Professional Documents
Culture Documents
OF THE FUTURE:
Integrating variable renewable energy
sources in Brazil's energy matrix
PRODUCT 1:
TECHNICAL REGULATION
STUDIES
Energy systems of the future: Final Report
Integrating variable renewable energy sources in Brazil's energy matrix
This study was carried out within the scope of the German Cooperation for Sustainable
Development, through the Deutsche Gesellschaft für Internationale Zusammenarbeit
(GIZ), within the Energy Systems of the Future Program. On the Brazilian side, the
Program has as its political coordinating partner the Ministry of Mines and Energy
(MME), also counting on the participation of other relevant institutions in the national
electricity sector, such as the Empresa de Pesquisa Energetica (EPE) and the Operador
Nacional do Sistema Eletrico (ONS), technical implementing partners of this study.
Legal Information
1. All indications, data and results of this study were compiled and carefully reviewed
by the author(s). However, errors regarding the content cannot be avoided.
Consequently, neither GIZ or the author(s) can be held responsible for any direct or
indirect claim, loss or damage resulting from the use or reliance placed on the
information contained in this study, or directly or indirectly resulting from errors,
inaccuracies or omissions of information in this study.
2. Duplication or reproduction of all or parts of the study (including the transfer of data
to media storage systems) and distribution for non-commercial purposes is
permitted, provided GIZ is cited as the source of the information. For other
commercial uses, including duplication, reproduction or distribution of all or parts of
this study, written consent from GIZ is required.
Informações Legais
Presentation
The study “Integrating Variable Renewable Energy Sources in Brazil's Energy Matrix”
was conceived within the scope of German Cooperation for Sustainable Development,
through Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ), within the
“Energy Systems of the Future” Program. On the Brazilian side, the Program has as its
political coordinating partner the Ministry of Mines and Energy (MME), also counting on
the participation of other relevant institutions in the national electricity sector, with an
emphasis to the Empresa de Pesquisa Energetica (EPE) and the Operador Nacional
do Sistema Eletrico (ONS), technical implementing partners of this study.
The study was structured into five main products: Technical Regulation Studies (Grid
Codes); Energy Studies; Power System Studies; Methodology Studies and Technology
Studies, which, all together, have as an end result an analysis of the impacts of the
integration of large amounts of variable renewable energy sources in the National
Interconnected System (SIN). The study takes into account the analysis of energy and
power aspects and considers technological and cost trends, as well as a methodological
proposal and analytical tools for studies of this nature.
In order to carry out the study, an international bidding process was carried out, in which
the Consortium formed by the companies Lahmeyer International, Tractebel and PSR
was awarded to carry out the work.
One aspect that should be highlighted was the active participation of EPE and ONS
experts in the project execution, who, together with the contracted consultant, made
their knowledge available in the preparation of the products, as well as in the
participation of the various training sessions that were carried out during the work.
Objective
The study aims to analyse the impacts of the integration of large amounts of variable
renewable energy sources in the National Interconnected System and has the following
main objectives: i) to review the planning practices for the integration of renewable
energy sources in Brazil; ii) identify any gaps in current planning practices in Brazil with
respect to international practices; iii) to propose improvements in terms of
methodologies and analytical tools for the planning of the Brazilian electrical system;
and iv) carry out a case study using the methodologies and analytical tools proposed in
the study. Additionally, technical training sections carried out by the Consultant to
experts of EPE and ONS teams constituted an important part of this project.
Apresentação
Objetivo
O estudo visa analisar os impactos da integração de grandes quantidades de fontes
renováveis de energia no Sistema Interligado Nacional e possui os seguintes objetivos
principais: i) revisar as práticas de planejamento para a integração de fontes renováveis
de energia no Brasil; ii) identificar eventuais lacunas das práticas de planejamento
atuais no Brasil com respeito às práticas internacionais; iii) propor melhorias em termos
de metodologias e ferramentas analíticas para o planejamento do sistema elétrico
brasileiro; e iv) realizar um estudo de caso aplicando as metodologias e ferramentas
analíticas propostas no estudo. Adicionalmente, ações de capacitação técnica das
equipes da EPE e ONS constituem parte importante deste projeto.
Boa leitura.
Energy systems of the future: Final Report
Integrating variable renewable energy sources in Brazil's energy matrix
Acknowledgements
At the conclusion of this study, the project team could not fail to pay
a special tribute to our friend and colleague Juarez Castrillon Lopes,
who toasted us with his presence, joy, friendship and knowledge
during the execution of the study, but which unfortunately left us on
15 April 2020.
From the first conversations in the conception of this study, Juarez
has always shown himself as an idealizer and encourager of work.
The first ideas for this study were written by him in conversations
over coffee, on napkins, which were later refined until the elaboration
of the terms of reference detailing the content of the study. From the
beginning defending a greater interaction between system operation and planning, he
motivated the joint participation of EPE and ONS in all discussions about the study.
During its execution, Juarez always kept the work in the direction that the final objective
was reached, participating in all study working groups, always actively, enriching the
discussions with his high technical knowledge and creating a fraternal work environment
within the team. His always active participation was one of the factors that led to the
end of delivering a study of technical excellence. Juarez will definitely be missed by his
friends and colleagues who had the opportunity to share the life and work with him.
This acknowledgment does not intend to reflect everything that this electrical engineer,
promoter of wind energy and “Botafoguense”, contributed to the electricity sector in
these almost 45 years of dedication, but rather, to leave a simple and sincere tribute to
those who had the opportunity to enjoy his presence in the execution of this study.
Agradecimentos
Product 1:
Technical Regulation Studies
Final Report
RESTRICTED
May 2019
20-26-00173
Final Report
Transaction 81212141
number:
Project Number 15.2126.9-001.00
Country Brazil
Tractebel Engineering
Avenue Simon Bolivar 34-36,
1000 Brussels, Belgium
May 2019
20-26-00173
© Lahmeyer International GmbH, 2020
The information contained in this document is proprietary, protected and solely for the use of the Client
identified on the cover sheet for the purpose for which it has been prepared. Lahmeyer International GmbH
and its consortium partners Tractebel Engineering S.A. and PSR Soluções e Consultoria em Energia Ltda.
undertake no duty, nor accept any responsibility, to any third party who may wish to rely upon this document.
Save to the extent agreed otherwise with the Client all rights are reserved and no section or element of this
document may be removed from this document, reproduced, electronically stored or transmitted in any form
without written permission of Lahmeyer International GmbH and Tractebel Engineering S.A. and PSR
Soluções e Consultoria em Energia Ltda.
May 2019
20-26-00173
TABLE OF CONTENTS
1 INTRODUCTION 11
2.1 Acknowledgement 12
2.2 Background 12
3.3 Implementation 21
3.4 Enforcement 21
4.4 Implementation 28
5.1 Methodology 29
5.4 Synthesis 67
6.1 Introduction 69
6.2 Technical requirements for the connection of new facilities to the transmission network
(Module 3) 71
May 2019
20-26-00173
Energy systems of the future:
Integrating variable renewable energy sources in Brazil's energy matrix
6.3 Technical requirements for the connection of VRE generators to the transmission system 72
LIST OF FIGURES
Figure 2: Conditions for the successful VRE integration (adapted from [1]) 15
Figure 4: Aspects to be considered when drafting a grid connection code (adapted from [1])
16
Figure 7: Frequency tolerances, delays and authorized active power reduction for SG in
Denmark 35
Figure 8: Authorized active power reduction in case of low frequency for SG in Germany 35
Figure 9: Frequency envelope in which there may be no active power output limitation –
Germany 35
Figure 11: Authorized active power reduction in case of low frequency for SG in United
Kingdom 36
Figure 12: V/f range for Belgium to stay connected for an unlimited time in the hatched area
and with a commonly agreed time in the white area 37
Figure 15: V/f range with permitted active power reduction for Germany 38
Figure 19: Reactive power range requirements in function of the voltage – Spain 45
Figure 22: Frequency range imposed for offshore wind farms – Germany 50
Figure 23: Frequency range imposed for wind and solar power plants – Philippines 51
Figure 24: Active power (absorption) decrease for DC converters in case of frequency drop –
UK 51
Figure 25: Voltage operation ranges - comparison of different grid codes (VRE power plants)
51
Figure 27: V/f range of operation for wind power plants - Denmark 52
Figure 28: Fault ride through - comparison of different grid codes (VRE power plants) 52
Figure 29: FRT envelope for wind farms connected in 110 kV or above – Belgium 53
Figure 30: FRT envelope for wind farms connected below 110 kV – Belgium 53
Figure 32: FRT envelope for wind farms larger than 1.5 MW (zone A: remain connected and
operate normally, zone B: remain connected and offer full voltage support, zone C: disconnect)
– Denmark 54
Figure 33: FRT envelope for units not connected directly to the grid (through converters) –
Germany 55
Figure 36: FRT requirements for Special thermo solar units net equipped with synchronous
generators – Spain 56
Figure 37: FRT envelope requirement for a 140 ms fault – point of view from the LV side of the
platform – UK 56
Figure 38: FRT envelope requirement for a fault lasting more than 140 ms – point of view from
the LV side of the platform – UK 56
Figure 39: Reactive power requirements for on-shore wind farms – Belgium (blue area:
mandatory, grey area: not mandatory) 57
Figure 40: Reactive power requirements for off-shore wind farms – Belgium (blue area:
mandatory, grey area: not mandatory) 58
Figure 41: Reactive power capacity required for wind farms between 25 kW and 1.5 MW –
Denmark 58
Figure 42: Reactive power capacity required for wind farms between 1.5 MW and 25 MW –
Denmark 58
Figure 43: Reactive power capacity required for wind farms larger than 25 MW – Denmark 59
Figure 44: Reactive power capacity required for wind farms larger than 25 MW – Denmark 59
Figure 45: V/cosphi range of operation for wind farms with unrestricted power output –
Germany 59
Figure 46: P/Q requirements for wind farms when 0.95 pu< U <1.05 pu – Germany 60
Figure 48: P/Q requirements for wind farms (A and B = 0.95 lagging and leading, C and D =
5% Pnom, E = 12 % Pnom) – UK 60
Figure 49: Requirements on rapid voltages changes limitations for wind farms – Denmark 61
Figure 50: Flicker requirements for wind farms between 11 to 1500 kW – Denmark 61
Figure 51: Flicker requirements for wind farms larger than 1.5 MW – Denmark 61
Figure 52: Active power reduction requirement in case of over-frequency for wind farms larger
than 50 MW – Belgium 62
Figure 53: Example of P/f primary control required for wind farms larger than 25 MW –
Denmark 62
Figure 54: Active power reduction in case of over-frequency for renewable generation units –
Germany 63
Figure 57: Requirement for reactive power supply, IQ, during voltage drops for wind power
plants with a power output greater than 1.5 MW (zone B: priority to Q supply, not P supply) –
Denmark 64
Figure 58: Reactive current droop for offshore wind farms – Germany 65
Figure 59: Reactive current droop for units not directly connected to the grid (through
converters) – Germany 65
Figure 61: Current injection of wind farms during and after fault - Spain 66
Figure 63: Power factor requirement within the voltage operating range 74
