Wärtsilä id: DBAC537648 -

Wärtsilä Finland Oy Power plants VEO Oy Diesel and Gas

Document ID: KD.10817.D5001


Date: 12.02.2013
Status: RELEASE
Made: Sami Hurin
Checked: MW
Approved: KeR
Revision: - 18.02.2013
Project: KD.10817 PAD 9
Document type: Setting document

5. SETTING DOCUMENT

doc rev 1.13


Wärtsilä id: DBAC537648 -

TABLE OF CONTENTS

5.1 SETTINGS FOR CFA901


5.2 SETTINGS FOR CFC0_1
5.3 SETTINGS FOR CFE0_1
5.4 OTHER SETTINGS
5.4.1 SETTINGS BAO901 & BAO902 OUTGOING FEEDER PROTECTION RELAY VAMP 50
5.4.2 SETTINGS BAA901 STATION TRAFO PROTECTION RELAY VAMP 50
5.4.3 SETTINGS BAM901 BUSBAR RELAY VAMP 55

doc rev 1.13


PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

SETTING VALUES ACCORDING TO:


a) Wärtsilä order no: Dated:
or b) Technical specification no: WDAAA114515k Dated: 4.6.1999 MOe/Östman
or c) VEO document no: Dated:

TEST ACCEPTANCE CRITERIA:


a) Wärtsilä order no: Dated:
or b) VEO test&inspection plan: Doc no:
or c) VEO internal procedure: Doc no:

TEST PERFORMED BY:


a) Made:
b) Checked:
c) Approved:

Wärtsilä id: DBAC537648 -


doc rev 1.13
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

AUTO SYNCHRONIZER A10 LOCATION CFA901


Description Pos. Area Setting value Unit Remark
Maximum voltage difference Vmax 2 … 12% 5 %
Maximum frequency difference fmax 0.1 … 0.5 Hz 0.3 Hz
Proportional band of PI controller Xp 0 … 2.5 Hz 1.0 Hz
Pulse lenght of PI controller Tn 0 … 500 ms 250 ms
Breaker closure time 0 … 200 ms 80 ms

CHECK SYNCHRONOSCOPE P3 LOCATION CFA901


Description Pos. Area Setting value Unit Remark
Maximum voltage difference U +/- 1 … 10% +/- 8 %
Maximum phase difference φ +/- 5 … 20 deg +/- 10 deg
Synchronizing delay tR 0…1s -
Synchronizing delay td 0…1s 0.1 s
Ubus offset % OFF, 10, 20, 30, 40 % OFF

PARALELLING RELAY A4 LOCATION CFA901


Description Pos. Area Setting value Unit Remark
Voltage difference U 10 … 15% 10 %

POWER MONITORING UNIT VAMP 260 LOCATION CFA901


Description Pos. Area Setting value Unit Remark
SCALING For BAO901

Wärtsilä id: DBAC537648 -


Current transformer Iprim 2000 A
Isec 1 A
Voltage transformer Uprim 13800 V
Usec 110 V
Voltage meas mode 3LL

doc rev 1.13 Page 4/30 Note! Settings to be checked at site


PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

POWER MONITORING UNIT VAMP 260 LOCATION CFA901


Description Pos. Area Setting value Unit Remark
SCALING For BAO902

Current transformer Iprim 2000 A


Isec 1 A
Voltage transformer Uprim 13800 V
Usec 110 V
Voltage meas mode 3LL

POWER MONITORING UNIT VAMP 96 LOCATION CFA901


Description Pos. Area Setting value Unit Remark
SCALING For BAA901

Current transformer Iprim 150 A


Isec 1 A
Voltage transformer Uprim 13800 V
Usec 110 V
Voltage meas mode 3LL

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 5/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

GENERATOR PROTECTION RELAY VAMP 210 LOCATION CFC0_1


Description Pos. Area Setting value Unit Remark
SCALING

Generator nom power Sgn 10913 kVA EngineType W32B2


Generator nom voltage Ugn 13800 V Cyl 20
Nominal shaft power Pm 8347 kW Pcyl 450 Nominal shaft power 8730kW without derating
Nominal frequency Hz 60
Nominal Current Ign 457 A
Current transformer Iprim 500 A
Isec 1 A

