Gate Controller Manual

AAD03010
Frequency Control System

Jutong Group
Wujiang oteppe elevator parts plant
1. Note...........................................................1

2. Terminal definition............................................1

4. Wiring diagram.................................................2

5. the door switches that process.................................3

6. basic debugging 1..............................................5

7. basic debugging 2..............................................5

8. function parameters............................................7

9. monitoring and fault show Schedule............................11


1. Note
1. Must be a qualified staff to the controller debugging, maintenance
or inspection. Please read carefully before operating the manual.
2. Sure to enter completely disconnect the power supply in the
circumstances, to carry out wiring work.
3。Not to enter Terminal 3 (L. N) and output terminals (U. V, W)
confusion, otherwise it will damage controller
4 controller will be the connection to reliable ground terminal, or a
risk of electric shock.
5 electricity circumstances, not hand-touch control terminal, or else
they risk of electric shock.
6 In the charging indicator light completely extinguished or positive
and negative voltage lines in the following when 36 V
7 drive to prevent screws, gaskets and metal such as foreign bodies
into the internal converter, or a fire and the risk of damage to
property.
8 main circuit wiring with the exposed part of the first cables,
insulation tape dress must use good, otherwise the risk of damage to
property
2. Terminal definition
cable terminations
Terminal name
number
single-phase AC power input
L/N/grounding brown/blue/Yellow-green
terminal
U/V/W U/V/W Electrical Connection
8 1# Public input switch(COMI)
2# the switch-door public
1
input(NO)
3# the door opened often enter
2
order(NO)
--* an order to close a regular
3
input(NC)
--* open the door often closed
4
limit the importation(NC)
--* close the door often closed
6
limit the importation(NC)
--* close spacing normally closed
7
input (NC)
4# open the door for speed
C2-C3
normally closed input(COM2)
A2 5# output of public-place, (NC)
6# often in place to open the
A3
door closed input(NC)
PREPAID often in place to close the
C1
door closed input(COM3)
PREPAID Failure normally closed
B1
output(NC)
PREPAID Failure normally open
A1
output(NO)
Note: --* controller for the internal wiring, not 6-control cable,
3. button names and basic operation
3.1 The key name

Keys, Help

MODE Model DR, FR, parameters P and D,


N parameters of the switch
select the data surveillance and
SET data into the model confirmed
the data or the incremental
∧ feature code
∨ data or feature code of decline
out of control for operation up
RUN and running
the face Plate operation under
way for the shutdown and reset
STOP operation

3.2 keys basic operation


To change the parameters of P05 as an example:

Key priorities contents


Connect to power

Press the MODE button under the corresponding changes to be key


parameters, to modify or keys into the parameters of monitoring,

Press the ∧or∨key to get the key parameters of change,nearly


SETbutton to confirm the revised parameters

Press SET key to enter parameters to modify or monitor

Press the ∧or∨key to change the key parameters

Press the revised SET button to confirm the parameters

Press mode switching MODE button to return to power display

4、4. Wiring diagram


A1,B1,C1-Output Fault
N-3core cable
M-Motor

1-Open the door


2-Close the door
3-Limit to open the door
4-Closed limit
6-Shift to open the door
7-shift to close the door
8-input pulbic terminal
C2-output public terminal
B2-open output
B3-close output

Note: The switch to the door in place with output cable, it is


necessary to confirm the logic gate output controller and state
control in line with the logic of reception counters, the doors of
the factory state controller is normally closed output, the main
users according to the actual situation choose Control Output in
place the logic of state. (Terminal A2) - a place normally open
output, (Terminal A3) - Commissioner of place normally open output,
(terminal C2-C3) - Public-output.
5. the door switches that process
5.1 open process
1, with torque upgraded to P05, acceleration and deceleration time
for the d28, frequency d15 start, and then to increase deceleration
time d29, target values for the d16 start to open the door to enter
low-speed operation.
2, the time-d47, began to slow down time and d30, target values for
the d17 into the open high-speed operation.
The general frequency of high-speed section that is set to set the
parameters d17 = d19.
3, when the doors open the door to running speed switching position,
through the delay d48, began to slow down time and d33, target values
for
d20 open the door into the low-speed operation.
4, run to open the door when the door position switch in place, the
doors to maintain the frequency d21, to maintain current d40 torque
remain in place to open the door to enter.

