Professional Documents
Culture Documents
Although, the output power of hydro generator is decided Fig. 6. Single line diagram
by the water level. The run of river designed hydro power
plant will keep the output power to remain constant, as
much as possible. Fig. 4, shows the annual generation The RTDS test environment is as below:
profile in year 2007. It can be seen that the power
generation is very low during March and April. On the
other hand, the output power is very high during in the
raining season, between June and November.
PV generation (kW)
80
60
40
20
0
0:00
1:50
3:40
5:30
7:20
9:10
11:00
12:50
14:40
16:30
18:20
20:10
22:00
23:50
878
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on March 24,2022 at 08:05:37 UTC from IEEE Xplore. Restrictions apply.
Proceedings of the 2019 IEEE PES GTD Asia
879
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on March 24,2022 at 08:05:37 UTC from IEEE Xplore. Restrictions apply.
Proceedings of the 2019 IEEE PES GTD Asia
880
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on March 24,2022 at 08:05:37 UTC from IEEE Xplore. Restrictions apply.
Proceedings of the 2019 IEEE PES GTD Asia
the setting. After detecting the power exchange is lower time, there is less power requirement from power grid to
than the setting , will send the command to change the reduce the power loss in transmission line, and during
control mode of PCS from PQ to VSG mode, and trip the afternoon, the PV power is more than load, so after charge
LBS1 of PCC. full the battery, the PV power will send back to power
grid. By using the PV smoothing function, the fluctuation
3, Automatic black start
of PV output can be compensate to be more stable power
When microgrid area outage, microgrid output. Fig 19 shows the performance of PV smoothing
controller(MGCC) ensure there is no internal fault inside function. It also can seamless switching from grid
microgrid area, trip LBS1 to confirm isolate with power connecting to island, in case incoming distribution line
grid and then closes the LBS2, LBS3 and LBS4 , then has been tripped due to fault or lost power due to other
starts the PCS to set up the voltage with load, in order to reason, the microgrid system can automatically black start
improve the stability of black start, the voltage increase to set up a island operation to enhance the power supply
speed should not be too fast. At the same time, all the reliability. During island mode, load shedding function is
protection functions of the MGCC are disabled, to avoid provided to ensure the stable power supply of important
the voltage and frequency protection operating. By using load uninterrupted. Fig 20 shows that in island mode, load
the automatic black start function to ensure that in case shedding function shed LBS S2 and S4 to ensure
the incoming line has been tripped by fault or lost power important load under LBS S3 can get power supply until
for other reason, the microgrid area still can get power power grid recover. After the power grid has been recover,
from local sources. the microgrid system can automatically synchronize back
to power grid to increase the power supply reliability.
4, Automatic switching from island to grid connecting
The controller provides automatic synchronous
switching-on function for a safe and reliable grid inter-
connection of microgrid.
When the power system recover from the fault, to
improve the reliability of power supply of microgrid area,
it will switch back to grid connecting mode. The MGCC
will control the U and f both less than the setting, and then
close the LBS1 for PCC , and then send the command to
change the control mode of PCS from VSG mode to PQ
mode .
5, Island control
In island mode, the power deficiency or excess may
lead to the sharp variation of frequency and voltage. This
severely impacts the normal operation of loads within
Fig. 17. Dispatching curve
microgrid and causes the system breakdown. The
frequency & voltage emergency control is set to balance
the power demand within microgrid and to recover the
voltage and frequency within the allowable operating
ranges by the energy storage output control, fast load
shedding and DG disconnection.
V. OPERATION PERFORMANCE
In grid connecting mode , The microgrid system can
be consider as the controllable curve for outer power grid
by dispatch the internal DGs, BESS and load ,which
especially for BESS we can preset the charge and
discharge curve for maximize the local generation local
consumption to reduce the power loss in transmission line
to make microgrid system cost effective and environment Fig. 18. Energy management in microgrid
friendly.
Fig 17 shows the dispatching curve from microgrid
EMS. Fig 18 shows the curve for PV ,BESS, Grid and
load, by adjust the output of DGs, BESS, load, the
microgrid output can be flexible curve for power grid. It
also shows that compare with load curve, during peak
881
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on March 24,2022 at 08:05:37 UTC from IEEE Xplore. Restrictions apply.
Proceedings of the 2019 IEEE PES GTD Asia
[1] PCS-9617MG_X_Instruction
Manual_EN_Customized_ECKF170198_R1.00.
[2] Microgrid Controller :Control and Operation-Thailand
IEEE,Session 3.2 13 Sep 2018,Dr.Suttichai
Premrudeepreechacharn.
[3] MICROGRID COORDINATED CONTROL SYSTEM
WITH VSG-CIRED Workshop - Ljubljana, 7-8 June 2018-
Haobin ZHU Guangfu XU Xianwen ZHU Qunbing YU
Jun CHEN XU LI.
[4] Tirapong Kasirawat,Patompong Boonsiri,Titti
Saksornchai,"PEA Microgrid Design for Coexistence with
Local Community and Environment: Case Study at Khun
Pae Village Thailand."
[5] N. Eghtedarpour and E. Farjah, “ Power control and
882
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on March 24,2022 at 08:05:37 UTC from IEEE Xplore. Restrictions apply.