Professional Documents
Culture Documents
handled wrongly.
MEMO : This means convenient informa-
CAUTION : This is a caution. This assumes possible tion to know.
injury to the operator and physical
IMPORTANT
damage only, if handled wrongly.
HIA-527
Characteristics of this Manual
This manual serves daily operators and maintenance personnel of the compressor as an
instructive materials including its introduction, operation, daily control and periodic ser-
vicing.
Before installation of the compressor, read the manual carefully and understand its con-
tent and follow the instructions given by it when in use.
Also, prepare the manual near the machine to make it available at anytime, and refer to it
as the need arises.
If you have anything unclear or any question, please ask your dealer or your nearest
Hitachi regional office.
It is convenient for ordering spare part, periodic maintenance and overhaul if type and
serial number of the compressor are filled into the back cover of the manual.
WARNING
NEVER USE THIS COMPRESSOR AS AN APPLIANCE BY
WHICH A PERSON BREATHES THE COMPRESSED AIR
DIRECTLY.
THE COMPRESSED AIR FROM THIS MACHINE CONTAINS
OIL AND THIS OIL MAY CAUSE SERIOUS ACCIDENTS LIKE
DYSPNEA IF ASPIRATED IN THE HUMAN BODY.
■ Description of Type:
O S P - 55 S 5 A
Oil Flooded Type Air Cooled Type
SCREW Type Frequency (5:50Hz, 6:60Hz)
Package Type S: I-Type Control, M: P-Type Control
Output (kW)
PERIODIC MAINTENANCE
2.1 Appearance ········································ 4
8.4 Performance Check of Safety Valve ···· 41
2.2 Main Component Units and their Functions ···· 5
8.5 Performance Check of
Capacity Control System ················ 41
3. HOW TO OPERATE ································· 6
8.6 Check and Cleaning of
3.1 Air Compressor Instrumentation ····· 6 Oil Scavenge Filter ·························· 42
3.2 How to Use Digital Monitor 8.7 Replacement of Oil Filter ················ 43
and Operation Switches ··················· 8 8.8 Cleaning and Replacement of
3.3 Initial Start-Up ·································· 10 Air Intake Filter ································ 44
3.4 How to Set Control Functions ········ 12 8.9 Cleaning of Cooler ·························· 45
3.5 Daily Operation ································ 14 8.10 Inspection and Replacement of
Minimum Pressure / Check Valve ········ 46
DAILY CHECK
1
1. TO USE IN SAFETY
In order to operate the machine properly and safely, it is indispensable to read care-
fully and follow warnings and instructions hereunder mentioned prior to its use.
The warnings and instructions on labels are attached to the places shown in the
figure below.
WARNING
;;;;;
When in automatic operation, compressor
may automatically restart. Keep hands and
other materials away from rotating parts, such
as Belts, fans, and couplings. Shut down
compressor, lock the power OFF, and relieve
of all pressure before any service work.
WARNING
;;;;
HOT OIL UNDER PRESSURE !
Do not open drain valve during operation.
Hot oil under pressure can burn or cause
injury.
WARNING
HOT LUBRICATING OIL !
Do not touch the drain or oil right after the
stoppage to avoid the burn.
2
1. TO USE IN SAFETY
CAUTION WARNING
USE GENUINE SYNTHETIC OIL ONLY ! DO NOT USE THE DISCHARGE AIR OF
NEW AOIL is filled in as lubricat- THIS UNIT FOR BREATHING !
ing oil. No other lubricating oil may be Usage of the discharge air of this unit for
refilled nor mixed. Exchange the lubricating breathing may cause severe injury or
oil periodically as instructed in the manual. death.
WARNING WARNING
HOT OIL UNDER PRESSURE ! When in automatic operation, compressor
When in automatic operation, compressor may automatically restart.
may automatically restart. Shut down Before doing any service work, including oil
compressor, lock the power OFF, and filling, shut down the unit, lock the power
relieve of all pressure before lubricating oil OFF, and relieve of all pressure.
refill.
WARNING
Keep flammable agent away from this unit,
to avoid unexpected explosion.
Use genuine NEW AOIL only for
lubricating oil. Periodical exchange of
lubricating oil and oil separator element as
instructed in the manual, is required to
avoid the potential fire or explosion.
WARNING
When in automatic operation, compressor
may automatically restart. Keep hands and
other materials away from rotating parts,
such as Belts, fans, and couplings. Shut
down compressor, lock the power OFF, and
WARNING relieve of all pressure before any service
work.
Replace oil separator element, housing and
lubricating oil periodically as instructed in
the manual. Lubricant deterioration can WARNING
cause fire or explosion.
ELECTRICAL SHOCK, CAN BURN OR
Any defect, distortion, or corrosion on
CAUSE INJURY OR DEATH!
housing can spout, burst or explosion. DO
NOT operate the unit with damaged ● Lock the power OFF before inspection or
housing. wiring works.
● Electrical wiring and other electrical
works must be carried out by a licensed
WARNING personnel.
DO NOT loosen the housing during ● All electrical enclosures and compo-
operation and while still under pressure. nents must be grounded.
Hot, pressurized air or lubricating oil can
burn or cause injury. CAUTION
● DO NOT use fire at or around this unit.
CAUTION Otherwise, struck sparks may cause
burning inside the unit.
Read instruction manual before inspection ● DO NOT remove protection relay and/or
or replacement of oil separator. safety device, nor make any modification
● Shut the unit down, disconnect the work which may interrupts the protecting
power, and relieve all pressure before and safety function.
the work. Without protecting function, the unit can
● Be careful for the hot surface of the oil burn or cause fire.
separator housing. ● Provide leakage breaker at the power
● To remove housing, a special wrench is source.
required. An ordinary filter wrench or ● Observe and confirm that lubricating oil
pipe wrench will damage the housing is filled at proper level by the oil gauge.
and can cause bursting or spouting
accident. Contact HITACHI distributor
for the special wrench. CAUTION
● Replace housing and O-ring by new
HOT !
ones at the same time of the element
replacement. Do not touch the parts, drain or oil right
after the stoppage to avoid the burn.
For details, refer to the instruction manual.
3
2. PARTS DESCRIPTION AND THEIR FUNCTIONS
2.1 Appearance
Intake air
Specification Plate
Front Cover Oil Level Gauge Fork Slot Power Cable Conduit Hole
To pull its upper part to (inside the cover) To be used when carry- and External Wiring Port
open. Take this off for To indicate oil level in oil ing and installing the unit. Be sure to connect the
maintenance servicing. tank. Put the attached noise- power cable with care for
proof covers on them af- the power source elec-
ter installation. tricity specification (volt-
age and frequency).