Voltage transformer Uprim 13800 V


Usec 110 V

Core-balance current transf. 1 I01prim 50 A


I01sec 1 A

Core-balance current transf. 2 I02prim 50 A


I02sec 1 A

UNIT TRANSFORMER
Unit transformer Transf. OFF
Busbar nominal voltage 13800 V
Generator side nominal voltage 13800 V
Unit transf. connection group Yd11

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 6/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

GENERATOR PROTECTION RELAY VAMP 210 LOCATION CFC0_1 TESTED GENSET


Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

OVERCURRENT STAGE I> (51) ON


Overcurrent stage I> I> 0.5 … 4.00 * Ign 548 A 1.2 Ign
Time multiplier of stage I> k 0.05 … 3.2 s 0.2 s
IDMT function Type NI

OVERCURRENT STAGE I>> (50) ON


Overcurrent stage I>> I> 0.5 … 20 x Ign 1141 A 2.5 Ign
Operating time of stage I>> t> 0.04 … 300 s 0.6 s

OVERCURRENT STAGE Iv> (51V) OFF


Overcurrent stage Iv> Iv> 0.5 … 20 x Ign 457 A 1.0 Ign
Operating time of stage Iv> tv> 0.04 … 300 s 10 s
start x1 13110 V 0.95 Un
stop x2 14490 V 1.05 Un
start y1 525 A 1.15 In
stop y2 457 A 1.0 In

UNBALANCE LOAD STAGE I2> (46) ON


Unbalance load stage I2> K2 0.02 … 0.2 x Ign 37 A 0.08 pu
Operating time of stage I2> K1> 1 … 40 s 10 s
Type of op.time Type INV
Inverse delay K1 1 … 40 s 20 s

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 7/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

GENERATOR PROTECTION RELAY VAMP 210 LOCATION CFC0_1 TESTED GENSET


Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

RESIDUAL CURRENT STAGE I0>>> (51N) OFF


Residual current stage I0>>> I0> 0.02 … 1.0 x I01n 5.0 A 0.10 pu
Delay for stage I0>>> t0> 0.1 … 300 s 0.5 s
Io Input I0 Io1 … Io2 Io1

RESIDUAL CURRENT STAGE I0>>>> (51N) OFF


Residual current stage I0>>>> I0> 0.02 … 1.0 x I01n 10 A 0.20 pu
Delay for stage I0>>>> t0> 0.1 … 300 s 1.0 s
Io Input I0 Io1 … Io2 Io1

DIRECTIONAL RESIDUAL CURRENT STAGE I0DIR> (67N) ON


Residual current stage I0DIR>> I0> 0.02 … 1.0 x I01n 2.0 A 0.04 pu
Delay for stage I0DIR>> t0> 0.1 … 300 s 0.3 s
Uo for stage I0DIR>> 10 %

RESIDUAL CURRENT STAGE I0> (51N) ON


Residual current stage I0> I0> 0.02 … 1.0 x I01n 2.0 A 0.04 pu
Delay for stage I0> t0> 0.1 … 300 s 1.0 s
IDMT function Type DT
Io Input I0 Io1 … Io2 Io2

RESIDUAL CURRENT STAGE I0>> (51N) ON


Residual current stage I0>> I0> 0.02 … 1.0 x I01n 7.5 A 0.15 pu
Delay for stage I0>> t0> 0.1 … 300 s 0.3 s

Wärtsilä id: DBAC537648 -


Io Input I0 Io1 … Io2 Io2

doc rev 1.13 Page 8/30 Note! Settings to be checked at site


PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

GENERATOR PROTECTION RELAY VAMP 210 LOCATION CFC0_1 TESTED GENSET


Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

EARTH FAULT STAGE U0> (59N) ON


Earthfault stage U0> 0.01 … 0.50 x U0n 797 V 10 %
Operating time of stage U0> t> 0.3 … 300 s 2.0 s