Figure 69: Requirement for reactive current injection during faults (Brazilian grid code) 78
Figure 70: Recommendations for improvement of the requirement for reactive current injection
during faults 81
Figure 71: Definition of technical requirements at different locations (Brazilian grid code) 85
LIST OF TABLES
Table 1: Overview of technical requirements for VRE connection according to VRE share
(adapted from [1]) 22
Table 2: Transmission System Operators selected for the grid code review 30
Table 3: Main characteristics of the systems for which the grid codes were evaluated 30
Table 7: Fault ride through - comparison of different grid codes (synchronous generators) 38
Table 8: Power factor and reactive power capabilities - comparison of different grid codes
(synchronous generators) 41
Table 9: Phase unbalance, harmonics and flicker - comparison of different grid codes
(synchronous generators) 42
Table 10: P/f control - comparison of different grid codes (synchronous generators) 44
Table 11: V/Q control - comparison of different grid codes (synchronous generators) 44
Table 12: Earthing and protections - comparison of different grid codes (synchronous
generators) 46
Table 13: Islanding, black-start and synchronisation - comparison of different grid codes
(synchronous generators 48
Table 14: Information exchange - comparison of different grid codes (synchronous generators
48
Table 15: Frequency operation ranges - comparison of different grid codes (VRE power plants)
50
Table 17: Power factor and reactive power capabilities - comparison of different grid codes
(VRE power plants) 57
Table 18: Phase unbalance, harmonics and flicker - comparison of different grid codes (VRE
power plants) 61
Table 19: P/f control - - comparison of different grid codes (VRE power plants) 61
Table 20: P/f control - - comparison of different grid codes (VRE power plants) 63
Table 21: Earthing and protections - comparison of different grid codes (VRE power plants)
66
Table 22: Islanding and synchronisation - comparison of different grid codes (VRE power
plants) 67
Table 26: Technical requirements for energy storage applications in UK (transitory phase) [10]
86
Table 27: Benchmark of the Brazilian grid code with respect to the international practice
(synthesis of analyses) 87
List of Acronyms
Acronym Definition
AC Alternating Current
ANA Agência Nacional de Águas (National Water Agency)
ANAREDE Programa de Análise de Redes
ANATEM Programa de Análise de Transitórios Eletromecânicos
ANEEL Agência Nacional de Energia Elétrica (Regulator of the Brazilian Electricity
Sector)
ATP Another Transient Program
AVR Automatic Voltage Regulator
BESS Battery Energy Storage Solution
BIPS Brazilian Interconnected Power System
CCEE Câmara de Comercialização de Energia Elétrica (Brazilian Electricity Market
Operator)
CSP Concentrated Solar Power
DC Direct Current
DISCO Distribution Company
EPE Empresa de Pesquisa Energética (Energy Research Enterprise)
ENTSO-E European Network of Transmission System Operators for Electricity
RfG Requirements for Generators
FRT Fault Ride Through
GC Grid Code
HVDC High Voltage Direct Current
HVRT High Voltage Rider Through
IEC International Electrotechnical Commission
IEEE Institute of Electrical and Electronics Engineers
IRENA International Renewable Energy Agency
ISO Independent System Operator
KSA Kingdom of Saudi Arabia
LV Low Voltage
LVRT Low Voltage Ride Through
NSG Non-Synchronous Generators
PACDYN Small-Signal Stability Software Package
PDE Plano Decenal de Energia (10-year Energy Master Plan)
PF Power Factor
PoC Point of Connection
PP Power Plant
PPA Power Purchase Agreement
PPC Power Plant Control
PPM Power Park Modules
PSP Pumped Storage Power Plant
PSS Power System Stabilizer
PV Photovoltaic
pu Per Unit
RoCoF Rate of Change of Frequency
RRG Renewable Resource Generator
Acronym Definition
SG Synchronous Generator
SIN Sistema Interligado Nacional (National Interconnected System)
SPP Solar Power Plant
TSO Transmission System Operators
UK United Kingdom
UTC Coordinated Universal Time
VRE Variable Renewable Energy
VSC Voltage Source Converter
WPP Wind Power Plant
1 INTRODUCTION
The project “Energy systems of the future: Integrating variable renewable energy sources in Brazil's
energy matrix” aims at studying the impact of the integration renewable energy sources to the Brazilian
interconnected power system (BIPS) in both expansion and operation planning standpoints.
The general objective of the project, as specified in the ToR, is “to improve the prerequisites for systematic
integration of renewable energy and energy efficiency into the Brazilian Energy System”.
In this assignment, a pilot study on integrating renewable energies into the Brazilian energy system will be
performed. It will cover both operation and expansion planning aspects. More specifically, the objectives of
the project are:
· Perform an assessment of the current practices on VRE integration in Brazil;
· Perform an assessment of the international practices on VRE integration;
· Carry out a gap analysis between the international and the National practices in VRE integration;
· Carry out an expansion planning exercise composed by energetic and power system analyses consid-
ering power system operation aspects;
· Propose upgrades to the current practices in Brazil based on the results of the gap analysis and the
detailed energy and power system studies.
In order to accomplish the aforementioned objectives, the project is organized in eight (8) products, as fol-
lows:
· Product 0: Work Methodology
· Product 1: Technical Regulation Studies
· Product 2: Energy Studies
· Product 3: Power System Studies
· Product 4: Methodology Studies
· Product 5: Technology Studies
· Product 6: Final Report
· Product 7: Workshops
This report comprises the Product 1 of the project (“Technical Regulation Studies”). The report is structured
as follows:
· Chapter 2: General overview of grid codes and its role for VRE integration
· Chapter 3: Process for developing a VRE connection code
· Chapter 4: Description of technical requirements for VRE connection
· Chapter 5: International grid code benchmarking
· Chapter 6: Analysis of the Brazilian grid code
· Chapter 7: Conclusions and recommendations
2.1 Acknowledgement
This report focuses exclusively on grid connection codes and on the provisions relevant to the connection
of VRE generators. For the purpose of this report these refer to wind and solar Photovoltaic (PV) generators
of any size. The general term ‘VRE grid codes’ here specifies the minimum technical and design require-
ments for VRE generators so that their behaviour is compatible with system stability and safety requirements.
By providing appropriate technical and legal rules for VRE generators, VRE grid codes can support the
effectiveness of national and regional energy policies for renewables integration.
The content of this chapter is based on [1].
2.2 Background
The open formulation and implementation of enforceable grid codes first became necessary with the liber-
alisation of power systems. While some form of technical regulation for generators has always existed, en-
forceable grid codes have enabled the co-ordination of multiple individual stakeholders in decentralised
power systems. During the unbundling process, vertically integrated utilities were split up into their genera-
tion, grid and electricity sales parts and often privatised. The increasing numbers of small, private generators
and the separation of generation from operation of the network required clear rules on how these new gen-
erators should connect to the public grid.
Grid codes are not only useful in fully unbundled power markets. As technical rules, they regulate grid access
and network user operation regardless of whether the power system is operated and supervised by a specific
operator or by a vertically integrated utility. The establishment of a grid code is an important step in opening
up the power sector to private and especially VRE generators. It increases transparency and provides equal
treatment by making the same rules applicable to all. Like other governing frameworks, grid codes have
continuously been adapted to changing technologies, system conditions and political aspirations. This is
also reflected in the ongoing adaptation of grid codes to enhance the development of regional power markets
and integration of renewable energy generators.
The rise of renewables has been driven by the need to reduce carbon dioxide emissions, the plummeting
costs of renewable power plants and concerns about energy independence. VRE grid codes seek to ensure
that VRE generators contribute towards the safety, stability and reliability of the power system. Many VRE
generator grid code requirements show the desire to ensure the fair treatment of conventional and renewable
generators in terms of technical requirements on new generation assets of similar sizes. This is achieved by
making comparable demands of each in terms of to their contribution to system stability.
In many countries, the rise of renewables has not coincided with unbundling. Some countries, such as Japan
or small island states like Barbados, have retained vertically integrated utilities alongside private renewable
generators which feed into the utility’s grid. In these cases, VRE grid codes are still required to provide
technical regulations for the connection of renewables. Similarly, unbundled electricity systems may require
grid codes for conventional generators in the absence of renewables.
on the weather. This variability can present challenges depending on the level of penetration and the char-
acteristics of the conventional generators in the grid. Conventional generators must be able to compensate
for the difference between variable renewable output and consumer demand fast enough not to affect fre-
quency stability. Major, quick voltage changes due to variable feed-in can also disturb electricity consumers
nearby and should be avoided.
Individual VRE generators (as opposed to aggregated solar or wind farms) are usually smaller than conven-
tional generators. This is an advantage in that single VRE generator failure has less of a negative impact on
the power system than the sudden disconnection of conventional generators. The small size of some VRE
generators may mean there is no need to equip them with the functionality to provide certain system ser-
vices. However, as the technology is evolving rapidly, these services may become more and more common
among small VRE generators.
Conventional generators feed directly into the transmission network in a centralised manner. By contrast,
small VRE generators, particularly rooftop solar PV, are often distributed across the power system and feed
electricity in at low voltage levels. In the past only electricity consumers were connected at low voltage levels.
If distributed PV feed-in exceeds the local electrical load, the voltage can exceed regulated limits. The re-
versed power flow on the low voltage power line may then exceed line or transformer capacity limits.
As well as being smaller and variable, renewable generators such as wind turbines and PV systems have
different technical properties from conventional power stations. At first, inverter-connected wind and solar
plants could not match the services provided by traditional power plants. However, technological innovation
parallel with the development of grid codes has allowed VRE generators to be subject to requirements to
help stabilise the network. For example, VRE generators can now provide reactive power for voltage control,
active power reduction during congestion or over-frequency events, and network support during faults.
Synchrhonous
Operational Security Generation Planning
Generator Connection Planning Code Market Rules Code
Code Code
Code
Network Capacity
VRE Generator Operational Planning Network Planning Allocation and
Connections Code
Connection Code and Scheduling Code Code Congestion
Management Code
Load Frequency
Demand Connection System
Operations Code Control and Reserve
Code Interconnection Code
Code
Interchange
HVDC Connection Emergency Procedure
Scheduling and
Code Code
Balancing Codes
Operator Training
Data Exchange Code
Code
Metering Code
Operator Training
Code
Technical requirements in grid codes are determined by the need to maintain the reliability, security and
quality of the power supply and fulfil the objectives below.
· The electrical power needs of all consumers must be met reliably.
· Voltage and frequency must be maintained within set limits to avoid damaging equipment connected to
the grid.
· The system must be able to recover quickly from system disturbances.