4
2. PARTS DESCRIPTION AND THEIR FUNCTIONS [Main Component Units and their Functions]
Suction Throttle Valve Fan Motor Air Intake Duct Air Intake Filter
This controls capacity of Totally enclosed fan type This prevents foreign
air intake against load 4-pole flange motor is bodies in the air from
fluctuation. used. being taken in the com-
pressor.
Starter
5
3. HOW TO OPERATE
Switches commonly
used at operation
Ammeter Discharge Air Pressure Gauge Digital Monitor Running Condition Lamp
Indicates the current of Indicates the pressure of Displays running time, discharge tem- Displays type of shutdown
air compressor motor. discharge air. perature, shutdown codes, etc. and running condition.
100
300
50 600 0.5 1 吐 出 温 度 起 動 待 ち
0
AIR TEMP AUTO START
A
× 10 h
MPa リセット
0 1.5 C:温度 表示切替 運 転 停 止
電 源
15
6
3. HOW TO OPERATE [Air Compressor Instrumentation]
Switches to change
Display Select Switch Remote Lamp (Yellow)
function setting display Press this switch to display Displays by glow or blink
discharge temperature and when status of remote op-
shutdown code on a digital eration is selected.
monitor.
“Remote Operation” means a mode by which the unit starts or stops by the control signal from other than the control
panel of the compressor.
“On-Panel Operation” means a mode by which the unit starts or stops by the control signal from the control panel.
Display at Shutdown
or Caution status.
7
3. HOW TO OPERATE [How to Use Digital Monitor and Operation Switches]
Press.
8
3. HOW TO OPERATE [How to Use Digital Monitor and Operation Switches]
3.2.2 How to Operate Display SELECT Switch (Lamp Test, Check and Change of Pressure Setting)
(1) How to test a lamp and check pressure setting
[Lamp Test] While pressing “RESET” switch, press “Display
Digital Monitor Turn all lamps except operation SELECT” switch for more than 3 times. The
lamp ON for 5 seconds.
リセット monitor performs its lamp test for 5 seconds then
表示切替
SELECT
RESET 5 seconds later. it returns to pressure setting display.
[Display of control pressure value] To check the reset pressure, press “Display SE-
1 : means cut out pressure. LECT” switch.
While pressing A : means type of capacity control. Display further than dlxx are not used. Press
“RESET” switch, 表示切替 70: means I-type cut out press
SELECT “RESET” switch to return to normal digital
press “Display SELECT” at 0.69 MPa {7 kgf/cm2}.
switch for more than monitor display after confirmation.
Press.
3 times.
[Display of reset pressure value]
2 : means cut in pressure.
A : means of capacity control.
60: I-type cut in press IMPORTANT
リセット at 0.59 MPa {6 kgf/cm2}.
RESET At pressure setting display mode, the screen dis-
Press. plays type of capacity control, as follows;
A: P-type (AUTO) setting, L: I-type setting,
U: U-type setting. (See p.26)
9
3. HOW TO OPERATE [Initial Start-Up]
IMPORTANT IMPORTANT
Capacity control of S-series is preset to I-type control, The HISCREW uses the NEW A OIL (a dedi-
and M-series is to P-type (AUTO) control. cated synthetic oil).
Refer to P.12 for the setting of control function when the
control type is changed.
Compressor shifts repeatedly between full-load and no-
load operation within the range of its discharge pres-
sure between 0.69 MPa {7 kgf/cm 2} and 0.59 MPa {6
kgf/cm2}.
3.3.2 Power on
Main q Turn the MAIN POWER ON.
③② Power
IMPORTANT
For safety, the unit will not operate for 5 seconds after
the power is ON, even START switch is pressed.
10
3. HOW TO OPERATE [Initial Start-Up]
3.3.3 Operation
q Press “START” switch.
④① Start lamp glows and the compressor starts.
3.3.4 Stop
q Press “STOP” switch.
② ① Main
Power The compressor stops.
11
3. HOW TO OPERATE [How to Set Control Functions]
IMPORTANT
CN13
SW3
13
③ capacity control.
SW2
1 5
Y52C
I -type
CN5
AUTO Y2D
CN7
U-type
3.4.2 How to switch Type of Control
7
CPU Y52
1
I -type
to U-Type)
1 5
HC30CPU−
AUTO
21
Y42
U-type
CN4
21
GND Y6
JP2 JP4
C38
JP1 JP3
C39
1
CN14
C4D
e Shift the slide switch knob (SW2) on the print
4
2 1 5 14 1 ICO
CN8 CN16 CN17
circuit board down to the bottom.
Print circuit board
r Put the cover back to its place.
12
3. HOW TO OPERATE [How to Set Control Functions]
CN13
13
Y2D
change the setting, or q Turn main power OFF.
CN7
Y52
unit will be changed,
CPU
w Remove the panel cover.
e Connect wires between remote operation panel
1
too.
CN6
4
CN9 CN10 CN11
Y42
gram of P.34 to 37.)
CN4
21
SW1
r Turn OFF dip switch No.4 (SW1) on the print
7
GND Y6
JP2 JP4
SW1
C38
JP1 JP3
5∼8
C39 circuit board in the starter panel.
1
CN14
Setting for 4
remote operation 3
C4D
t Put the cover to its place.
4
2 2 1 5 14 1 ICO
④ 1 CN8 CN16 CN17 y Turn main power ON.
ON OFF
u Turn ON outside remote operation set switch.
Dip switch Print circuit board
i Remote operation lamp blinks to display the
remote operation is set by an outside switch.
o To make the setting back to on-panel operation,
turn OFF the outside remote operation set
switch. Remote operation lamp is out to show
the control has shifted to on-panel.
故 障 内 容 運 転 状 況
SHUT DOWN RUNNING MODE
⑦ Glow Remote setting
過 負 荷 メンテナンス 遠 方 from panel side. IMPORTANT
OVERLOAD MAINTENANCE REMOTE
Remote setting
吐 出 温 度
AIR TEMP
起 動 待 ち
AUTO START
⑧ Blink
from outside. In case the compressor is operated by an outside equip-
リセット
⑨ OFF On-panel setting. ment such as multiple unit operation or alternating op-
運 転 停 止
RESET
電 源
POWER START STOP
eration, set its control to remote operation at the panel
side. Do not make remote operation setting by an op-
eration switch at outside the unit.