EARTH FAULT STAGE U0>> (59N) ON


Earthfault stage U0> 0.01 … 0.50 x U0n 1593 V 20 %
Operating time of stage U0>> t> 0.3 … 300 s 1.0 s

OVERVOLTAGE STAGE U> (59) ON


Overvoltage stage U> U>/Un 0.5 … 1.5 x Un 15456 V 112 %
Operating time of stage U> t> 0.08 … 300 s 4.0 s

OVERVOLTAGE STAGE U>> (59) ON


Overvoltage stage U>> U>/Un 0.5 … 1.5 x Un 19320 V 140 %
Operating time of stage U>> t> 0.08 … 300 s 0.5 s

UNDERVOLTAGE STAGE U1< (27) ON


Undervoltage stage U1< U1</Un 0.2 … 1.2 x Ugn/ 3 11040 V 80 %
Operating time of stage U1< t> 0.08 … 300 s 20 s
Undervoltage blocking NoCmp 2 … 80% x Ugn 20 %
Blocking time I<Blk 0 … 30 s 10 s

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 9/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

GENERATOR PROTECTION RELAY VAMP 210 LOCATION CFC0_1 TESTED GENSET


Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

UNDERVOLTAGE STAGE U1<< (27/60) OFF


Undervoltage stage U1<< U1</Un 0.2 … 1.2 x Ugn/ 3 11040 V 80 %
Operating time of stage U1<< t> 0.08 … 300 s 20 s
Undervoltage blocking NoCmp 2 … 80% x Ugn 20 %
Blocking time I<Blk 0 … 30 s 10 s

OVERLOAD STAGE T> (49) OFF


Max cont. load current k (T>) 484 A 1.06 Ign
Generator heating time const Tau (τ) 60 min
Generator thermal alarm level T> (θ) 90 %

LOSS OF EXCITATION STAGE Q< (40) ON


Underexcitation stage Q< Q@P0% -0.05 … -1.0 x Pm -3274 kVAr -30 %*Sn
Underexcitation stage Q< Q@P80% -0.05 … -1.0 x Pm -3274 kVAr -30 %*Sn
Operating time of stage Q< t< 0.1 … 300 s 2.00 s
Release delay t< 0.1 … 300 s 0.5 s

REVERSE POWER STAGE P< (32) ON


Reverse power P< P</Pn 1 … 20.0 % -334 kW -4.0 %
Operating time of stage P< t< 0.3 … 300 s 2.00 s

REVERSE POWER STAGE P<< (32) OFF


Reverse power P<< P</Pn 1 … 20.0 % -835 -10.0 %

Wärtsilä id: DBAC537648 -


Operating time of stage P<< t< 0.3 … 300 s 2.00 s

doc rev 1.13 Page 10/30 Note! Settings to be checked at site


PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

GENERATOR PROTECTION RELAY VAMP 210 LOCATION CFC0_1 TESTED GENSET


Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

OVERFREQUENCY STAGE f> (81) ON


Over frequency stage f> f> 40 … 70 Hz 69.0 Hz 69.0 Hz (1.15 * Fn)
Operating time of stage f> t> 0.1 … 300 s 3.00 s

OVERFREQUENCY STAGE f>> (81) OFF


Over frequency stage f>> f> 40 … 70 Hz 72.0 72.0 Hz (1.20 * Fn)
Operating time of stage f>> t> 0.1 … 300 s 1.0 s

UNDERFREQUENCY STAGE f< (81L) ON


Under frequency stage f< f< 40 … 64 Hz 57.0 Hz 57.0 Hz (0.95 * Fn)
Operating time of stage f< t< 0.1 … 300 s 4.00 s
Undervoltage blocking Ublock 10 … 100 % x Ugn 40 %Un

UNDERFREQUENCY STAGE f<< (81L) OFF


Under frequency stage f<< f< 40 … 64 Hz 57.0 57.0 Hz (0.95 * Fn)
Operating time of stage f<< t< 0.1 … 300 s 4.0 s
Undervoltage blocking Ublock 10 … 100 % x Ugn 40 %Un

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 11/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

