Date 05-01-2021 Kruger Ventilation Industries Pte Ltd

Company No. 17 Tuas Avenue 10


-
Attention Singapore 639141
-
Project
-
Reference Tel: +65 6861 Fax: +65 6861 3577
1577
Email: mktg@krugerasia.com

Fan Selection
Fan Type
Unit CPF/BDB710/TIM (I)
Operating Conditions Ducted
Air Volume 12,000 cfm
Static Pressure 30.0 mmwg
Velocity Pressure 2.85 mmwg
Total Pressure 32.9 mmwg
Outlet Velocity 7.03 m/s
Fan Total Efficiency 67.4 %
Fan Static Efficiency 61.5 %
Fan Speed 768 rpm
Air Temperature 20 °C
Altitude 559 m
Fan Absorbed Power 2.71 kW
Motor Selection
Recommended Motor D132M (4.00 kW)
Motor Speed 950 rpm
Service Factor 5%
Operating Limits
Max. Absorbed Power 18.00 kW
Max. Fan Speed 1350 rpm
Temperature (Min-Max) -20° to 85°C

Hz 63 125 250 500 1k 2k 4k 8k Overall


Lwi(Lin) 80 82 83 78 72 67 62 57 87 dB
Lwi(A) 54 66 74 74 72 68 63 56 79 dB(A)
Lpi(A) 47 59 67 67 65 61 56 49 72 dB(A)
* Sound data is for the inlet side * Sound Pressure Level 1m, Room Conditions

Version: 1.19.12.103 (Database: 33.6) (INT) Date: 05-01-2021 Time: 12:15:19