SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
Directory
2
Ensure the function of system is steady the reliable, the hardware of system are
adopted FR-S520S inverter and FX1S-14MR programmable logic controller.
ELEX DOOR SYSTEM MANUAL
3
(r ed 4#) out put common
(bl ack 5#)
i nput common ( yel l ow 1#) (whi t e 6#)
open but t on
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD.
cl ose but t on
power suppl y i nput chang swi t ch
out put common ( r ed 4#)
I.
modul e
Not e: x0, x1 i s i nput of A, B phase on encoder , r ed l i ne connect s t o +24V,
bl ack l i ne connect s t o COM t er mi nal .
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
Control input:
X0, X1——input of A, B phase on encoder
X2——pulse density (pulse input)
X3——close signal
X4——close complete input
X5——open complete input
X7——open signal
Control output:
Y4——close complete output
Y5——open complete output
4
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
P26 P4
P25 P27
P24 P5
Open complete
门到位 Open processP6
开门过程
Close complete
门到位
P87 P86
5
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
(2) Run frequency is controlled by signals Y1, Y2, Y3, detail control signals as
below:
Y1(RH) Y2(RL) Y3(RM) Frequency output
ON OFF OFF P4
OFF OFF ON P5
OFF ON OFF P6
OFF ON ON P24
ON ON OFF P25
ON OFF ON P26
ON ON ON P27
6
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
(1) Do not connect an AC power supply to the output terminals(U/T1, V/T2, W/T3).
(2) Input power supply mustn’t exceed 240VAC, and should be steady voltage, to
prevent burning out the inverter.
(3) Do not allow water enter the inverter, to prevent damage by short circuits.
Environment temperature of inverter is 0~55 ºC. Its relative moisture is
35~85%RH.
(4) If the door is at middle position, when power supply is on, It tunes itself. When
self-tuning, the door will be open first then be closed. During self-tuning,
open-door frequency is P25 and close-door frequency is P5.
(5) Inverter and PLC have R485 communication function. When normal, two
communication indication lights (SD, RD) may glint together. If there is only
SD indication light glinting, it means the communication is abnormal, Inverter
parameters P83~P90 is not able to be read out.
(6) Power supply initialization, when reading the parameter, open and close will not
be answered.
(7) During debugging, if change the setting of P83~P90, the parameters should be
read again. (to switch the PLC running switching or to power on after power
off is ok). When reread the parameters, it should be operated under complete
state, to prevent self-tuning again.
(8) Redefine some important parameter:
P82——Switch between N.C. and N.O. of open or close complete signal
P83——Auto open and close running (It plays when setting value is larger than
1.0. The value is set at 0 before leaving factory)
P84~P87 denotes acceleration or deceleration position of open and close, they
are based on the percentage of door opening distance. Open complete
is 100%.
P88——switch between N.O. and N.C. of open or close complete output
P89——the time from close complete till the end of P4 running frequency
P90——Keep torque time of open or close complete. Keep torque frequency of
open complete at P24. Keep torque frequency of close complete at
P27 (If P89 is larger thanP90, keep the frequency at P4)
P91——compare value of pulse density (It means the pulse numbers passed in a
unit of time. The Inverter has set that 1.0 denotes 10 pulse)
P92——corresponding time of P91 (The inverter has set that 1.0 denotes 10ms;
The setting value of P92 should not too large, it is suggested that the
value is between 4.0 to 5.0)
During close process, if the practical pulse numbers passed during the unit
of time set by P92 is smaller than the setting value of P91, reopen the door.
The door closing force could be adjusted according to P91 and P92. When
debugging, P92 should be fixed first, then increase the setting value of P91
7
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
gradually.
(9) The fault met in debugging and remedy:
1) If the start torque of open or close is not large enough, the setting value of
torque raising P0 could be increased properly, or increase the setting
frequency.
2) If there is reopen signal all the while, parameter values of P91~P92 were
not read in, check if there is any problem in communication.
3) Open or close running curve is abnormal. (There is no high-speed part)
a) Parameter values of P84~P87 may not be read in, check if there is any
problem in communication.
b) Maybe A and B phase of encoder were in reverse (The value of
high-speed counter is minus)
4) If communication is well-balanced, the two indicator light (SD,RD) will
glint together. If there is some problem in communication, there is only SD
indicator light glinting.
a) Check the communication parameter N1~N17 of inverter
b) Check if the connecting of cable is correct, or check if the contact is
OK.
8
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
Set the setting value of P30 ‘Expansion function display select’ to be ‘1’, Expansion function
parameter is effective.
