WATER-COOLED DIESEL GENSET

MODEL LP5.6
Stand-by Power @ 50Hz, 1500rpm 6.1 kW / 6.1 kVA
Prime Power @ 50Hz, 1500rpm 5.6 kW / 5.6 kVA

General features :
· Engine (Lister Petter, LPW2)
· Charge alternator 12 V
· Alternator
· Single bearing alternator IP 23 , insulation class H /H
· Radiator with coolant cap
· Skid and vibration isolators
· Dry type air filter
· Main line circuit breaker
· Microprocessor control panel
· 12 V battery, rack and cable
· Fuel lift pump
· Inlet and exhaust manifolds
· Gear driven lubricating oil pump
· Galvanised steel base-plate with forklift pockets and
bunding for the fuel tank
· Anti-vibration mountings
· Emergency stop button (lock-down type)
· 66-litre polypropylene fuel tank with contents gauge
· User manual

GENERAL RATING
Voltage HZ Phase P.F Standby Ratings Prime Ratings
kW/kVA kW/kVA
240 50 1 1.0 6.1 / 6.1 5.6 / 5.6
230 50 1 1.0 6.1 / 6.1 5.6 / 5.6
220 50 1 1.0 6.1 / 6.1 5.6 / 5.6
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10% overload capability is
available for a period of 1 hour within 12-hour period of operation, in accordance with ISO 3046-1
ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed.

ENGINE SPECIFICATION
Manufacturer / Model Lister Petter, LPW 2, 4-cycle
Aspiration Natural
Cylinder Arrangement 2XL
Displacement 0.93L [56.75in³]
Bore and Stroke 86mm [3.39in.] X 80mm [3.15in.]
Compression ratio 18.5 : 1
Rated RPM 1500 Rpm
Direction of Rotation (Flywheel end) Anti-Clockwise
Continuous Power at rated RPM 7.5kW [10.1BHP]
Maximum permissible intake restriction at full rated speed and load 25 mbar
Maximum permissible exhaust back pressure 75 mbar
Type of fuel injection Direct
Governor : type Mechanical
Fuel consumption @ 100% load 1.9 L/H
Fuel consumption @ 75% load 1.5 L/H

LP5.6 1/3
ALTERNATOR DATA
Number of phase 1
Power factor (Cos Phi) 1.0
Pole : number 4
Insulation : class, temperature rise H /H
Bearing : number 1
Coupling Direct
Brush/Brushless Brushless
Voltage regulation Solid state AVR with ±1.5% as standard

CONTROL SYSTEM SPECIFICATION


DSE 7110 The control module gives digital readouts of:
- Generator voltage (phase-to-phase and phase-to-neutral)
- Generator current (each phase displayed separately)
- Output frequency
- Engine speed
- Engine coolant temperature
- Battery voltage
- Engine hours run
The control module has indicators for:
- Overspeed/underspeed
- Emergency stop
- Engine oil pressure
- Engine temperature
All LLD and LLDA sets have a control cubicle mounted on a vibration- - Failure to start
isolated support, which has the following features: - Battery charger failure
- Electronic digital control module with monitoring/control facility and Automatic shutdown occurs under:
warning indicators. - Low engine oil pressure
- Automatic shutdown protection. - High engine temperature
- Emergency stop button (lock-down type). - Overspeed/underspeed
- AC output circuit breaker with over-current protection. - Failure to start after three attempts
- DC circuit control switch and overload circuit breaker. Manual/Remote Start Sets
- Manual operation is by START and STOP push-buttons on the control
module
- Remote operation is achieved by connecting a 2-wire circuit to the relevant
terminals on the control module and is activated by setting the control
module to AUTO
The wall-mounted cubicle features:
- Mains monitoring unit to control set operation
- Load-transfer contactors, mechanically and electrically Interlocked (rated for
set output)
- Indicator for mains-on-load or plant-on-load
Automatic Mains Failure Sets (AMF)
- Wall-mounted cubicle governing automatic mains failure operation
- Control module timer circuits set to delay start, delay transfer back to mains
and delay stop to allow for engine cooldown
- Solid-state automatic battery charger that maintains charge when set is not
running

Conditions of sale

· Safesidepower SB provides a full line of products with high · Each and every units is factory tested. All generator sets are
quality recognized engines and alternators. also prototype tested.
· Service and parts are available from Safesidepower SB as a · Warranty according to our standard conditions. Five years
single source of responsibility. extended also available with extra charges.

LP5.6 2/3
Weight and Dimensions
Open Model

Overall size l x w x h :
1442mm [56.8in] x 715mm [28.1in] x 997mm [39.3in]

Weight :
396kg [873lbs]

With Optional Enclosure

Overall size l x w x h :
1700mm [67in] x 750mm [29.5in] x 1150mm [45.3in]

Weight :
500kg [1102lbs]

Acoustic sets, 75% load at 7m; 50 Hz, 1500 r/min: 65dBA

SAFESIDEPOWER SDN BHD


Head Office : Shah Alam, Selangor, Malaysia - www.safesidepower.com
Tel: +603 5638 6860
Fax: +603 5638 6867
Email: sales@safesidepower.com

Our Diesel Electric Generators ranges from 2kVA to 2500kVA

We sell Diesel Power Generators from Pramac, Volvo, Yanmar, Perkins, Cummins and Daewoo. We also designed and manufactured our own Diesel Generators. Electric Diesel Generators ranges from 2kVA to 2500 kVA. We
have diesel generator distributor in Malaysia, Singapore, Brunei, Vietnam, Cambodia and Laos
Specifications and design liable to modifications without prior notice

LP5.6 3/3

You might also like