GENERATOR PROTECTION RELAY VAMP 210 LOCATION CFC0_1 TESTED GENSET


Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

VT SUPERVISION STAGE (60) ON


VT Supervision stage U2> 0 … 100 %Un 9660 V 70 %Un
VT Supervision stage I2< 0 … 100 %In 46 A 10 %In
Operating time of stage VT t> 0.02 … 300 s 0.2 s

CT SUPERVISION STAGE (Ctsup) ON


CT supervision stage Ctsup Imax 0 … 10 x In 91 A 20 % In
CT supervision stage Ctsup Imin 0 … 10 x In 46 A 10 % In
Operating time of stage Ctsup t> 0.02 … 300 s 2.0 s

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 12/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

GENERATOR PROTECTION RELAY VAMP 210 LOCATION CFC0_1 OUTPUT MATRIX


Description Valid Stage T1 T2 A1 A2 A3 A4 A5 BO Al Tr DR Remark

X = connected. XX = connected and latched

I> START (51) ON - - - - - - - - X - -

I> TRIP (51) ON - XX XX - - - - - - XX X

I>> START (50) ON - - - - - - - - X - -

I>> TRIP (50) ON - XX XX - - - - - - XX X


Iv> START (51V) OFF - - - - - - - - - - -
Iv> TRIP (51V) OFF - - - - - - - - X - -
I2> START (46) ON - - - - - - - - - - -
I2> TRIP (46) ON - - - - - - - - X - -
I0>>> START (51N) OFF - - - - - - - - - - -
I0>>> TRIP (51N) OFF - - - - - - - - - - -
I0>>>> START (51N) OFF - - - - - - - - - - -
I0>>>> TRIP (51N) OFF - - - - - - - - - - -
I0Dir> START (67N) ON - - - - - - - - X - -
I0Dir> TRIP (67N) ON - XX XX - - - - - - XX X
I0> START (51N) ON - - - - - - - - X - -
I0> TRIP (51N) ON - XX XX - - - - - - XX X
I0>> START (51N) ON - - - - - - - - X - -
I0>>TRIP (51N) ON - XX XX - - - - - - XX X
U0> START (59N) ON - - - - - - - - X - -
U0> TRIP (59N) ON - XX XX - - - - - - XX X
U0>> START (59N) ON - - - - - - - - X - -
U0>> TRIP (59N) ON - XX XX - - - - - - XX X