Even though the unit is operating by remote operation, it
can be stopped by “STOP” switch at the compressor side.
13
3. HOW TO OPERATE [Daily Operation]
Upper
Oil level varies between before starting and after start-
Oil replenish red line ing. The oil level stays between the two red lines during
port
Lower
operation, and rises to over the upper bolt after stop-
level line ping the A. This is because oil in the oil cooler
Bolt
and oil piping returns to the oil tank after stopping, and
is not abnormal. Do not fail to check the oil level, there-
fore, during operation.
3.5.2 Power on
Main q Turn the POWER ON.
② Power
w POWER Lamp on the operation panel glows.
①
e Fully open the valve on discharge side.
14
3. HOW TO OPERATE [Daily Operation]
3.5.3 Operation
3.5.4 Stop
q Press “STOP” switch.
Main
② ① Power The compressor stops.
④
w Be sure that the pressure at DISCHARGE AIR
PRESSURE GAUGE indicates 0 (It returns to 0
for about 1 or 2 minutes after stop.)
15
4. DAILY CHECK
WARNING
1. Before check and maintenance of the compressor , carefully read “TO USE IN SAFETY” (See page 2)
again.
2. Be sure to turn OFF the POWER when check or maintenance is carried out.
3. Never touch rotating parts of the compressor (Motor Shaft, M-Sheave, V-Pulley, V-Belt and Cooling
Fan).
16
4. DAILY CHECK [Lubricant Management]
Bolt
IMPORTANT
CAUTION
● Replenish the oil (genuine synthetic oil) periodically to
maintain the proper oil level. Long time operation without
the oil replenishment at low oil level, can cause the shorter
;;
oil life or oil deterioration.
● Oil replenishment shall be carried out every 1,500 to 2,000
;;
operating hours. Replenish amount might be 4 to 5 liters.
(Actual replenish amount shall be determined by the oil
;
level, as it is varied by the load rate of the compressor.)
● Sampling analysis of the oil at every 3000 hours interval is
recommended. Earlier oil replacement might be necessary,
depending on the result of the analysis.
Consult HITACHI dealer for the sampling analysis.
17
4. DAILY CHECK [Lubricant Management]
Discharge
replenish port on the oil tank.
t Put a saucer beneath the port and open the
Drain Valve to empty the lubricant inside the
Oil Tank completely.
When the Oil Tank is completely emptied, close
the Drain Valve again.
Oil drain port Oil level gauge y Drain lubricant inside the oil cooler from its oil
Oil tank
Oil cooler drain port drain port. After draining, put the plug on the
port.
● Be sure to drain oil in use (old oil) with !4 Tightly fasten the oil replenish port plug.
condensate in whole before replacement. !5 Turn on the main power again, and press START
switch. Make sure that the oil level lowers and
Check
CAUTION
● If oil is so deteriorated as to produce the sludge or to be green, you can not recover the system’s
function even by cleaning the oil cooler and oil piping. You may have to replace the oil cooler and
overhaul the entire system (including the air end).
● Optional Low Oil Level Alarming Feature:
If the MAINTENANCE lamp glows and the error code E-22 is displayed on the digital monitor, stop the
A, make sure that the system has been depressurized, and turn off the main power; then add
oil. Restart and fully load the A; then press the RESET switch.
18
5. TROUBLESHOOTING
CAUTION
In case where WARNING is given or a SHUTDOWN happens, remove its causes before restart the unit.
Ask your dealer or your nearest Hitachi Service Station if you have any question or unclear point.
19
5. TROUBLESHOOTING [Setting OVERRIDE]
IMPORTANT
(1) Power supply interruption means the instantaneous drop (3) When such time is longer than 5 seconds, the sensor
of voltage to 0 V. detects it as a power failure and stops the unit. In such
(2) The compressor continues its normal operation without case, the unit will not restart automatically. So, press
stop if the said drop time is shorter than 20 ms. the START switch to start the unit again.
②④
20
5. TROUBLESHOOTING [Setting OVERRIDE]
CN13
SW3
13
③ • ALARM performance.
CN3
SW2
U-type
• Remote Operation.
1 5
setting Y52C
Capacity
• Switching function of “Display SELECT” switch.
CN5
Y2D
control
CN7
switch
CPU Y52 7
1 • Dry contact external output function.
Remember that this OVERRIDE is a tempo-
CN6
4
CN9 CN10 CN11
Y42
your nearest Hitachi Service Station immedi-
CN4
21
SW1
7
Override 8 ③ GND Y6
JP2 JP4
SW1
C38
JP1 JP3
operation
C39
setting
1
CN14
4 C4D
3
4
2 2 1 5 14 1 ICO
1 CN8 CN16 CN17
ON OFF IMPORTANT
Dip switch Print circuit board
Use capacity control by changing the setting to U-type
control (suction unload type).
When a failure happens to the pressure sensor only, the
unit is operable by setting capacity control switch (SW2)
運 転 時 間
RUNNING HOUR
to U-type mode without override operation.
In case the monitor displays fault of the micro computer,
⑥
Override operation display turn the power OFF once, then turn ON again to see if
the unit returns to normal status. If the fault cannot be
× 10 h
canceled, no override operation is available. Call your
C:温度 表示切替
TEMP SELECT dealer or Hitachi service station immediately, and ask
E:故障コード
ERROR CODE for repair.
21
5. TROUBLESHOOTING [A List of ALARM and SHUTDOWN Displayed on Instrument Panel]
Discharge Blink − ○ Increase in ambient Keep ventilation to keep ambient tempera- Discharge Press reset 18
temp. temperature ture below 40 degree C. temp. over switch.
110 degree
Oil level lowered Replenish lubricant. Turn the power OFF
C at main
and make sure that pressure is 0 before
body outlet.
replenishment.
Oil cooler contamination and Clean cooling fin of the oil cooler. Refer to
clogging p.45.
Oil filter contamination and Replace oil filter. Refer to p.43.
clogging
Glow − Same as the above Blink Same as the above Blink case. Discharge temp. Auto reset. 23
case. over 105 degree C at
main body outlet.
Maintenance Blink E-01 ○ Power connection; Reversal Turn power OFF and replace 2 of 3 electri- Detectable for Power reset. 01
phase cal cables. 3 seconds af-
ter power in-
E-02 ○ Power supply; Phase failure Turn power OFF and check loose wires and put. 02
power facilities.
