Professional Documents
Culture Documents
Name Configuration
Normal Open tie-breaker CB3 and CB4 and close all other CBs
Load Shift Close tie- breaker CB3 & CB4 and open both side CBs of T5 and Cable5
T3 Down Based on Normal configuration, close CB3 and open CBs on both sides of
T3
T4 Down Based on Normal configuration, close CB4 and open CBs on both sides of
T4
TieCBClosed Close both tie-breakers CB3 and CB4
1. Check Cable2 rating (use the load flow analyzer to check the cable ratings)
Run different cases to see if Cable2 is over/under sized
Consider different operating conditions
Use derated ampacity based on default tray setup (ICEA P54-440, H=6, W=18, Fill=30%, no
cover, no cumulative effect and no fire protection)
2. Check Cable5 & Cable7 rating (use the load flow analyzer to check the cable ratings)
Run different cases to see if Cable5 & Cable7 are over/under sized
Consider all possible configurations
Use derated ampacity based on default tray setup (ICEA P54-440, H = 6 in, W = 18 in, Fill =
30%, no cover, cumulative effect and fire protection)
3. Check XFMR T4 and T5 ratings (use the load flow analyzer to check the transformer ratings)
For all cases under consideration, are T4 and T5 under/oversized
What size would be more adequate?
Check system voltage condition again
1. Size Cable 2
2 by 2 conduit
Ta = 25 °C, Tc = 90 °C, Rho = 95 °C-cm/W
3. Select and Size equipment cable for Mtr4 (You can size the equipment cable in Base)
Set up Ampacity page data: Ta = 35 °C, Tc = 90 °C, NEC, A/G tray with top cover
Size requirements: Vd (2%), Vst (80%), ampacity (Mtr4 with MF), and Short-Circuit (26 kA,
0.06 seconds)
Use library: ICEA, rubber, magnetic installation, 100% insulation level, 0.6kV, 3/C, CU
conductor, 200 ft