U> START (59) ON - - - - - - - - X - -

Wärtsilä id: DBAC537648 -


U> TRIP (59) ON - XX XX - - - - - - XX X

U>> START (59) ON - - - - - - - - X - -

U>> TRIP (59) ON - XX XX - - - - - - XX X

CBFP (50BF) OFF - - - - - - XX - - XX -

doc rev 1.13 Page 13/30 Note! Settings to be checked at site


PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

GENERATOR PROTECTION RELAY VAMP 210 LOCATION CFC0_1 OUTPUT MATRIX


Description Valid Stage T1 T2 A1 A2 A3 A4 A5 BO Al Tr DR Remark

X = connected. XX = connected and latched

U1< START (27) ON - - - - - - - - - - -

U1< TRIP (27) ON - - - - - - - - X - -

U1<< START (27/69) OFF - - - - - - - - - - -

U1<< TRIP (27/60) OFF - - - - - - - - - - -

T> START (49) OFF - - - - - - - - - - -

T> TRIP (49) OFF - - - - - - - - X - -

Q< START (40) ON - - - - - - - - X - -

Q< TRIP (40) ON - XX XX - - - - - - XX X

P< START (32) ON - - - - - - - - X - -

P< TRIP (32) ON - XX XX - - - - - - XX X

P<< START (32) OFF - - - - - - - - X - -

P<< TRIP (32) OFF - - - - - - - - - - -

f> START (81) ON - - - - - - - - X - -

f> TRIP (81) ON - XX XX - - - - - - XX X

f>> START (81) OFF - - - - - - - - - - -

f>> TRIP (81) OFF - - - - - - - - - - -

f< START (81) ON - - - - - - - - X - -

f< TRIP (81) ON - XX XX - - - - - - XX X

f<< START (81) OFF - - - - - - - - - - -

f<< TRIP (81) OFF - - - - - - - - - - -

VT supervisor (60) ON - - - - - - - - X - X

CT supervisor (Ctsup) ON - - - - - - - - X - X

Z < START (21) OFF - - - - - - - - X - -

Z < TRIP (21) OFF - XX XX - - - - - - XX X

Wärtsilä id: DBAC537648 -


X < START (40) OFF - - - - - - - - X - -

X < TRIP (40) OFF - XX XX - - - - - - XX X

U0f3 < START (64) OFF - - - - - - - - - - -

U0f3 < TRIP (64) OFF - - - - - - - - X - -

Uf> START (24) OFF - - - - - - - - - - -

Uf> TRIP (24) OFF - - - - - - - - X - -

df/dt START (81R) OFF - - - - - - - - X - -


df/dt TRIP (81R) OFF XX - - - - - - - - XX X

doc rev 1.13 Page 14/30 Note! Settings to be checked at site


PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

DIFFERENTIAL RELAY VAMP 265 LOCATION CFC0_1


Description Pos. Area Setting value Unit Remark
SCALING

Current transformer Iprim 500 A


Isec 1 A

Current transformer I'prim 500 A


I'sec 1 A

Core-balance current transf. 1 I0prim 50 A


I0sec 1 A

Core-balance current transf. 2 I02prim 50 A


I02sec 1 A

IL side nom voltage Un 13800 V


I'L side nom voltage U'n 13800 V
Transformer nom power (gen. power) Sn 10913 kVA
Nominal current Ign 457 A

Connection group Yy0

I0 compensation OFF
I'0 compensation OFF

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 15/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

DIFFERENTIAL RELAY VAMP 265 LOCATION CFC0_1 TESTED GENSET


Description Pos. Area Primary values Unit Setting value Setting Unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

DIFFERENTIAL CURRENT STAGE ∆I> (87) ON


∆I> pick-up (Ibias < 0.5Ign) ∆I> 5 … 50 %In 114 A 25 %
Slope 1 5 … 100 % 25 %
Ibias for start of slope 2 1.00 … 3.0xIn 1370 A 3.00 In
Slope 2 100 … 200 % 100 %

∆I> 2.harm. block enable ON


∆I> 2.harm. block limit 5 … 30 % 15 %

DIFFERENTIAL CURRENT STAGE ∆I>> (87) ON


Overcurrent stage ∆I> ∆I> 1.0 … 40.0 xIn 2283 A 5.0 In

OVERCURRENT STAGE I> (51) OFF


Overcurrent stage I> I> 0.5 … 4.00 x Ign 548 A 1.2 Ign
Delay for stage I> t> 0.1 … 300 s 2.0 s

RESIDUAL CURRENT STAGE I0> (51N) OFF


Residual current stage I0> I0> 0.02 … 1.0 x I01n 2.5 A 0.05 pu
Delay for stage I0> t0> 0.1 … 300 s 1.0 s
IDMT function Type DT
Io Input I0 Io1 … Io2 Io1

RESIDUAL CURRENT STAGE I0>> (51N) OFF

Wärtsilä id: DBAC537648 -


Residual current stage I0>> I0> 0.02 … 1.0 x I01n 5.0 A 0.10 pu
Delay for stage I0>> t0> 0.1 … 300 s 1.0 s
Io Input I0 Io1 … Io2 Io1

doc rev 1.13 Page 16/30 Note! Settings to be checked at site


PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

DIFFERENTIAL RELAY VAMP 265 LOCATION CFC0_1 TESTED GENSET


Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

RESIDUAL CURRENT STAGE I0>>> (51N) OFF


Residual current stage I0>>> I0> 0.02 … 1.0 x I01n 5.0 A 0.10 pu
Delay for stage I0>>> t0> 0.1 … 300 s 0.5 s
Io Input I0 Io1 … Io2 Io2