E-11 ○ Excessive temp. at oil Separator fault. Temp. over 110 Press reset 11
separator outlet Replacement of separator or lubricant is degree C. at switch.
separator ele-
required. ment outlet.
E-12 ○ Excessive press. at air end discharge Replacement of separator is required. Detectable while Press reset 12
operation switch.
Electromagnetic contactor (52) fault Turn power OFF and check loose wires. and later.
E-14 ○ Pressure sensor fault Actuates when output from pressure sensor is Detect max. Press reset 14
short circuited. Sensor must be replaced. pressure. switch.
E-16 ○ Electromagnetic contactor Turn power OFF and check electromagnetic Detectable while Press reset 16
operation switch.
(42) fault. (42 answer) contactor (6) (42) failure or loose wire. and later.
E-51 ○ Electromagnetic contactor Turn power OFF and check electromagnetic Detectable while Press reset 51
(52) fault. (52 answer) contactor (52) failure or loose wire. operation. switch.
E-31 ○ Thermistor (TH1) disconnect, contact fault Turn power OFF and check looseness in Disconnection Auto reset. 31
thermistor wiring. Change thermistor if it recognized
E-32 ○ Thermistor (TH2) disconnect, contact fault (lower than –30 32
is fault. degree C.)
E-33 ○ Pressure sensor disconnect, Turn power OFF and check loose wire of pres- P r e s s u r e 0 Auto reset. 33
contact fault sure sensor. Change thermistor if it is fault. while operation.
22
5. TROUBLESHOOTING [A List of ALARM and SHUTDOWN Displayed on Instrument Panel]
AUTO-RESET: ·········· functions automatically when the detected portion recovers to the allowable level.
POWER RESET: ······ Turn power OFF once. And reset functions automatically after repair and the power is re-input.
RESET SWITCH: ····· After repair, reset the unit by pressing the reset switch on the operation panel.
RE-USE NOT ALLOWED: ···· Not usable unless failed parts are replaced.
23
5. TROUBLESHOOTING [A List of SHUTDOWNS Not Displayed on Instrument Panel]
WARNING
1. Running the unit with deteriorated lubricant unchanged or in a very hot condition brings the lubricant
ignites and this may cause serious accident.
Keep the lubricant well controlled (See pages 17 and 18).
2. Do not operate the unit without protective equipment. In case of SHUTDOWN, read articles of SHUT-
DOWN and SOLUTIONS of the manual to remove the cause. If the cause is unknown, inform and ask
your dealer or Hitachi Service Station.
CAUTION
● Running the unit with its loose belt brings not only lowered discharge air capacity due to its slipping,
but also life of belt shortened. If belt is broken during the operation, the lubricant blows out of the
Suction Throttle Valve. Be sure to carry out your constant check on belt.
● If the unit stops due to the function of Temperature Relay, check leakage in the mechanical seal and
replace it if lubricant leak is found there.
24
6. SYSTEM OF EACH COMPONENT
Air discharge
Cooling fan
Fan motor
Minimum Pressure/
Aftercooler
;; ; ; ;;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;
; ;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;
;;
;; ;
;;
;; ;;
;
Discharge
;;;
; ;
Compressor
;;
air end
;;
63E
;;; ;; ;;; ;; Oil tank
;;
;;
;;; ;; ;;; ;; Oil separator
;;
;;;
;;;
;;
;;
;;;
;;;
;;
;;
;;;
;;;
;;
;;
;;;
;;;
;;
;;
;;;
;;;
;;
;; ;;;
;;; ;;
;;
;;;
;;;
;;
;; ;;;
;;; ;;
;;
;;; ;; ;;; ;;
Oil cooler
;;;
;;;
;;
;; ;;;
;;; ;;
;;
;;; ;; ;;; ;; TH1
;;; ;; ;;; ;; Motor
;;; ;; ;;; ;;
Oil filter
Oil
discharge
;
25
6. SYSTEM OF EACH COMPONENT [Capacity Control System]
;;;;;;;;
;;;;;;;;
;;;;;;;;
;;;
2φ Orifice 2φ Orifice From
suction
;
2φOrifice filter
NC
NC NO NC NO
NO
Pressure
; Check Valve
To Compressor
air end
Operation air flow
At start : 20P (NO-COM)
Suction throttle
20U (NO-COM)
To primary side valve closed.
To aftercooler 20UV (NO-COM)
of Air End
Load : 20P (NC-COM)
Pressure Suction throttle
sensor
20U (NC-COM)
valve open.
20UV (NC-COM)
PS Scavenge filter U-type: Pressure modulator Suction throttle
with orifice opens valve closes partly.
Unload
I-type: 20P (NO-COM)
Suction throttle
20U (NO-COM)
valve closed.
20UV (NC-COM)
At stop : 20P (NO-COM)
Suction throttle
;;;
;
20U (NO-COM)
;;;
valve closed.
20UV (NO-COM)
;
Oil separator ☞ See p.12 for capacity control type setting change.
p.9 for setting change of reset pressure.
6.2.1 Types of Capacity Control
Type of capacity control Purpose S-series M-series
U-type (Suction unload type): Gradually controls discharge This is applicable when fluctuation
air capacity by opening or closing the suction throttle valve of discharge pressure must be kept ○ ○
according to the increase in discharge pressure. less.
I-type (Integral unload type): Fully closes the suction throttle This is applicable when air con-
valve when discharge pressure reaches to cut out pressure, sumption is less and the unit is in
and fully opens by cut in pressure. At full close, pressure continuous use, and when the
inside the oil separator is discharged until it reaches to the power consumption at unload op-
atmosphere and economize power consumption more . eration must be kept less.
The discharge pressure of the compressor is variable within
the pressure range as follows: (Each pressure value is set
by digital monitor on the panel) ◎ ○
Specification MPa 0.69 0.83 0.92 (Standard setting)
discharge pressure kgf/cm2 7.0 8.5 9.4 At delivery from factory.
P-type (Motor ON-OFF control type): In addition to This is applicable when the unit is
U-type and I-type control, the system automatically very often operated unloaded, or − ◎
stops the motor when a consumed air capacity is less. when the air consumption intermit- (Standard setting)
(This type fluctuates pressure like I-type.) tently fluctuates. At delivery from factory.
26
6. SYSTEM OF EACH COMPONENT [Capacity Control System]
Time
The I-type models control the capacity as shown
by the figure below.