· At all times the system must operate without endangering the public or operating staff.
These basic needs are translated in the grid code into operational requirements demanded to all generators
including VRE based on their technical impact described above. System operators make use of the services
provided by power plants and other equipment to maintain system stability and safety.
A VRE grid code allows the network operator to provide clear rules and technical requirements for wind and
solar plant operators when connecting to the country’s electricity networks. Depending on the country, the
network operator may use the fulfilment of the grid code as a precondition for connection to the network.
The code can act as a legal requirement for connected generators, who may be prosecuted if the require-
ments are not fulfilled. As binding rules, grid codes help to ensure that generator owners and operators are
treated fairly in terms of grid connection while ensuring system stability and reliability.
Technical
Regulation -
Grid Codes
Successful
VRE
Integration
Evolution of
System Technology
Operation Developments
Practices
Figure 2: Conditions for the successful VRE integration (adapted from [1])
The sub-code that is the focus of VRE integration analyses is the Grid Connection Code1. The function of
a grid connection code applied to VRE is to provide a set of technical requirements for the connection of
1
In this project, the focus of the grid code analysis is on the Connection Codes and on the provisions related to the
connection of VRE generators (wind and solar PV).
wind and solar PV power plants to a given power system. This code is in charge of establishing a fair treat-
ment for all VRE power plants in which regards the technical requirements for the power plant to access the
grid. This helps to ensure the fair treatment of generator owners and operators concerning grid connection
while maintaining system stability and reliability. By providing appropriate technical and legal rules for VRE
generators, VRE connection codes can support the effectiveness of energy policies for VRE integration.
The process of developing a VRE connection code usually comprises the steps depicted in Figure 3.
Implementation
Revision based on policy changes and experience after employing the grid code
The development of a VRE connection code should count on the previous experience from different systems
around the world. However, the connection code of another system cannot be directly adopted. A great
portion of the requirements for the connection of VRE generating units depend on the specific needs and
characteristics of the local power system. Figure 4 shows the aspects that need to be taken into account
when developing a VRE connection code.
Figure 4: Aspects to be considered when drafting a grid connection code (adapted from [1])
Many requirements can be harmonised internationally, enabling countries to pool their resources in areas
such as certification. This also makes it easier for manufacturers to access more markets, resulting in lower
costs to consumers. The use of international standards to prepare VRE grid codes is another relevant in-
strument for harmonising requirements, as well as a valuable platform for experts to exchange international
experiences and document good practices. The integration of regional power markets also requires regula-
tory efforts through, for example, regional grid codes like the Nordic Grid Code and European Network of
Transmission System Operators for Electricity (ENTSO-E) Network Codes. These regional grid codes do
not replace national grid codes but instead provide a common framework for minimum requirements that all
national grid codes should meet.
Enforcing technical requirements in VRE grid codes means using mechanisms to verify compliance with the
codes. There are different strategies with differing costs and degrees of feasibility depending on country
context. These mechanisms include, for example, on-site inspection, use of certification systems or verifica-
tion of whole plants instead of verification of each and single unit in a plant.
Policy-makers and regulators have to support the development and implementation of VRE grid connection
codes in association with the national renewable energy goals, by:
· Ensuring that grid connection codes include appropriate requirements for VRE. Electricity system stud-
ies can play a role in the identification of appropriate requirements. Also, other sources of information
regarding local considerations should be used as input for the code.
· Consulting with all relevant stakeholders. Grid connection codes have an impact on all actors involved
in the power system. Therefore, engagement of all parties will ensure that the codes can be imple-
mented without putting the system security in peril and at the same time the responsibilities are fairly
distributed between all actors.
· Setting a predictable and reliable grid code revision process in place. This increases system reliability
and security by coordinating changes as technology and operation practices develop, also facilitating
the future planning of the system.
· Anticipating technical requirements based on future VRE targets. Grid codes should not only consider
the architecture of today’s power system, but already anticipate the future system requirements in line
with national VRE goals.
· Learning from other countries experience. Identify best practices and lessons learnt from frontrunner
countries in integrating a high share of VRE in power systems. However, avoid to implement a carbon
copy of other countries grid codes without considering local aspects.
· Joining regional initiatives to harmonize requirements and share resources. Regional initiatives and
engaging in international standardisation processes may facilitate the development and implementation
of grid codes by sharing experiences, deploying regional infrastructure for verification and certification
processes, and harmonising requirements resulting in cost reduction due to market scale for technology
suppliers.
Grid connection codes help in ensuring that ambitious policy targets for the deployment of VRE are met
without compromising the security of the electricity system. All relevant stakeholders follow the same rules
as defined in the code, facilitating therefore the operation of the system. As VRE grid codes have evolved
hand-in-hand with technology and operational practice, they have also pulled through the deployment of
best available technologies for VRE grid integration. What could be considered advanced technologies for
integrating VRE a few years ago is now becoming commercially available technology provided by most
technology suppliers. A country investing in sound VRE grid code development and implementation will
enjoy a guaranteed benefit in terms of reliably integrating high shares of VRE at an affordable grid cost.
provides some guarantee that the requirements have been tested and reviewed in other countries. It is also
easier for manufacturers to conform to international standards than to comply with each different national
set of rules. These cost savings can then be passed to the consumer.
Grid codes must be tailored to the specific requirements of individual countries. It is important to ensure that
the international standards referred to make sense for that country. System operators responsible for grid
codes also often take part in the development of standards. However, as more stakeholders are involved,
revising international standards may prove to be more difficult than simply changing national regulations.
Countries usually strike a balance by writing their own grid codes and selectively referring to specific inter-
national standards where appropriate or in areas where there are no known considerations specific to that
country. Since grid code harmonisation across countries is still desirable, standards concerning additional
aspects of VRE grid connection are emerging and may shift the relationship between standards and grid
codes in the coming years.
3.3 Implementation
The fulfilment of grid code requirements may require additional investment by VRE and conventional gener-
ator operators and/or other stakeholders such as manufacturers. If these extra costs are too onerous for
these stakeholders, new generators may not get built and VRE generation targets might not be reached.
The fulfilment of grid codes can be facilitated in two ways through policy instruments. Firstly, stakeholders
can be consulted in the process of drafting the rules. Secondly, support mechanisms can be provided to
incentivise the fulfilment of advanced technical and operational capabilities.
The collection of stakeholder feedback (e.g. from manufacturers and operators) during the draft phase of
both technical requirements and operational regulations is an important step. It ensures that requirements
can be met without too much effort from the generators.
Policy makers and network operators or regulators can compensate the costs of advanced capabilities either
through existing support mechanisms, such as feed-in tariffs, or by directly incentivising VRE equipment to
meet VRE grid code requirements. The cost to generators of grid code compliance will arise anyway. How-
ever, providing a defined way for generator operators to recover this cost encourages investment, drives
technology development and decreases costs in the long run.
3.4 Enforcement
The legal status and enforcement of grid codes vary from country to country depending on the institutional
set-up of their power and legal system. In some countries, the grid code is both mandated and established
in law. This means non-compliance with grid code requirements counts as a civil penalty, which can result
in fines. In other countries, the development and publication of technical grid connection conditions by the
network operators is mandated by law. However, the requirements are only a precondition for the network
operator to connect the VRE unit.
Mechanisms to verify compliance with grid connection codes by generators should be in place. Certification
is a way to assure compliance with the grid code but it requires resources and technical capacity. Rather
than checking that each individual VRE unit fulfils the grid code requirements of particular manufacturer
models, network operators can mandate VRE grid code compliance through certification mechanisms. They
can then stipulate in the grid code that the VRE operator only needs to present the certificate for its generator
model to be able to connect to the grid. This can lower costs and encourage a higher VRE share.
Table 1: Overview of technical requirements for VRE connection according to VRE share (adapted from
[1])
VRE PENETRATION
TECHNICAL REQUIREMENTS
LEVEL
• Protection
• Power quality
Always needed
• Power reduction during over-frequency
• Commissioning and compliance tests
• Communication
Low VRE share • Adjustable reactive power
• Constraining active power (active power management)
• Voltage control
• Active power gradient limitation
Very high VRE share
• Reduced output duration mode for reserve provision
• Synthetic inertia
2
It should be noticed that the classification according to VRE share are system-dependent. These values should be
seen from the perspective of the expected impact of VRE in a given system for different penetration levels. All listed
requirements remain necessary when the next VRE share level is reached.
VRE PENETRATION
TECHNICAL REQUIREMENTS
LEVEL
The following sub-sections briefly describe the different technical requirements for VRE connection typically
imposed in grid codes around the world.
3
These requirements are set for permanent (continuous) deviations from the nominal values.
4
For a VRE generator to provide regulation in under-frequency events it is needed that the plant be operated below its
maximum power point or be equipped with a local energy storage unit, which increases significantly the operational
and capital expenditures, respectively.
contrast to the aforementioned frequency support requirement, the objective of this requirement is not the
response to disturbances but the probability that such disturbances will be caused by VRE fluctuations.
The maximum power ramps induced by VRE can be adapted to the ramping capability limits of the frequency
regulation services by imposing ramping constraints on VRE power plants. The easiness of implementing
such ramping constraints depends on the cause of the power ramps. An increase in primary power can be
mitigated relatively easily by limiting the power injection ramp. However, a quick unforeseen decrease in
primary power can only be limited if local energy storage can be released when the power injection drops
too fast. Besides primary energy fluctuations, ramps can also result from a number of events. These include
VRE plant start-up and shutdowns in normal operation and during or after fault incidents, wind park shutdown
during high winds, and activation or deactivation of reduced output operation modes. Limiting the resulting
ramps in these situations is common practice.
4.1.8 Communication
Power system operation requires communication in multiple ways. Real-time measurement data transmis-
sion is necessary to assess the system state. Control commands (e.g. desired state of switching equipment,
generator setpoints, etc.) must be communicated to the corresponding actors. Communication must there-
fore extend to all significant generation assets, and security of communication must be provided in order not
to risk system operation in case of communication failures.
In addition to the need of monitoring the power plant operation, VRE power plants need communication
interfaces to implement the advanced features required by the grid code. Active power management and
power reduction for reserve provision purposes is especially relevant. However, gradient limitations and
reactive power controllability all also necessitate dynamic control access by the system operator.
Requirements for communication should be based on international standards to avoid vendor dependency,
encourage competition and ensure cost efficiency.
4.1.9 Protection
Grid codes not only specify when generators need to remain connected to the grid during faults, but also
stipulate requirements of how the protection system at the point of connection shall be designed and which
settings are to be used. Generator owners are normally responsible for additional measures that prevent
damage to the equipment internal to the power plant. All settings should be compatible with the requirements
concerning fault behaviour.
complete and accurate models of the grid and the generator systems dominating its behaviour. Grid opera-
tors and planners depend on plant operators to provide models for their power plants. Generator owners are
thus often required by the system operator to hand in simulation models that adequately represent the real
behaviour of the plant in a specified format before they are allowed to connect their unit to the grid.