Frequency(频率)
Door open process (开门过程)
open the door in place to maintain(开门到位保持)

                  Doors open at maintaining current(门开到达保持电流)

                Doors open at maintaining frequency(门开到达保持频率)

Doors from the location of the region(门区域位置)

Signal to open the door (开门信号)

Close signal (关门信号)

Signal arrived to open the door (开门到达信号)


Open the door speed signals(开门变速信号)

Closed at Signal(关门到达信号)

Running curve to open the door(开门运行曲线图)

Note:
1, opened the door in place to maintain the frequency d21, to
maintain current d40. Hold time for the d42, the range of 0.1 到 999
(sec), when set to 0:00, the long-term.
2, the general frequency of high-speed section that is set to set the
parameters d17 = d19, this time between 19 and d17 and d32 slowdown
will not work.
3, if low-speed torque to open the door of the smaller, may be
appropriately increased the value of P05. Note: too great a P05 value
may lead to over-current protection.

5.2 closed process:


1, with torque upgraded to P05, acceleration and deceleration time
for the d34, frequency d22 start, and then to increase deceleration
time d35, target values for
d23 into the closed start low-speed operation.
2, the time-d49, began to slow down time and d36, target values for
the d24 into the closed high-speed operation.
The general frequency of high-speed section that is set to set the
parameters d24 = d26.
3, when the doors close to running speed switching position, through
the delay d50, began to slow down time and d39, target values for
d27 into the closed low-speed operation.
4, when the operation to close the door in place when the switch
position, the doors to maintain the frequency d14, maintain the
current close d41 into place Moment

Frequency (频率)
open the door in place to maintain(开门到位保持)
close process(关门过程) in place to maintain close(关门到位保持)

                   Doors open at maintaining current(门开到达保持电流)

                 Doors open at maintaining frequency(门开到达保持频率)

Doors from the location of the region (门区域位置)

Closed signal (关门信号)


Signal to open the door(开门信号)

Closed at Signal (关门到达信号)

Closed speed signals (关门变速信号)

Signal arrived to open the door(开门到达信号)

Closed operation curve(关门运行曲线图)

Note:

1, closed in place to maintain the frequency d21, to maintain current


d41. Hold time for the d42, the range of 0.1 到 999 (sec), when set to
0:00, the long-term.
2, the general frequency of high-speed section that is set to set the
parameters d24 = d26, this time between 26 and d24 and d32 slowdown
will not work.
3, if low-speed torque of the closed smaller, appropriately increase
the value of P05. Note: too great a P05 value may lead to over-
current protection.

6. basic debugging 1
    Door machine factory has been completed feature set of
parameters. According to actual needs, the user can control switch
operation curve of the door
    And the corresponding parameters, regulating the operation of the
door switch.
Steps:
1, set up control panel for the keyboard approach: p08 = 1.
2, door control switch operation curve and the corresponding
parameters, regulating operation of the door switch parameters.
3, push∧ + RUN or∨+ RUN (first push∧ and then click RUN button,
following the same operation) Show opened / closed the operation
curve.
4, set up control terminal control this way: p08 = 2 (default
setting).
Note: If the controller in operation, the parameters of p08 will not
be able to be modified. Please click "STOP" button. Then switch
"MODE" button to p parameters field parameters p08 changes.
The replacement of motors, variable speed switch or place the logic
of (NO / NC) Please confirm that the following steps:
7,1 monitoring input and output signals (parameters n16, parameters
n17) confirmed
   N16 parameters for the input signal monitoring, including: 1 to 9.

   N17 output signal parameters for monitoring include: a limit


output, the Commissioner limit output, fault output.

1 ---- command signal to open the door / RY1 output signal


2 ---- closed command signal / RY2 output signal
3 ---- a landing signal / RY3 output signal
4 ---- Commissioner landing signal
5 ---- screen / touch-signal
6 ---- a speed signal
7 ---- Commissioner speed signal
Note: monitoring the factory did not signal 5,8,9 ,
Definition, do not be here to monitor

The "MODE" button to switch to n parameter model, and then click


∧or∨ button control the Senate by the corresponding parameters
Then "SET", observed input and output signals in the state.
7,2 input terminals of logic (NO / NC) set to confirm
   Input logic setting parameters - P43

1, settings: 0 --- signal input terminals and public-closed,


effective at this time of the signal (NO).
1 --- signal input terminals and public-off, effective at this time
of the signal (NC).