(1) When “pressure fluctuation cycle: t” is less t <1min. t ≧1min.
t =?min.
than 60 seconds, U-type (suction unload type)
control is adopted.
(2) When “pressure fluctuation cycle: t” is longer
than 60 seconds, I-type (integral unload type)
control is adopted.
q w
Suction Integral
Unload Unload
once every
3 minutes
;;;;;
Load Factor %.
100
q
;;;;;
w w w
0 Time
Type) is adopted.
(2) If “pressure fluctuation cycle: t” is over 60 sec- t <1min. t ≧1min.
t =?min.
onds and the air consumption is larger than
50% of its rated capacity, I-Type control (Inte-
gral Unload Type) is adopted. Q≧50% Q<50%
Air Consumption Q
(3) If “pressure fluctuation cycle: t” is over 60 sec-
onds and the air consumption is less than 50% NO Number of Stops
of its rated capacity, P-Type control (Motor ON- q w Less than 3 within
60 minutes ?
;;;;;;;
3 minutes
is limited to 3 times during 60 minutes.
;;;;;;;
Load Factor %.
IMPORTANT 100
q
In case of P-Type (Motor ON-OFF Control Type), w w w
(1) The Motor will not start again for 45 seconds when e e
0 Time
it stops.
(2) Pressure in discharge pipes may largely decrease
before restarting. Installation of an air reservoir
(larger than 0.7 m3) is required.
27
7. INSTRUCTIONS FOR INSTALLATION
28
7. INSTRUCTIONS FOR INSTALLATION [Instructions When Installing]
CAUTION
● Use the compressor in a room. Moisture or powder dust will damage the compressor when it is installed outside.
● Install the compressor in a room equipped with both intake air port and discharge air port and where enough
ventilation is available. Otherwise, discharged heat from the compressor makes room temperature rise and will
cause shutdown to the compressor.
Fan
If the location is not roomy enough,
provide a ventilation fan to main- Maintenance Space (Back space)
tain the ambient temperature Keep a space of 0.5m or more.
around the unit at 40 degree C. or
below.
29
7. INSTRUCTIONS FOR INSTALLATION [Instructions When Piping]
Discharging Air
Stop Valve
Drain Valve
Drain Valve
Drain valve
From Compressor
30
7. INSTRUCTIONS FOR INSTALLATION [Compressor Room Ventilation]
31
7. INSTRUCTIONS FOR INSTALLATION [Instructions on Electrical Wiring]
IMPORTANT
Right cover
These are values for the cables less than 10m in length.
For over 10m, thicker cable is required. In such case,
keep the thickness below its maximum value on the com-
pressor side by using intermediate terminals.
Terminal board
7.6.2 Connecting earth leakage circuit breaker Ground terminal
Rubber bush
CAUTION
● Be sure to equip a earth leakage circuit breaker to the Power. Wiring with only disconnector like Knife
Switch is not sufficient and may not protect the compressor and cause burning when short circuit occurs.
● Be sure that the compressor is appropriately grounded. If not, this can cause electric shock accident or
shutdown to the compressor. Do not use Steel Skeleton as a ground for the compressor. This may cause
malfunction. Ground the cable by itself into the earth.
32
7. INSTRUCTIONS FOR INSTALLATION [Instructions on Electrical Wiring]
33
7. INSTRUCTIONS FOR INSTALLATION [Instructions on Electrical Wiring]
42 EF3 ON
TB1 R S T B3 B4 T2 OFF
12345 678
SW1
C
(R) CN11
1
T1 (W)
S1 PS 2 PWB1(HC30)
R1 3
(B)
CT 4
(I) 11 12 13 TH2
(2)A (1) CN10
∼ 1
(K)
88F
2
21 22 23
TH1
CN9
1
49M2 2
11 12 13 11 12 13 63SV CN8
2 4 6 1 Y6 Y42
52 42
2
21 22 23 21 22 23
Y Z X
19.2V 9.2V
49M1 CN4
U V W
2 4 6 4 3 2 1 7 5 3 1
CN14
U V W
11 12 13
IM2
(O)
(O)
(Y)
(Y) 11 10 9
IM1 6
55kW 21 22 23
Z X Y
S3
8
7
9 CE
10
11
95
49M1
ATTENTION: 96
B1 B1
1. Wiring and device shown with short dashes line is option 12 6 42
or out of scope of supply. 95 B2 B2
2. Rated no-voltage contact is AC200/220V3A (Max.). 49M2
3. Signal input for remote operation/stop is AC200/220 V. 96
Connect it each with one-shot circuit of 500 ms or more. 1 14
CE 88F CN20 CN23
Symbol Part name Symbol Part name CE CN28 3 A1
IM1 Compressor motor CT Current transformer
52 15 16 3 1 1 2
IM2 Cooling fan motor PS Pressure sensor 2 1 13 A2
FM Cooling fan motor (for starter) 63E Pressure switch
CE
52 Main electromagnetic contactor 63SV Pressure differential sensor of air intake filter
C2 C1 C1 C1 C1 CE CE CE CE
42 Electromagnetic contactor for SW1 Dip switch for setting
S S S 42 6 S
6 Electromagnetic contactor for SW2 Dip switch for capacity control FM K 88F 52 K K K 63E
20UV
88F Electromagnetic contactor for fan SW3 Slide switch for dryer operation C1 C2 C2 C2 C2
34
7. INSTRUCTIONS FOR INSTALLATION [Instructions on Electrical Wiring]
Set switch
Model
Symbol Name
OSP-55MA OSP-55SA
Flat cable SW1 Function No.5 ON(55kW) No.5 ON(55kW)
SW2 Capacity control setting AUTO I - type
SW3 Dryer operation setting Stop Stop
AUTO name plate provided not provided
CN12
19
DC24V 1
SW2 SW3 Tr(Y1) 2 20
CN7 13 RY1 14
3 Short circuit
AUTO
JP1: External reversal phase
relay setting
name
plate
4
5
TB2
( In case of remote operation,
be sure to remove short circuit line. )
CN2 AC200V
30 30
1 External remote setting
AC200/220V input 3
23 29 :“a”contact
Y3 24 AC200V 28
5
}
Remote setting Remote stop
CN1 27 500ms or more
Remote operation 25
Dryer answer 1 26 One-shot input.