Correlating with system impact, simulation models are usually required for the large power plants (including
VRE). They are also required for smaller plants connected to lower voltage levels with an increasing share
of distributed generation. To maintain the accuracy of the operator’s general system models, rules on plant
models in grid codes cover model functionality, accuracy and validation procedures. The models are usually
developed and provided by the project developers.
5
Typical values:
- Single line-to-ground faults: 70%; line-to-line faults: 15%; double line-to-ground faults: 10%; symmetrical
faults: 5%.
6
A historical reason for this fact is that synchronous generators provide unbalanced fault currents during faults as an
intrinsic characteristic of the machine.
7
Reference: https://www.entsoe.eu/network_codes/rfg/
8
ENTSO-E RfG statement: “… with regard to the supply of fast fault current in case of asymmetrical (1-phase or 2-
phase) faults, the relevant system operator in coordination with the relevant TSO shall have the right to specify a re-
quirement for asymmetrical current injection.” And “Fault-ride-through capabilities in case of asymmetrical faults shall
be specified by each TSO”.
This list only includes studies relating to VRE grid code parameter creation and should be added to studies
to be conducted for system planning and operation purposes.
4.4 Implementation
Depending on the type of VRE generation, technical requirements imposed on generators can be easy to
implement or require significant effort. The subsection below therefore lists the most important technologies
and provides a brief discussion on the ease of implementation of different technical requirements. Since
requirements are also of different importance from a power system and VRE share perspective, another
subsection follows that provides a prioritisation of requirements within the power system context. The last
subsection in this chapter lists the most important types of studies that help determine the technical param-
eters of requirements when drafting or revising a VRE grid code.
5.1 Methodology
This state of the art is established by comparing the grid codes of several operators around the world in
order to integrate different points of view. The following countries were considered:
· Belgium
· Canada
· Denmark
· Germany
· Spain
· The Philippines
· United Kingdom (UK)
These countries were chosen to cover:
· Different VRE technologies: solar (PV and CSP), wind, etc.
· Different types of power systems around the world: Europe, America, Asia
· Significant VRE shares in their energy mix:
· Denmark is a pioneer of wind energy
· Germany has a very high VRE integration level
· Belgium combines a mix of VRE with strong inflexible generation basis (about 60% of nuclear)
· grids presenting similar characteristics than the Brazilian grid:
· Canada, Germany and UK present long transmission lines
· UK and Canada have few interconnections with neighbouring countries and these interconnections
are mostly HVDC.
· Canada and Philippines are operated in 60 Hz
· Spain has utility-scale CSP.
These arguments are summarized in the table on the next page.
The grid codes of the corresponding transmission system operators (TSO) were examined. Sometimes sev-
eral companies operate the network of a single country, or several operators worked together to release a
single grid code.
· In Canada, there are different utilities in each geographical region. This document focuses on the British
Columbia area, where BC Hydro is in charge of the transmission grid.
· In Germany, the TSOs released a common grid code but each of them also has its own grid code with
more recent updates. The requirements applied in one of the TSO have been analysed.
· In United Kingdom, in the grid code, when different rules apply for England, Wales and Scotland, the
rules for England are presented.
The table below shows, for each country, the voltage levels managed by the TSO.
Table 2: Transmission System Operators selected for the grid code review
COUNTRY COMPANY VOLTAGE LEVEL
Belgium ELIA 380 to 30 kV
Canada (British Columbia) BC Hydro 500 to 60 kV
Denmark Energinet 400 to 132 kV
Germany Tennet TSO Gmbh 380 and 220 kV
Philippines TransCo 500 to 69 kV
Spain Red Electrica de España 220 to 400 kV
National Grid Electricity
UK 400, 275 and 132 kV
Transmission
This review of the grid codes considers only the requirements on VRE power plants. It first focuses on the
classification applied to the different resources, which can be different for each system operator. This clas-
sification is achieved with the purpose of associating different requirements to each class of resources,
depending on the issues faced by the operator in its network and on the characteristics of the resources.
The main classification factors are usually:
· The primary source of energy for generation: thermal, wind, solar…
· The size of the generation plant: MVA, MW…
· The connection voltage of the power plant
· The geographical location of the power plant and of its connection: onshore, offshore…
· The type of connection to the grid: AC line, AC cable, AC submarine cable, HVDC, VSC…
Table 3: Main characteristics of the systems for which the grid codes were evaluated9
LONG DIS- EXPECTED
SHARE EXPECTED EXPECTED
VRE TANCE HVDC INTER-
COUNTRY OF SHARE OF SHARE OF
SHARE TRANS- CONNEC-
NPP WIND SOLAR
MISSION TIONS
United
++ + ++ ++
Kingdom
Denmark +++ + +++
British Co-
lumbia + +++ + +
(Canada)
++
Belgium ++ ++ + +
(rooftop PV)
9
The legend of this table is the following. A “+” denotes a country that performs above average in the category of the
column, a “++” represent a country that for with the category is significant and a “+++” denotes a country which has to
modify greatly its power system development, planning and operation to allow its secure operation.
After this classification is assessed, the requirements for grid access and operation are investigated, for
each category. The issues examined are:
· Capabilities to stay connected: frequency and voltage tolerances, low voltage ride through, reactive
power capabilities;
· Power quality: phase unbalance, harmonics and flicker;
· Controls: active power/frequency regulation, voltage/reactive power regulation, excitation system, PSS
and damping;
· Protections and earthing philosophy;
· Islanding, synchronisation, black start capacities;
· Information exchange.
In all countries, the grid codes documents were initially written for onshore synchronous generators. Indeed,
in the past, the latter were the main generation technology connected to the network. Then these grid codes
had to be adapted, amended and/or completed with the growing development of new technologies such as
wind power, HVDC, offshore generation and distributed energy resources. Consequently, the presentation
of grid codes often follows the same structure: it first describes the minimum technical requirements for
onshore synchronous generators, and then provides amendments, or even sometimes dedicated docu-
ments, to particular issues concerning other technologies.
The presentation of the connection and operation conditions for the various categories follows the same
structure as well, presenting the grid codes requirements for onshore synchronous generators (including
VRE based on Synchronous Generation, if any) first, and then giving details and differences for Power Park
Modules (PPM) which are mainly for VRE.
The proposed definition for PPM is: a unit or ensemble of units generating electricity, which is connected to
the network non-synchronously or through power electronics, and has a single PoC to the transmission
system. It includes all wind and solar PV power plants, among others.
The full set of references used in this analysis is given in Annex A.
Liberalisation of the electricity industry made it sometimes more complex due to the various stakeholders,
network operators in the same region, several documents sometimes overlapping, yielding a final classifica-
tion that does not always cover all possibilities.
This chapter is willing to identify the different categories of generation considered by the network operators
selected in this study.
Table 4 gives, for each country, the different categories of generation considered in the grid codes. A label
is given to each category. First, the category corresponding to Synchronous Generators (SG) is identified.
Second, a Power Park Module (PPM) label is put on the other categories. These categories differ from the
technology, the voltage of the connection point and the size of the rated power of the generation, but also
from other distinctions considered in the different grid code documents of each country.
· In Belgium, PPM have the opportunity to fulfil a separate set of requirements, better adapted to non-
synchronous generation, than the main grid code requirements which were initially designed for syn-
chronous generating units.
· In Canada, British Columbia, the connection of DC power station is examined case by case by the TSO
to provide the minimum technical requirements. It is therefore not included in this analysis.
· In Denmark, as it is done in Belgium, exceptions are mentioned for power converters, but no information
could be found for the latter.
· Voltage: Voltage ranges for which the generator must remain connected, sometimes with time delays
before authorized disconnection, and often function of the frequency.
· Fault ride through (FRT): Voltage dips with duration, whether or not associated to faults, for which the
generator has to remain connected to the grid, sometimes with active and reactive power requirements.
· Power factor and reactive power capabilities: P/Q ranges required.
Frequency:
Table 5: Frequency operation ranges - comparison of different grid codes (synchronous generators)
CONTINUOUS CONTINUOUS
OPERATION AT OPERATION AT OPERATION WITH DELAY
COUNTRY
CONSTANT ADJUSTABLE BEFORE DISCONNECTION
RATED POWER POWER
See Figure 12 See Figure 12 and in addition
and in addition for for all voltage value for fre-
Belgium all voltage value quency ranges [48 Hz; 48.5 Hz]
with the range and [51 Hz; 52.5 Hz]
48.5 to 51 Hz
For frequencies in For frequency ranges [56.4 Hz;
Canada the range 59.5 to 59.5 Hz] and [60.5 Hz; 61.7 Hz]
60.5 Hz (see Figure 6)
For frequencies in For frequency ranges [47 Hz;
Denmark the range 49 to 49 Hz] and [50.5 Hz; 53 Hz]
50.5 Hz (See Figure 7)
For frequencies in For frequency ranges [47.5 Hz;
Germany the range 49 to 49 Hz] and [50.5 Hz; 51.5 Hz]
50.5 Hz (See Figure 8 and Figure 9)
For frequencies in For frequencies below 59.6 and
Philippines the range 59.7 to above 60.4 Hz for at least 5
60.3 Hz seconds
Below 48 Hz for 3 seconds.
Spain
Above 51.5 Hz
For frequencies in For frequency ranges [47 Hz;
UK the range 49 to Figure 11 49 Hz] and [51 Hz; 52 Hz] (See
51 Hz Figure 10)
Figure 7: Frequency tolerances, delays and authorized active power reduction for SG in Denmark
Figure 8: Authorized active power reduction in case of low frequency for SG in Germany
Figure 9: Frequency envelope in which there may be no active power output limitation – Germany
Figure 11: Authorized active power reduction in case of low frequency for SG in United Kingdom
Voltage:
Table 6: Voltage operation ranges - comparison of different grid codes (synchronous generators)
COUNTRY REQUIREMENT
Belgium Figure 12
Maintain constant active power between 0.95 and 1.05 pu
Canada
Remain connected between 0.9 and 1.1 pu (Figure 13)
Denmark Figure 14
Germany Figure 15
Maintain constant active power between 0.95 and 1.05 pu
Philippines
Remain connected between 0.9 and 1.1 pu
Maintain operation and active power output for normal grid voltage
conditions are:
Spain
- From 390 to 420 kV for 400 kV level
- From 205 to 245 kV to 220 kV level
Maintain constant active power in the +/-5% range.