Factory
Function Parameter Name Setting value range Min unit
setting
P10 DC brake frequency 0~120Hz 0.1Hz 3Hz
P11 DC brake time 0~10s 0.1s 0.5s
Standard Running Function
9
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
Acceleration and
P20 deceleration datum 1~120Hz 0.1Hz 50Hz
frequency
Stalling prevent
P21 0~31,100 1 0
function select
Stalling prevent
P22 0~200% 1% 150%
action level
Compensate factor
of stall prevent
P23
action when 0~200% 1% ---
multiplying speed
Open low-speed
P24 0~120Hz 0.1Hz 2Hz
frequency
Close start
P25 0~120Hz 0.1Hz 6Hz
frequency
Close high-speed
P26 0~120Hz 0.1Hz 16Hz
frequency
close low-speed
P27 0~120Hz 0.1Hz 2Hz
frequency
Acceleration start
frequency when
P28 0~120Hz
Standard Running Function
10
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
Output frequency
P43 1~120Hz,--- 0.1Hz ---
check when reversal
Second acceleration
Second Function P44 0~999s 0.1s 5s
time
Second deceleration
P45 0~999s,--- 0.1s ---
time
Second torque
P46 0~15%,--- 0.1% ---
increase
Second V/F (base
P47 0~120Hz,--- 0.1Hz ---
frequency)
Output current
P48 0~200% 1% 150%
check level
Delay of output
P49 0~10s 0.1s 0
current check signal
Current Check
Operation panel
P52 0,1,100 1 0
display code select
0: output frequency
AM terminal
P54 supervise
function select 1 0
1: output current supervise
Frequency supervise
P55 0~120Hz 0.1Hz 50Hz
datum
Current supervise
P56 0~50A 0.1A 2.5A
datum
Reset inertia run
P57 0~5s 0.1s ---
time
P58 Reset rising time 0~60s 0.1s 1s
0: no remote setting function
Additional Function
function select
Terminal
RM terminal
P61 0~10,14,16 1 1
function select
RH terminal
P62 1 2
function select
11
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
STR terminal
P63 0~10,14,16 1 ---
function select
RUN terminal
P64 1 0
function select
0,1,3,4,11~16,98,99
A, B, C terminal
P65 1 99
function select
P66 Retry select 0~3 1 0
Alarm occur retry
P67 0~10, 101~110 1 0
times
P68 Retry wait time 0.1~360s 0.1s 1s
Retry operation
Action Function Select
12
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
Switch between
normally open and 20: N.O.
P88
normally close 21: N.C. 1 20
complete output
P89 door vane start time 0.1~999s, --- 0.1s 1.5s
Complete torque
P90 0.1~999s, --- 0.1s 180s
keep time
Compare value of
P91 0~1000, ---- 1 8.0(80)
pulse density
P92 pulse density time 0~1000ms, ---- 1ms 5.0(50)ms
P93 0~100% 0.01% 0%
P94 0.01~10, --- 0.01 ---
P95 Rated slip of motor 0~50%, --- 0.01% ---
Compensation
Slip compensation
Slip
Frequency setting
C2 voltage deviation 0~60Hz 0.1Hz 0Hz
frequency
Frequency setting
C3 0~300% 0.1% 0%
voltage deviation
Adjust Parameter
Frequency setting
C4 0~300% 0.1% 96%
voltage plus
Frequency setting
C5 current deviation 0~60Hz 0.1Hz 0Hz
frequency
Frequency setting
C6 0~300% 0.1% 20%
current deviation
Frequency setting
C7 voltage deviation 0~300% 0.1% 100%
plus
Parameters set by
C8 Not be able to set
factory
CLR Parameters clear 0, 1, 10 1 0
To clear
13
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
N8 Running instruction
1: running instruction is out 1 1
of computer
0:running instruction is in
computer
N9 Speed instruction
1: running instruction is out 1 1
of computer
14
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL
VIII. Troubleshooting
Fault codes and solving plans provided by SH2 door inverter are given as following
Display Name Check details and cause Solution
Operate at a large
Over current during acceleration Prolong the acceleration
OC1
acceleration Output short circuit, or time
ground
Sudden change of load Cancel sudden change of
Over current during
OC2 Output short circuit, or load
constant speed
ground
Operate at a large
deceleration
Prolong the acceleration
Over current during Output short circuit, or
OC3 time
deceleration ground
Check the brake action
Mechanical brake of
motor is too early
Shorten deceleration time
Over voltage again Acceleration is too
OV1 Install reactor with
during acceleration small
ameliorated power factor
Cancel sudden change of
Over voltage again Sudden change of load load
OV2
during constant speed Install reactor with
ameliorated power factor
Prolong the deceleration
Over voltage again
Operate at a large time
OV3 during deceleration or
deceleration Decrease brake
stop
frequency
Decrease load
Set P71 suitable motor to
THM Overload on motor Motor is overloaded be constant torque motor
when using constant
torque motor
THT Overload on inverter Motor is overloaded Decrease load
Temperature around is Adjust temperature
FIN Overheat on heatsink too high around to the prescribed
Heatsink is blocked range
Ground over current Motor, wire is connect
GF Cancel ground connect
prevent when start to ground
Decrease load and
OHT External hot relay action Motor overheated
running frequency
OLT Stall prevent (overload) Motor overloaded Decrease load
Communication Check communication
OPT Port is fixed
abnormal port
Preserved parameter is Too many Times of
PE Decrease load
abnormal Parameter input
FR-PU04 is installed
PUE PU dropped Fix FR-PU04
too lax
Check the cause of Deal with the anomaly
RET Retry times exceeded
anomaly before this anomaly
CPU CPU error
15
SHANGHAI HYUNDAI ELEVATOR MFG. CO., LTD. ELEX DOOR SYSTEM MANUAL