2, set way :0 --- 15 bit 10-band number of input


The right to set the value of total value = (as a set value)
For example: a variable input signal, the Commissioner of variable
input signal, opened at the input signal, the Commissioner arrived at
the input signal
Is set to: NC; divided into: NO
Is set = 1 16 +1 8 +0 4 +1 2 +1 1 = 27
Then set the parameters P43 (input signal logic set) = 27
signal (no) Open Close Light open close
shift shift curtain
No ------ 7 6 5 4 3
right(BIT 5—15 4 3 2 1 0

Set 0 0/1 0/1 0/1 0/1 0/1
total 0 16 8 4 2 1

7,3 motor is, to confirm the reversal

Conditions: Set frequency (Fr mode) for about 3 Hz. P09 = 0


Steps: Click ∧+ RUN button to confirm a movement;
By∨ + RUN button to confirm clearance action.

Note: If the motor did not move, the appropriate increase P05 (torque
increase) value.
     If the motor running direction is not correct, change the output
phase sequence.
7,4 operational control of the set to confirm

P08 settings Control way


0 Panel operation(RUN/STOP)
1 Panel operation( +RUN、
+RUN、STOP)
2 terminal(NO:1、2)
3 communication(communication terminal)

7,5-frequency set to confirm

P09settings Control way


0 manual(in the mode set the frequency FR)
1 Encoder way
2 Encoder mode of operation cycle
3 Encoder means the door wide self-study
4 4way switch locations
5 4locations switch modes of operation cycle
6 communication

8. function parameters
No. Parameter name value Range multiple unit editor
P0
Test mode
0
P0
Main acceleration time
1
P0
Lord deceleration time
2
P0
V/F character
3
P0
V/F curve
4
P0
Torque upgrade
5
P0 Select electronic thermal
6 features
P0
Set thermal relay
7
P0
Choice of operating instructions
8
P0
Set frequency signal
9
P1
Stop mode
0
P1
Stop frequency
1
P1
DC braking time
2
P1
DC braking Level
3
P1
Maximum output frequency
4
P1
Basement frequency
5
P1 Stall function to prevent over-
6 current
P1 Stall function to prevent over-
7 voltage
P1
1 jumping frequency
8
P1
2 jumping frequency
9
P2
3 jumping frequency
0
P2
Width of the frequency jump
1
P2
Current limit function
2
P2
Started way
3
P2
Choose when to stop-start again
4
P2
Standby time
5
P2
Choose to trial
6
P2
The number of re-trial
7
P2
Lower frequency
8
P2
Upper frequency
9
P3
Select Monitor
0
P3
Line speed ratio
1
P3
Maximum output voltage
2
P3
OCS Level
3
P3
Carrier frequency
4
P3
Station,
5
P3
Communication Speed
6
P3
Stop bit
7
P3
Check -
8
P3
communications
9
P4
Communication response time
0
P4
password
1
P4
Clear data set
2
P4
Input logic set
3
P4 Screen / security breach-response
4 time
P4
Landing signal response time
5
P4
Encoder anomaly detection time
6
P4
SW anomaly detection at the time
7
P4
Select RY1 output
8
P4
Select RY2 output
9
P5
Very few motor
0
P5
Encoder lines
1
P5
System parameters (not revised)
2
P5
System parameters (not revised)
3
P5
System parameters (not revised)
4
P5
System parameters (not revised)
5
P5
System parameters (not revised)
6
P5
System parameters (not revised)
7
P5
Overload a frequency detection 1
8
P5
Overload detection frequency 2
9
P6
Overload detection current 1
0
P6
Overload detection current 2
1
P6
Overload detection time
2
P6 Overload frequency ratio (Low
3 speed)
P6 Overload frequency ratio (high
4 speed)
P6 Overload detection switch
5 frequencies
P6
Overload detection time
6
Before moving to confirm the time
P6
7 Repeated at a time when
maintaining
P6 Mandatory opening movement
8 detection time
P6 Abnormal movements were opened,
9 mandatory action time
P7 Anomaly at a time when the
0 waiting time
P7 Repeated at a time when
1 maintaining
Repeated at a time when
P7 maintaining
2 Repeated to maintain the arrival
of the Commissioner of time
P7 Acceleration and deceleration of
3 choice
P7 Open / Closed choose to stop in
4 the action
P7 Enter password parameters
5 District D
D0
Pulse a few doors wide
1
D0
Closed to_location
2
D0
A variable position 1
3
D0
A variable position 2
4
D0
A variable position 3
5
D0
A variable position 4
6
D0
A variable position 5
7
D0 Reach a position
8
Closed speed positions 1
Closed speed position 2
Closed speed position 3
Closed speed position 4
Closed speed position 5
Closed at maintaining frequency
A frequency of 1
A frequency of 2
A frequency of 3
A frequency of 4
A frequency of 5
A frequency of 6
Maintain the frequency at open
Closed frequency
1
Closed frequency 2
Closed frequency 3
Closed frequency 4
Closed frequency 5
Closed frequency 6
Opening acceleration and
deceleration time 1
Opening acceleration and
deceleration time 2
Opening acceleration and
deceleration time 3
Opening acceleration and
deceleration time 4
Opening acceleration and
deceleration time 5
Opening acceleration and
deceleration time 6
Close acceleration and
deceleration time 1
Close acceleration and
deceleration time 2
Close acceleration and
deceleration time 3
Close acceleration and
deceleration time 4
Close acceleration and
deceleration time 5
Close acceleration and
deceleration time 6
To maintain current open
To maintain current closure
Open / Closed maintain action to
stop time
Maintain a standby time of
arrival
Closed at maintaining standby
time
Regular time to start moving (SW
way)
Timing started by the time (SW
way)
Power ON when the frequency of
action
The door wide frequency of self-
learning
D District passwords
9. monitoring and fault show Schedule
9.1 Monitoring