UK
Q range available for V+-5% for all voltage levels
Figure 12: V/f range for Belgium to stay connected for an unlimited time in the hatched area and with a
commonly agreed time in the white area
Figure 15: V/f range with permitted active power reduction for Germany
Denmark
· 1 or 2 ph above 100 kV
Germany
Philippines No requirement
Spain
UK onshore
Germany
Table 9: Phase unbalance, harmonics and flicker - comparison of different grid codes (synchronous gener-
ators)
FLICKER AND
COUNTRY PHASE UNBALANCE HARMONICS VOLTAGE VARIA-
TIONS
Belgium IEC 61000 IEC 61000 IEC 61000
FLICKER AND
COUNTRY PHASE UNBALANCE HARMONICS VOLTAGE VARIA-
TIONS
Canada 1% phase voltage and IEEE Std 519 See Figure 16
5% phase current
Denmark IEC 61000 IEC 61000 IEC 61000
No requirement No requirement de- No requirement de-
fined. fined.
Germany Checked by TSO Checked by TSO
during grid connec- during grid connec-
tion study tion study
Philippines Zero and negative se- Should ensure that V steps 1% max
quences voltage imbal- levels in Figure 17 V changes 3% max if
ance below 1% and Figure 18 are re- not steps
spected
5% of inverse current
Spain must be supported by
the unit
V imbalance below 1% Engineering recom- Engineering recom-
in Wales and England, mendation G5/4, ap- mendation P28
below 2% in Scotland. pendix A for onshore
UK
generation
To be agreed for off-
shore generation
5.3.1.3 Controls
The two different controls usually required on generators are here investigated:
· Active power/frequency control: obligation of providing primary frequency control, permissible droop
and dead band range, response performance, etc.;
· Reactive power/voltage control: obligation of providing primary voltage control, permissible droop,
damping performance, etc.
P/f control:
Table 10: P/f control - comparison of different grid codes (synchronous generators)
DEAD-
COUNTRY PRIMARY DROOP PERFORMANCE
BAND
50% within 15s, 100% within
Belgium Not mandatory 30s
Sustainable for 15 min
IEEE Std 125 Section 4 for
Max +/- 36
Canada Speed control available 5% hydro and Std 122 Section 4
mHz
for ST
Between 2 Max +/-200
Denmark Mandatory Table with ramp rates
and 8% mHz
Full activation for 200 mHz
Max +/-10 deviation. 100% reserve
Germany Mandatory if >100MW adjustable
mHz provided within 30s
(Figure 9)
Maximum response time of
5 s and 25 s for primary and
Philippines Mandatory 5% or less
secondary control respec-
tively
Unblock 1.5% Pnom in 15s
Spain Mandatory Not allowed
for deviation of 100 mHz
Response according to en-
Between 3 Max +/-15
UK Mandatory velope (appendix 3 of the
and 5% mHz
grid code)
V/Q control:
Table 11: V/Q control - comparison of different grid codes (synchronous generators)
COUNTRY REGULATION DROOP DAMPING
If Pn>25 MW, Automatic Voltage Range
Regulation (AVR), continuous, V given for
setpoint adjustable on demand units with
Belgium
If Pn<25MW, no AVR, Q setpoint Pn>25MW
adjustable on demand within a
range agreed
Continuous voltage support. V and PSS mandatory,
Q control, with adaptation on de- tuned by TSO
Canada mand.
Particular requirements on excita-
tion system capabilities
Automatic, continuous V control for Non oscillating for
all voltage levels, adjustable on de- a 10% V in-
mand crease, with time
+Automatic tgphi control if con- requirements.
Denmark
nected above 100 kV PSS mandatory if
Particular requirements on excita- >25 MW
tion system capabilities Overshoot limita-
tion
Mandatory. Constant V control can
Germany
be required
Figure 19: Reactive power range requirements in function of the voltage – Spain
Table 12: Earthing and protections - comparison of different grid codes (synchronous generators)
NON-MANDA-
MANDATORY
COUNTRY EARTHING TORY PROTEC-
PROTECTIONS
TIONS
Belgium To be discussed Grid operator indi- Discussed and de-
and agreed with cates the protec- tailed in the con-
grid operator tions on the con- nection agreement
nection contract
Canada Source of ground May be required to Recommended:
current required on participate to SPS negative sequence
HV side Over/under V/f
mandatory (WECC
compliant settings)
Overcurrent
Denmark According to speci- Figure 20 Figure 21
fications from grid
utility
Germany To be discussed To be discussed To be discussed
and agreed with and agreed with and agreed with
grid operator grid operator grid operator
Min distance relay
on connection link
with defined set-
tings
Philippines In 115 kV and Connection protec-
above: Earth fault tion with min clear-
factor of 1.4 max, ing times
HV side of trans- Circuit breaker fail-
former must be Y ure
with neutral availa- Loss of excitation
ble and LV connec- Pole slipping
tion and grounding
to be specified by
the Grid Owner.
To be decided by
the Grid owner be-
low 115 kV
Spain To be discussed To be discussed ”Criterios gener-
and agreed with and agreed with ales de protección
grid operator. grid operator. del system eléc-
trico peninsular es-
pañol”
UK Earth fault factor of Connection protec- Pole slipping (may
1.4 max tion with min clear- be required by grid
Transformer Y HV ing times operator)
config suitable for Circuit breaker fail-
connection to ure
earth. LV and Main and back-up
earthing arrange- protection delays
ment such that Loss of excitation
earth fault factor is
respected
Table 13: Islanding, black-start and synchronisation - comparison of different grid codes (synchronous
generators
SYNCHRONISA-
COUNTRY ISLANDING BLACK START
TION
Not mandatory.
Specific require-
Allowed below 48 To be discussed
Belgium ments apply if an-
Hz with grid operator
cillary service is
provided.
Automatic equip-
May be required. No requirement. To ment required.
Canada To be specified by be discussed with Synchrocheck re-
BC hydro. grid operator. quired if parallel
path could exist
No requirement. To
<25 MW: no re- be discussed with
quirement grid operator.
Automatic equip-
Denmark >25 MW: require- Capable of ener-
ment required
ments, automatic gising dead grid
for some conditions from house load
operation.
>100 MW: must be
May be required by Automatic equip-
Germany able to support is-
the grid operator. ment required
landing
10
It should be noticed that in some cases, requirements for HVDC systems are also included. This is due to the fact
that some system operators set common requirements for converter-based equipment in their grid codes
Consequently, it is important to keep in mind that the requirements presented for the synchronous generators
in Section 5.3.1 are valid for all VRE power plants, unless stated otherwise in the tables below. The following
sections focus only on the differences.
Frequency:
Table 15: Frequency operation ranges - comparison of different grid codes (VRE power plants)
COUNTRY AND
DIFFERENCES WITH SG REQUIREMENTS
CATEGORY
Belgium wind See Table 16
In addition to the capability to stay connected, there is a manda-
tory disconnection below 47.5 Hz and above 52.5 Hz
Germany Wind Remain connected between 46.5 to 47.5 for 10 s
Remain connected between 51.5 to 53 Hz for 10 s
Beyond 46.5 and 53 Hz, disconnection after 300 ms
See Figure 22
Philippines See Figure 23
Wind, Solar and
Small Solar
Spain special No disconnection below 50.5 Hz for unit sizes above 10 MW
non-dispatchable Disconnection mandatory if frequency above 51 Hz for 200 ms
and if unit size is lower than 10 MW
Spain special Disconnection mandatory if frequency is above 51 Hz
dispatchable
UK DC See Figure 24
Figure 22: Frequency range imposed for offshore wind farms – Germany
Figure 23: Frequency range imposed for wind and solar power plants – Philippines
Figure 24: Active power (absorption) decrease for DC converters in case of frequency drop – UK
Voltage:
Figure 25: Voltage operation ranges - comparison of different grid codes (VRE power plants)
COUNTRY AND
DIFFERENCES WITH SG REQUIREMENTS
CATEGORY
Belgium Wind Voltage above material limit (to be asked to TSO)
Voltage below 92.5%
Denmark Wind See Figure 26 and Figure 27
Philippines Wind, 5% reduction of active or reactive power may be allowed if the
Small Wind, Solar voltage goes beyond the range +/- 5%
and Small Solar
Figure 27: V/f range of operation for wind power plants - Denmark
COUNTRY AND
DIFFERENCES WITH SG REQUIREMENTS
CATEGORY
same envelope with minimum level 0.5 pu instead of 0 pu for
phase to phase faults.
Wind farms must support the same requirements than synchro-
nous generators.
UK offshore Choice must be made between the same requirements as SG or
new requirements expressed from the point of view of the LV side
of the platform (see Figure 37and Figure 38)
UK Power park No requirement if operating at P<5% Pn or in case of such high
wind speed that 50% of the park has been shut down under emer-
gency conditions
Figure 29: FRT envelope for wind farms connected in 110 kV or above – Belgium
Figure 30: FRT envelope for wind farms connected below 110 kV – Belgium
Figure 32: FRT envelope for wind farms larger than 1.5 MW (zone A: remain connected and operate nor-
mally, zone B: remain connected and offer full voltage support, zone C: disconnect) – Denmark
Figure 33: FRT envelope for units not connected directly to the grid (through converters) – Germany
Figure 36: FRT requirements for Special thermo solar units net equipped with synchronous generators –
Spain
Figure 37: FRT envelope requirement for a 140 ms fault – point of view from the LV side of the platform –
UK
Figure 38: FRT envelope requirement for a fault lasting more than 140 ms – point of view from the LV side
of the platform – UK
Figure 39: Reactive power requirements for on-shore wind farms – Belgium (blue area: mandatory, grey
area: not mandatory)
Figure 40: Reactive power requirements for off-shore wind farms – Belgium (blue area: mandatory, grey
area: not mandatory)
Figure 41: Reactive power capacity required for wind farms between 25 kW and 1.5 MW – Denmark
Figure 42: Reactive power capacity required for wind farms between 1.5 MW and 25 MW – Denmark
Figure 43: Reactive power capacity required for wind farms larger than 25 MW – Denmark
Figure 44: Reactive power capacity required for wind farms larger than 25 MW – Denmark
Figure 45: V/cosphi range of operation for wind farms with unrestricted power output – Germany
Figure 46: P/Q requirements for wind farms when 0.95 pu< U <1.05 pu – Germany
Figure 48: P/Q requirements for wind farms (A and B = 0.95 lagging and leading, C and D = 5% Pnom, E =
12 % Pnom) – UK
Figure 49: Requirements on rapid voltages changes limitations for wind farms – Denmark
Figure 50: Flicker requirements for wind farms between 11 to 1500 kW – Denmark
Figure 51: Flicker requirements for wind farms larger than 1.5 MW – Denmark
5.3.2.3 Controls
P/f control:
Table 19: P/f control - - comparison of different grid codes (VRE power plants)
COUNTRY AND
DIFFERENCES WITH SG REQUIREMENTS
CATEGORY
Belgium Wind Capable of decreasing the power with a rate of 10%
Pnom/min
If onshore, reduction can be required down to 60%Pnom in
Winter, 50% in Autumn and Spring, and 40% in Summer
If offshore, reduction can be required down to 50%Pnom in
Winter, 45% in Autumn and Spring, and 40% in Summer.