27 Remote start
Operation answer 3 25
Y1 26 S2 phase
Overload 5 24
28
7 23 Shutdown (Y3):dry“a”contact (3A)
CN15 S2
1 22 22
Y52 Y20 Y52C Reversal phase 3
T3 21 21 Operation (Y1):dry“a”contact (3A)
R2
5 RY1
DSA 7 (G)
TR1
CN6 CN5 CN3
5 3 1 7 5 3 1 5 3 1 3 2 1 CN13
8 7 S3 S3 6 (W)(R)
(G)
CE
S
K
CE CE
Relay output
Symbol Name Performance
Y1 Operation relay ON at operation self-hold
RY1 Operation output ON at operation self-hold
CN24
Y3 Shutdown output ON at shutdown
2 1 Y52 Operation relay ON at motor operation
Y6 Relay for ON at operation, OFF at operation
C Y42 Relay for ON at operation
CE CE CE Y20 Blow-off valve relay 2 sec. later ON at Load
CE
20P 20U Y52C Dryer operation relay OFF at ordinary times
CE CE
Thermal set value (200 /220 V class)
Set Value 49M1 49M2
Note: Wiring Color Model Type A Type A
R : Red
W : White TR150B-2E TR12B-2E
OSP-55S/M5A 128 11
B : Black (130A) (11A)
O : Orange TR150B-2E 119 TR12B-2E
Y : Yellow OSP-55S/M6A 11
(130A) 112 (11A)
G : Green Note) 49M1 Setting Value for 60Hz Spec. shows in case of 200/220V.
35
7. INSTRUCTIONS FOR INSTALLATION [Instructions on Electrical Wiring]
EF2 SP SS
EF4 S2
TR 46 42 ON
T3
TB1 R S T (500VA) OFF
B3 B4 12345 678
46 SW1
C
(R) CN11
1
(W)
PS 2 PWB1(HC30)
T1
S1 3
(B)
R1 4
CT TH2
(2) (1)
(I) CN10
A
∼
1
(K) 2
TH1
CN9
11 12 13 1
11 12 13 11 12 13 2
88F
52 42 63SV
21 22 23 CN8
21 22 23 21 22 23 1 Y6 Y42
Y Z X 2
49M1 49M2
19.2V 9.2V
2 4 6 2 4 6
CN4
U V W
11 12 13 4 3 2 1 7 5 3 1
U V W CN14
IM1 6
55kW 21 22 23 IM2 (O)
(O)
(Y)
(Y) 11 10 9
Z X Y
2.2kW
S3
8
7
9 CE
10
11
95
ATTENTION: 49M1
1. Wiring and device shown with short dashes line is option 96
B1 B1
or out of scope of supply. 12 6 42
2. Rated no-voltage contact is AC200V3A (Max.). 95 B2 B2
3. Signal input for remote operation/stop is AC200 V. 49M2
Connect it each with one-shot circuit of 500 ms or more. 96
1 14
Symbol Part name Symbol Part name
CE 88F CN20 CN23
IM1 Compressor motor PS Pressure sensor CE CN28 3 A1
IM2 Cooling fan motor 63E Pressure switch
52 15 16 3 1 1 2
FM Cooling fan motor (for starter) 63SV Pressure differential sensor of air intake filter 2 1 13 A2
52 Main electromagnetic contactor DSA Arrestor
CE
42 Electromagnetic contactor for SW1 Dip switch for setting
C2 C1 C1 C1 C1 CE CE CE CE
6 Electromagnetic contactor for SW2 Dip switch for capacity control
S S S 42 6 S
88F Electromagnetic contactor for fan SW3 Slide switch for dryer operation FM K 88F 52 K K K 63E
20UV
49M Thermal relay TR,TR1 Control transformer C1 C2 C2 C2 C2
36
7. INSTRUCTIONS FOR INSTALLATION [Instructions on Electrical Wiring]
Set switch
Model
Symbol Name
OSP-55MA OSP-55SA
Flat cable SW1 Function No.5 ON(55kW) No.5 ON(55kW)
SW2 Capacity control setting AUTO I - type
SW3 Dryer operation setting Stop Stop
AUTO name plate provided not provided
CN12
19
DC24V 1
SW2 SW3 Tr(Y1) 2 20
CN7 13 RY1 14
3 Short circuit
AUTO
JP1: External reversal phase
relay setting
name
plate
4
5
TB2
( In case of remote operation,
be sure to remove short circuit line. )
CN2 AC200V
30 30
1 External remote setting
AC200V input 3
23 29 :“a”contact
Y3 24 AC200V 28
5
}
Remote setting Remote stop
CN1 27 500ms or more
Remote operation 25
Dryer answer 1 26 One-shot input.
27 Remote start
Operation answer 3 25
Y1 26 S2 phase
Overload 5 24
28
7 23 Shutdown (Y3):dry“a”contact (3A)
CN15 S2
1 22 22
Y52 Y20 Y52C Reversal phase 3
T3 21 21 Operation (Y1):dry“a”contact (3A)
R2
5 RY1
DSA 7 (G)
TR1
CN6 CN5 CN3
5 3 1 7 5 3 1 5 3 1 3 2 1 CN13
8 7 S3 S3 6 (W)(R)
(G)
CE
S
K
Relay output
CE CE
Symbol Name Performance
Y1 Operation relay ON at operation self-hold
RY1 Operation output ON at operation self-hold
Y3 Shutdown output ON at shutdown
Y52 Operation relay ON at motor operation
Y6 Relay for ON at operation, OFF at operation
Y42 Relay for ON at operation
CN24 Y20 Blow-off valve relay 2 sec. later ON at Load
Y52C Dryer operation relay OFF at ordinary times
2 1
CAUTION
● Before Maintenance work, read “To Use in Safety” (page 2) again carefully.
● Be sure to turn the POWER OFF when check or maintenance is carried out. If not, such work may cause
serious accident like electric shock.
● When part of the unit needs to be disassembled or removed, be sure to release its internal pressure to
the level of ambient air pressure. Residual high pressure inside the unit will blow out of it when a bolt,
pipe or other part is removed, and may cause unexpected accident.
IMPORTANT
(1) ○ mark on the maintenance standard chart at pages 39 to 40 means an item which the user can carry out.
(2) mark means that you ask your dealer or Hitachi’s Service Station to do.
(3) Except for the case as specifically stated otherwise, maintenance time means consecutive maintenance schedule, e.g., once
every year stands for another maintenance for the next year, and after next year, and so forth.
(4) Operation Record Logbook is quite important for periodic maintenance as well as for finding out of cause for repair promptly in
case of Shut-Down. It is recommended to record the Logbook which is attached to the end of this manual.
