R0 Date Document Reference: FCN/TDS/MAY.2020 Content 14/05/2021 Guaranteed Technical Parameter for 60KVA UPS
Guaranteed Technical Parameter – Falcon X5
a. Input Parameters
Capacity in KVA 60KVA
Nominal Voltage 415V AC (3Ph +N) +20%, -40%* Frequency 50Hz +/-6% Rectifier Bridge 3-level IGBT Based Power Factor >0.99 DC Voltage Ripple <3% without Battery, <1% with Battery DC Current Ripple Approx. 0 Power Walk in Up to 60 sec, settable THDI < 3%
b. Output Parameters
Nominal rating in KVA 60KVA
Nominal power in KW 54KW Inverter Bridge PWM & 3-level IGBT Technology Output Wave Form Sine Wave Controller 32bit DSP based Voltage 400V/415V AC (380V Optional) Voltage Stability Steady State +/-1% Dynamic Response +5% (for 0 -100% load), +3% (for 0 -50% load) Recovery time 98% recovery within 20ms Frequency 50Hz +/-0.1Hz Output Voltage THD <1% (Typical) for 100% linear load Output Voltage THD for 100% non- linear load <5% Power Factor 0.6 to unity within KVA & KW rating handling Capacity Overload capacity from 110% for 60 min inverter at 125% for 10 min nominal voltage 150% for 60 sec Duty Continuous Crest Factor 3:1 Parallel Up to 8 units Overall Efficiency at Up to 95.5% 100% load Efficiency on Eco Mode Up to 99% Wound Components Inbuilt Output Isolation Transformer
Document version Fuji Electric Consul Neowatt Pvt. Ltd. R0 Date Document Reference: FCN/TDS/MAY.2020 Content 14/05/2021 Guaranteed Technical Parameter for 60KVA UPS
c. Battery Parameters
Nominal rating in KVA 60KVA
Nominal power in KW 54KW Battery Voltage 480-528 VDC Battery Type 12V SMF VRLA (Option-Ni-Cd, Li-ion) Float Voltage 2.27 V/cell Boost Voltage 2.35 V/cell Minimum Discharge Voltage 1.75 V/cell
d. Bypass Parameters
Nominal rating in KVA 60KVA
Nominal power in KW 54KW Input Connection Common with mains input Bypass Voltage & 400V/415V AC (3 Ph + N), +/- 15% (380V Optional) Variation Frequency Sync range 50 Hz +/-2.5 Hz Transfer Time Sync Mode: No Break, Async Mode: <5ms Retransfer Time Sync mode: No Break, Async Mode: Inhibited Primary Components Static Switch (SCR-SCR module) Static Bypass Inbuilt
e. Environmental & Mechanical Parameters
Nominal rating in KVA 60KVA
Nominal power in KW 54KW Operating Temperature UPS: 0 to 40deg C Storage Temperature UPS: 0 to 70deg C Relative Humidity Up to 95% RH Non-Condensing Maximum Operating Altitude 1000m above MSL Acoustic Noise < 65dBA @ 1m Cooling Forced Air Cooling
Document version Fuji Electric Consul Neowatt Pvt. Ltd. R0 Date Document Reference: FCN/TDS/MAY.2020 Content 14/05/2021 Guaranteed Technical Parameter for 60KVA UPS
f. Display Characteristics
Nominal rating in KVA 60KVA
Nominal power in KW 54KW Input voltage, Output voltage, Input current, Output current, Battery voltage, Output KVA, Battery current, Output KW, LCD Display Bypass voltage, Output PF, Bypass frequency, Output frequency, Temperature, Output Load in %, Date & time. Rectifier ON / OFF, Load ON, Inverter ON / OFF, Float Charge, Bypass available, Boost Charge, Manual bypass ON, LED indication Battery low, SW I (Inverter Switch ON), Battery Charging/Discharging, SW b (Bypass Switch ON). Alarm For Fault condition. Input UV/OV, Battery current limit, Rectifier OV, Output Protection UV/OV, Battery low, Output overload, Over temperature, Output short circuit, Battery OV.
g. Physical Characteristics
Nominal rating in KVA 60KVA
Nominal power in KW 54KW Ingress Protection IP 20 Cable Entry Bottom Front Cabinet Colour RAL 9005 -Front door RAL 7016-Rest of all Frame 2mm, Cabinet Steel Thickness Front door 2mm, Covers 1.2mm Installation Free Standing, Floor Mounting Dimension in mm W800 X D900 X H1700mm Weight in kg 750 kg
h. Communication
Nominal rating in KVA 60KVA
Nominal power in KW 54KW Communication Protocols RS 232, USB Available Option SNMP, MODBUS & PFC
Document version Fuji Electric Consul Neowatt Pvt. Ltd. R0 Date Document Reference: FCN/TDS/MAY.2020 Content 14/05/2021 Guaranteed Technical Parameter for 60KVA UPS
f. Applicable Standards
Nominal rating in KVA 60KVA
Nominal power in KW 54KW General safety requirements for UPS used in operator access EN50091-1-1/IEC62040-1-1/AS 62040-1-1 areas Electromagnetic compatibility EN50091-2/IEC62040-2/AS 62040-2 (EMC) requirements for UPS Method of specifying the performance and test EN50091-3/IEC62040-3/AS 62040-3 requirements of UPS