FIRE & GAS NOTES :

FIRE PANEL SYSTEM MODBUS COMMUNICATION FAULT ALARM


CAUSE & EFFECT
MATRIX DIAGRAM

ACTIVE EXTINGUSER SYSTEM AT ELECTRICAL ROOM


ORF SEMARANG

FIRE PANEL COMMON FAULT ALARM IN F&G PANEL


GRSM-04-INS-LIST-009 DATE . : 13- 02- 2015

ACTIVE EXTINGUSER SYSTEM AT CONTROL ROOM

ACTIVE EXTINGUSER SYSTEM AT BATTERY ROOM


SMOKE DETECTOR FAULT ALARM TO F&G PANEL
REVISION . : A PAGE . : 05 OF 05

POWER SUPPLY NORMAL LAMP INDICATION


POWER SUPPLY NORMAL LAMP INDICATION

VOTING DETECTED - CONFIRM FIRE ALARM

VOTING DETECTED - CONFIRM GAS ALARM

SMOKE ALARM AT ELECTRICAL ROOM


FIRE PANEL COMMON FAULT ALARM
OUTPUT

SMOKE ALARM AT CONTROL ROOM

SMOKE ALARM AT BATTERY ROOM


SMOKE DETECTOR FAULT ALARM
POWER SUPPLY TO PLC FAILURE

FLAME DETECTOR FAULT ALARM


LEGEND :

BELL - 2 AT ELECTRICAL ROOM


SINGLE ALARM TO F&G PANEL

POWER SUPPLY FAULT ALARM


GAS DETECTOR FAULT ALARM

BELL - 1 AT CONTROL ROOM

BELL - 3 AT BATTERY ROOM


A : AND FUNCTION

START FIRE WATER PUMP


+ : OR FUNCTION
P : PREVENT ACTION
F : FAULT AS "AND" WITH OTHER

INTERNAL BUZZER
f+ : FAULT AS "OR" / INDEPENDENT

AUDIBLE ALARM
I : INVERSE FUNCTION

STROBE LIGHT
SZ : SMOKE ZONE
HZ : HEAT ZONE
GZ : GAS ZONE
FZ : FLAME ZONE

PREPARE : CHECKED: APPROVED :

NO. LOC ZONE INPUT


FIRE ALARM PANEL

1 MODBUS COMM LOSS +

2 POWER SUPPLY TO POWER PANEL NORMAL +

POWER SUPPLY TO POWER PANEL FAILURE + HPW ICH ALI

4 FIRE PANEL COMMON FAULT ALARM +

5
6 FAULT
SZ-1 (BUILDING)

SMOKE DETECTOR AT CONTROL ROOM A ft A A A A ft A A A A A A


7 SMOKE DETECTOR AT ELECTRICAL ROOM FAULT A ft A A A A ft A A A A A A
UNCLASSIFIELD AREA

8 SMOKE DETECTOR AT BATTERY ROOOM FAULT A ft A A A A ft A A A A A A


9
10
11 HEAT DETECTOR AT OFFICE ROOM FAULT A ft A A A A ft A A A A A A
(BUILDING)

12 HEAT DETECTOR AT CONTROL ROOM FAULT A ft A A A ft A A A A A A


13 HEAT DETECTOR AT ELECTRICAL ROOM FAULT A ft A A A ft A A A A A A
HZ-1

15
16
F & G PANEL

17 POWER SUPPLY TO PLC, NORMAL +


18 POWER SUPPLY TO PLC,FAILURE +
19
60% LEL
20 FLAME DETECTOR AT PRESSURE CONTROL PUMP STATION A A A A A A A ft
FAULT
60% LEL
21 FLAME DETECTOR AT PRESSURE CONTROL PUMP STATION A A A A A A ft
FZ-1 (IN/OUTLET)

FAULT
60% LEL
22 FLAME DETECTOR AT INLET METERING SKID A A A A A A ft
FAULT
60% LEL
23 FLAME DETECTOR AT METERING SKID A A A A A ft
FAULT
CLASSIFIELD AREA

24 FLAME DETECTOR AT OUTLET METERING SKID FAULT A A A A A ft


60% LEL
25 FLAME DETECTOR AT PIG LAUNCHER METERING SKID A A A A A ft
FAULT
60% LEL
26 GAS DETECTION AT INLET PRESSURE PUMP STATION A A A A
FAULT A A A ft A
60% LEL
GZ-1 (IN/OUTLET)

27 GAS DETECTION AT OUTLET PRESSURE PUMP STATION A A A A


FAULT A A A ft A
60% LEL
28 GAS DETECTOR AT INLET METERING SKID A A A A
FAULT A A A ft A
60% LEL
29 GAS DETECTOR AT METERING SKID A A A A
FAULT A A A ft A
30 GAS DETECTOR AT OUTLET METERING SKID FAULT A A A A A A A ft A
60% LEL
31 GAS DETECTOR AT PIG LAUNCHER METERING SKID A A A A
FAULT A A A ft A