Over-frequency above 50.5 Hz => power reduction (Figure
52)
Canada Wind May be required to have frequency regulation for islanding
conditions if Pn >10 MW
Denmark Wind Complex droop curve allowing parameters tuning (Figure
53)
Constraints to be set up on max power, reserve level (if >25
MW), power gradients
Germany RRG Primary control not mandatory, even if >100 MW
Active power reduction in case of over-frequency (Figure
54)
Philippines Wind and Constant active power mode with gradients modification as
Solar per Figure 55.
Change requests must be started after 2 s and completed
after 30 s, with accuracy of 2% of entered value or 0.5% of
rated power, whichever the most constraining.
COUNTRY AND
DIFFERENCES WITH SG REQUIREMENTS
CATEGORY
If frequency goes above 61Hz, the active power should be
decreased according to Figure 56.
If the frequency drops below 59Hz, the active power should
be set to Pmax.
Spain special dis- Accreditation mandatory to participate to services markets
patchable Change requests must be fulfilled within 15 minutes
UK others No requirements for off shore power park smaller than 50
MW
Figure 52: Active power reduction requirement in case of over-frequency for wind farms larger than 50 MW
– Belgium
Figure 53: Example of P/f primary control required for wind farms larger than 25 MW – Denmark
Figure 54: Active power reduction in case of over-frequency for renewable generation units – Germany
V/Q control:
Table 20: P/f control - - comparison of different grid codes (VRE power plants)
COUNTRY AND
DIFFERENCES WITH SG REQUIREMENTS
CATEGORY
Belgium Wind Q control is required
Canada Wind PSS may be needed but not mandatory
Constant voltage control at point of interconnection
Q control may be required
Small farms (<10 MVA) may be dispensed from V control
Denmark Wind Q control, cosphi control and V control (with droop) mandatory
COUNTRY AND
DIFFERENCES WITH SG REQUIREMENTS
CATEGORY
V control in operation if >25 MW
Voltage support in case of voltage dip (Figure 57)
Germany Wind Reactive power changes should be applied within 30 s
Voltage support according to Figure 58
The HV/MV transformers must be equipped on their HV side with a
tap changer to provide +/- 13 % variation in +/- 6 steps
Germany Converter Voltage support according to Figure 59
Philippines Wind and Constant power factor or constant voltage control required, to be de-
Solar cided by the System Operator.
For 3ph faults, maximum possible current should be injected 150 ms
after the fault occurrence or elimination, as per shaded area in Figure
60. Before these 150 ms, net reactive power consumption should not
be higher than 60% Pn
For other faults, 150 ms after the fault occurrence or elimination, the
reactive power consumption cannot exceed 40% Pn and the active
power consumption cannot exceed 30%.
Spain special (dis- Special thermo solar units not equipped with synchronous generators:
patchable and non- - For voltage dips, should provide at least 2 times the nominal current.
dispatchable) - should have a voltage regulation/controller providing the same re-
sponse than a synchronous machine.
For wind farm, see Figure 61 for current injection during and after
faults for 3ph faults. (See “Resolución de 4 de octubre de 2006” for
phase to phase fault, and for details of current injection/absorption
limits)
Philippines Solar Constant power factor or constant voltage control required, to be de-
cided by the System Operator.
See Figure 60
Must be capable of injecting reactive power in the grid during the fault
Must be capable of absorbing reactive power from the grid after the
fault clearing
Philippines Small So- See Figure 60
lar
UK onshore Continuous V control (details in appendix 7 of grid code)
Figure 57: Requirement for reactive power supply, IQ, during voltage drops for wind power plants with a
power output greater than 1.5 MW (zone B: priority to Q supply, not P supply) – Denmark
Figure 58: Reactive current droop for offshore wind farms – Germany
Figure 59: Reactive current droop for units not directly connected to the grid (through converters) – Ger-
many
Figure 61: Current injection of wind farms during and after fault - Spain
MANDATORY NON-MANDATORY
COUNTRY EARTHING
PROTECTIONS PROTECTIONS
Germany HV/MV Trans- Two independent
Wind former in vector systems must be
group YN/d5 implemented
Low resistance Some other de-
neutral point tailed requirements
Non-switchable
neutral point with
direct connection to
earth
5.4 Synthesis
This grid code benchmarking has analysed the best practices around the world in contexts which can be
compared to the one of KSA. These practices were taken from Belgium, Canada (British Columbia), Den-
mark, Germany, Philippines, and UK.
In the analysed grid codes, the following common features were observed:
· The main part of grid codes is dedicated to Synchronous Generating Units.
· Exceptions, derogations and specific requirements are required for VRE power plants, especially for
units based on power electronic conversion to produce electricity.
· The location-specific requirements are not included in the grid codes but are agreed between network
operator and plant owner in connection contracts.
· The requirements for less common technologies are usually treated in bilateral agreements and based
on the main grid code part dedicated to Synchronous Generation.
· In each of the grid codes, the categories of requirements are the same... Requirements are often clas-
sified in Frequency, voltage, power quality, Q-Range, P/f control, Q/V control, information exchange...
Furthermore, the same requirement is often written following the same technical principle.
However, in these grid codes, the main differences are observed in:
· The type of generating units for which a dedicated grid code is available (conventional, wind, solar,
etc.). This mainly depends on the expected energy mix of the country.
· The thresholds/criteria for categorisation of the generating units (size, voltage level, etc.) highly depends
on the structure of the grid and energy mix.
· The numerical values used in requirements, such as values of Q-range, Voltage control droops, also
depend on grid structure.
· The approach chosen for modifying the grid code is different from country to country:
· Some chose one grid code for integrating every type of generation
· Other prefer dedicated grid codes for Wind Farms, PV, …
· Finally, other countries proposed amendments to existing grid codes, without modification to the
existing requirements.
6.1 Introduction
This chapter presents a detailed analysis of the requirements for VRE connection as defined in the current
version of the grid code of Brazil (“Procedimentos de Rede”) [6]. The version of the grid code analysed in
this study is Rev. 2016.12, from 12 December 2016.
The Brazilian regulation for electrical power systems and services establishes the national grid code through
a set of documents entitled “Procedimentos de Rede”. This set of documents is made available at ONS’
website11.
Any electrical device connected to the Brazilian Interconnected Power System (BIPS) is directly subject to
the coordination of ONS, which plays the role of an Independent System Operator (ISO).
The grid code of Brazil is organized in 26 different modules, as follows:
· Module 1: Introduction
· Module 2: Minimum requirements for transmission facilities and management of performance indicators
Defines the minimum requirements for transmission facilities and establish the system for the manage-
ment of basic network performance indicators and transmission network functions.
· Module 3: Access to transmission facilities
Establishes the instructions and processes for the feasibility of access (including the connection and
the use) to the transmission facilities that are part of the main transmission network.
· Module 4: Expansion and reinforcements
Proposes to the Granting Authority the extensions and reinforcements in the main transmission network
and other transmission facilities.
· Module 5: Consolidation of load forecasting
Allocates responsibilities and establish the procedures and deadlines for the consolidation of the load
forecast, which implies: organizing the temporal chaining of the various load forecasting processes;
make the products and data available for carrying out studies under responsibility of ONS; establish the
load forecasting process and describe it clearly to the stakeholders and seek improvement of forecasts.
· Module 6: Planning and scheduling of the electrical operation
Establishes guidelines, criteria, systematics and processes to be used in planning studies and sched-
uling of the electrical operation. The studies should define actions to solve the problems identified in a
given horizon; define guidelines to be applied to the main operation network to ensure service to the
load; to reconcile the requests of the different stakeholders for interventions in the system; visualize the
impact of the new works on the operation of the system; and subsidize the Granting Authority in decision
making.
· Module 7: Planning of the energetic operation
Assigns responsibilities and establishes procedures for ONS to develop its energy operation planning
duties.
· Module 8: Daily schedule of the electro-energetic operation
Establishes daily load, generation and exchange schedules to ensure the energy optimization of the
generation resources and the operational safety of national interconnected system.
· Module 9: Water resources and meteorology
11
Source: http://ons.org.br/paginas/sobre-o-ons/procedimentos-de-rede/vigentes
Establishes the responsibilities and processes for obtaining the inputs for the planning and scheduling
of the operation of the national interconnected system, in which regards hydrological information and
data, hydro-energy and meteorological data, technical data and hydraulic restrictions of hydroelectric
power plants, as well as requirements for the operation of control of floods of the reservoirs.
· Module 10: Operation Procedures Manual
Regulates the activities of standardization, pre-operation, real-time operation and post-operation; es-
tablishes the concepts of the ONS’ networks necessary to fulfil the responsibilities of ONS; to concep-
tualize and establish operating rules, operating instructions, operative messages, operational routines,
operational information registers, operational adjustments and international regulations; defines the or-
ganization of the operation as to the functional and operational hierarchy, establishing the levels of
authority, the duties, responsibilities and area of operation involved.
· Module 11: Protection and control
Establishes guidelines for the treatment of the macroprocess of system-level protection and control,
defines the processes and determine the inputs, means of execution, products, users and responsibili-
ties of ONS and generation, transmission, distribution, import and export markets, as well as free and
potentially free consumers.
· Module 12: Billing Measurement
Establishes the responsibilities, systematics and deadlines for the preparation and approval of the de-
sign, assembly and commissioning of the billing measurement systems, for the maintenance and in-
spection of this measurement system, for the reading of the meters and for certification of working
standards of the system.
· Module 13: Telecommunications
Establishes the telecommunication service requirements for the operating network, under the respon-
sibility of the ONS, applicable to the ONS and the stakeholders that own the facilities and equipment
belonging to the operating network. It also deals with the implementation of new telecommunication
services, as well as the maintenance and evaluation of the performance of telecommunication services
in operation.
· Module 14: Administration of ancillary services
Presents the criteria for the administration of ancillary services, that is, to establish the criteria not only
for the commercial arrangements of the ancillary services provided by the stakeholders, but also for the
conclusion of the ancillary service provision contracts and for the verification process related to these
services.
· Module 15: Administration of transmission services and charges
Explains the criteria and processes inherent to the contracting and administration of the transmission
services and the use of the transmission system, by means of the standardization of the practices of
the ONS and the stakeholders involved in compliance with the regulation of the electricity sector.
· Module 16: Maintenance follow-up
Monitors maintenance and provides necessary inputs to an electric power supply service at the levels
and standards of quality and reliability required by consumers and approved by ANEEL.
· Module 17: Not Available at ONS’ Website
· Module 18: Computer systems and models
Defines the computational tools - systems and computational models - used in the grid code.
· Module 19: Identification and treatment of nonconformities
Establishes the process of identification, treatment and application of penalties by ONS, resulting from
the non-fulfilment of the grid code requirements by the stakeholders; establishes the process for stake-
holders to identify the nonconformities practiced by ONS and the referral to be given by the ONS Board.
