You are on page 1of 4

Document version

Fuji Electric Consul Neowatt Pvt. Ltd.


R0
Date Document Reference: FCN/TDS/MAY.2020 Content
14/05/2021 Guaranteed Technical Parameter for 60KVA UPS

Guaranteed Technical Parameter – Falcon X5


a. Input Parameters

Capacity in KVA 60KVA


Nominal Voltage 415V AC (3Ph +N) +20%, -40%*
Frequency 50Hz +/-6%
Rectifier Bridge 3-level IGBT Based
Power Factor >0.99
DC Voltage Ripple <3% without Battery, <1% with Battery
DC Current Ripple Approx. 0
Power Walk in Up to 60 sec, settable
THDI < 3%

b. Output Parameters

Nominal rating in KVA 60KVA


Nominal power in KW 54KW
Inverter Bridge PWM & 3-level IGBT Technology
Output Wave Form Sine Wave
Controller 32bit DSP based
Voltage 400V/415V AC (380V Optional)
Voltage Stability Steady State +/-1%
Dynamic Response +5% (for 0 -100% load), +3% (for 0 -50% load)
Recovery time 98% recovery within 20ms
Frequency 50Hz +/-0.1Hz
Output Voltage THD
<1% (Typical)
for 100% linear load
Output Voltage THD for
100% non- linear load <5%
Power Factor
0.6 to unity within KVA & KW rating
handling Capacity
Overload capacity from 110% for 60 min
inverter at 125% for 10 min
nominal voltage 150% for 60 sec
Duty Continuous
Crest Factor 3:1
Parallel Up to 8 units
Overall Efficiency at Up to 95.5%
100% load
Efficiency on Eco Mode Up to 99%
Wound Components Inbuilt Output Isolation Transformer

©Copyrights Reserved Page|1


Document version
Fuji Electric Consul Neowatt Pvt. Ltd.
R0
Date Document Reference: FCN/TDS/MAY.2020 Content
14/05/2021 Guaranteed Technical Parameter for 60KVA UPS

c. Battery Parameters

Nominal rating in KVA 60KVA


Nominal power in KW 54KW
Battery Voltage 480-528 VDC
Battery Type 12V SMF VRLA (Option-Ni-Cd, Li-ion)
Float Voltage 2.27 V/cell
Boost Voltage 2.35 V/cell
Minimum Discharge Voltage 1.75 V/cell

d. Bypass Parameters

Nominal rating in KVA 60KVA


Nominal power in KW 54KW
Input Connection Common with mains input
Bypass Voltage &
400V/415V AC (3 Ph + N), +/- 15% (380V Optional)
Variation
Frequency Sync range 50 Hz +/-2.5 Hz
Transfer Time Sync Mode: No Break, Async Mode: <5ms
Retransfer Time Sync mode: No Break, Async Mode: Inhibited
Primary Components Static Switch (SCR-SCR module)
Static Bypass Inbuilt

e. Environmental & Mechanical Parameters

Nominal rating in KVA 60KVA


Nominal power in KW 54KW
Operating Temperature UPS: 0 to 40deg C
Storage Temperature UPS: 0 to 70deg C
Relative Humidity Up to 95% RH Non-Condensing
Maximum Operating
Altitude 1000m above MSL
Acoustic Noise < 65dBA @ 1m
Cooling Forced Air Cooling

©Copyrights Reserved Page|2


Document version
Fuji Electric Consul Neowatt Pvt. Ltd.
R0
Date Document Reference: FCN/TDS/MAY.2020 Content
14/05/2021 Guaranteed Technical Parameter for 60KVA UPS

f. Display Characteristics

Nominal rating in KVA 60KVA


Nominal power in KW 54KW
Input voltage, Output voltage, Input current, Output current,
Battery voltage, Output KVA, Battery current, Output KW,
LCD Display
Bypass voltage, Output PF, Bypass frequency, Output
frequency, Temperature, Output Load in %, Date & time.
Rectifier ON / OFF, Load ON, Inverter ON / OFF, Float
Charge, Bypass available, Boost Charge, Manual bypass ON,
LED indication
Battery low, SW I (Inverter Switch ON), Battery
Charging/Discharging, SW b (Bypass Switch ON).
Alarm For Fault condition.
Input UV/OV, Battery current limit, Rectifier OV, Output
Protection UV/OV, Battery low, Output overload, Over temperature,
Output short circuit, Battery OV.

g. Physical Characteristics

Nominal rating in KVA 60KVA


Nominal power in KW 54KW
Ingress Protection IP 20
Cable Entry Bottom Front
Cabinet Colour RAL 9005 -Front door
RAL 7016-Rest of all
Frame 2mm,
Cabinet Steel Thickness Front door 2mm, Covers 1.2mm
Installation Free Standing, Floor Mounting
Dimension in mm W800 X D900 X H1700mm
Weight in kg 750 kg

h. Communication

Nominal rating in KVA 60KVA


Nominal power in KW 54KW
Communication Protocols RS 232, USB
Available Option SNMP, MODBUS & PFC

©Copyrights Reserved Page|3


Document version
Fuji Electric Consul Neowatt Pvt. Ltd.
R0
Date Document Reference: FCN/TDS/MAY.2020 Content
14/05/2021 Guaranteed Technical Parameter for 60KVA UPS

f. Applicable Standards

Nominal rating in KVA 60KVA


Nominal power in KW 54KW
General safety requirements for
UPS used in operator access EN50091-1-1/IEC62040-1-1/AS 62040-1-1
areas
Electromagnetic compatibility
EN50091-2/IEC62040-2/AS 62040-2
(EMC) requirements for UPS
Method of specifying the
performance and test EN50091-3/IEC62040-3/AS 62040-3
requirements of UPS

©Copyrights Reserved Page|4