80 3.97 3.97 2500 x 1500 1.90

6 West of PAM II West 2WS SOXAL (AS-2) 0.55 0.43 0.61 0.61 1050 (Dia) +2.315

TPC-1 2.38 - -
4.17
7 South of PAM IV South 1WS CPSC-1 1.21 - - 2200 x 1500 -1.50
Subtotal 3.59 4.59 4.59
1WS ST 0.09 - 0.09
-
8 South of PAM - South 2WS 2ST 0.09 - 0.09 - -
Subtotal 0.17 - 0.17
9 South of PAM - South 1WS 1SE WSIS - 0.032 - 0.032 - -

Fire Water (uncontaminated) Outlets


PAM WF discharging flow
No. WF DISCHARGE location WF supply Plant
DIRECTION (m3/s)

P-101A/B/C WI 350m3/hr x 3 0.29

PD-903 WI 360m3/hr x 1 0.10


1 South of PAM (?) - South SE/SA/SB/SC/ST
P-901 WI 900m3/hr x 1 0.25
PM-901A, PD-
WS 900m3/hr x 3 0.75
902B/C
2P-101A/B WI 350m3/hr x 2 0.10
North of PAM
2 - North 2P-901 WI 942m3/hr x 1 2SE/2SA/2SC/2SP/2ST 0.26
(next to 2Z-508)
2PD-902A WS 945m3/hr x 1 0.26

Sea Water Intake


INTAKE WS FLOW (m3/s)
PAM OUTLET SIZE INVERT LEVEL
No. WS INTAKE location Plant/Equipment
DIRECTION Original Design Additional from new plant developments Total Flow (+10%) (mm) (m ACD)

1 South of PAM I North 1WS 16.67 NA NA 18.337 7000 X 3550 -4.5

2 South of PAM IX South 2WS 22.20 NA NA 24.42 2 nos 2800 (Dia) -10.5

Rain/Storm Outlets
DISCHARGING RAIN/STORM FLOW (m3/s)

Additional from new plant developments OUTLET SIZE INVERT LEVEL


No. Rain/Storm Outlets location PAM Direction Plant/Equipment
Original Design Total Flow (+10%) (mm) (m ACD)
Flow Quantities
Catchment Area (hectare)
(m3/s)

1 1 West 1.0068 NA NA 1.107 900 (Dia) +2.555

2 2 West 1.8180 NA NA 2.000 1200 (Dia) +2.315

3 3 South 1.1897 NA NA 1.309 1050 (Dia) +2.535

4 4 South 1.4955 NA NA 1.645 1200 (Dia) +2.335

5 5 South 0.8381 NA NA 0.922 1200 (Dia) +2.375

6 6 South 2.8933 NA NA 3.183 2200 x 1500 -1.50

7 7 South 0.8657 NA NA 0.952 900 (Dia) +2.575

3SB Plant fire water 1.0550


8 8 North 1.5508 3.691 1200 (Dia) +2.315
WS cooling for 3SB Plant 0.75

9 9 West 0.7101 NA NA 0.781 1050 (Dia) +2.315

10 10 South 0.9572 NA NA 1.053 900 (Dia) +2.695

11 C5 North 0.2772 NA NA 0.305 800 (Dia) +2.340

12 A10 North 0.1788 NA NA 0.197 600 (Dia) +2.540

13 B86 North 4.3652 2SP Plant fire water 0.5358 4.802 2 x 1500 (Dia) +1.640

14 D13 North 3.8464 NA NA 4.231 1800 (Dia) +1.340

(4.6639E4x0.117x0.9)
15 E16 East 1.0290 4.6639 1.132 750 (Dia) RL+101.62
3600=1.364

CPSC-1 cooling water 0.5500


3mW x 3.7mD
16 F30 East 1.4003 9.122 +1.940
JTC reclamation= (21.6842E4x0.117x0. (U-drain)
(10.8606+5.0684+5.7552) 9)/3600=6.3426

17 G25 South 5.0290 NA NA 5.532 2 x 1200 (Dia) +1.94; +1.84