· Module 20: Glossary of technical terms
Ensure uniformity of use and appropriate understanding of technical terms used in the grid code.
· Module 21: Studies to strengthen the safety of electrical operation, systemic control and facility integra-
tion
Defines inputs, establishes responsibilities and systematic regarding the evaluation and reinforcement
of electrical operational safety and systemic control.
· Module 22: Analysis of events and disturbances
Assigns responsibilities in the processes of analysis of events and disturbances and establishes the
basic guidelines, methodology and criteria for the analysis of the technical aspects of the events and
disturbances in the operating network and for the technical analysis of the causes of failures observed
in equipment, main network facilities and power plants centrally dispatched by ONS.
· Module 23: Criteria for studies
Establishes guidelines and criteria for studies carried out by ONS in the fulfilment of its legal responsi-
bilities.
· Module 24: Facility integration process
Presents the process for integration of facilities and reservoirs to the operation of the national intercon-
nected system, defines the responsibilities of the parties involved, and formalizes the relations between
ONS and ANEEL, ANA, CCEE and the stakeholders that participate in this process.
· Module 25: Verification of data, reports of the operation of the National Interconnected System and
performance indicators
Allocates responsibilities and systematics for data collection, reporting of the system operation and for
the calculation of performance indicators and indicators of compliance with the recommendations made
by ONS in analysis and studies reports.
· Module 26: Power plant operating modes
Establishes a methodology to classify the operating modes of the power plants, which are: TYPE I -
Centralized scheduling and dispatch; TYPE II - Centralized scheduling and non-centralized dispatch;
and TYPE III - Non-centralized scheduling and dispatching.
In this Product, the emphasis of the analyses is in the Module 3, where the technical requirements for the
connection of new facilities to the transmission network are defined.
· The instructions for the issuance of a Technical Advice, at the request of a distribution company, on the
impacts of the required access to the distribution system on the transmission system12;
· The minimum technical requirements for generating units connected (or requesting connection) to fa-
cilities under the responsibility of a DISCO with a voltage level higher than 69 kV;
· The minimum technical requirements for generating units that are centrally dispatched by ONS con-
nected (or requesting connection) to facilities under the responsibility of a TSO or DISCO;
· Guidelines for the DISCO to elaborate the Access Notice in the case of connection of a power plant
that is centrally dispatched by ONS to the facilities under responsibility of a DISCO.
The Module 3 of the grid code is organized in 6 different sub-modules, as follows:
· Sub-module 3.1: Introduction
· Sub-module 3.2: Access query
· Sub-module 3.3: Access request
· Sub-module 3.4: Information to the access request
· Sub-module 3.5: Inspection and tests in the connection facilities
· Sub-module 3.6: Minimum technical requirements for the connection to transmission facilities
As described above, the technical requirements for the connection of new generating units to the transmis-
sion system are defined in Sub-Module 3.6.
12
Assess the impact on the transmission network from the integration of new facilities to the distribution networks.
Table 24 presents the minimum requirements to be respected in order to minimize the risk of disconnection
due to under- or over-frequency events.
13
The values presented in this table refer to the minimum amount of time to withstand the given voltage at the PoC
prior to disconnection.
14
The values presented in this table refer to the minimum amount of time to withstand the given system frequency
value prior to disconnection
Figure 63: Power factor requirement within the voltage operating range
This control mode must be implemented at the power plant control (PPC) level but activated only when
request by ONS.
15
This figure is not presented in the Brazilian grid-code. However, it is included in this document to illustrate the ex-
pected behaviour of the reactive power and power factor control functions as per the Brazilian grid code.
For system frequency between 57.0 Hz and 58.5 Hz, it is allowed to reduce the power output of the VRE
power plant up to 10%.
These requirements apply for steady-state and quasi steady-state operating conditions.
This FRT characteristic applies to any type of disturbance, whether caused by load rejection, symmetric or
asymmetric faults, and must be satisfied by the phase voltage that undergoes the most significant variation.
16
Upper limit: HVRT; lower limit: LVRT
Figure 69: Requirement for reactive current injection during faults (Brazilian grid code)
Where:
· ∆ = −
· : reactive current
· : pre-fault reactive current
· : nominal current
· ( )=
6.4.1 Requirements for WPP only in the current version of the grid code
Analysis:
In the current version of the grid code, there are a few technical requirements that are specified only for wind
power plants, as follows:
· Fast reactive current injection;
· Over-frequency control;
· Synthetic inertia.
The first two requirements are in practice already being required from solar PV power plants. This seems to
be a text imprecision in the grid code that could be easily fixed.
In which regards the requirement for the provision of synthetic inertia, it is imposed exclusively to wind power
plants. It is important to highlight that if this requirement is imposed to solar PV power plants as well, it will
require the PV power plants to operate de-rated with respect to the maximum available power or to be
equipped with a local energy storage device.
Recommendations:
The following recommendations are made by the Consultant with respect to the identified issues:
· Sub-module 3.6, chapter 8.2.1, paragraph 9:
“Os aerogeradores As unidades geradoras de centrais geradoras eólicas ou fotovoltaicas com potência
instalada superior a 10 MW deverão dispor de controladores sensíveis às variações de frequência, que
promovam a redução da potência de saída quando em regime de sobrefrequência na faixa de frequên-
cias de 60,2 Hz a 62,5 Hz.
Este controle deverá ser do tipo proporcional com ganho de 3% / 0,1Hz na base da potência disponível
no aerogerador na unidade geradora no momento.”
· Sub-module 3.6, chapter 8.2.1, paragraph 8:
The technical requirements for the provision of synthetic inertia should remain being imposed to wind
power plants only.
· Sub-module 3.6, chapter 8.8:
“Quando de variações transitórias de tensão, além de cumprir os requisitos de manter-se conectadas
pelo período descrito no item 8.7.1 deste submódulo, os aerogeradores as unidades geradoras
deverão ser capazes de dar suporte de tensão à rede elétrica através da injeção de corrente reativa
adicional, para tensões de sequência positiva inferiores a 85%, e de absorção de corrente reativa adi-
cional de sequência positiva para tensões acima de 110%, conforme a Figura 6...”
Figure 70: Recommendations for improvement of the requirement for reactive current injection during
faults
Analysis:
As mentioned before, the current version of the grid code requires that the VRE power plants be able to
guarantee 0 Mvar injection at the PoC when not producing active power. However, for certain regions of the
system and for given operating conditions, there could be an interest to use VRE power plants to provide
voltage/reactive power support when not producing.
In today’s situation, the current requirement is enough for the needs of the system. Moreover, as there is no
ancillary services market in place in Brazil, it is not straightforward to give incentives to VRE power plants to
provide voltage/reactive power support in periods of null production.
However, considering the foreseen growth of VRE in the Brazilian energy mix, it might be that in the future
such support to system duties becomes necessary from VRE power plants.
Recommendations:
· Maintain the requirement as it is in the current grid code;
· When dealing with higher VRE shares in the future, it is recommended to perform a dedicated analysis
in order to identify if the need for reactive compensation is a structural or a local issue:
· Structural issue: recommend grid reinforcement (e.g. synchronous condensers, SVCs, reactor/ca-
pacitor banks, etc.);
· Specific issue: provide specific requirements for the power plant to be connected at that specific
location (included in the PPA), or promote the development of a competitive ancillary services
market.
Analysis:
In the current version of the Brazilian grid code, the FRT requirements are defined at the terminals of the
generating unit (e.g. terminals of the wind turbine or the inverters). In addition to that, a single FRT charac-
teristic is defined for the entire system, independent of the location and/or voltage level.
The justification to set the FRT requirements to the terminal of the generating units is to facilitate the grid
code compliance assessment process, which is currently performed via an equipment certification mecha-
nism. However, the implementation of FRT requirements to the terminal of the generating units leads to
several challenges when trying to predict the behaviour of the power plant.
The main reasons for defining a single FRT characteristic for the entire system are:
· Non-discriminatory nature of the grid code (to not favour specific locations of the system);
· The transient behaviour of the voltage in the different subsystems in todays grid configuration is very
similar, allowing to set a single FRT characteristic for the entire system.
Considering the expected growth of VRE power plants in the Brazilian energy mix, it is expected that the
dynamic behaviour of the system changes drastically and the aforementioned characteristics might not re-
main valid anymore.
Recommendations:
· Specify the FRT requirements at the VRE power plant PoC;
· Assess the transient behaviour of the system voltages in every medium-term transmission planning
study in order to anticipate future needs of the system. In case the behaviour of the different regions of
the system becomes significantly different, it might be needed to specify a dedicated FRT characteristic
for each region of the grid.
Analysis:
The requirements for performance of VRE power plant control functions must be clearly defined in the grid
code. These requirements have a significant impact to the design of the power plant and to the selection of
the equipment that compose this plant.
The current version of the Brazilian grid code provides clear requirements for the types of control functions
that need to be implemented. However, it does not explicitly define the performance requirements for the
different control functions, such as:
· Maximum setpoint update delay;
· Response time to a new setpoint;
· Setpoint accuracy;
· Accuracy of the control action;
· Open and closed loop response times;
· Maximum setpoint tracking error;
· etc.
As these requirements have an impact on the design and equipment choice (CAPEX and OPEX impacts),
they must be clearly known in the very early stages of the project development in order to not jeopardize the
feasibility of a project.
An example of such requirements is given in the VRE grid code of South Africa [7], described as follows:
· Q control mode:
· The generator shall update its set point value in response to the new value within 2 sec;
· The PP shall respond to the new set point within 30 seconds after receipt of an order to change
the setpoint;
· The accuracy of the control performed and of the setpoint shall not deviate by more than ±2% of
the setpoint value or by ±0.5% of maximum reactive power, depending on which yields the highest
tolerance;
· The PP shall be able to receive a Q setpoint with an accuracy of at least 1kVar.
· PF control mode:
· The generator shall update its set point value in response to the new value within 2 sec;
· The PP shall respond to the new set point within 30 seconds after receipt of an order to change
the setpoint;
· The accuracy of the control performed and of the setpoint shall not deviate by more than ±0.02.
· V control mode:
· Voltage control is a control function controlling the voltage at the PoC;
· The generator shall update its set point value in response to the new value within 2 sec;
· The PP shall respond to the new set point within 30 seconds after receipt of an order to change
the setpoint;
· The accuracy of the voltage setpoint shall be within ±0.5% of nominal voltage, and the accuracy
of the control performed shall not deviate by more than ±2% of the required injection or absorption
of reactive power according to droop characteristics.
Recommendations:
· Define a minimum set of performance indicators and the associated numerical values
· Maximum setpoint update delay;
· Response time to a new setpoint;
· Setpoint accuracy;
· Accuracy of the control action;
· Maximum setpoint tracking error;
· Open and closed loop response time.
