MULTI FUNCTION WARNING Warnings are indicated when mishandling this product might result in death or serious injury
to user.
DIGITAL VOLTAGE RELAY Cautions are indicated when mishandling this product might result in minor injury to the user,
CAUTION or only physical damage to the timer.
User's Manual
WARNING
RESTRICTIONS ON USE
‧Note this incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has
When using this product in applications been correctly wired before turning the power ON.
that require particular safety or when ‧Before wiring, or removing / mounting the product, be sure to turn the power OFF. Failure to do so might cause
using this product in important facilities, electric shock.
please pay attention to the safety of the ‧Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
overall system and equipment. Install fail- ‧Do not disassemble the product. Doing so might cause electric shock or faulty operation.
safe mechanisms, perform redundancy
checks and periodic inspections and
CAUTION
adopt other appropriate safety measures ‧Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage,
when it is necessary. This product is rated shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation.
at Class Ⅱ . ‧Firmly tighten the wires to the terminal. Insufficient tightening of the wires to the terminal might cause fire.
SETTING PROCEDURE
1. Voltage Trip Delay Time 3. Under Voltage Setting 5. DIP Switch Functions
Monitored Voltage
L-L L-N
Set the dsired trip delay time from Set the desired Under Voltage trip Reset time Phase Reversal 200 115
0.1 sec to 30 sec. point, from 5% to 20% of the rated Type 220 127
voltage Monitored Voltage
230 133
ON Auto reset with 5 sec delay
2. Over Voltage Setting 4. Phase Unbalance Setting 5S/1S 240 138
OFF Auto reset with 1 sec delay
380 220
ON L-N (L1-L2-L3-N)
Type 400 230
OFF L-L (L1-L2-L3)
Set the desired Over Voltage trip Set the desired Phase Unbalance ON Phase reversal protection On 415 240
REV.
point, from 5% to 20% of the rated trip point, from 2% to 22% or turned OFF Phase reversal protection Off 480 277
voltage off
CONNECTION
16 18 N 16 18 16 18 26 28 N 16 18 26 28
Over Voltage
L1 L3 L2 L1 L2 L3
LINE L3
Normal
L3
Under Voltage
90.6
68.1
94.6
45
Reverse LED
Normal LED
Over LED
Under LED
Loss LED
Unbalance LED
M-EP42-O-C