8.2 Maintenance Standards (A) · · · In case of annual run hour less than 6,000 hours
The maintenance items marked with ○ must be carried out by users or, optionally, may be ordered to the dealer.
The maintenance items marked with must be ordered to the dealer.
Inspection time Reference
Maintenance part and item Check Note page No.
Daily weekly 1 Month 1 Year 2 Years 4 Years 8 Years
Oil level gauge Oil level check ○ Oil level must be within red lines during operation. 17
Discharge temp. Discharge temp. check ○ Must be between 65 and 100 degree C. 8
Oil tank drain Condensation check ○ 16
Oil scavenge filter Clogging check ○ Feel recovery pipe by hand. 42
Safety valve Performance check ○ Check by hand 41
Replenish every 1,500~2,000 hours
Lubricant (genuine synthetic oil) Replenish/Analysis (○) Sampling analysis every 3,000 hours 17
Mechanical seal Oil leak check ○
Clean if the error code of an element clogging appears on
Air intake filter Replacement ○ the digital monitor. Replace whenever the number of times of 44
cleaning has reached 6 times even within one year interval.
39
8. PERIODIC MAINTENANCE [Maintenance Standards (B)]
8.3 Maintenance Standards (B) · · · In case of annual run hour less than 3,000 hours
The maintenance items marked with ○ must be carried out by users or, optionally, may be ordered to the dealer.
The maintenance items marked with must be ordered to the dealer.
Inspection time Reference
Maintenance part and item Check Note page No.
Daily weekly 1 Month 1 Year 2 Years 4 Years 8 Years
Oil level gauge Oil level check ○ Oil level must be within red lines during operation. 17
Discharge temp. Discharge temp. check ○ Must be between 65 and 100 degree C. 8
Oil tank drain Condensation check ○ 16
Oil scavenge filter Clogging check ○ Feel recovery pipe by hand. 42
Safety valve Performance check ○ Check by hand 41
Replenish every 1,500~2,000 hours
Lubricant (genuine synthetic oil) Replenish/Analysis (○) Sampling analysis every 3,000 hours 17
Mechanical seal Oil leak check ○
Belt, Pulley Inspection ○ Visual check of wear, check abnormal noise. 49
Clean if the error code of an element clogging appears on
Air intake filter Replacement ○ the digital monitor. Replace whenever the number of times of 44
cleaning has reached 6 times even within two years interval.
40
8. PERIODIC MAINTENANCE [Safety Valve, Capacity Control System]
WARNING
Oil scavenge
filter
Do not place your face near Safety Valve
when to check its performance. Compressed
air can come out and it is dangerous.
41
8. PERIODIC MAINTENANCE [Oil Scavenge Filter]
Scavenge pipe
Air blow by
compressed air
42
8. PERIODIC MAINTENANCE [Replacement of Oil Filter]
Open Close
CAUTION
Saucer ● If a tool like filter wrench or pipe wrench is
used to fasten the oil filter element,
element’s housing part may be damaged
or deformed, and will cause leak or break-
ing. Be sure to fasten it by the hand tightly.
● When the Oil Filter clogged, lubricant sup-
ply to the compressor lessens and dis-
charged air temperature rises.
This makes Discharge Temperature Relay
to actuate and the compressor eventually
stops. Also, lubricant feeding to the bear-
ings becomes insufficient and this may
cause shutdown of the unit.
● Be sure to change oil filter element peri-
odically.
43
8. PERIODIC MAINTENANCE [Cleaning and Replacement of Air Intake Filter]
CAUTION
If atmospheric air contains the car fumes and/
or the soots from incinerators and boilers, the
air intake filter element will be clogged very
earlier than otherwise. If this is the case,
check the atmosphere around the A
installed, and take effective measures that will
enable the A to suck the fume-less
and soot-less air. For example, provide a suc-
tion duct or re-select a cleaner installation
location.
44
8. PERIODIC MAINTENANCE [Cleaning of Cooler]
400∼500mm
IMPORTANT
Cleaning cover
45
8. PERIODIC MAINTENANCE [Minimum Pressure / Check Valve]
Pull down.
CAUTION
Do not fail to replace the two oil separators
Remove. at the same time.
Housing
47
8. PERIODIC MAINTENANCE [Replacement of Oil Separator]
;;;;;;
Element Attach the housing r Out of the two oil separators, install first the
;;;;;;
[Figure D] rear one as follows.
;;;;;;
Head
;;;;;;
t Silicon grease is spread on the O-ring. Do not
wipe it off and just set in a ditch on the element
O-ring ;;;;;;
;;;;;;
head.
y Reverse the above procedure and set the ele-
;;;;;;
Element Element
Gasket ment into the housing. While taking care not to
Push
up. ;;;;;;
;;;;;;
bend the recovery pipe, and set it at right under
the element head by sliding along the recovery
;;;;;;
;;;;;;
pipe. [Figure D]
u Firstly, pull only the element up. Hold it with
;;;;;;
Gasket both hands and push it up so that the end plate
;;;;;;
Head
;;;;;;
of the element adheres to the head. At this time,
be careful not to allow the gasket slip out from
[Figure E]
Housing
;;;;;;
O-ring
;;;;;;
the head. [Figure E]
;;;;;;
Housing i Hold the housing by both hands and put it on
the thread portion of the head. At this time, be
careful not to allow the gasket slip out from the
head.
o Fasten the housing in by the hand instead of
using a tool. Housing must be securely fastened
by turning it at 1/5 round or more.
Housing [Figure F]
Turn
here. !0 Put the attached caution plate on a clearly vis-
ible position on the front surface of the unit.
Attached
caution [Figure G]
plate
!1 Repeat the above steps to install the front oil
separator.
[Figure F] [Figure G]
48
8. PERIODIC MAINTENANCE [Inspection of Belt]
49
9. WHEN IT IS NOT USED FOR LONG TIME
Be sure to follow the measures below if the compressor is stored or stopped by reason of
Power supply problem for a long time. (Follow ○ marked items)
CAUTION
● The compressor air end (screw block) can have rustings if no anti-rusting measure
(Measures before storing, sealing) are done to it. If the unit is restarted, this may
result breakage in Locks or Bearings of the compressor.
● If necessary measures are failed when to restart the unit, it may result damage to the
Locks or Bearing, burning in the motor, excessive wear of M-sheave and V-Pulley,
breakage of V-Belt to the compressor.