The numerical values for the requirements depend on the intrinsic behaviour of the system and on the ca-
pabilities of the VRE generation technologies. Therefore, these values should be set based on technical
studies of the dynamic behaviour of the system, as well as taking into account the existing and forecasted
capabilities of the VRE generation technologies.
Analysis:
The current version of the Brazilian grid code does not provide specifications for commissioning and com-
pliance tests for VRE power plants. However, these requirements are defined in dedicated documents made
available to power plant developers during the execution of the projects.
The following topics are covered by these documents:
· Testing conditions are specified for the following aspects:
· Active power control;
· Frequency control;
· Reactive power control at the PoC;
· Voltage control at the PoC;
· Power factor control at the PoC;
· Transformer energizing;
· Power quality.
· Variables to be measured and/or monitored.
A very good example of requirements and test procedures for VRE power plants is given in the grid code of
Ireland [8].
Recommendations:
· Make the requirements for commissioning and compliance tests available to the project developers in
a very early stage of the project or (preferably) publicly available as an annex of the grid code;
· Details of the following aspects, for each test to be performed, should be specified:
· Purpose of the test;
· Pass criteria (in line with the minimum requirements defined in the grid code);
· Instrumentation and data recording;
· Initial conditions for the test;
· Step-by-step test procedures;
· Test reporting procedures.
Analysis:
The Brazilian grid code specifies the following responsibilities for the power plant owner in which regards
the provision of simulation models of the VRE power plant (Sub-Module 21.4):
· Provide to ONS the data and information necessary to carry out the data and model validation process
for electrical studies;
· Provide the necessary data and participate in model validation activities;
· Update the computational models used for electrical studies according to the adjustments made during
project commissioning;
· Present simulation results using the updated computational models and the records obtained from the
commissioning tests, considering the adjustments made in the field during the commissioning, in order
to attest the performance of the models.
Despite the provision in the grid code, details on the requirements for these models are not defined. The
following relevant topics are not clearly defined in the grid code:
· Model extent: a trade-off between model complexity and model quality has to be achieved
· Application for power plant design purposes: detailed power plant model and simplified grid model;
· Application for system-level analyses: detailed grid model and simplified power plant model.
· Responsibility for model reduction/simplification:
· Should be in the hands of the system operator given that it requires deep understanding of the
modelled process and the application of the models.
· Simulations to be carried out in the model validation process in line with the commissioning and com-
pliance tests:
· Same initial conditions
· Same pass criteria
Moreover, as indicated in Figure 71, the technical requirements specified in the grid code are defined at
different locations at the VRE power plant (PoC, collector busbar, terminal of generating units), posing sev-
eral technical challenges for the development and validation of simplified/reduced models of VRE power
plants.
Figure 71: Definition of technical requirements at different locations (Brazilian grid code)
Recommendations:
· Power plant owners/project developers should be in charge of providing a full model (including internal
MV network and detailed model of the generating units) of the power plant to the system operator;
· The performance of the model should be assessed via simulations aiming at reproducing the commis-
sioning and compliance tests in a simulated environment;
· The model validation should be subject to expert judgement by the system operator;
· The model reduction/simplification should be a responsibility of the system operator.
Figure 72 presents a simplified model management process recommended by the Consultant.
•Measurements
(commissioning •Development of
PP •Measurements
tests) a reduced-order
•Models PP System
Owner / •Detailed model (equivalent)
(equipment Owner (used for Operator model
OEM level)
compliance
studies)
Analysis:
Asymmetrical faults are the most common types of faults occurring in transmission networks. However, the
majority of the VRE grid codes do not specify technical requirements for the behaviour of the power plants
under asymmetrical faults.
With increasing VRE shares in the system the importance of VRE power plant behaviour during asymmet-
rical faults is increasing. For example, the European framework for the grid codes specifies the following [9]:
“With regard to the supply of fast fault current in case of asymmetrical (1-phase or 2-phase) faults, the
relevant system operator in coordination with the relevant TSO shall have the right to specify a requirement
for asymmetrical current injection.”
The Brazilian grid code does not specify the technical requirements for negative sequence current injection
for VRE power plants during asymmetrical faults.
Recommendations:
It is recommended that in in every medium-term transmission planning study the behaviour of the system
with respect to asymmetrical faults be analysed in details. Specific requirements in the grid code should be
defined as soon as it is detected problems in terms of dynamic performance of the system or malfunctioning
of protection systems under unbalanced faults (e.g. the case of the German grid code).
Analysis:
The majority of the grid codes around the world do not currently define Energy Storage or specify technical
requirements for Storage technologies (Pump Storage Plants aside). However, with the expected growth in
the application o BESS in power systems, there are several ongoing discussions around this topic in different
countries. An example of these discussions is the ongoing one at National Grid UK, who’s receiving an
increasing number of connection applications from energy storage project developers.
As technical requirements for energy storage applications have not yet reached a sufficient maturity level,
National Grid UK is temporarily applying technical requirements derived from either generation or HVDC
requirements. However, these requirements do not necessarily reflect the nature of the technology, and is
inefficient for all concerned.
Table 26 presents the treatment of energy storage applications by National Grid UK during the period when
tailor-made requirements are not yet available.
Table 26: Technical requirements for energy storage applications in UK (transitory phase) [10]
Battery connected directly to the Battery would be treated in the same way as a
4
Transmission or Distribution System Voltage Source HVDC Converter
Recommendations:
Considering that the technical requirements for energy storage applications have not yet reached sufficient
maturity level, it is recommended to not define such requirements in the Brazilian grid code in the short-term.
However, it is recommended that ONS follows the international discussions in this subject in order to capi-
talize on the international experience when defining the technical requirements for energy storage to the
Brazilian case.
Table 27: Benchmark of the Brazilian grid code with respect to the international practice (synthesis of anal-
yses)
• Protection J
• Power quality J
Always needed
• Power reduction during over-frequency J
• Commissioning and compliance tests K
• Communication J
Low VRE share • Adjustable reactive power J
• Constraining active power (active power management) J
• Voltage control J
• Active power gradient limitation K
Very high VRE share
• Reduced output duration mode for reserve provision L
• Synthetic inertia J
It must be highlighted that the grid code should be permanently reviewed in order to enable the deployment
of VRE without jeopardizing the quality and security of the system operation. Careful should be taken in the
grid code update process in order to avoid regulatory instabilities
17
Requirements for cases of exclusive use of VRE are not applicable (N/A) to the Brazilian system reality.
References
[1] International Renewable Energy Agency (IRENA), “Scaling up Variable Renewable Power: The Role
of Grid Codes,” IRENA, Abu Dhabi, UAE, 2016.
[2] J. Fortmann, F. Schaube, A. Mendon-ca, A. Morales, Ö. Göksu and P. E. Sørensen, “Latest
Developments of Negative Sequence Extensions for Generic RMS Models ofvWind Turbines,” in
Proceedings of the 15th Wind Integration Workshop, 2016.
[3] P. M. Anderson, Analysis of Faulted Power Systems, Wiley-IEEE Press, 1995.
[4] VDE Verlag, “Technical requirements for the connection and operation of customer installations to
the high-voltage network (VDE-AR-N 4120),” VDE, 2015.
[5] VDE Verlag, “Technische Regeln für den Anschluss von Kundenanlagen an das Mittelspan-
nungsnetz und deren Betrieb (VDE-AR-N 4110),” VDE, 2015.
[6] Operador Nacional do Sistema (ONS), “Procedimentos de Rede - Vigentes,” ONS, [Online].
Available: http://ons.org.br/paginas/sobre-o-ons/procedimentos-de-rede/vigentes. [Accessed 10 June
2019].
[7] National Energy Regulator of South Africa (NERSA), “Grid Connection Code for Renewable Power
Plants (RPPs) connected to the electricity Transmission System (TS) or the Distribution System (DS)
in South Africa,” NERSA, Germiston, South Africa, 2014.
[8] EIRGRID, “WFPS Reactive Power Control Test Procedure,” EIRGRID.
[9] “Network Code on Requirements for Generators,” ENTSO-E, [Online]. Available:
https://www.entsoe.eu/network_codes/rfg/. [Accessed 10 June 2019].
[10] National Grid UK, “GC0096: Energy Storage,” National Grid UK, May 2016. [Online]. Available:
https://www.nationalgrideso.com/codes/grid-code/modifications/gc0096-energy-storage. [Accessed
10 June 2019].
[11] Moniteur belge, “Arrêté royal établissant un règlement technique pour la gestion du réseau de
transport de l’électricité et l’accès à celui-ci,” 2002.
[12] ELIA, “Islanding of wind power plant, grid connection requirements and guidelines,” ELIA, 2011.
[13] ELIA, “QV-control requirements for large wind power plants,” ELIA, 2011.
[14] ELIA, “Prescriptions spécifiques pour le raccordement de grands parcs d’éoliennes,” ELIA, 2011.
[15] BC Hydro, “60 to 500 kV technical interconnection requirements for power generators (Rev. 1.3),” BC
Hydro, Canada, 2012.
[16] Energinet.dk, “Technical Regulation for Thermal Power Station Units of 1.5 MW and higher (ver.
5.1),” Energinet.dk, Denmark, 2008.
[17] Energinet.dk, “Technical regulation 3.2.5 for wind power plants with a power output greater than 11
kW (rev. 4.1),” Energinet.dk, Denmark, 2010.
[18] Tennet TSO Gmbh, “Grid code – high and extra high voltage,” Tennet TSO Gmbh, Germany, 2012.
[19] Tennet TSO Gmbh, “Requirements for Offshore Grid Connections in the Grid of TenneT TSO
GmbH,” Tennet TSO Gmbh, Germany, 2012.
[20] N/A, “Resolución de 30 de Julio de 1998 (BOE 18/08/1998),” N/A, Spain, 1998.
[21] N/A, “Resolución de 18 de Mayo de 2009 (BOE 28/05/2009),” N/A, Spain, 2009.
[22] N/A, “Resolución de 10 de marzo de 2000 (BOE 18/03/2000),” N/A, Spain, 2000.
[23] N/A, “Especificaciones funcionales para los centros de control de generación interlocutores del
CECRE,” N/A, Spain, 2007.
[24] Red Electrica de Espana, “Criterios generales de protección del system eléctrico peninsular
español,” Red Electrica de Espana, Spain, 2012.
[25] Red Electrica de Espana, “Criterios generales de protección del system eléctrico peninsular
español,” Red Electrica de Espana, Spain, 2012.
[26] ERC, “Philippine grid code,” ERC, Philippines, 2001.
[27] ERC, “A resolution adopting and approving addendum to amendment no 1 of the Philippine Grid
Code (PGC), establishing the connection and operational requirements for variable renewable
energy (VRE) generating facilities,” ERC, Philippines, 2013.
[28] National Grid Electricity Transmission, “The grid code,” National Grid Electricity Transmission, United
Kingdom, 2013.