No. Name precision units Remarks


N0 The board CODE
of
0
software

N0 Output 0.001 HZ
frequency
1
N0 Output 0.1 A
current
2
N0 Output 0.1 VAC
voltage
3
N0 DC input 0.1 VDC
voltage
4
N0 Set 0.01 HZ
frequency
5
N0 The 0.01 HZ SET UP
detection
6 ELECTRICAL
frequency
MACHINE
POLES\ENCOD
E LINE
N0 Gate 1 0-7:OPEN
location
7 AREA
region
8-13:CLOSE
AREA
N0 The door 0.01 0.01=1;100=1000
wide
8 0
(pulses)
N0 Reach a 0.01
position
9 (DATA)
N1 witching 1 TIMES 0.01=1TIMES;10
the number
0 0=10000TIMES
of doors
N1 Encoder 0.1 KHZ
detection
1 state
N1 Abnormal 1 CODE
2
N1 Abnormal 1
3
N1 Abnormal 1
4
N1 Abnormal 1
5
N1 Input
terminals
6
state
N1 Output
terminals
7 state
9.2 fault
show
Panel fault reasons countermeasures related
display contents parameters
Sc1 Over- Output short- Connection to Accelerati
current / circuit, short- confirm on and
Sc2
abnormal to-ground Reduce decelerati
Sc3 overheating Environmental temperature on time
temperature is Acceleration
too high time delay
Speed up the
time is short

Oc1 Over-current Output of less Output of less Accelerati


Enhance high confirmed on and
Oc2 torque Reduce the decelerati
Oc3 Acceleration increase torque on time
time is short P05
Acceleration
time extension
Ov1 Over-voltage Deceleration Prolonged Accelerati
time is short slowdown on and
Ov2
Resistance is decelerati
Ov3 connected to on time
brake P17
LV Less voltage Low-voltage Power to P23-25
power confirm
Instantaneous Start to start
power outage
OL Over-load Electronic Load state
thermal relay recognition
moves too Electronic
heavy-load thermal relay
confirmed
AU External The message was Communications
abnormalities unusual to stop confirmed
sending
OP Abnormal Power ON, Operation
operation Operation signal to
signal ON confirm
settings, operation panel
ON signal wiring
operation in confirmed
the operation,
Communications
operation panel
falling out
parade
Er1 Without Without Enter Encoder power
pulse encoder pulse encoder to confirm
Encoder to
confirm the
wiring

Er2 Enter the Encoder pulse Encoder, the


contrary direction and A / B match of
encoder running in the confirmation
direction
opposite
direction
Er3 Arrival O on / off on / off signal
signals are signal arrived to confirm
ON at the same arrival
time ON
Opened at no Location data A signal to
signal opened the door confirm arrival
to reach the
state did not
reach the
signal
Er5 No signal clearance arrived signal
arrival Location data to confirm
opened the door
to reach the
state did not
reach the
signal
Commissioner
Note:
End set the parameters of the data, in order to prevent careless
change data, you can set your password.
Parameters P41: the region password (P regional parameters, D
parameters of the region) the parameters of a password.
Set: 000; 1-999 (set to: "000" that does not set a password)

After the data parameters set password changes steps:


P41 password to set parameters for the 777 as an example
1 by "STOP" button so that the elevator door controller to stop
running.
2 by 4 MODE button, enter your password into a show (PS), shows
flashes.
3 Press (rising bond) or drop key, so that it shows that the password
set by the previous (show flashes)
4 by "SET"∧or∨ button, showing that the parameters of (the last of
the parameters: For example, P01, etc.)
(Such as plants are not password settings, if a password, please
record your password, to prevent forget.

You might also like