You are on page 1of 1

Date Kruger M & E Industries Corp.

Company B3 Welborne Industrial Park, Bancal,


Attention Carmona Cavite, Philippines 4116
Project - LAROSSA
Reference LPF-R-01 Tel: +639175519265 Fax: +63 8622891
Email: mktg@krugerph.net

Fan Selection
Fan Type BSB
Unit BSB900/TM (I)
Fan Quantity 1
Operating Conditions Ducted
Required Volume 5,990 l/s
Required Static Pressure 225 Pa
Air Volume 5,990 l/s
Static Pressure 225 Pa
Velocity Pressure 46.2 Pa
Total Pressure 271 Pa
Outlet Velocity 8.91 m/s
Fan Total Efficiency 63.6 %
Fan Static Efficiency 52.7 %
Fan Speed 614 rpm
Air Temperature 30 °C
Altitude 1m
Fan Absorbed Power 2.56 kW
Motor Selection
Recommended Motor D132 6p (3.00 kW)
Motor Speed 1150 rpm
Service Factor 5%
Operating Limits
Max. Absorbed Power 14.00 kW
Max. Fan Speed 1050 rpm
Temperature (Min-Max) -20° to 100°C

Hz 63 125 250 500 1k 2k 4k 8k Overall


Lwi(Lin) 88 90 82 79 74 68 62 57 93 dB
Lwo(Lin) 92 94 86 82 77 71 65 60 96 dB
Lwi(A) 61 74 74 75 74 69 63 56 81 dB(A)
Lpi(A) 45 57 57 59 58 53 46 39 64 dB(A)
Sound Pressure Level "Lpi" 3m from the inlet side, Room Conditions

0DL A B C D E F F1 G H
55 1648 1408 971 1130 595 455 189 604 1319
J K L M N P R S t t1
645 695 906 141 651 89 7 1186 16 10
UxS V v1 v2 w X Y z
17x22 900 934 986 90 623 1158 53.5