● If lubricant has not been replaced when necessary or if enough flashing has not
been done to the unit, the lubricant deteriorates earlier than usual and this may
result clogging in Lock and Oil Cooler to the compressor.
50
10. PARTS LIST
Motor Pulley
ITEM
NO. DESCRIPTION
101 Motor
106 M-Sheave
108 Motor Base
112 101 109 Belt
112 M-Sheave Key
120 V-Pulley
121 V-Pulley Washer
122 V-Pulley Bolt
140 129 Main Base
130 Rubber Plate (1)
132 Rubber Plate (2)
137 Square Washer
140 Belt Adjusting Bolt
120
121
122
109 108
106 132
129
130
137
51
10. PARTS LIST
Cooling Fan
ITEM
NO. DESCRIPTION
622
156 Bell-mouse
540 Cooler
621 Fan Motor
622 Fan Shaft Key
624 Fan washer
625 Set-bolt
650 Air exhaust duct
621 652 Impeller
650
652 540
156
624
625
ITEM
NO. DESCRIPTION
201 Unloader Case
219 202 Unloader Cover
203 Cap Seal
204 Piston
205 Spindle
206 Unloader Spring
218
202 209 Unloader Valve
214 210 Valve Seat
212 233
211 211 Valve Seat Holder
220 212 Unloader Cover Packing
210 213 Bush Metal
204 209 214 Bolt, valve seat holder
237
203 215 215 Unloader Body Packing
217 Suction Pipe
205 224 218 Unloader O-ring
235
219 Unloader Body
213 217 220 Unloader Joint
206 201 221 Suction Packing
235 224 Pressure Differential Sensor
233 Air Intake Filter Element
235 Band
237 Air Intake Filter Housing
221
52
10. PARTS LIST
ITEM
NO. DESCRIPTION
507 Modulator Valve
508 Modulator Valve Cover
509 Modulator Valve Spring
510 Modulator Valve Diaphragm Assembly
511 Modulator Valve Rubber Packing
512 Modulator Valve Body
518 517 Regulator Valve
508 518 Regulator Valve Cover
519 Regulator Valve Spring (1)
556 520 Regulator Valve Diaphragm
519 521 Regulator Valve Body
522 Regulator Valve Set
509 520 523 Regulator Valve Spring (2)
524 Regulator Valve O-Ring
552 Minimum Pressure / Check Valve
510 556 O-ring
521 557 557 Minimum Pressure Valve Piston
558 Check Valve Piston
522
511
523
524
558
512
Modulator Valve 507 Regulator Valve 517 Minimum Pressure / Check Valve 552
ITEM
305 NO. DESCRIPTION
I
A CH
306 HITW 138 Vibration-proof rubber
※330 NE 301 Oil Tank
※332 302 Oil Separator
307 320 303 O-ring
305 Safety Valve
319 306 Scavenge Filter with Orifice
307 Scavenge Pipe Joint
550
313 Oil Level Gauge
314 Bolt
315 M12 Seal Washer
317 Float
319 Replenish Port O-ring
320 Replenish Port Plug
324 Thermister
324 313 325 Oil Level Gauge Assembly
301 ※ 330 Lubricant (NEW A OIL 4R)
303 ※ 332 Lubricant (NEW A OIL 20R)
※ 333 Special tools (for oil separator)
550 Element head
※ Option
314
315
302
325
138
※333
53
10. PARTS LIST
561
664
670
562
Oil Piping
325
ITEM
NO. DESCRIPTION
325 Thermister
531 Check Valve
571 Oil Temperature Control Valve Body
572 Oil Temperature Control Valve
573 O-ring
579 Drain Valve
531 583 Check Valve
585 Oil Filter
591 Oil Filter Element
696 Oil Temperature Control Valve Spring
585
591
696
583
572
573
571
579
54
10. PARTS LIST
Control Piping
672
ITEM
NO. DESCRIPTION
To 533 501 Solenoid valve
Starter 505 Pressure gauge
Panel
506 505 506 Pressure gauge piping
532 507 Modulator Valve
517 Regulator Valve
531 Check Valve
531 533 Pressure sensor
588 Adaptor
672 Pressure switch
501
501
531
588
501
588
532
588
517
507
532
650
779
55
10. PARTS LIST
Enclosure
717 ITEM
714 NO. DESCRIPTION
419 Rubber Bush
708 435 Rubber Bush
713 701 Door
435 702 Magnet
704 Front Cover
706 Instrumental Panel
707 Chain
708 Right Side Cover
419 711 Power Cover
706 713 Top Cover
711
714 Inspection Cover, air intake filter
723 717 Rear Top Cover
752 718 Left Side Cover
737 720 Noise Proofing Plate
721 Common Base
702 723 Rear Frame
737 Side Cap
752 Rear Bottom Cover
721
720
701
718 707
704
Instrumental Panel
ITEM
427 NO. DESCRIPTION
420 Instrumental Panel Seat
428 423 Operation Printed Circuit Board
427 Printed Circuit Board Cover
428 Ammeter
706 Instrumental Panel
706 737 Side Cap
423
737
420
56
10. PARTS LIST
Starter Panel
ITEM
400 NO. DESCRIPTION
400 Starter Panel Assembly
436 401 Electromagnetic Switch (52)
403 Glass Tube Fuse
408 Electromagnetic Contactor (42)
437 424(S-series) 409 Electromagnetic Contactor (6)
425(M-series) 410 Electromagnetic Switch (88F)
412 Terminal Board
418 426 413 Terminal Board
403 415 Copper Plate Assembly
418 Control-Relay
413 419 Rubber Bush
473 424 CPU Printed Circuit Board (for S-series)
425 CPU Printed Circuit Board (for M-series)
426 Printed Circuit Board Transformer
410 435 Rubber Bush
408 436 Rubber Bush
437 Rubber Bush
468
401 468 Rubber Bush
473 Cooling Fan
486 Rubber Bush
412
419
57
This page is intentionally blank.
58
11. OPERATION RECORD LOGBOOK
Suction Air Current Discharge Remarks
Operation Hour Integral Discharge
Temperature Temperature Lubricant
Operating Pressure
Date ℃ A ℃ Replenishment
Hours MPa Parts Replacement,
Start Stop h {kgf/cm2} Control Value Control Value Control Value R Other matters and To be Recorded
0∼40 Under Rating Under 100
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
59
12. STANDARD SPECIFICATION
■ Compressor Specification
60
Note down your Compressor’s Specifications for reference in the future.
Model OSP- kW Hz