RESIDUAL CURRENT STAGE I0>>>> (51N) OFF


Residual current stage I0>>>> I0> 0.02 … 1.0 x I01n 10 A 0.20 pu
Delay for stage I0>>>> t0> 0.1 … 300 s 1.0 s
Io Input I0 Io1 … Io2 Io2

CIRCUIT BREAKER FAILURE PROTECTION CBFP (50BF) OFF


Relay to supervise TR T1,T2 T1
Delfinite operation time t> 0.1 … 10.00 s 0.15 s

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 17/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

DIFFERENTIAL RELAY VAMP 265 LOCATION CFC0_1 OUTPUT MATRIX


Description T1 T2 A1 A2 A3 A4 A5 BO Al Tr DR Remark

X = connected. XX = connected and latched

Id> TRIP (87) ON - XX XX - - - - - - XX X


Id>> TRIP (87) ON - XX XX - - - - - - XX X

I> START (51) OFF - - - - - - - - - - -

I> TRIP (51) OFF - - - - - - - - - - -


I0> START (51N) OFF - - - - - - - - - - -
I0> TRIP (51N) OFF - - - - - - - - - - -
I0>> START (51N) OFF - - - - - - - - - - -
I0>> TRIP (51N) OFF - - - - - - - - - - -
I0>>> START (51N) OFF - - - - - - - - - - -
I0>>> TRIP (51N) OFF - - - - - - - - - - -
I0>>>> START (51N) OFF - - - - - - - - - - -
I0>>>> TRIP (51N) OFF - - - - - - - - - - -

CBFP (50BF) OFF - - - - - - XX - - XX -

DI 1 connection - - - - - - - - - - -

DI 2 connection - - - - - - - - - - -

DI 3 connection - - - - - - - - - - -

DI 4 connection - - - - - - - - - - -

DI 5 connection - - - - - - - - - - -

DI 6 connection - - - - - - - - - - -

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 18/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

POWER MONITORING UNIT VAMP 260 LOCATION CFC0_1


Description Pos. Area Setting value Unit Remark
SCALING

Current transformer Iprim 500 A


Isec 1 A
Voltage transformer Uprim 13800 V
Usec 110 V
Voltage meas mode 3LL
Analog output 1
AO1 Coupling P.F.
AO Scaled minimum -0.5
AO Scaled maximum 0.5
Analog output min value 4 mA
Analog output max value 20 mA
Analog output 2
AO2 Coupling Q
AO Scaled minimum -2000 kVAr
AO Scaled maximum 8000 kVAr
Analog output min value 4 mA
Analog output max value 20 mA
Analog output 3
AO3 Coupling P
AO Scaled minimum 0 kW
AO Scaled maximum 10000 kW
Analog output min value 4 mA
Analog output max value 20 mA
Analog output 4
AO4 Coupling P

Wärtsilä id: DBAC537648 -


AO Scaled minimum 0 kW
AO Scaled maximum 10000 kW
Analog output min value 4 mA
Analog output max value 20 mA

doc rev 1.13 Page 19/30 Note! Settings to be checked at site


PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

PARALELLING RELAY A4 LOCATION CFE0_1


Description Pos. Area Setting value Unit Remark
Voltage difference U 10 … 15% 10 %

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 20/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

OUTGOING FEEDER PROTECTION RELAY VAMP 50 LOCATION BAO901 & BAO902


Description Pos. Area Setting value Unit Remark
SCALING

Generator rated current Ign 455 A


No of gensets installed pcs 4 pcs
% of total output on this feeder % 100 %

Current transformer Iprim 2000 A


Isec 1 A

Core-balance current transf. 1 I01prim 50 A


I01sec 1 A

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 21/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

OUTGOING FEEDER PROTECTION RELAY VAMP 50 LOCATION BAO901 & BAO902 TESTED
Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

OVERCURRENT STAGE I> (51) 1.2 ON


Overcurrent stage I> I> 0.5 … 4.00 * Ign 2184 A 1.092 pu
Time multiplier of stage I> k 0.05 … 3.2 s 0.1 s
IDMT function Type NI

