Fan Selection
Fan Type BSB
Unit BSB900/TM (I)
Fan Quantity 1
Operating Conditions Ducted
Required Volume 5,990 l/s
Required Static Pressure 225 Pa
Air Volume 5,990 l/s
Static Pressure 225 Pa
Velocity Pressure 46.2 Pa
Total Pressure 271 Pa
Outlet Velocity 8.91 m/s
Fan Total Efficiency 63.6 %
Fan Static Efficiency 52.7 %
Fan Speed 614 rpm
Air Temperature 30 °C
Altitude 1m
Fan Absorbed Power 2.56 kW
Motor Selection
Recommended Motor D132 6p (3.00 kW)
Motor Speed 1150 rpm
Service Factor 5%
Operating Limits
Max. Absorbed Power 14.00 kW
Max. Fan Speed 1050 rpm
Temperature (Min-Max) -20° to 100°C
0DL A B C D E F F1 G H
55 1648 1408 971 1130 595 455 189 604 1319
J K L M N P R S t t1
645 695 906 141 651 89 7 1186 16 10
UxS V v1 v2 w X Y z
17x22 900 934 986 90 623 1158 53.5