Characteristic Strength of concrete = 25 N/mm2

Zd Y Major axis Parameters = Mz, Yd, Ly, ery. Yield Strength of Main RF Steel = 415 N/mm2
Minor axis Parameters = My, Zd, Lz, erz. Yield Strength of Stirrups = 415 N/mm2 20
Z Clear Cover to the RF = 40 mm 25
28
Column Membe Load Axial Min. Moment Moment due Final Design Dia of Dia of % (Muz/Muz1)an
Column Moment Unsupported Size Eff. length Eff length Pbz Pby No of No of
Grid r Case load eccentricity due to emin to slenderness moments k1z k1y k2z k2y Bar Bar steel + Result Column Details.
Type (kNm) length(m) (mm) ratio (m) (kn) (kn) Bar. Bar.
mark Number Number (kN) (m) (kn.m) (kNm) (kNm) (mm) (mm) p (Muy/Muy1)an

Pu Mz My ly lz Yd Zd ery erz ley lez eymin ezmin Mez Mey Maz May Muz Muy

C3 C6 141 118 166.09 180.4 106.11 4.4 4.4 600 400 1.35 1.25 5.94 5.50 0.029 0.022 4.783 3.7 7.3 8.9 180.4 115.0 0.207 0.196 0.328 0.203 1389 1267 25 4 20 8 1.87 0.937 Pass 600x400 with 4 X Y25 + 8 X Y20 Tor HYSD Bars.

C2 C7 142 118 175.85 201.4 116.35 4.4 4.4 600 400 1.35 1.25 5.94 5.50 0.029 0.022 5.064 3.9 7.5 9.2 201.4 125.5 0.207 0.196 0.328 0.203 1435 1296 25 12 2.45 0.841 Pass 600x400 with 12 X Y 25 Tor HYSD Bars.

C3 C8 143 117 117.51 116 110.24 4.4 4.4 600 400 1.50 1.65 6.60 7.26 0.029 0.022 3.384 2.6 6.4 11.1 116.0 121.4 0.207 0.196 0.328 0.203 1389 1267 25 4 20 8 1.87 0.812 Pass 600x400 with 4 X Y25 + 8 X Y20 Tor HYSD Bars.

24021-CS-3212 R1 Electrical Inverter room and Substation Building ANNEXURE-C M-25 COLUMN 1