OVERCURRENT STAGE I>> (50) 2.5 ON


Overcurrent stage I>> I> 0.5 … 20 x Ign 4550 A 2.275 pu
Operating time of stage I>> t> 0.04 … 300 s 0.4 s

RESIDUAL CURRENT STAGE I0> (51N) ON


Residual current stage I0> I0> 0.02 … 1.0 x I01n 2.0 A 0.04 pu
Delay for stage I0> t0> 0.1 … 300 s 0.8 s
IDMT function Type DT

RESIDUAL CURRENT STAGE I0>> (51N) ON


Residual current stage I0>> I0> 0.02 … 1.0 x I01n 7.5 A 0.15 pu
Delay for stage I0>> t0> 0.1 … 300 s 0.1 s
IDMT function Type DT

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 22/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

OUTGOING FEEDER PROTECTION RELAY VAMP 50 LOCATION BAO901 & BAO902 OUTPUT MATRIX
Description Valid Stage T1 T2 A1 A2 A3 Al Tr Remark

X = connected. XX = connected and latched

I> START (51) ON - - - - - X -

I> TRIP (51) ON XX XX XX XX XX - XX

I>> START (50) ON - - - - X -

I>> TRIP (50) ON XX XX XX XX XX - XX


I0> START (51N) ON - - - - - X -
I0> TRIP (51N) ON XX XX XX XX XX - XX
I0>> START (51N) ON - - - - - X -
I0>> TRIP (51N) ON XX XX XX XX XX - XX

DI 1 connection - - - - - - -

DI 2 connection - - - - - - -

DI 3 connection - - - - - - -

DI 4 connection - - - - - - -

DI 5 connection - - - - - - -

DI 6 connection - - - - - - -

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 23/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

STATION TRAFO PROTECTION RELAY VAMP 50 LOCATION BAA901


Description Pos. Area Setting value Unit Remark
SCALING

Aux transformer rating Sn 2500 kVA


Aux transformer voltage Un 13800 V

Phase CT Iprim 150 A

Cable CT I01prim 50 A
I01sec 1 A

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 24/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

STATION TRAFO PROTECTION RELAY VAMP 50 LOCATION BAA901 TESTED


Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

OVERCURRENT STAGE I> (51) 1.2 ON


Overcurrent stage I> I> 0.5 … 4.00 * Ign 126 A 0.837 pu
Time multiplier of stage I> k 0.05 … 3.2 s 0.1 s
IDMT function Type NI

OVERCURRENT STAGE I>> (50) 2.5 ON


Overcurrent stage I>> I> 0.5 … 20 x Ign 261 A 1.743 pu
Operating time of stage I>> t> 0.04 … 300 s 0.2 s

RESIDUAL CURRENT STAGE I0> (51N) ON


Residual current stage I0> I0> 0.02 … 1.0 x I01n 2.0 A 0.04 pu
Delay for stage I0> t0> 0.1 … 300 s 0.8 s
IDMT function Type DT

RESIDUAL CURRENT STAGE I0>> (51N) ON


Residual current stage I0>> I0> 0.02 … 1.0 x I01n 7.5 A 0.15 pu
Delay for stage I0>> t0> 0.1 … 300 s 0.1 s
IDMT function Type DT

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 25/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

STATION TRAFO PROTECTION RELAY VAMP 50 LOCATION BAA901 OUTPUT MATRIX


Description Valid Stage T1 T2 A1 A2 A3 Al Tr Remark

X = connected. XX = connected and latched

I> START (51) ON - - - - - X -

I> TRIP (51) ON XX XX XX XX XX - XX

I>> START (50) ON - - - - - X -

I>> TRIP (50) ON XX XX XX XX XX - XX


I0> START (51N) ON - - - - - X -
I0> TRIP (51N) ON XX XX XX XX XX - XX
I0>> START (51N) ON - - - - - X -
I0>> TRIP (51N) ON XX XX XX XX XX - XX

DI 1 connection - - - - - - -

DI 2 connection - - - - - - -

DI 3 connection - - - - - - -

DI 4 connection - - - - - - -

DI 5 connection - - - - - - -

DI 6 connection - - - - - - -

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 26/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

