15.1.2 Date: 1/29/2022
Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1,00 kVA
Model Equations 0,10 %
Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 1
rated Active Reactive Power
Voltage Bus-voltage Power Power Factor Current Loading Additional Data
[kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%]
Barra1
8,50 1,00 8,50 0,00
Cub_1 /Sym Generador1 10,75 3,66 0,95 0,77 75,71 Typ: SL
Cub_2 /Tr2 T1 10,75 3,66 0,95 0,77 67,48 Tap: 0,00 Min: 0 Max: 0
Barra2
100,00 0,84 84,37 -1,30
Cub_2 /Lne LineA2_3 10,75 3,39 0,95 0,08 14,43 Pv: 1249,58 kW cLod: -0,00 Mvar L: 1,00 km
Cub_1 /Tr2 T1 -10,75 -3,39 -0,95 0,08 67,48 Tap: 0,00 Min: 0 Max: 0
Barra3
100,00 0,76 75,50 0,84
Cub_2 /Tr2 T2 9,50 3,39 0,94 0,08 67,48 Tap: 0,00 Min: 0 Max: 0
Cub_3 /Lne LineA2_3 -9,50 -3,39 -0,94 0,08 14,43 Pv: 1249,58 kW cLod: -0,00 Mvar L: 1,00 km
Barra4
10,00 0,75 7,48 -0,62
Cub_2 /Lod Carga 9,50 3,12 0,95 0,77 Pl0: 9,50 MW Ql0: 3,12 Mvar
Cub_1 /Tr2 T2 -9,50 -3,12 -0,95 0,77 67,48 Tap: 0,00 Min: 0 Max: 0
DIgSILENT Project:
PowerFactory
15.1.2 Date: 1/29/2022
Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1,00 kVA
Model Equations 0,10 %
Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 2
rtd.V Bus - voltage Voltage - Deviation [%]
[kV] [p.u.] [kV] [deg] -10 -5 0 +5 +10
Barra1
8,50 1,000 8,50 0,00
Barra2
100,00 0,844 84,37 -1,30
Barra3
100,00 0,755 75,50 0,84
Barra4
10,00 0,748 7,48 -0,62
DIgSILENT Project:
PowerFactory
15.1.2 Date: 1/29/2022
Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1,00 kVA
Model Equations 0,10 %
Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 3
Volt. Generation Motor Load Compen- External Power Total Load Noload
Level Load sation Infeed Interchange Interchange Losses Losses Losses
[MW]/ [MW]/ [MW]/ [MW]/ [MW]/ to [MW]/ [MW]/ [MW]/ [MW]/
[kV] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar]
8,50 10,75 0,00 0,00 0,00 0,00 0,00 0,00 0,00
3,66 0,00 0,00 0,00 0,00 0,00 0,00 0,00
100,00 kV 10,75 0,00 0,00 0,00
3,66 0,27 0,27 0,00
10,00 0,00 0,00 9,50 0,00 0,00 0,00 0,00 0,00
0,00 0,00 3,12 0,00 0,00 0,00 0,00 0,00
100,00 kV -9,50 0,00 0,00 0,00
-3,12 0,27 0,27 0,00
100,00 0,00 0,00 0,00 0,00 0,00 1,25 1,25 0,00
0,00 0,00 0,00 0,00 0,00 -0,00 -0,00 0,00
8,50 kV -10,75 0,00 0,00 0,00
-3,39 0,27 0,27 0,00
10,00 kV 9,50 0,00 0,00 0,00
3,39 0,27 0,27 0,00
Total: 10,75 0,00 9,50 0,00 0,00 0,00 1,25 1,25 0,00
3,66 0,00 3,12 0,00 0,00 0,00 0,54 0,54 0,00
DIgSILENT Project:
PowerFactory
15.1.2 Date: 1/29/2022
Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1,00 kVA
Model Equations 0,10 %