Date 01-02-2021 Kruger Ventilation Industries Pte Ltd

Company No. 17 Tuas Avenue 10


-
Attention Singapore 639141
-
Project
-
Reference Tel: +65 6861 Fax: +65 6861 3577
1577
Email: mktg@krugerasia.com

Fan Selection
Fan Type
Unit TDC630/C12/G/7-5V / 27°
Operating Conditions Ducted
Required Volume 8,100 cfm
Required Static Pressure 15.0 mmwg
Air Volume 8,390 cfm
Static Pressure 16.1 mmwg
Velocity Pressure 9.91 mmwg
Total Pressure 26.0 mmwg
Outlet Velocity 12.71 m/s
Fan Total Efficiency 67.6 %
Fan Static Efficiency 41.8 %
Fan Speed 1450 rpm
Air Temperature 20 °C
Altitude 0m
Fan Absorbed Power 1.49 kW
Motor Selection
Recommended Motor D100L (2.20 kW)
Motor Speed 1450 rpm
Service Factor 5%
Operating Limits
Max. Absorbed Power -
Max. Fan Speed -
Temperature (Min-Max) -

Hz 63 125 250 500 1k 2k 4k 8k Overall


Lwi(Lin) 93 91 84 84 81 79 78 77 96 dB
Lwi(A) 66 75 76 81 81 81 79 76 87 dB(A)
Lpi(A) 56 64 65 70 70 70 69 65 77 dB(A)
* Sound data is for the inlet side * Sound Pressure Level 1.5m, Room Conditions