BUSBAR RELAY VAMP 55 LOCATION BAM901


Description Pos. Area Setting value Unit Remark
SCALING

Generator rated voltage Un 13800 V

Rated Frequency Fn 60 Hz

Busbar PT primary voltage Uprim 13800 V

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 27/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

BUSBAR RELAY VAMP 55 LOCATION BAM901 TESTED


Description Pos. Area Primary values Unit Setting value Setting Unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

OVERVOLTAGE STAGE U> (59) ON


Overvoltage stage U> U>/Un 0.5 … 1.5 x Un 15456 V 112 %
Operating time of stage U> t> 0.08 … 300 s 3.0 s
Release delay t> 0.06 … 300 s 0.06 s
Hysteresis Hyst 0.1 … 20 % 3.00 %

UNDERVOLTAGE STAGE U< (27) ON


Undervoltage stage U< U</Un 0.2 … 1.2 x Ugn/ 3 11040 V 80 %
Operating time of stage U< t> 0.08 … 300 s 10 s
Undervoltage blocking Ublock 2 … 80% x Ugn 10 %
Release delay t> 0.06 … 300 s 0.06 s
Hysteresis Hyst 0.1 … 20 % 3.0 %

EARTH FAULT STAGE U0> (59N) ON


Earthfault stage U 0> 0.01 … 0.80 x U0n 797 V 10 %
Operating time of stage U0> t> 0.3 … 300 s 2.5 s
Release delay t> 0.06 … 300 s 0.06 s

EARTH FAULT STAGE U0>> (59N) ON


Earthfault stage U 0> 0.10 … 1.00 x U0n 1593 V 20 %
Operating time of stage U0>> t> 0.3 … 300 s 1.5 s

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 28/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

BUSBAR RELAY VAMP 55 LOCATION BAM901 TESTED


Description Pos. Area Primary values Unit Setting value Setting unit Valid Stage 1 2 3 4 5 6 7 8 9 10 11 Remark

OVERFREQUENCY STAGE f> (81) ON


Over frequency stage f> f> 46 … 70 Hz 69.0 Hz 69.0 Hz (1.15 * Fn)
Operating time of stage f> t> 0.1 … 300 s 2.00 s

UNDERFREQUENCY STAGE f< (81L) ON


Under frequency stage f< f< 40 … 64 Hz 57.0 Hz 57.0 Hz (0.95 * Fn)
Operating time of stage f< t< 0.1 … 300 s 3.00 s
Undervoltage blocking Ublock 10 … 100 % x Ugn 40 %Un

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 29/30 Note! Settings to be checked at site
PROTECTION RELAYS SETTING AND TEST REPORT
Project Name KD.10817 PAD 9

Document ID KD.10817.D5001 Made Sami Hurin

Date 12.02.2013 Checked MW

Status RELEASE Approved KeR

Revision - 18.02.2013

BUSBAR RELAY VAMP 55 LOCATION BAM901 OUTPUT MATRIX


Description T1 T2 A1 A2 A3 Al Tr Remark

X = connected. XX = connected and latched

U> START (59) ON - - - - - X -

U> TRIP (59) ON XX XX XX XX XX - XX

U< START (27) ON - - - - - X -

U< TRIP (27) ON XX XX XX XX XX - XX


U0> START (59N) ON - - - - - X -
U0> TRIP (59N) ON XX XX XX XX XX - XX
U0>> START (59N) ON - - - - - X -
U0>> TRIP (59N) ON XX XX XX XX XX - XX

f> START (81) ON - - - - - X -

f> TRIP (81) ON XX XX XX XX XX - XX

f< START (81) ON - - - - - X -

f< TRIP (81) ON XX XX XX XX XX - XX

DI 1 connection - - - - - - -

DI 2 connection - - - - - - -

DI 3 connection - - - - - - -

DI 4 connection - - - - - - -

DI 5 connection - - - - - - -

DI 6 connection - - - - - - -

Wärtsilä id: DBAC537648 -


doc rev 1.13 Page 30/30 Note! Settings to be checked at site